Effects of GIC on Power Transformers and Power Systems

Similar documents
G. KOBET, I. GRANT, G. GOZA Tennessee Valley Authority USA. R. GIRGIS, M. ESPINDOLA ABB Corporation USA SUMMARY

2013 Grid of the Future Symposium. Effect of GIC and GIC Capability of EHV Power Transformers A Case Study on an AEP 765 kv Power Transformer Design

IEEE PES/IAS Joint Chapter July Technical Presentation Meeting Basics of solar phenomena & How transformers react and handle events

A Process for Evaluating the Degree of Susceptibility of a fleet of Power Transformers to Effects of GIC

Evaluating Transformer Heating due to Geomagnetic Disturbances

Transformer Thermal Impact Assessment White Paper Project (Geomagnetic Disturbance Mitigation)

Disturbances. Their Impact on the Power Grid. By the IEEE Power & Energy Society Technical Council Task Force on

Transformer Thermal Impact Assessment White Paper (Draft) Project (Geomagnetic Disturbance Mitigation)

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Transformer Thermal Impact Assessment White Paper TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Vulnerability Assessment and Planning

TPL is a new Reliability Standard to specifically address the Stage 2 directives in Order No. 779.

Transformer Technology Seminar GIC Capability of Power Transformers

Dietrich Bonmann, ABB AG Bad Honnef, March 15, Impact of GIC on transformers and the transmission network

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

Screening Criterion for Transformer Thermal Impact Assessment Summary Justification Figure 1 Figure 1

DIRECT CURRENT COMPENSATION FIELD EXPERIENCE UNDER SERVICE CONDITIONS

See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in RM15-11 on June 28,

See Benchmark Geomagnetic Disturbance Event Description white paper, May 12, Filed by NERC in Docket No. RM15 11 on June 28, 2016.

FINNISH EXPERIENCES ON GRID EFFECTS OF GIC'S

Case Study Effects of Geomagnetically Induced Current (GIC) Neutral Blocking Device

High-Level Harmonic Distortion During Geomagnetic Disturbances - a Hidden Threat to Grid Security

Power System Impacts of Geomagnetic Disturbances

SolidGround TM grid stability and harmonics mitigation system Geomagnetic Storm Induced Current (GIC) and Electromagnetic Pulse (EMP) protection

Geomagnetic Disturbances. IEEE PES Chicago Chapter Technical Presentation March 12, Alan Engelmann Transmission Planning ComEd.

Hydro One GMD Preparedness Plan for Cycle 24

Modeling and Evaluation of Geomagnetic Storms in the Electric Power System

The Engineering Problem. Calculating GIC Flow through the EHV System

GMD Impacts on Generators

Comprehensive Study on Magnetization Current Harmonics of Power Transformers due to GICs

GIC Neutral Blocking System Prototype to Production

ANALYSIS OF THE MITIGATION METHODS OF GEOMAGNETICALLY INDUCED CURRENT

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Impact of Solar Storms on the Swiss Transmission Network

Solving old problems with new technology: How to monitor and measure GIC and OPD currents

Interfacing Power System Simulators with Geomagnetically Induced Currents (GIC) Simulation Programs. Luis Marti Hydro One, Canada

TPL Project Geomagnetic Disturbance Mitigation. Technical Conference May 20, 2014

Geo-Magnetic Disturbance Analysis of HV and EHV Grids

MHD-EMP (E3) Assessment of the US Power Grid GIC and Transformer Thermal Assessment

STRAY FLUX AND ITS INFLUENCE ON PROTECTION RELAYS

Problems connected with Commissioning of Power Transformers

Low-Frequency Protection Concepts for the Electric Power Grid: Geomagnetically Induced Current (GIC) and E3 HEMP Mitigation

GIC Distribution. Carlos David Fernández Barroso. Division of Industrial Electrical Engineering and Automation Faculty of Engineering, Lund University

Space Weather Impact on the Scandinavian Interconnected Power Transmission System

TPL Project Geomagnetic Disturbance Mitigation. Technical Conference July 17, 2014

Model, Monitor & Mitigate Geomagnetically Induced Currents

A Novel Method to Analyse the Effects of Geomagnetic Induced Current on Transformer

GMD Voltage Collapse Study

Tertiary Winding Design in wye-wye Connected Transformers Restricted Siemens Energy 2013 All rights reserved.

GIC Analysis using PSS E. K.V. PATIL Siemens Power Technologies International Schenectady, New York, USA

DISTURBANCES IN THE SOUTHERN AFRICAN POWER NETWORK DUE TO GEOMAGNETICALLY INDUCED CURRENTS

Operational Experiences of an HV Transformer Neutral Blocking Device

concerning the risks to the electric power grid from geomagnetic storms,

Silent Transformers to Help Consolidated Edison Meet New York City s Ultrastrict Noise Ordinances

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks

Geomagnetic Disturbance Planning Guide

Comparative Study of Various Filtering Techniques to Reduce Harmonics in HVDC Converter Transfomer Due to GIC

Long lasting transients in power filter circuits

Generator Advanced Concepts

Consolidated Edison s Experience with On-line Monitoring and Mitigation of Geomagnetic Disturbances

CHAPTER 2 ELECTROMAGNETIC FORCE AND DEFORMATION

Voltage and Current Waveforms Enhancement using Harmonic Filters

Investigation of Geomagnetic Induced Current Effects on Power Transformer

Mitigation of an Inrush Current of Power Transformer by using PWM-Inverter based Series Voltage Compensator

Emicon Engineering Consultants L.L.C.

Effects of Harmonic Distortion I

CERN - ST Division THE NEW 150 MVAR, 18 KV STATIC VAR COMPENSATOR FOR SPS: BACKGROUND, DESIGN AND COMMISSIONING

2012 Grid of the Future Symposium. Geomagnetic Disturbance Impacts and AEP GIC/Harmonics Monitoring System

ISSUES OF SYSTEM AND CONTROL INTERACTIONS IN ELECTRIC POWER SYSTEMS

Demagnetization of Power Transformers Following a DC Resistance Testing

CHAPTER 4 POWER QUALITY AND VAR COMPENSATION IN DISTRIBUTION SYSTEMS

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

System Protection and Control Subcommittee

22.0 Harmonics in Industrial Power Systems

North Europe power transmission system vulnerability during extreme space weather

Detecting and Managing Geomagnetically Induced Currents With Relays

POWER TRANSFORMERS: Saturation Compensation Modeling, Simulation, and Experiments

Loss prophet. Predicting stray losses in power transformers and optimization of tank shielding using FEM

Unofficial Comment Form Project Geomagnetic Disturbance Mitigation

Tuningintobetter power quality

Application of SVCs to Satisfy Reactive Power Needs of Power Systems

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

TPL Transmission System Planned Performance for Geomagnetic Disturbance Events

Course ELEC Introduction to electric power and energy systems. Additional exercises with answers December reactive power compensation

PRACTICAL CONSIDERATIONS FOR CONTROLLED SWITCHING OF POWER TRANSFORMERS

The power transformer

Power Quality Improvement in Distribution System Using D-STATCOM

Making VSC-HVDC Control Robust to Geomagnetically Induced Current

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Impact of transformer saturation from GIC on power system voltage regulation

Integration of Geomagnetic Disturbance Modeling into the Power Flow: A Methodology for Large-Scale System Studies

System Protection and Control Subcommittee

Power Quality Solutions

Transformer Protection Principles

Effect of Geomagnetically Induced Currents on Protection Systems

Pinhook 500kV Transformer Neutral CT Saturation

POWER TRANSFORMER SPECIFICATION, DESIGN, QUALITY CONTROL AND TESTING 18 MARCH 2009

Transcription:

Effects of GIC on Power Transformers and Power Systems Prepared by Dr. Ramsis Girgis and Kiran Vedante (USA) in the name of CIGRE SC A2 Background There has been some misconception in the electric power industry that Geo magnetically Induced Currents (GIC) have caused, and would cause, significant overheating damage to the majority of power transformers installed around the World and consequent system blackouts of a large scale [1]. The purpose of this paper is to present to the power industry the true effect of GIC on power transformers and the power system and its components. Phenomenon of Part Cycle, Core semi saturation under effect of DC When a power transformer is subjected to DC, unidirectional DC flux results in the core. The magnitude of this flux depends mainly on magnitude of the DC current, number of turns in the windings carrying the current, and reluctance of the DC flux path. The result is that the DC flux adds to the AC flux in one half cycle. When large enough, this leads to core peak flux densities in the range of core pre saturation. For higher magnitudes of DC, the core provides a much higher reluctance to the DC Ampere Turns; resulting in a smaller further increase in the DC flux density shift. Correspondingly, the magnetizing current becomes a high peak of short duration pulse, Figure 1. The duration of this pulse is in the range of only 1/6 th to 1/1 th of the cycle. Because of the nature of its magnetic circuit, the DC flux density shift in a 3 phase, 3 limb core form transformers would be the lowest of all core types. AC + DC AC B Time I AC AC + DC Time Figure 1: Part Cycle, Semi Saturation of Transformer cores when subjected to DC Magnitudes and harmonic content of the magnetizing current pulse The high peak magnetizing current pulse, seen in red above, increases the reactive power absorbed by the transformer. Hence, the power network sees a large increase in VAR demand for the duration of the GIC. Figure 2 depicts the relationship between the Transformer VAR demand and the GIC for a large power transformer. This increase in VAR demand is one of the major concerns during Geo magnetic disturbances (GMD). If VAR resources are exhausted during a GMD event, voltage collapse can occur. Therefore, accurate estimation of the VAR consumption of the transformer during a GMD event is critical for proper mitigation of effects of GIC on power system stability. 1

5 45 4 35 % MVA Rating 3 25 2 15 1 5 5 1 15 2 25 3 35 4 GIC, Amps/Phase Figure 2: Calculated reactive power drawn by a large Transformer subjected to GIC The magnetizing current pulse additionally injects significant even and odd harmonics into the power system as presented in figure 3 below. The figure shows that the short duration nature of the magnetizing current pulse results in an almost uniform magnitude of low and high order harmonics. These harmonics can have a significant impact on the power system. Shunt capacitor banks used for VAR support become low impedance paths for harmonic currents, and can lead to tripping of the bank by relay protection schemes. Harmonic filters for SVCs banks create parallel resonances which can exacerbate voltage distortion issues and result in tripping of the protection devices. Harmonics can also cause the unintended operation of relays. Harmonic Amplitude, % of Rated Current 6% 5% 4% 3% 2% 1% Hamonic Spectrum of Magnetizing Current with same DC Current/Phase 1-Phase, 3 Limb 3-Phase, 3 Limb % 6 12 18 24 3 36 42 48 54 6 66 Harmonic Frequency, Hertz Figure 3: Harmonics of magnetizing current of transformers subjected to 3A/phase GIC 2

Increase of hot spot temperatures in transformers when subjected to GIC The high peak magnetizing current pulse produces correspondingly higher magnitudes of leakage flux that is also rich in harmonics; resulting in much higher eddy and circulating current losses in the transformer windings and the structural parts; increasing their temperatures. Figure 4, below, presents calculated hot spot temperature of flitch plates of a 1 phase large power transformer subjected to different levels of DC current. As the figure shows, the hot spot temperature reached close to its final value within 1 minutes from the application of the DC as determined by the time constant of the structural parts. 16 Flitch-Plate Temperature vs Time 14 Flitch-Plate Tempt, Degree C 12 1 8 6 4 Idc = 2 Amps Idc = 3 Amps Idc = 5 Amps 2 2 4 6 8 1 12 Time, Minutes Figure 4: Calculated Flitch Plate hot spot temperature for three values of DC However, in order to determine the true thermal effects of GIC on transformers, one needs to consider the nature of the GIC profile; namely its magnitudes and duration. Figure 5, below, presents measured GIC at the neutral of a 3 phase transformer in a generating station during a recent GMD event. As demonstrated in figure 5, below, GIC current is characterized by a large number of consecutive narrow pulses of low medium levels over a period of hours and occasional high peaks of short duration pulses. 5 4 3 2 GIC, Amps 1-1 -2-3 -4 Figure 5: Measured GIC at a GSU transformer; during a 7 hours period 3

Due to the short duration of these high peaks of GIC pulses and the fact that the duration of the resulting magnetizing current pulse is only a small fraction of a cycle, the actual duration of the resulting core part cycle, semi saturation and associated high peak pulses of the core magnetizing current is only a few seconds. Hence, temperature rises in the transformer windings and structural parts due to GIC would be expected to be much lower than that estimated based on continuous duration DC. In order to illustrate the above, the winding hot spot temperature was calculated for a fully loaded large 1 phase power transformer when subjected to an assumed GIC current profile that has a base level of 2 Amps / phase; and two 2 minute duration high peak pulses of 4 Amps / phase. The resulting calculated winding hot spot temperatures are shown in Figure 6 below. 16 Winding Hot Spot Temperature vs Time 14 Winding Hot Spot Tempt, Degree C 12 1 8 6 4 2 1 2 3 4 5 6 7 8 Time, Minutes Figure 6: Calculated Winding Hot Spot Temperature due to GIC profile described above The figure demonstrates that the increase in the hot spot temperature is limited by the duration of the GIC pulse, and drops to the original temperature after the pulse is over. The winding temperature reached (146ºC) in this case of an extremely high peak of GIC would be much lower when the transformer is not fully loaded and ambient temperature is lower than 3 C. The same is true for structural parts, except that the temperature rise will be governed by the higher time constant of the structural parts. Also, such hot spot temperatures for such a short duration would not cause any appreciable damage of the windings, structural parts, or loss of insulation life of the transformer. Industry Standards for overload (IEEE and IEC) allow much higher hot spot temperature levels for much longer times under emergency loading conditions (16 2 C). Actual measurements of thermal effects of GIC on power Transformers Two experiments were performed by Hydro Quebec and Fingrid [2, 3]; where large in-service single phase and three phase power transformers were injected at no load with high levels of DC. Temperature rises were measured in the windings and structural parts of the transformers. When compared to limits established by Industry Standards, winding temperature rises were 4

low and temperature rises in the structural parts were moderate. Both reports concluded that at GIC levels injected no transformer damage would occur. Transformers reported as having failed or suffered overheating damage due to GIC Reference [1] reports several of those cases. One of these is a Shell form transformer that experienced significant overheating of the LV leads during the March 13, 1989 K9 GIC event. Same design transformers at the same general location experienced similar but less overheating. These were old transformers that had an old winding lead design that made it susceptible to high circulating currents when the leakage flux pattern changed as the core experienced saturation [4]. Another case reported in Reference [1] is a Shell form Transformer that had tank wall heating during the same GMD event. The construction of these transformers is such that wood slabs are placed between the core and tank walls. With core saturation, part of the core and leakage flux travels to the tank wall causing localized eddy losses in the tank. Being blanketed by the wood slabs, these regions of the tank overheated. It was also reported in Reference [1] that within 2 years of the 1989 GMD event, 11 nuclear plants experienced failures of several GSUs. During that period, a number of these failures were studied and found to be caused by back feed mode operation. Significant winding overheating was also reported to have occurred in a few large core form power transformers in S. Africa between 23 and 24 [5]. These incidents were found to coincide with winding overheating caused by the phenomenon of the conducting Copper Sulphide forming and causing winding failures of transformers World wide. It is believed that the increase in the winding temperature, caused by GIC, could have accelerated the formation of Copper Sulphide in the windings of these transformers [5, 6]. It was also reported by HQ in reference [7] that two transformers were subjected to external faults during the GIC event and are believed to have been caused by over voltages due to System instability. Finally, 4 kv large power transformers in southern Sweden were reported to have been subjected to as much as 33 Amps in the October 23 GMD event. No transformer damage was reported. Instead, a black out occurred; caused by tripping of a 13 kv line resulting from operation of a relay that reacted to a 3 rd harmonic current [8]. Conclusions The paper demonstrates that, because of the short duration nature of the high GIC current peaks, the great majority of power transformers would not experience damaging overheating due to even high levels of GIC. Only transformers with certain design features could suffer some winding damage due to high winding circulating currents when exposed to high levels of GIC. Also, the paper presents the real issue with GIC; namely, its effects on the power system and its components. The large peak magnetizing current pulses caused by core semi saturation represents a large increase in VAR demand and can, if not planned for, result in voltage collapse. Additionally, the magnetizing current pulse injects significant harmonics into the power system; which can have a significant impact on shunt capacitor banks, SVCs, and relays, and could compromise the stability of the grid. 5

References [1] J. Kappenman, Geomagnetic Storms and Their Impacts on the U.S. Power Grid, Report # Meta-R-319, Oak Ridge National Laboratory. [2] P. Picher, L. Bolduc et al, Study of the acceptable DC current limit in core-form Power Transformers, IEEE Transactions on Power Delivery, Vol. 12, No. 1, January 1997, Page 257-265. [3] Matti Lahtinen & Jarmo Elovaara, GIC Occurrences and GIC Test for 4 kv System Transformer, IEEE Transactions on Power Delivery, Vol. 17, No. 2, April 22, Page 555-561. [4] Ramsis Girgis & Chung-Duck KO, Calculation Techniques And Results Of Effects Of GIC Currents as Applied to Two Large Power Transformers, IEEE Transactions on Power Delivery, Vol. 7, No. 2, April 1992, Page 699-75. [5] C. T Gaunt, G. Coetzee, Transformer failures in regions incorrectly considered to have low GICrisk, IEEE Power Tech Proceedings, 27, Lausanne, Switzerland, pp. 87 812. [6] R. Girgis, K. Vedante, and K. Gramm: Effects of GIC on Power Transformers and Power Systems, CIGRE paper # A2-34, August 212. [7] Jean Beland, Kevin Small, Space Weather Effects on Power Transmission Systems: The Cases of Hydro-Quebec and Trans power New Zealand Ltd, Proceedings of the NATO Advanced Research Workshop on Effects of Space Weather on Technology Infrastructure, NATO Science Series, Vol. 176, 24 [8] M. Wik et al, Space weather events in July 1982 and October 23, and the effects of geo magnetically induced currents on Swedish technical systems, Annales Geophysicae, 27, 1775-1787, 29. 6