TRV OVERVIEW FOR REACTANCE LIMITED FAULTS

Similar documents
ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

REDUCING ARC FLASH HAZARD BY REMOTE SWITCHING

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

THE HISTORY OF FLICKER LIMITS

Tab 2 Voltage Stresses Switching Transients

THREE-PHASE SHORT-CIRCUIT TESTING OF HIGH-VOLTAGE CIRCUIT-BREAKERS USING SYNTHETIC CIRCUITS

Effects of Transient Recovery Voltages on Circuit Breaker Ratings

Transient Recovery Voltage at Transformer Limited Fault Clearing

2. Current interruption transients

Transient Recovery Voltage (TRV) and Rate of Rise of Recovery Voltage (RRRV) of Line Circuit Breakers in Over Compensated Transmission Lines

Transient Recovery Voltage Analysis on a Series Power Flow Control Device

Short-Circuit Analysis IEC Standard Operation Technology, Inc. Workshop Notes: Short-Circuit IEC

Shunt Reactor Switching

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

Chapter # : 17 Symmetrical Fault Calculations

High-Power Testing of Circuit Breakers

A TECHNICAL REVIEW ON CAPACITOR BANK SWITCHING WITH VACUUM CIRCUIT BREAKERS

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

AORC Technical meeting 2014

GUIDE FOR APPLICATION OF IEC AND IEC

(2) New Standard IEEE P (3) Core : (4) Windings :

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

G. KOEPPL Koeppl Power Experts Switzerland

High voltage engineering

System grounding of wind farm medium voltage cable grids

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Medium voltage circuit breaker technical guide

Simulations of open phase conditions on the high voltage side of YNd05-power plant transformers

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

This is a preview - click here to buy the full publication

A Guide to the DC Decay of Fault Current and X/R Ratios

DC current interruption tests with HV mechanical DC circuit breaker

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

COMPARATIVE PERFORMANCE OF SMART WIRES SMARTVALVE WITH EHV SERIES CAPACITOR: IMPLICATIONS FOR SUB-SYNCHRONOUS RESONANCE (SSR)

3Ø Short-Circuit Calculations

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

Chapter -3 ANALYSIS OF HVDC SYSTEM MODEL. Basically the HVDC transmission consists in the basic case of two

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Surge Protection for Ladle Melt Furnaces

Modelling of Sf6 Circuit Breaker Arc Quenching Phenomena In Pscad

Power Quality and Reliablity Centre

Power Factor & Harmonics

Switching Induced Transients:

A Methodology for the Efficient Application of Controlled Switching to Current Interruption Cases in High-Voltage Networks

CONTENTS. 1. Introduction Generating Stations 9 40

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

Contents. Reignition and Restrikes. Reactor Switching. Normal and Abnormal Transients. Normal and Abnormal Transients Reignition.

Short Circuit Current Calculations

Curso de Transmissão em Corrente Continua Rio de Janeiro, de Junho, 2007

Harmonic control devices

Safety through proper system Grounding and Ground Fault Protection

5. Black box arc modelling

Revision of TRV Requirements for the Application of Generator Circuit-Breakers

In Class Examples (ICE)

Power System Stability. Course Notes PART-1

Tab 8 Surge Arresters

Past CIGRE and Emerging IEEE Guide Documents on FCLs

Fixed Series Compensation

ACS 1000 Transformer Failure Investigation. Nathan Schachter, Peng

ELECTRICAL POWER TRANSMISSION TRAINER

Insulation Co-ordination For HVDC Station

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

FERRORESONANCE SIMULATION STUDIES USING EMTP

Electrical Engineering. Power Systems. Comprehensive Theory with Solved Examples and Practice Questions. Publications

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

PROTECTION APPLICATION HANDBOOK

UNDERSTANDING SUB-HARMONICS

Impact Assessment Generator Form

INTERNATIONAL STANDARD

In power system, transients have bad impact on its

STANDARDIZING ARC FLASH PPE LABELS

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

PERFORMANCE ANALYSIS OF SURGE CURRENT PROTECTION USING SUPERCONDUCTORS

HIGH VOLTAGE CIRCUIT BREAKERS

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Power Systems Modelling and Fault Analysis

Effects of Harmonic Distortion I

Analysis of a 405 km transmission line with series compensation

Stress Analysis of HVDC Circuit Breakers for Defining Test Requirements and its Implementation

Three-phase short-circuit current (Isc) calculation at any point within a LV installation using impedance method

ISSN: Page 298

EDS FAULT LEVELS

Fault Analysis. EE 340 Spring 2012

DC VACUUM CIRCUIT BREAKER

Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Accurate Current Measurement Transducer for Relaying Purpose

Utility System Lightning Protection

Embedded Generation Connection Application Form

{40C54206-A3BA D8-8D8CF }

Protection of Electrical Networks. Christophe Prévé

DC Chopper Based Test Circuit for High Voltage DC Circuit Breakers

Substation Design Volume VII

Electricity Ten Year Statement November Electricity Ten Year Statement November Appendix D

Transcription:

The Electrical Power Engineers Qual-Tech Engineers, Inc. 201 Johnson Road Building #1 Suite 203 Houston, PA 15342-1300 Phone 724-873-9275 Fax 724-873-8910 www.qualtecheng.com TRV OVERVIEW FOR REACTANCE LIMITED FAULTS 1.0 INDUCTIVE REACTANCE LIMITED FAULT One of the most severe conditions for a medium voltage circuit breaker to clear is an inductive reactance limited fault. For this condition the rate-of-rise of the transient recovery voltage (TRV) on the circuit breaker after the fault current has been interrupted is often quite high. If the voltage recovers too quickly after the fault current has been interrupted, the circuit breaker may reignite resulting in the resumption of the fault current which may cause the failure of the breaker. This fast recovering voltage across the breaker contacts often occurs because the capacitance of the circuit is generally quite low if there is no significant cable or a surge capacitor between the operating breaker and the reactance. This type of fault condition is discussed in detail in this section. Circuit breakers are built to standards that define the rated TRV capability of the breaker. The two circuits, which are illustrated in Figures 1 and 2, often result in TRV s that exceed the limits defined by standards. When the limits are exceeded, the circuit breakers may fail to clear the fault current, possibly resulting in a catastrophic failure. The two cases illustrated here are transformer-limited faults and reactor-limited faults. In Figure1 the fault current is fed predominantly by a transformer. C 1 represents the capacitance of the circuit between the transformer and the circuit breaker. C 1 includes the capacitance of the transformer and the capacitance of the bus or cable that connects the transformer to the circuit breaker. If there is no significant cable length and if the circuit breaker is physically close to the transformer, this capacitance is often quite small. Figure 1 TRV Overview Page 1 Qual-Tech Engineers, Inc.

Figure 2 represents the condition of a fault limited by a current limiting reactor. C 1 represents the capacitance of the circuit between the transformer and the circuit breaker. C 2 represents the capacitance between the circuit breaker and the reactor. In this circuit, C 1 is often fairly large due to cable capacitances of other circuits that are connected to the bus behind the breaker. C 2 is often quite small if there is no significant cable between the breaker and the reactor. (Another example of a similar circuit would be where the reactor is replaced by a transformer.) Figure 2 The worst-case fault condition for the TRV occurs for the first pole of a three-pole circuit breaker to clear a three-phase unearthed fault. (This applies to systems that are earthed or unearthed.) Also, the clearing of a symmetrical fault current causes a higher TRV than does the clearing of an unsymmetrical fault current. Consequently, in this analysis the TRV is calculated in each case for the first pole to clear the symmetrical fault current due to a three-phase unearthed fault. TRV Overview Page 2 Qual-Tech Engineers, Inc.

2.0 SINGLE PHASE FAULT The equivalent circuit for a single phase fault is illustrated in Figure 3 for the simple circuit of Figure 3. L 1 represents the transformer impedance and the current source represents the short circuit current that is being interrupted. The TRV that the circuit breaker would see in this case is also illustrated in Figure 3. The equations that define the TRV are summarized as follows: V TRV = E (1 cos ( t / L 1C1 ) where, E = 2 I SC L 1 in kv = 2 f = 314 radians/second for 50 Hz systems I SC is short circuit current in ka rms L 1 is inductance in Henries C 1 is capacitance in Farads t is time in seconds The parameters for V TRV in Figure 3 are defined as follows: E 1 = 2 E T 1 = L 1C1 Figure 3 TRV Overview Page 3 Qual-Tech Engineers, Inc.

3.0 THREE PHASE UNEARTHED FAULT The equivalent circuit for a three phase unearthed fault is illustrated in Figure 4 for the simple circuit of Figure 1. The TRV that the circuit breaker would see in this case is illustrated in Figure 5. The equations that define the TRV are summarized as follows: E 3 = 1.5 E 1 T 3 = T 1 where E 1 and T 1 are defined in Section 2.0. For the case illustrated in Figure 4, there is often some significant capacitance on the load side of the circuit breaker. This is illustrated in Figure 6. In that case, the TRV is composed of two different frequencies. The TRV on the source side of the circuit breaker will be of a higher frequency and faster rate-of-rise than the TRV on the load side of the circuit breaker. If the capacitance is much higher on the load side of the TRV, then the initial TRV will approach that for a single phase fault. (See Section 2.0) Figure 4 TRV Overview Page 4 Qual-Tech Engineers, Inc.

Figure 5 Figure 6 TRV Overview Page 5 Qual-Tech Engineers, Inc.

4.0 EQUIPMENT CAPACITANCE VALUES In doing a transient recovery voltage (TRV) study, one of the key parameters is the capacitance characteristic of each system component. However, the capacitance is not typically provided with other nameplate information. A good source of capacitance values is given in Annex B of IEEE Standard C37.011-2011 Application Guide for Transient Recovery Voltage for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis. 5.0 TRV STANDARD For reactor limited faults, the two-parameter reference line, as defined in IEEE Standard C37.06-2009, is generally applicable. This capability is illustrated in Figure 7. The prospective TRV of the system is not to exceed the reference line, defined by u c and t 3 ; it should cross the specified delay line, defined by t d, u, and t, close to zero voltage but should not recross it later. The standard values that define the TRV rating are given at 10%, 30%, 60%, and 100% of rated current. Two-Parameter Reference Line Figure 7 TRV Overview Page 6 Qual-Tech Engineers, Inc.

An example of a TRV that exceeds the TRV rating is illustrated in Figure 8. The TRV standard is illustrated by the dashed lines. An example of a TRV that is within the TRV rating is illustrated in Figure 9. 1gg> CPB3A- CP57A(Type 4) 1gg> CPB3A- CP57A(Type 4) t1ggx> REC1A(Type 4) 30000 t1gg> REC1A- RES1A(Type 4) 20000 10000 Voltage (V) 0-10000 -20000-30000 9.795 9.800 9.805 9.810 9.815 Time (ms) Example TRV That Exceeds The TRV Rating Figure 8 1ggs> CPB3A- CP57A(Type 4) 1ggs> CPB3A- CP57A(Type 4) t1ggsx> REC1A(Type 4) 30000 t1ggs> REC1A- RES1A(Type 4) 20000 10000 Voltage (V) 0-10000 -20000-30000 9.78 9.80 9.82 9.84 9.86 9.88 Time (ms) Example TRV That Is Within The TRV Rating Figure 9 TRV Overview Page 7 Qual-Tech Engineers, Inc.

The two-parameter reference line of Figure 7 has two key characteristics: the initial rateof-rise of the TRV and the peak of the TRV. The initial rate-of-rise is governed by the capacitance of the circuit between the circuit breaker and the reactance, which is limiting the fault current. Consequently, if the TRV duty is too severe, the rate-of-rise can be reduced by adding adequate capacitance from line to earth at that location. If the peak of the transient is too severe, the remedy for that is generally to use a circuit breaker with a higher voltage rating. Referring back to Section 3.0, the theoretical maximum peak value of the TRV for the conditions being evaluated here would be 1.5 x 2 x 2 x V LL / 3 = 2.45 x V LL where V LL is the system operating voltage. Qual-Tech Engineers, Inc. QT-628-0314 201 Johnson Road Building #1. Suite 203 Houston, PA 15342-1300 724-873-9275 FAX 724-873-8910 www.qualtecheng.com TRV Overview Page 8 Qual-Tech Engineers, Inc.