NIPSCO Energy Symposium

Similar documents
SECTION AUTOMATIC TRANSFER SWITCH

TOSHIBA International Corp

SUGGESTED SPECIFICATION for Series 300 Automatic Transfer Switches

Section 16621A - AUTOMATIC TRANSFER SWITCH. Part 1 General

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

Capstone Turbine Corporation Nordhoff Street Chatsworth CA USA Phone: (818) Fax: (818) Web:

Education & Training

Utility Interconnection and System Protection

The Connecticut Light and Power Company

Power Quality Symptoms What Is Normal? Power Quality Approach. Other Power Quality Solutions

Table 6.1 Fault Code List Code indication (Note 3)

MITSUBISHI ELECTRIC 2033A DDC SERIES SPECIFICATIONS

Generation Interconnection Requirements at Voltages 34.5 kv and Below

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

SECTION THREE-PHASE UNINTERRUPTIBLE POWER SYSTEM

GUIDE SPECIFICATIONS 40-80kVA, kVA and kVA Scalable Three-Phase Uninterruptible Power System 1.0 GENERAL

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Power-Sure 700. Technical Data TD158001EN. Contents

CROSS Chassis from 160 A to 450 A

Connection of Embedded Generating Plant up to 5MW

Guide and Requirements for Service. at 69,000 to 287,000 Volts R 0.2

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

Title: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards

Power Processor - Series 700F 10KVA to 150KVA

Wisconsin Contractors Institute Continuing Education

E N G I N E E R I N G M A N U A L

Industrial Electrician Level 3

System Protection and Control Subcommittee

Short Circuit Current Calculations

1C.6.1 Voltage Disturbances

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

TN, TT & IT Earthing Arrangements

Distribution/Substation Transformer

Modbus Register Map: InfraStruXure Symmetra 3-Phase Absolute Starting Register Number, (Decimal)

1. All electrical switches and outlets used shall be equal to Hubbell heavy duty, specification grade or equivalent quality.

The power to work. Power conditioning products. Harmonic correction unit Sag ride-through power conditioner

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

ULTRA-K Series 600K - he

Protecting Large Machines for Arcing Faults

120/240 Watt AC-DC Front End with PFC W Series Convert Select 120 Convert Select 240

Eliminating Power Transients When Switching Large Motors or Transformers during Power Outages or Engine Testing

Contents. 1 Introduction Assessment criteria Assessment Recommendations References... 8

NZ7. NZ7 Automatic Transfer Switching Equipment. 2. Type designation. 1. General. 3. Operation conditions N Z 7- /

Selective Coordination for Emergency and Legally-Required Standby Power Distribution Systems

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

SECTION POWER SYSTEMS STUDIES

UNDERSTANDING POWER QUALITY

ATC Controllers. High efficiency Comprehensive function The new generation VFD

Technical catalogue. Emax Low voltage air circuit-breakers. Hotline:

Introduction to Harmonics and Power Quality

NAME OF (VENDOR/MANUFACTURER) Clause No. Clause Description Comments, if any Remarks, if any

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

SECTION PANELBOARDS

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

Switching power supplies CP range, Linear power supplies CP-L range. Content

STATIC UNINTERRUPTIBLE POWER SYSTEM Revised 4/30/ Electrical Systems

Grounding Recommendations for On Site Power Systems

G8000MM Series IGBT. 100 to 750 KVA UPS UNINTERRUPTIBLE POWER SYSTEMS. 94% Efficiency. Input PF >0.98 DESIGN

SUGGESTED SPECIFICATION DUAL OPERATOR OPEN TRANSITION AUTOMATIC TRANSFER SWITCH WITH RPTCS MICROPROCESSOR CONTROL

Table of Contents. 1.0 Intent and Limitations Intent Limitations Contact Information General Requirements...

Power Protection and Conditioning

Liebert Datawave GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System

First Draft Language

Liebert Datawave. GUIDE SPECIFICATIONS kva Magnetic Synthesizer Power Conditioning System 1.0 GENERAL

SECTION 16496G CONTACTOR BASED AUTOMATIC TRANSFER SWITCHES LOW VOLTAGE

NERC Protection Coordination Webinar Series July 15, Jon Gardell

Design Approaches for Hospital Distribution Systems With Considerations for Future Expansion, Operator Safety, and Cost

Power systems Protection course

COPYRIGHTED MATERIAL. Index

There s Gold in Those Waveforms Richard P. Bingham, Dranetz-BMI

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Roadmap For Power Quality Standards Development

TECHNICAL DESCRIPTION TD-77A/3 170 KV COMPACT GAS INSULATED INTEGRATED SUBSTATION MODULES

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Please use the Q & A utility to ask us any questions concerning the material being presented.

PART 1 OWNER/APPLICANT INFORMATION

B. Manufacturers: Square-D, G.E. or Westinghosue.

E S C R I P T I V E B U L L E T I N .,.,.,. Bulletin DB-106. October, Square D Company Power System Studies ---1 I SQU ARED COMPANY --

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

Protective Relaying for DER

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

Power System Protection Manual

I WP Asset # I ~:2 3. I Review Annual. ~c~~ Date: 'l/j(j/! ZL>IJ,...

1. Institute of Electrical and Electronic Engineers (IEEE) a. Standard , IEEE Guide for Harmonic Content and Control.

UNINTERRUPTIBLE POWER SUPPLY SINGLE MODULE SYSTEM SPECIFICATIONS MODEL 9800AE

J7M-AM/-BM. Motor--protective circuit--breaker system. J7M -BM System IEC 947, EN IEC 947, EN 60947

3Ø Short-Circuit Calculations

Low Voltage Power Factor Correction Equipment Specifications Automatic, Automatic Detuned, Automatic Tuned

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

PREFACE ********************************************************** IT IS NOT INTENDED THAT THESE STANDARDS BE COPIED AND USED AS A SPECIFICATION!

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

T-68 Protecting Your Equipment through Power Quality Solutions

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Transcription:

Backup Power Automatic Transfer NIPSCO Energy Symposium symposium Backup Power Applications/Considerations Backup Power Types Automatic Transfer Switch Basics Presenters McGill Power - Jeremy Irmeger Eaton - Barry Graves 2007 Eaton Corporation. All rights reserved.

Objective & Agenda Bypass Isolation Magnum Front Access Objective Understanding the basics of how to identify and properly apply UPS s Uninterruptible Power Supplies) and ATS (Automatic Transfer Switches) for accommoding for seamless systems. Agenda What is a UPS UPS Types What is a Automatic Transfer Switch Transfer Switch Types Transfer Switch Application Categories Transition Types Basic Components of a Transfer Switch Application Considerations Questions

The 9 Common Power Problems Interruption Sag Swell Undervoltage Overvoltage Line Noise Frequency Variation Switching Transients Harmonic Distortion

3 (+1) Basic Types of UPS Standby Off Line Normal Operation Power Failure Event Powerware Series 3 The Series 3 (Stand-By) UPS delivers power protection from 3 of the most common power problems that threaten your equipment and data Interruption Sag Swell Line Interactive Buck/Boost Powerware Series 5 The Series 5 (Line-Interactive) UPS delivers power protection from 5 of the most common power problems that threaten your equipment and data Undervoltage Overvoltage Ferroresonant +1 Powerware Series Ferro The Series Ferro UPS delivers galvanic isolated power protection from 8 of the most common power problems that threaten equipment and data Harmonic distortion Line noise Switching transients On Line Double Conversion ( Powerware Series 9 The Series 9 (On-Line) UPS delivers power protection from all 9 of the most common power problems that threaten your equipment and data Frequency variation

What is a UPS System? Maintenance Bypass Panel System Input N.O. System Output To PDU AC DC AC UPS Power Module 1. Double Conversion 2. Online System Battery Cabinet

How Much Downtime is Acceptable? Power Availability Equivalent Power Disruptions (yr) 99.9999999% ISPs, e-business, Communications, Electronics mfg. N+ Redundancy < 3 seconds 99.999% Food Processing Server Operating Systems Generators and Some UPS 5.3 minutes 99.99% 99.9% Hospitals, Airports Generator Only Residential Homes Typical Grid Power 0.88 hours 8.8 hours

Automatic Transfer Switch A device which transfers electrical loads between two sources of power by using either manual or automatic controls. UTILITY LOAD GENERATOR UTILITY UTILITY

Bypass Isolation Transfer Switch An automatic transfer switch with an additional bypass isolation switch Provides ability to perform maintenance of the main transfer switch power device, without interruption of power to the load Applied in high reliability applications: Provides emergency power to life safety and other critical loads

Transfer Switch Types There are only two ways to transfer power: Automatic If loads are very critical, an automatic transfer switch would probably be used insure the fastest possible transfer. Non-Automatic (manual, or electrically operated) If loads are not quite as critical, but still cannot go for any extended period of time without power, a Non-Automatic or manual transfer switch could be used.

Non-automatic vs Manual Transfer Electrically operated non-automatic transfer switches. The switch electrically transfers power when a pushbutton, usually mounted on the switch s enclosure, is pushed. If necessary, the switch can also be manually operated. Manually initiated, Electrically operated Manually operated transfer switches provide all the mechanics to effect the transfer from source to source. The actual transfer of power, however, is by true hand operation of the transfer switch. Manually initiated, Manually operated

Application Category NFPA 70 National Electric Code NFPA 70 - National Electric Code Article 700 - Emergency Systems Article 701 - Legally Required Standby Systems Article 702 - Optional Standby Systems Article 708 - COPS Article 517 - Health Care Facilities NFPA 99 - Health Care Facilities NFPA 110 - Emergency & Standby Systems NFPA 20 - Fire Pumps NFPA 70E Workplace Safety

Article 700 Emergency Systems Article 701 Legally Required Article 702 Optional Systems Article 708 COPS Application examples include any system where a power interruption would create life safety or health hazards. Must automatically transfer in 10 seconds Shall be listed for emergency use (UL 1008 only). Shall supply only emergency loads. Application examples include any system where a power interruption would create hazards or hamper rescue or fire fighting operations. Must automatically transfer in 60 seconds Shall be listed for emergency use (UL 1008 only). Application examples include any system where a power interruption would cause discomfort or disrupt a process. Automatic/manual transfer. No transfer time requirement. Allows for option as such as: Go to neutral position Auto/Manual Selector switch Application examples include emergency call centers ATS labeled for use on emergency systems. No requirement for transfer time. Transfer equipment separate from other emergency, legally required, or optional loads. Must include provisions for roll-up generator if using one generator.

Transfer Switch Transition Types 2007 Eaton Corporation. All rights reserved.

Open Transition Also called a break-before-make switch. One set of contacts opens before the other set closes There is a definite break in power as the load is taken off one source and connected to another. This is the most common and least expensive Normal Loads TS N TS E Emergency

Delayed Transition Break Both Sides Delayed Transition One set of contacts opens before the other The other set of contacts delays in closing Load is disconnected from power during all transfers Normal Loads TS N TS E Emergency

Delayed Transition Time delay neutral Requires a 3 position mechanism Timed delay in the neutral position, typically 0-120sec 3 sec is typically a good starting point Load Voltage Decay Senses back emf voltage Will pause in neutral position until regenerative voltages are at 10-30% On Eaton transfer switches option 32 cannot be reprogrammed in the field. A new controller must be purchased. 32a 32b

Closed Transition Normal Loads TS N TS E Emergency 100 m/secs overlap-time

Closed Transition Closed Transition is also called a make-before-break switch. There is no interruption in power to a critical load when using this type of switch. Both power sources are connected to the load before the break occurs. Parallels the loads for < 100ms The two power sources have to have the same voltage and frequency and be synchronized for the switch to transfer. Permits the periodic testing of an emergency source, such as a generator, without interrupting power to the loads

Consideration for selecting Transition Types When transferring two live sources, abnormal motor inrush current can occur leading to possible damage of motor windings, insulation, couplings and in some cases, the load itself. Inrush currents are caused by the motor s residual voltage being out of phase with the voltage source to which it s being transferred. Methods of control are: Open Inphase transfer Motor load disconnect control circuit Delayed transition - Time Delay Neutral, Load Voltage Decay Closed transition less than 100 ms paralleling of sources

Open In-phase Transfer 32f Feature that allows a live transfer between two sources only when the phase difference between the two is near to zero. This feature prevents in-rush currents from exceeding normal starting currents in the case where motor loads are being transferred How it works: Monitor samples the relative phase angle between the two sources being transferred When the two sources are within the desired phase angle different and are approaching zero phase angle difference, the inphase monitor signals the transfer switch to operate. The operating time of the transfer switch is key in utilizing an inphase monitor (must transfer in less than ten cycles) In-phase monitor and VFD s do not work well together, use TDN. In-phase doesn t give the VFD s time to reset.

Motor Load Disconnect Control Circuit 45 Selected motor loads are de-energized during transfer operation Controller signals contact to open approx. 3 seconds prior to transfer, thus de-energizing selected loads. Loads are turned onto the generator after a designated time delay. Loads can be turned on at one time or sequentially so as to not block load the generator. Motor load disconnect works well when the generator is sized at the min.

Automatic Transfer Switches - Main Components 2007 Eaton Corporation. All rights reserved.

Transfer Switch Main Components An automatic transfer switch (ATS) is made up of several main components Controller Continually monitors the condition of the power sources Initiates start command to backup generator, Initiates transfer and retransfer to good power source Power switching device Power device rated to transfer the load to/from the power sources Control Power Transformer panel Supplies operational power to the switching device/controller

Main Components - Controller In an ATS, the controller is basically the brains of the ATS, that contains all the logic/intelligence to initiate the switching. The controller performs following functions: Senses the source voltage and frequency Sends a start command to the back up power if the main source is lost. Commercial ATC-300+ Controller

Main Components Switching Device The switching device is the main power device that transfers the load from one power source to another. The switching device includes the main power device and the transfer mechanism. The ATS controller tells the switching device when to make the transfer/retransfer to a good source Two basic types of switching devices: Contactor Specifically designed contactors to perform load transfer between to AC sources. Transfer switches do not use motor starting/lighting type contactors. Molded Case/Power Case Switch A molded case or power case circuit breaker without and /or with a trip unit. Used when a circuit requires a compact, high capacity disconnect device.

Main Components Contactor Switching Device Contactor based The contactor switching device includes the main power assembly and the operating mechanism. The power assembly is composed of the individual power poles. The operating mechanism includes the solenoid and the mechanical interlock. Power Assembly 3 Pole Contactor Source 2 Bus Moving Contact Source 1 Bus Load Bus Operating Mechanism Single Power Pole

Main Components Molded Case or Power Case Circuit Breaker Switching Device Molded Case or Power Case Circuit Breaker Based The molded case/power case circuit breaker switching device is a circuit breaker without and/or with the overcurrent trip. The switching device is composed of two separate power devices. One device is for closing on source 1 and the other for closing on source 2. The operating mechanism includes the motor operator. 3 Pole Molded Case Switch Power Assembly 3 Pole Power Case Switch Power Assembly Motor Operating Mechanism Source 1 Device Source 2 Device Motor Operator in Power Case Switch

Main Components Transformer Panel Control Power Provided by small Control Power Transformers CPT- connected to the normal and the emergency source. The good source then provides the control power needed for the ATS to properly operate. Provided with a multi tap primary allowing the CPT to be used on different voltage applications permitting a simple field change from one voltage to another.

Basic Information for ATS Selection When selecting a Transfer Switch, review the following: Types of load to be transferred Transition type Open In phase, Delayed, Closed Transition Application Type Life Safety, Emergency, Optional Switch Ratings Voltage rating, Phase, # poles Continuous Current rating/amps Overload and fault current withstand ratings Configuration Type Service Entrance Bypass Isolation

UPS and ATS Basics Questions?