Ferroresonance Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers

Similar documents
Spectral analysis of voltages and currents during different modes of ferroresonance in switchgear

Characteristic analysis of low voltage arcing current considering short circuit impedance

TECHNICAL BULLETIN 004a Ferroresonance

FERRORESONANCE SIMULATION STUDIES USING EMTP

Ferroresonance Experience in UK: Simulations and Measurements

Improving Current and Voltage Transformers Accuracy Using Artificial Neural Network

Power Quality Monitoring of a Power System using Wavelet Transform

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Wavelet Transform for Classification of Voltage Sag Causes using Probabilistic Neural Network

ANALYSIS OF VOLTAGE TRANSIENTS IN A MEDIUM VOLTAGE SYSTEM

Long lasting transients in power filter circuits

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Electrical Power and Energy Systems

[Nayak, 3(2): February, 2014] ISSN: Impact Factor: 1.852

Research Article Resistive Ferroresonance Limiter for Potential Transformers

Chapter 5. Signal Analysis. 5.1 Denoising fiber optic sensor signal

Ferroresonance in MV Voltage Transformers: Pragmatic experimental approach towards investigation of risk and mitigating strategy

EFFECT OF CORE CUTTING TOPOLOGY AND MATERIAL OF THREE PHASE TRANSFORMER ON MAGNETIZATION CURVE AND INRUSH CURRENT: EXPERIMENTAL APPROACH

DEVELOPMENT OF NUMERICAL ALGORITHMS FOR FERRORESONANCE MONITORING

Fault Location Technique for UHV Lines Using Wavelet Transform

Accurate Current Measurement Transducer for Relaying Purpose

Keywords: Wavelet packet transform (WPT), Differential Protection, Inrush current, CT saturation.

Wavelet Transform Based Islanding Characterization Method for Distributed Generation

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

Detection of Fault in Fixed Series Compensated Transmission Line during Power Swing Using Wavelet Transform

Detection, localization, and classification of power quality disturbances using discrete wavelet transform technique

Multi-Resolution Wavelet Analysis for Chopped Impulse Voltage Measurements

Neutral Reactor Optimization in order to Reduce Arc Extinction Time during Three-Phase Tripping

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Comparative Performance of Conventional Transducers & Rogowski Coil for Relaying Purpose

FGJTCFWP"KPUVKVWVG"QH"VGEJPQNQI[" FGRCTVOGPV"QH"GNGEVTKECN"GPIKPGGTKPI" VGG"246"JKIJ"XQNVCIG"GPIKPGGTKPI

Ferroresonance Conditions Associated With a 13 kv Voltage Regulator During Back-feed Conditions

Keywords: Power System Computer Aided Design, Discrete Wavelet Transform, Artificial Neural Network, Multi- Resolution Analysis.

IDENTIFYING TYPES OF SIMULTANEOUS FAULT IN TRANSMISSION LINE USING DISCRETE WAVELET TRANSFORM AND FUZZY LOGIC ALGORITHM

Simulation Analysis of Ferromagnetic Resonance of Low Magnetic Flux Density-Type PT under Single-Phase Earth Fault of 10kV Power Grid

Power Quality Disturbaces Clasification And Automatic Detection Using Wavelet And ANN Techniques

Selection of Mother Wavelet for Processing of Power Quality Disturbance Signals using Energy for Wavelet Packet Decomposition

Literature Review for Shunt Active Power Filters

Application of Wavelet Transform in Power System Analysis and Protection

Simulation and Analysis of Ferroresonance in Power System

DEPARTMENT OF EEE QUESTION BANK

Comparison of Wavelet Transform and Fourier Transform based methods of Phasor Estimation for Numerical Relaying

Short Circuit Detection in Stator Winding Of Three Phase Induction Motor Using Wavelet Transform and Quadratic Discriminant Analysis

POWER QUALITY A N D Y O U R B U S I N E S S THE CENTRE FOR ENERGY ADVANCEMENT THROUGH TECHNOLOGICAL I NNOVATION

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Do Capacitor Switching Transients Still Cause Problems?

Sound pressure level calculation methodology investigation of corona noise in AC substations

CLASSIFICATION OF POWER QUALITY DISTURBANCES USING WAVELET TRANSFORM AND S-TRANSFORM BASED ARTIFICIAL NEURAL NETWORK

Dwt-Ann Approach to Classify Power Quality Disturbances

Analysis of Power Quality Disturbances using DWT and Artificial Neural Networks

Ironing out resonance

DWT ANALYSIS OF SELECTED TRANSIENT AND NOTCHING DISTURBANCES

Harmonic Analysis of Power System Waveforms Based on Chaari Complex Mother Wavelet

Power System Failure Analysis by Using The Discrete Wavelet Transform

Distribution System Faults Classification And Location Based On Wavelet Transform

I. INTRODUCTION IJSRST Volume 3 Issue 2 Print ISSN: Online ISSN: X

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

Keywords: Transformer, differential protection, fuzzy rules, inrush current. 1. Conventional Protection Scheme For Power Transformer

EVALUATION OF DIFFERENT SOLUTIONS OF FAULTED PHASE EARTHING TECHNIQUE FOR AN EARTH FAULT CURRENT LIMITATION

USING OVER-DAMPING METHOD TO SUPPRESS THE FERRO-RESONANCE OF POTENTIAL TRANSFORMER

Data Compression of Power Quality Events Using the Slantlet Transform

Modeling Ferroresonance Phenomena on Voltage Transformer (VT)

Review of Signal Processing Techniques for Detection of Power Quality Events

Transients under energizing multiple power filter circuits

p. 1 p. 6 p. 22 p. 46 p. 58

Analysis Of Induction Motor With Broken Rotor Bars Using Discrete Wavelet Transform Princy P 1 and Gayathri Vijayachandran 2

EEE508 GÜÇ SİSTEMLERİNDE SİNYAL İŞLEME

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

FAULT DETECTION, CLASSIFICATION AND LOCATION ON AN UNDERGROUND CABLE NETWORK USING WAVELET TRANSFORM

Classification of Signals with Voltage Disturbance by Means of Wavelet Transform and Intelligent Computational Techniques.

Discrete Wavelet Transform and Support Vector Machines Algorithm for Classification of Fault Types on Transmission Line

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Design, Control and Application of Modular Multilevel Converters for HVDC Transmission Systems by Kamran Sharifabadi, Lennart Harnefors, Hans-Peter

INFLUENCE OF INSTRUMENT TRANSFORMERS ON POWER SYSTEM PROTECTION. A Thesis BOGDAN NAODOVIC

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

HIGH IMPEDANCE FAULT DETECTION AND CLASSIFICATION OF A DISTRIBUTION SYSTEM G.Narasimharao

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Electric Stresses on Surge Arrester Insulation under Standard and

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

MITIGATION OF POWER QUALITY DISTURBANCES USING DISCRETE WAVELET TRANSFORMS AND ACTIVE POWER FILTERS

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

AP Physics C. Alternating Current. Chapter Problems. Sources of Alternating EMF

Bus protection with a differential relay. When there is no fault, the algebraic sum of circuit currents is zero

A COMPARATIVE STUDY: FAULT DETECTION METHOD ON OVERHEAD TRANSMISSION LINE

ISLANDING DETECTION IN DISTRIBUTION SYSTEM EMBEDDED WITH RENEWABLE-BASED DISTRIBUTED GENERATION. Saurabh Talwar

Study of High Voltage AC Underground Cable Systems Silva, Filipe Miguel Faria da; Bak, Claus Leth; Wiechowski, Wojciech T.

FPGA implementation of DWT for Audio Watermarking Application

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

Feature Extraction of Magnetizing Inrush Currents in Transformers by Discrete Wavelet Transform

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Power Quality Analysis in Power System with Non Linear Load

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

QUESTION BANK PART - A

Detection and classification of faults on 220 KV transmission line using wavelet transform and neural network

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Transcription:

Signal Analysis with Wavelet Transform on 500 kv Transmission Lines Capacitive Voltage Transformers I Gusti Ngurah Satriyadi Hernanda, I Made Yulistya Negara, Adi Soeprijanto, Dimas Anton Asfani, Mochammad Wahyudi, Surya Dwi Kisdarmawan, and Daniar Fahmi Department of Electrical Engineering Institut Teknologi Sepuluh Nopember Surabaya, Indonesia didit@ee.its.ac.id Abstract This paper deals with ferroresonance detection on a transmission line utilizing wavelet transform. The ferroresonance involving linear capacitor and non-linear inductor was triggered by the disturbances of power system, such as lightning strike, switching operation and ground fault. The primary voltage of capacitive voltage divider (CVT) was observed as response of the triggered ferroresonance. The voltage signal was processed using wavelet daubechies (db5) until 9 levels. The cyclic cumulative energy for each condition was then calculated and compared. The result shows that the cyclic cumulative energy ratio and duration of period of cumulative energy deviation can be used as ferroresonance detection parameters. Keywords ferroresonance; capacitive voltage divider, wavelet transform I. INTRODUCTION In modern era, electric power has been one of the fundamental needs. Consequently, reliability and stability of power system must be presented. On the other hand, the condition of power system is affected by performance of electric apparatus, such as transformer to convert voltage level. The occurrence of disruption can degrade performance of the transformer. Overvoltage is one of the disruption kinds that often contributes to this degradation. characterized by overvoltage is a result of interaction between linear capacitor and non-linear inductor [1-2]. The overvoltage due to ferroresonance belongs to abnormal overvoltage since its amplitude is very high with harmonics distortion [3]. Eventually, this effect leads to not only damage of transformer but also failure of power system. The complexity in detection of ferroresonance still becomes an important issue at this moment. As a result, ferroresonance cannot be mitigated effectively. In this paper, the discrete wavelet transform was applied to obtain the ferroresonance detection parameters. The transient disturbances due to lightning strike, ground fault and switching operation were choosen as triggers of ferroresonance. The response of ferroresonance observed was primary voltage of capacitive voltage transformer (CVT) of 500 kv transmission line. The result can be evaluated as a ferroresonance detection method based on wavelet [4-8]. A., also known as a non-linear resonance, is a complex non-linear disturbance of power system. One of the characteristic of this phenomenon is its abnormal overvoltage endangering transmission line, insulation, protection, apparatus and operator. If the power system is subjected by an unknown complex disturbance, the suspicion is ferroresonance contributing to this condition. The term of ferroresonance was known in 1920 [1]. This oscillation phenomenon involves non-linear inductor, linear capacitor and sinusoidal voltage source. The non-linear inductor origin from power transformer, voltage measuring transformer and shunt reactor, whereas the linear capacitor is sourced from line charging of transmission line and grading capacitance of circuit breaker. reduces impedance to its lowest value. As a result, the current flowing to transformer will rise significantly. Later, this high current increases flux density of the transformer until its iron core is saturated. Under this condition, the interaction between nonlinear inductance of transformer, capacitor, and iron core result in an abnormal response, such as overvoltage and overcurrent with its harmonic distortion. B. Wavelet Transform There are 2 types of wavelet transform, namely continuous wavelet transforms (CWT) and discrete wavelet transforms (DWT). By giving a function of wave, f(t), CWT provides many wavelet transform coefficients that leads to excessive output data. DWT is able to overcome this problem since it uses only some of wavelet transform coefficients. DWT is composed based on Mallat decomposition algorithm, in which the input signal is decomposed to be 2 signal types. The one is high frequency signal and the other 37

one is an approximation with its low frequency. In application of mother wavelet, DWT analyzes the detail using high frequency, whereas low frequency is used to analyze approximation. The mechanism can be explained more detail in the following. The input signal is divided to be 2 sub-signal types, that are high frequency and low frequency. The subsignal is then divided to be 2 sub-signals with different frequency. This mechanism takes a place continuously in accordance with level of wavelet transform used [4]. Wavelet transform develops a method to sample dynamics characteristic of non-stationary signal using short data. Wavelet transform is similar with fourier transform that is a signal classifier in sinusoidal form with variety of frequency. In this paper, detection of ferroresonance was conducted using high frequency daubechies wavelet transform. This mother wavelet is very crucial in detection of ferroresonance s characteristic. The order and level of this mother wavelet can be determined based on criteria of voltage signal extraction and mother wavelet itself [5]. The calculation of cumulative energy would be used as ferroresonance detection parameters. In this study, 4 conditions of transmission line were simulated as depicted on Fig 2. The result of simulation was primary voltage of CVT for 1 s with 100 khz sampling frequency. The voltage signal was processed using wavelet daubechies (db5) until 9 levels. After that, cyclic cumulative energy for each condition was calculated and compared. II. MODELLING OF FERRORESONANCE AND DETECTION METHOD CVT is a voltage measuring transformer of transmission line, as modelled in Fig. 1. The measured voltage, Vu, is in order of kilovolt hundreds. By using capacitive voltage divider, the capacitor voltage of C2 will be in order of kilovolt tens, such as 5, 10, 15 and 20 kv. Later, magnetic transformer will decrease the voltage to be standard secondary voltage, that is 100 or 100 3. The parameters of CVT is explained in detail as shown in Table 1. (b) Figure 1. Model of CVT using ATPDraw. TABLE 1. COMPARISON BETWEEN SIMULATION Parameter Value Rated voltage 500 3 kv Frequency 50 Hz Voltage divider capasitor C1 = 3300 pf, C2 = 79700 pf, load coil = 10 mh Step down transformer R1 = 220 Ω, L2 = 0.007 mh, ratio = 200 Burden 75 Ω Figure 2. Model of simulated condition: a) normal b) lightning strike c) switching operation d) ground fault. 38

III. RESULT AND ANALYSIS The comparison of CVT s primary voltage response for each scheme can be seen in Fig. 3. The amplitude of voltage for normal condition is 16.23 kv, as shown in Fig. 3. The amplitude of the voltage for the other conditions is higher than normal condition. Moreover, their voltage amplitude experiences increasing both on ferroresonance response and on non-ferroresonance response, as depicted on Fig. 3 (b-d). The daubechies (db5) wavelet transform for 9 levels is then applied to all simulation results. The output of signal processing can be seen in Fig. 4. The difference of wavelet daubechies for each conditions can be seen visually at level 8 of wavelet daubechies (d8), as depicted in Fig. 4. The d8 signal is relatively normal and unchanged for normal condition. This result is contrary with the other conditions. The d8 signal is then calculated its cumulative energy for each cycle using (1). The obtained cumulative energy is then compared at period of before and after disturbance, as shown in Fig. 5. The detail information of the cumulative energy in Fig. 5 can be explained in Table 2. (b) Figure 2. Model of simulated condition: a) normal b) lightning strike c) switching operation. 39

Time (ms) (b) Figure 4. Result of wavelet daubechies (db5) for 9 levels: a) normal b) lightning strike c) switching operation d) ground fault. 40

TABLE 2. COMPARISON OF CYCLIC CUMULATIVE ENERGY FOR EACH CONDITION Lightning Strike Switching Ground Fault Normal Non- Non- Non- 0.16-0.18 (T -2) 2.948 2.96 2.904 2.84 2.841 2.928 2.913 0.18-0.2 (T -1) 3.196 13.363 3.258 2.664 2.719 3.987 3.739 0.2-0.22 (T 1) 3.422 2534.2 14.49 10199 3.573 4447.7 13.294 0.22-0.24 (T 2) 3.141 648.29 10.5 18853 6.911 2995.7 6.273 0.24-0.26 (T 3) 2.602 113.44 8.224 11974 6.806 2075.8 5.18 n 2 ( A) E( t) = i= 0 F s (1) with, E = cumulative energy A = amplitude F s = frequency rate (100 khz) Figure 5. Comparison of cumulative energy: a) normal b) lightning strike c) switching operation d) ground fault. The ferroresonance response is colored as red, while the non-ferroresonance is blue. The average value of cyclic cumulative energy for normal condition was 3.035 x 10 4. This value was then used as a reference value showing the system was normal. The cyclic cumulative energy at period in which the disturbance taken a place deviated significantly from the reference value. Otherwise, the cyclic cumulative energy at period in which the disturbance had not occured was near with the reference value. The present of ferroresonance could also be recognized by duration of period of cumulative energy deviation 41

IV. CONCLUSION The present of ferroresonance due to lightning strike, switching or ground fault can be detected by its cyclic cumulative energy. It can be conducted by observing of cyclic cumulative energy ratio. Moreover, the duration in which deviation of cyclic cumulative energy from the reference value (the average value of cyclic cumulative energy for normal condition) is presented can be used as a ferroresonance detection parameter. For ferroresonance response, the amplitude and duration of the deviation in the case of lightning strike condition was 2534.2 x 10 4 for 6 cycles, switching condition was 10199 x 10 4 for 33 cycles and ground fault was 4447.7 x 10 4 for >40 cycles. For non-ferroresonance response, the amplitude and duration of the deviation in the case of lightning strike condition was 14.49 x 10 4 for 5 cycles, switching operation was 6.91 x 10 4 for 4 cycles and ground fault was 13.294 x 10 4 for 5 cycles, with average value in normal condition was 3.035 x 10 4. REFERENCES [1] Elmo Price, A Tutorial on, ABB Inc. [2] Ferraci, P.,, Group Schneider: Cahier no 190, pp. 1-28, 1998 [3] A.H.A. Bakar, Analysis of Lighting-caused in Capasitor Voltage Ekivier 2011 Electrical Power and Energy System33 pp 1536-1541 [4] Siavash Beheshtaein, Application of Wavelet-base Method and DT in Detection of from other Transient Phenomena, International Symposium on Innovations in Intelligent Systems and Applications, IEEE 2012 [5] Zhang Bo and LU Tiecheng, On The Use of Wavelet Decomposition for Detection in Power System, Asia-Pacific Power and Energy Engineering Conference, IEEE 2009 [6] G. Mokryani, et.al. Wavelet Based Kernel Fisher Classifier For Identification, International Conference on Intelligent System Applications to Power Systems, IEEE 2009 [7] J. A. C. Araujo, Modeling and Analysis of Power Transformers under Phenomenon, Universitat Rovira I Virgili, Tarragona, 2015 [8] Huang Chun-Wei, Jyh-Cherng Gu, Ming-Ta Yang, Applying Wavelet Transform to Detection and Protection, ICECECE 2014 42