A Hybrid Parallel Active Filter / Off-Line UPS Unit for Computer Loads

Similar documents
Power Quality Analysis: A Study on Off-Line UPS Based System

Current Rebuilding Concept Applied to Boost CCM for PF Correction

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

CHAPTER 5 CONTROL SYSTEM DESIGN FOR UPFC

DSP-Based Simple Technique for Synchronization of 3 phase Alternators with Active and Reactive Power Load Sharing

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 01, 2016 ISSN (online):

MODERN switching power converters require many features

A Comparative Study between DPC and DPC-SVM Controllers Using dspace (DS1104)

Demonstration. Agenda

POWER FACTOR CORRECTION AND HARMONIC CURRENT REDUCTION IN DUAL FEEDBACK PWM CONTROLLED AC/DC DRIVES.

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

SHUNT ACTIVE POWER FILTER

IJESRT. Scientific Journal Impact Factor: (ISRA), Impact Factor: [Chakradhar et al., 3(6): June, 2014] ISSN:

Power Factor Correction of LED Drivers with Third Port Energy Storage

Lecture 6 ECEN 4517/5517

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

Power Factor Pre-regulator Using Constant Tolerance Band Control Scheme

Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

AT present three phase inverters find wide range

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

2020 P a g e. Figure.2: Line diagram of series active power filter.

P. Sivakumar* 1 and V. Rajasekaran 2

Improved Power Quality Bridgeless Isolated Cuk Converter Fed BLDC Motor Drive

Chapter 1: Introduction

HARMONIC contamination, due to the increment of nonlinear

Control of Grid Interactive Inverter Systems

CURRENT HARMONICS REDUCTION IN 3 PHASES 4 WIRE SYSTEM USING HYBRID FILTERS R.Saravanakumar 1#, S.Amritha 2#

CHAPTER 3 SINGLE SOURCE MULTILEVEL INVERTER

Power Factor Corrected Zeta Converter Based Switched Mode Power Supply

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

A Novel Single-Stage Push Pull Electronic Ballast With High Input Power Factor

INTERNATIONAL JOURNAL OF ENHANCED RESEARCH IN SCIENCE TECHNOLOGY & ENGINEERING VOL. 2 ISSUE 2, FEB ISSN NO:

A Novel Cascaded Multilevel Inverter Using A Single DC Source

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Power Quality improvement of a three phase four wire system using UPQC

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

SINGLE PHASE MULTI STRING FIVE LEVEL INVERTER FOR DISTRIBUTED ENERGY SOURCES

Control of Power Converters for Distributed Generation

R. W. Erickson. Department of Electrical, Computer, and Energy Engineering University of Colorado, Boulder

A Pv Fed Buck Boost Converter Combining Ky And Buck Converter With Feedback

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

PLL based method for control of grid connected inverter for unbalanced grid frequency

645 P a g e. the quantity of compensate current needed accordingly. Fig. 1. Active powers filter with load current detection.

Power Factor Corrected Single Stage AC-DC Full Bridge Resonant Converter

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

H-BRIDGE system used in high power dc dc conversion

Chapter 2 Shunt Active Power Filter

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

CHAPTER-IV EXPERIMENTAL AND SIMULATION PROGRAM

29 Level H- Bridge VSC for HVDC Application

International Journal of Emerging Researches in Engineering Science and Technology, Volume 1, Issue 2, December 14

Control of buck-boost chopper type AC voltage regulator

A Novel Power Factor Correction Rectifier for Enhancing Power Quality

Delhi Technological University (formerly DCE) Delhi-42, India

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Published by: PIONEER RESEARCH & DEVELOPMENT GROUP(

Improving Passive Filter Compensation Performance With Active Techniques

CHAPTER 5 MODIFIED SINUSOIDAL PULSE WIDTH MODULATION (SPWM) TECHNIQUE BASED CONTROLLER

SINGLE STAGE LOW FREQUENCY ELECTRONIC BALLAST FOR HID LAMPS

ISSN Vol.03,Issue.07, August-2015, Pages:

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

CHAPTER 2 DESIGN AND MODELING OF POSITIVE BUCK BOOST CONVERTER WITH CASCADED BUCK BOOST CONVERTER

Harmonic Filtering in Variable Speed Drives

International Journal of Advance Engineering and Research Development

ABSTRACT I. INTRODUCTION

DYNAMIC VOLTAGE RESTORER USING THREE PHASE AC-AC CONVERTER

Three-Phase Four-Wire Active Power Conditioners for Weak Grids

Lecture 19 - Single-phase square-wave inverter

RECENTLY, the harmonics current in a power grid can

Micro-controller Based Three-phase Voltage Source Inverter for Alternative Energy Source. Abstract

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

Study on Voltage Controller of Self-Excited Induction Generator Using Controlled Shunt Capacitor, SVC Magnetic Energy Recovery Switch

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

IMPLEMENTATION OF FM-ZCS-QUASI RESONANT CONVERTER FED DC SERVO DRIVE

A Comparative Modelling Study of PWM Control Techniques for Multilevel Cascaded Inverter

Sepic Topology Based High Step-Up Step down Soft Switching Bidirectional DC-DC Converter for Energy Storage Applications

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Design of a Wide Input Range DC-DC Converter Suitable for Lead-Acid Battery Charging

This is the published version of a paper presented at EPE 14-ECCE Europe. Citation for the original published paper:

A Three-Phase AC-AC Buck-Boost Converter using Impedance Network

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

THE CONVENTIONAL voltage source inverter (VSI)

Comparative Study of Pulse Width Modulated and Phase Controlled Rectifiers

Generation of Voltage Reference Signal in Closed-Loop Control of STATCOM

Levels of Inverter by Using Solar Array Generation System

Phase Shift Modulation of a Single Dc Source Cascaded H-Bridge Multilevel Inverter for Capacitor Voltage Regulation with Equal Power Distribution

A Modular Single-Phase Power-Factor-Correction Scheme With a Harmonic Filtering Function

Modelling of Five-Level Inverter for Renewable Power Source

Buck-boost converter as power factor correction controller for plug-in electric vehicles and battery charging application

SINGLE STAGE SINGLE SWITCH AC-DC STEP DOWN CONVERTER WITHOUT TRANSFORMER

Analysis of Solar PV Inverter based on PIC Microcontroller and Sinusoidal Pulse Width Modulation

Three phase six-switch PWM buck rectifier with power factor improvement

Transcription:

Electrical Power Quality and Utilisation, Journal Vol. XIV, No. 2, 2008 A Hybrid Parallel Active Filter / Off-Line UPS Unit for Computer Loads Tarak Ghennam, Mohamed Darwish Brunel University, UK Summary: A hybrid parallel active filter / off-line uninterruptible power supply (UPS) system is proposed. The hybrid system contains a single inverter which acts as a parallel active filter during the normal mode of operation (when the AC supply is available); and also supplies the load with energy from the UPS back-up battery during the back-up mode of operation (when the AC supply is not available or is beyond the preset tolerance). In both modes of operations the inverter is controlled in such way so that the line current is a pure sinusoid. This is to improve the input power factor and to eliminate the current harmonics in the first mode and to remove any stress on the back-up battery caused by the discharging during the second mode of operation. A full simulation results and an experimental setup is presented together with a closed loop control algorithm. Key words: active filters, UPS systems, computer power supplies, current harmonics 1. Introduction In little more than 15 years, electricity power quality has grown from obscurity to a major issue. Particularly, the increasing penetration of power electronics-based loads is creating a growing concern for harmonic distortion in the AC supply system [1]. For example the current in each phase in a large office building, where there are a several hundreds of computers, contains a significant level of third harmonic [2]. This causes a high current in the neutral conductor normally with balanced linear load the neutral conductor would have to carry almost zero current. There have been cases where the neutral conductor has got very hot causing fire! [3]. Consequently, power conditioning equipment is becoming more important not only for electric utilities but also for their customers. Majority of these power conditioning devices are placed at the point of the incoming supply where the level of current harmonics is significant, and it is the responsibility of the customers whether to use them or not [4]. However, there is more and more pressure nowadays on computer power supply manufacturers to integrate such power conditional devices within their computer power supplies. Equally important for computer loads nowadays is the availability of the power supply and this is the reason for the increase demand in UPS systems in offices, banks, etc... One of the most popular UPS systems in such applications is the off-line system [5]. In an off-line UPS, the critical load (computer) is normally powered from the mains supply, and a small mains-driven charger keeps the UPS s batteries topped-up. An on-line filter is used to reduces spikes and RFI in the supply before it is supplied to the load and, under these conditions, the inverter does nothing. When the quality of the mains supply falls below a certain level, the inverter starts-up virtually instantaneously and takes over the task of supplying the critical load from the battery. This paper presents a hybrid parallel active filter / offline UPS unit which can be integrated in computer power supply. A block diagram of such proposed system is shown in Figure 1. 2. The proposed configuration (active filter mode) The circuit topology of the proposed system is shown in Figure 2. It consists of non-linear load with a switching function u 1 (t) and an active filter which can be divided into an inverter with a switching function u 2 (t), a bidirectional buck boost converter and a battery set. In this mode of operation, the inverter acts as a parallel active filter. It inverts through the switching function u 2 (t) the dc battery voltage; hence it injects the appropriate current in the PCC to achieve a unity power factor. Furthermore it charges the capacitor to the desired value. Figure 3 shows a model of the circuit in this mode of operation. The following equations can be derived from Figure 3: dvdc c = iu f t 2 Fig. 1. Block diagram of a hybrid active filter / off-line UPS system (1) Fig. 2. A hybrid active filter / off-line UPS system topology Tarak Ghennam and Mohamed Darwish: A Hybrid Parallel Active Filter / Off-Line UPS Unit for Computer Loads. 41

s vcf = vs Ls Substituting from equation (2) into equation (4): di di f Lf = vcf vdcu t 2 dvcf cf = is if iu t 0 1 (2) (3) (4) Where pt load, pt : is the instantaneous power desired by the is the instantaneous harmonic power that will be compensated by the active filter and p c (t) is the instantaneous power demanded for charging the capacitor which can be given: ( 2 ) p 1 c = d C dc.v (13) dc 2 pc = C dc.v d dc ref ( Vdc) (14) Substituting from equation (1) into equation (5): Equation (6) shows that the switching function u 2 (t) has to be determined in order to obtain a sinusoidal. Single phase PQ theory [6] is used for current harmonics, reactive power compensation and capacitor voltage regulation. In this theory the supply voltage and the load current are sensed and used for harmonic current identification as follows: Where: v s (t) and i L (t) v (t) and i (t) s r i (5) (6) v t = v t + jv t (7) ' s i r v t = v t + jv t (8) i t = i t + ji t (9) L r i ' L i r i t = i t + ji t (10) are the instantaneous load voltage and the instantaneous load current respectively, are the instantaneous load voltage and the instantaneous load current that, are shifted by p/2 with v(t) and i(t) respectively. are the real parts of v(t) and i(t) v r (t) and i r (t) respectively. v i (t) and i i (t) are the imaginary part of v(t) and i(t) respectively. The instantaneous active and reactive power are given by the following expression: V dc ( s) c( s) = p V C s (15) dc ref The reference current contains the harmonic current, the reactive current, and the current required for charging the capacitor C dc. It can be expressed as follows: 2 2 v ( t) + v ( t) vr t.pt+ vr t.pc t vi t.qt i = F r dc (16) It can be seen from equation (16), that the compensator current can be divided into three components. Figure 4 shows the reference current computation method which based on single-phase PQ theory including the voltage regulation capacitor. Due to the safety problem with regard to maintaining high voltage at the battery terminals [7], a bidirectional DC/DC converter shown in Figure 5 is used. In this mode of operation the buck converter (consists of a switch S B, a diode D A and an inductor L dc ) steps down the high voltage across the capacitor c dc to the low battery voltage V bat = V dc /D B, where D B is the duty cycle of switch S B. 3. The proposed configuration (Off-line UPS system mode) When the AC line is beyond the present tolerance, the static switch S W1 in Figure 1 disconnects the load from the AC line. Hence the load is supplied by the battery set through i pt v t v t i t r i r qt = vi t vr t ii t (11) The instantaneous power is divided into three components: = + + pt pt pt p t c (12) Fig. 3. Modelling of the circuit in the active filter mode 42 Power Quality and Utilization, Journal Vol. XIV, No 2, 2008

Fig. 4. Bloc diagram of current reference identification method dv cf f = 0 1 (18) f i i.u t c di v v.u2( t) L f cf = cd + (19) f Fig. 5. A bidirectional buck-boost DC/DC converter the step up converter and the inverter [7], until the AC line is available again. Figure 6 shows the configuration of the circuit in this mode. In this mode of operation the boost converter, consists of a switch S A, a diode D B and an inductor L dc, steps up the low voltage from the battery V bat to the high capacitor voltage V dc = V bat /1 D A. where D A is the duty cycle of switch S A. Figure 7 illustrates the model of the circuit in this mode of operation. The battery voltage is inverted, through the inverter and the switching function u 2 (t), into v cf. This voltage is filtered by L f and c f and then subjected to the switching function u 1 (t) of the AC/DC rectifier. The inverter current from this model can be evaluated as follows: dvcd icd = cdc = i f.u2( t) (17) Substituting from equation (19) into equation (18): ( t) 2 f dv du2 di cd i f = i 0.u1( t) c f u2( t) c f.vcd + L f.c f (20) and substituting equation (17) into (20): 2 di f c f 2 du2 t L f c f + u2( t ) 1.i f c f.vcd i 0.u1( t) = c dc (21) It is denoted from equation (21), that the magnitude and the shape of the inverter current in this mode depend on: L f and c f parameters of LC output filter of the inverter. c dc the dc-link capacitor. u 1 (t) and u 2 (t) are the switching functions of the AC/DC rectifier and the inverter respectively. Fig. 6. Off-line UPS system topology Tarak Ghennam and Mohamed Darwish: A Hybrid Parallel Active Filter / Off-Line UPS Unit for Computer Loads. 43

Fig. 7. Modelling of the proposed circuit in the UPS mode Fig. 8. Block diagram of the used control techniques in off-line UPS mode: a) voltage regulation, b) current and voltage regulation Two control strategies have been applied: the first uses a single feedback loop and PI controller to regulate the output voltage through the inverter. The second uses two closed loops, an inner and an outer loop, therefore it regulates the output voltage and provides a pure sinusoidal line current which resulting in removing any stress on the buck up battery. The output voltage feed-back is compared with a sine wave reference signal using a PLL (phased locked loop). The error signal is compensated by a PI controller to produce the current reference signal, the sensed current through the inductor L f is compared with the reference signal, and the error signal is compared with triangular waveform after being compensated by the PI regulator. Hence the control signal is generated providing a constant switching frequency. The block diagrams of both control strategies are shown in Figures 8a and 8b. 4. Simulation results To verify the performance of the proposed hybrid active filter /off-line UPS system, the simulation of the whole system is carried out using MATLAB-SUMILINK package. The parameters used in the simulation are as follows: AC supply voltage = 240Vrms (50Hz) DC capacitor C 0 =500uF, load resistance R 0 =40 ohm DC-link capacitor C dc = 600uF AC-capacitor C f = 50uF, filter inductor L f =3.2mH buck boost inductor L dc = 0.8mH, battery bank voltage = 48 V. Figure 9d shows the uncompensated load current, Figure 9b illustrates the filter current (after 0.205 sec). The supply current is shown in Figure 9c before compensation (t<0.0205) and after compensation (t>0.205 sec). Figure 7d illustrates the zero phase shift between the supply voltage and the compensated current, which displays the non-real power generation ability of the active filter. Figure 10 illustrates the results in both modes of operation (active filter mode and off-line mode). In Figure 10a, a typical computer load current is shown in the active filter and in the off-line UPS modes. The filter current and the supply current are shown in Figures 10b and 10c. It is obvious from these Figs that the power failure took place between 0.5 sec < t < 0.6 sec. it is important to illustrate the battery current in this case (Fig. 8) for future reference (next paragraph). In order to reduce the stress on the buck up battery, the inverter in the off-line mode is controlled to maintain a sinusoidal inverter current waveform. This is achieved by using the control technique shown in Figure 8b. As it can be seen from comparing Figures 10d and 11d that the battery current has almost halved. 5. Hardware set-up implementation on the DSP micro-controller board The control algorithms in active filter mode and off-line UPS mode are implemented on a DSP micro-controller board (TMS 320 LF2407A) 44 Power Quality and Utilization, Journal Vol. XIV, No 2, 2008

Fig. 9. Current waveforms in active filter mode: a) load current, b) active filter current, c) supply current (after compensation), d) supply voltage and supply current (after compensation) Figure 12 shows the basic overall block diagram of the experimental set up in the laboratory. The input signals to the DSP micro-controller across its ADC interface are; the supply voltage v s, the load current i L, the inverter current i F, the dc-link voltage across the dc capacitor v dc, the sin waveform signal sin(wt), and the inverter output voltage v cf, after being sensed and conditioned. Using the six analogue input signals and one hardware interrupt, the real time control algorithm for the hybrid Tarak Ghennam and Mohamed Darwish: A Hybrid Parallel Active Filter / Off-Line UPS Unit for Computer Loads. 45

Fig. 10. Current waveforms of the hybrid active filter/off-line UPS system with regulation of the output voltage of the inverter in the off-line UPS mode: a) load current, b) active filter current, c) supply current, d) battery current APF/off-line UPS system generates the appropriate signals through the digital output port. The control signals are then applied to the IGBT s drivers of the APF/UPS achieving a unity power factor and providing uninterrupted reliable power supply. 46 Power Quality and Utilization, Journal Vol. XIV, No 2, 2008

Fig. 11. Current waveforms of the hybrid active filter/off-line UPS system with regulation of current and output voltage of the inverter in the off-line UPS mode: a) load current, b) active filter current, c) supply current, d) battery current 6. Conclusion In this paper, a proposed hybrid parallel active filter /offline UPS unit for computer loads is presented. Harmonic mitigation, reactive power compensation and battery charging are achieved in active filter mode of operation where the inverter acts as an active filter using the single phase PQ theory control strategy. Furthermore an uninterrupted Tarak Ghennam and Mohamed Darwish: A Hybrid Parallel Active Filter / Off-Line UPS Unit for Computer Loads. 47

Fig. 12. Hardware set-up imlementation on the DSP micro-controller boar and reliable power supply system is provided in the off-line UPS mode using feedback loop control to regulate the output voltage and to provide a pure sinusoidal line current. Overall results show the effectiveness and efficiency of the proposed system. References 1. E l - H a b r o u k M., D a r w i s h M. K, M e h t a P. : Active power filters A review. 2000. Proc. IEE Elect. Power Applicat., vol. 147, no. 5, pp. 403 413. 2. Power Quality Survey, BSRIA, report 14419/1, may 1999. 3. P e a r s o n C. C., U t h a y a n a n V. : The BSRIA power quality guide, application guide. AG2/2000, July 2000. 4. A n d o I., T a k a h a s h i I., T a n a k a Y., I k e h a r a M.: Development of high efficiency UPS having active filter ability composed of a three arms bridge. 1997. Industrial Electronics, Control and Instrumentation. IECON 97. 23rd International Conference. 5. B e k i a r o v S. B., E m a d i A.: Uninterruptible power supplies: classification, operation, dynamics and control. In proceeding of the 17 th IEEE Applied power electronics Conference, Dallas, TX, March 2002, pp. 597 604. 6. Ta r a f d a r H a q u e M. Single-phase PQ theory for active filter. TENCON 02. Proceedings. 2002 IEEE Region 10 Conference on Computers, Communications, Control and Power Engineering Volume 3, 28 31 Oct. 2002 Page(s):1941 1944 7. E m a d i A., N a s i r i A., B e k i a r o v S. B.: Uninterruptible power supplies and active filters. CRC PRESS 2005. Tarak Ghennam was born in Ain Kercha, Oum El-Bouaghi, Algeria in 1977. He received his Engineering degree and master degree in 2000 and 2005 respectively in Electrical Engineering from the Polytechnic Military School of Algiers (EMP), Algeria. He is currently working as a Research and Teaching Assistant with the electrical engineering department of the Military Polytechnic School of Algiers (EMP). His main research interests are active filters, power quality and renewable energy based power systems. Mohamed K. Darwish (IEE Member 89 CEng 90) was born in Alexandria, Egypt in 1955. He received the BSc degree in Electrical Engineering from Helwan University, Cairo, Egypt, and the PhD degree from Brunel University in 1978 and 1987 respectively. Dr Darwish is currently a Senior Lecturer in Power Electronics. His research interests include active filtering techniques, UPS systems and Power Quality issues. Dr. Darwish has published over 70 papers in leading journals and conferences. Address: Brunel University, School of Engineering and Design, Uxbridge, Middlesex, UB8 3PH, UK, e-mail: Mohamed.darwish@brunel.ac.uk 48 Power Quality and Utilization, Journal Vol. XIV, No 2, 2008