Operating Instructions. SINGLE SBC Controller

Similar documents
Operating Instructions. Single SBC-Control Systems. Seite 1 von 13. U:\SINGLE\Regler\SBC\Englisch\SBC_e_Version 2_6.doc

O p e r a t i n g I n s t r u c t i o n s

Microprocessor-based Temperature Controller

Microprocessor Temperature Controller MP-988

Control solutions Biofloor

Introduction To Temperature Controllers

Micro-controller X SV C1 C2 AL1 AL2 SEL. Model: PXR3. Operation Manual TN5A2704-E

RWD68U Controller. Installation and Commissioning Guide Document No October 1, Function. Application

K3P ENG.qxd 23/10/ Pagina 1

INSTRUCTIONS FOR INSTALLATION AND USE. LTR15

SERVICE-MANUAL ROOM TEMPERATURE CONTROLLER NEA 230V / 24V. Construction Automotive Industry

Please enter the identity code of your device here!

PID Control Technical Notes

RWD44U Controller. Installation and Commissioning Guide Document No October 5, Function. Application

UNICONT. PMG-400 Universal controller and display unit USER'S AND PROGRAMMING MANUAL 1. pmg4111a0600p_01 1 / 24. ST edition

USER MANUAL. EPP Intelligent Positioner Control Unit 1/22.

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

Manual BC20 Control Service Guide

Fan Coil Actuator FCA 2

PID500 FULL FEATURED PID TEMPERATURE CONTROLLERS

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

C C1 C2 AL1 AL2 AL3. Micro-controller X. Model: PXR SEL PXR-4. Operation Manual. ECNO:406a

TC 405/30 THERMOCOMPUTER TC 405/30. temp rate. time. rate. temp time. fix prog. memo. pers. Operating Instructions. event kw/h.

BATCHMATE 1500 Batch Control Computer Technical Bulletin

SS2 Linear / Rotary. Smart Valve Positioner. Smart performance with innovative and ever-strong coil drive even under harsh working environments

CONFIGURING DRIVE PARAMETERS

HPVFP High Performance Full Function Vector Frequency Inverter

Humidity Controller TH136 INSTRUCTION MANUAL

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

IT.MLD900 SENSORS AND TRANSDUCERS TRAINER. Signal Conditioning

MPS SERIES. INSTALLATION and TECHNICAL MANUAL MPS 4 MPS 5 MPS 9 4 PV

Please enter the identity code of your device here!

Green-Mode PWM Controller with Integrated Protections

Please completely read through operating instructions! Do not discard! The warranty shall be invalidated by damage caused by operating errors!

Please enter the identity code of your device here!

Guidelines to Using a Three Phase Voltage Monitor

Description of functions Controller system VR660 / A200R

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

APPENDIX APPENDIX A 1

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Instruction Notes for 108A L Sensor Input

KNX manual 1-channel flush-mounted switch actuator SU 1

INTAC Microprocessor Humidifier Controller

1000TR. Instructions

Green-Mode PWM Controller with Integrated Protections

8003 1/8 DIN Temperature Controller

ERROR MESSAGES: Click on Error for further detail PROBE ERROR: PROBE IS OPEN OR NOT CONNECTED.

PMA KS 40. Compact industrial controller

TC LV-Series Temperature Controllers V1.01

Introduction To Temperature Controllers

2A, 23V, 380KHz Step-Down Converter

Modbus Integration Integration for Modbus Functionality for VT8300 Series

SeeTool - Solutions for KNX

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

Process controller with Modbus Master/Slave & PROFIBUS DP 1/8 DIN - 48 x 96 mm Platinum Series X5000 Line

Configuration Example of Temperature Control

- SMART TUNE - PID CONTROL - UNIVERSAL, 3 WIRE - TC, RTD AND LINEAR INPUT - 2 INDEPENDENT SET POINT RAMP UP/ DOWN PROFILES - SERVO VALVE POSITIONER

Blue Point Engineering

Microprocessor Transmitter/Controller for ph - Type for redox - Type B Operating Instructions 9.

Single Phase Full-Wave Motor Driver for Fan Motor AM7228

INSTRUCTION MANUAL Redox sensor M 1322 C

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller

TS16 - Pre-Instructional Survey

Application Programs Descriptions

Please enter the identity code of your device here!

2A, 23V, 380KHz Step-Down Converter

G1102 High Precision CC/CV Primary-Side PWM Controller

Current Mode PWM Power Switch. Code A B G H I J Year Code A B C Month Jan. Feb. Mar. Apr.

Application sheet for Green 300 series controllers. Title. Purpose. Application Controller Loop Configuration: Wiring: Explanation :

CONTROL MANUAL. Dry-Pic 09PE - 09VE

Jacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional)

Current Mode PWM Power Switch GR8935L XXXXX

170.IU0.LFS.0B /B r USER MANUAL LFS

GE Sensing. Introduction. Wiring Diagrams (Typical) Field Calibration. Installing the Sensor

KNX manual High-performance switch actuators RM 4 H FIX1 RM 8 H FIX2

Single-Phase Full-Wave Motor Driver with Built-in Hall Sensor. General Description

Single Phase Full-Wave Motor Driver with Built-in Hall Sensor for Fan Motor

N2000S UNIVERSAL PROCESS CONTROLLER FOR SERVO POSITIONING OPERATING MANUAL. (Manual Key): toggles the AUTO/MANUAL mode.

Operation Instruction Manual KAM-TC1000. Precision Temperature Controller

R2700 Compact Controller and Limiter with Program Functions

PLUG-IN DIGITAL TEMPERATURE CONTROLLER

Relay Driver Overview and Applications

Temperature Controller

200 us/2 ms/20 ms/200 ms, TDS ( PPM ) Real time data logger, Data logger no., RS232 CONDUCTIVITY METER Model : YK-2005CD

HC-220 PID Controller

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

Sturdy explosion proof housing and smart performance with innovative and ever-strong coil drive even under harsh working environments

Series F4P Communications Guide

PRODUCT / TEST MANUAL 2V162K4 VOLTAGE REGULATOR RELAY

CT435. PC Board Mount Temperature Controller

Instruction Manual (1/8 DIN) Controller With ma output.

Analogue temperature controllers

I/A Series Model 718TC 1/8 DIN Temperature Controller with ma Output

OVEN INDUSTRIES, INC. Model 5C7-362

Think About Control Fundamentals Training. Terminology Control. Eko Harsono Control Fundamental - Con't

15P0161B1 - DCREG for Applications to Electromagnets - SW Rev. D3.09 R.03 - Updated 01/04/04

PalmGauss SC PGSC-5G. Instruction Manual

PCB Relay. Ordering Information. SPST-NO Type Breaks 10-A Loads; SPST-NO + SPST-NC Type Breaks 8-A Load

2-Way Proportional Logic Cartridge Valve Model FE.. (Series 1X and 2X) PSI (315 bar) F with electrical connection 12 X Y

Transcription:

Operating Instructions SINGLE SBC Controller SBC_EN_15_06 Contents 1 Configuration and operation of the controller... 2 1.1 Operating elements... 2 1.2 Control panel... 2 1.3 Alarm panel and display information... 3 2 Parameter description... 4 2.1 Working level... 4 2.2 Parameter level... 6 2.3 Configuration level... 7 2.4 Setting the control parameter... 10 2.4.1 Determining the parameters with closed control circuit... 10 2.4.2 Self-optimisation... 11 3 Connecting diagram... 12 4 Technical data... 12

1 Configuration and operation of the controller 1.1 Operating elements -button (P) Button P gives access to the parameters of each level. For accessing the individual processing levels: working level: parameter level: configuration level: push the P key push P and ENTER keys simultaneously keep P and ENTER keys depressed simultaneously for about four seconds - button (Enter) All changes must be confirmed with this button. (set-point and parameter) - button (+) The (+) button is used to increase the set-point and parameter values. Each change must be confirmed by pressing the button. - button (Off) All systems are off. If power is still present the start screen is displayed. - button (On) The system is working, the pump and controller are active. - button ( ) The (-) button is used to decrease the set-point and parameter values. Each change must be confirmed by pressing the button. 1.2 Control panel Display PROCESS: Display of pre-run temperature's actual-value. Display of parameter designation, when operating at working-, parameter- and configuration-level. Display SET Display of the current or programmed set-values. Display of numerical values or parameter values when at working-, parameter- and configuration-level.

1.3 Alarm panel and display information Symbol Designation LED glows because: Rectification / explanation Water: with manual filling: Minimum level Minimum level not made replenish with heat transfer medium with automatic filling: open cooling water supply, wait till filled Oil: fill or replenish with oil Not up to temperature, or outside bandspread Limit-comparator Limit-comparator outside band-spread, limiting value exceeded (limit) Band-spread too narrow or limiting value made. Turn OFF at working level, parameter AL, or set band-spread. Pre-run temperature Pre-run temperature up to limiting value Heating switches OFF Heating Heating on - Check set limiting value; insufficient heat dissipation by consumer. Subsequent to cooling by 5 K, heating comes ON again Cooling Cooling on - Operating mode display Temperature control unit (TCU) activated LED flashes when the TCU is - switched off via the pump after-run control - too full in oil configuration

2 Parameter description 2.1 Working level Pushing the P-button, will access the working level. Individual parameters are accessed by pushing the button marked P. The PROCESS-display shows the parameter. The SET-display shows the parameter value. The first display shown after pressing button P is the status display. If an error has occurred, this will be displayed: ALAr FLO = flow error ALAr PUMP = motor contactor triggered ALAr FILL = filling time exceeded ALAr niv.h = max level. exceeded (only with oil units) Parameter description: Parameter Set-values range Signifying OFF OFF Alarm outputs selected. OFF, -99 100 Alarm output programmed as signal contact max. OFF-ON. The setting-value corresponds to the alarm s response value, relative to the set point-value. MR*-start MR*-end Alarm output programmed as limiting contact max OFF-ON. The set point-value corresponds to the absolute response-value of the alarm. OFF, 0 100 Alarm output programmed as limit comparator OFF-ON-OFF. The set point-value corresponds to the set point s tolerance-value. Alarm output, programmed as signal contact max. ON-OFF. AL OFF, -99 100 The setting-value corresponds to the alarm s response value, relative to the set point-value. Alarm output programmed as limiting contact max ON-OFF. MR-start MR-end The set point-value corresponds to the absolute response-value of the alarm. OFF, 0 100 Alarm output programmed as limit comparator ON-OFF-ON. The set point-value corresponds to the set point s tolerance-value. OFF, 0 100 Alarm output programmed as limit comparator ON-OFF-ON (with stand-by response). The set point-value corresponds to the set point s tolerance-value. No alarm during initial start-up, until the input range is made. SP2 MR-start Set-value limiting AP.I MR-start MR-end Ati OFF=0 40 Cti OFF, 10 900 LS OFF on Programmed value corresponds to 2 nd set-value. Change-over to 2 nd set-value takes place via parameter SET = SP.2 at working level. Also refer to configuration level. Programmed value corresponds to the response temperature of the inlet-temperature limitation. If up to end of measuring range is programmed, the value end of measuring range +5 C is displayed. Aquatimer: set point-value corresponds to the max. permissible filling cycles after 1 hour of operation. Change time; evacuation / vacuum time on units with automatic mold draining. Set point-value corresponds to the compressed-air assisted evacuation time or else the vacuum-time in seconds. Turning the leak-stop mode ON and OFF. ON means leak-stop mode turned ON. OFF means leak-stop mode turned OFF. remo OFF on Turning the remote function ON and OFF at units with interface. *MR = metering range

Parameter Set-values range Signifying Hand = manual filling of the unit niv Hand Auto Auto = automatic filling of the unit Auto not possible for heat transfer units with oil CHG no.ch Chg no.ch mould draining not active Chg mould draining active. Only for units with mould draining! Change-over must be set free in the configuration level! dir indi dir indi = Cooling via heat exchanger dir = direct Cooling Direct cooling only possible at units with water Change-over must be set free in the configuration level! bled OFF, 1 240 C.OFF OFF Co.OF SEt SP.1 SP.2 Adr 1 255 AL2 t.out Vent after switching on Setting in seconds OFF means, that the unit is turned OFF directly with the 0 key. Co.OF means, that when pushing the "0" key, the unit is cooled down first, before it is turned OFF. (Pump lag control) Change-over SP.1 = internal set-value active SP.2 = second set-value active Input of unit addressing. If several units are operated by the same interface, different addresses must be chosen. Compare with parameter AL Shows the pre-run temperature in the SET-display

2.2 Parameter level Pushing the buttons P and will access the parameter level. Individual parameters are accessed by pushing the P-button. The PROCESS-display shows the parameter. The SET-display shows the parameter value. Parameter Set-values range Signifying Y% Indication of the actual limitation of regulation ratio hl% 0 100 Limitation of regulation ratio for heating in % 1 cl% 0 100 Limitation of regulation ratio for cooling in % 1 hp OFF, 0.1 99.9 XP-Heating in %, the control system s proportional range hd OFF, 1 200 TV-Heating in sec., derivative action time of the control system h l OFF, 1 999 TN-Heating in sec., integral action (reset) time of control system cp OFF, 0.1 99.9 XP-Cooling in %, the control system s proportional range cd OFF, 1 200 TV-Cooling in sec., derivative action time of the control system c l OFF, 1 999 TN-Cooling in sec., integral action (reset) time of control system db OFF, 0.1 10.0 Switching hysteresis between heating and cooling. This parameter is used for increasing the set-value (switching point) for cooling by the value entered. That way, possibly too frequently occurring switching changes between heating- and cooling modes can be prevented. Simultaneous switching of heating and cooling can be ruled out generally. Settings are in C. hc 1 240 Heating switch-cycle time in sec. 2 cc 1 240 Cooling switch-cycle time in sec. 2 Upper set point limitation in C. SP.Hi SP.Lo MR-end SP.Lo MR-start SP.Hi SCL OFF, 35 90 C-F C 0,1 C Selection C, F or 1/10 C OPt OFF on SP/ OFF_ 0,1 99,9 Set point ramp rising SP\ OFF_ 0,1 99,9 Set point ramp decreasing HY.Hi 0,5 10,0 Cooling ON hysteresis HY.Lo 0,5 10,0 Cooling OFF hysteresis h Operating hours Here the final value for the set point setting range can be selected. Lower set point limit in C. The start value of the set point adjustment range can be preselected here. System Closed = system shut-off on units employable at > 90 C, the water system is shut-off to atmosphere. Water: temperature selection for system shut-off in C Oil: evacuation by vacuum only possible below the set SCL-value (CHANGE) Turning self-optimization ON and OFF. ON = Self-optimization started. The controller determines the optimum control parameters by closed-loop control. Also refer to Chapter 2.4 Setting the closedloop control parameters. 1 Limitation of the regulation ratio is only required with an excessively overdimensioned energy supply for the control system, or for turning-off the corresponding actuating output port (setting 0 %). It should be inoperative under normal circumstances (setting 100 %). Limitation of the regulation ratio becomes active, when the regulation ratio calculated by the controller is greater than the max. permissible (limited) regulation ratio. Please note: Limitation of regulation ratio is ineffective during the self-optimization phase. 2 The control element s maximum switching frequency is determined with the assistance of the switch-cycle time. This is the period during which the controller carries out one ON and one OFF switching action. We recommend the following settings: Relay-setting outputs with downstream installed contactors: switching cycle > 10 s Bi-stable voltage output ports for actuating Solid State Relays (SSR): Switch-cycle time 1... 10 s Continuous actuator output: Switch-cycle time 1 s

2.3 Configuration level Pushing the buttons P and for about four seconds will access the parameter level. Individual parameters are accessed by pushing the P-button. The PROCESS-display shows the parameter. The SET-display shows the parameter value. Parameter Set-values range Signifying Keyboard interlock OFF= parameter values can be changed. PC = Parameter level and configuration level barred. Parameters can only be viewed. SP.t = set point-value can be altered. All function keys are enabled, if not barred by the configuration level. LOC OFF ALL o.sp = all keys, except for 0 and I are barred; only the set point-value can be altered ALL = complete keyboard interlocking; it is only possible to switch ON and OFF; no set point-value alteration possible! ECO OFF on niv on LOC c60 OFF, 10 100 C.OIL AqUA OIL cdi OFF on C.AL OFF 7 C.SA op cl Please note! When changing the LOC-parameters, ENTER must be kept depressed, until the moving illumination has passed-through for the second time (about 5 s )! Configuration of external contact OFF: Pin 10 = inlet flow monitor on: Pin 10 = switch-over setpoint value 1 / setpoint value 2 Enabling the filling modes AUTOMATIC/MANUAL on = change-over facility of the key marked LEVEL is enabled LOC = change-over facility of the key marked LEVEL is blocked. Enabling or locking the software-key of the pump-lag control OFF = OFF -key blocked 10...100 C = adjustable switch-off temp. AQUA = water unit OIL = oil unit Interlocking of the direct cooling key (unit must be equipped with hydraulics) on = change-over to direct cooling is enabled OFF = no direct cooling allowed Configuration of the alarm output port OFF = Alarm has been turned OFF = Signal contact OFF-ON = Limiting contact OFF-ON = Limit comparator OFF-ON-OFF = Signal contact ON-OFF = Limiting contact ON-OFF = Limit comparator ON-OFF-ON = Limit comp. with stand-by response In the ON-position, output port is open. In OFF-position, output-port is closed. Configuration group interrupt op = n/c contact cl = n/o contact

Parameter Set-values range Signifying Change-logic configuration The change sequence will have to be preselected as a function of the unit s hydraulic and electrical specifications. dd = Mold evacuation by compressed air ChL dd Ldd LS = Mold evacuation by vacuum suction (leak stop-function) Ldd = at present as per dd 8-9 = Mold evacuation with compressed air, when units with System shut-off in cooling water return are employed, e.g. STW 1-HTK and STW 150/1-HK + HN Interlocking of LS leak-stop parameter at working level (when hydraulic prerequisite is missing). E.LS on LOC ON = Changing of the LS -parameter enabled at working level LOC = Changing of the LS -parameter blocked at workinglevel ASt 5 min 120 Aquatimer-Start-time (min) Aquatimer (filling-impulse-counter) becomes active following the time set in the "ASt". Previously not monitored random filling cycles. Renewed start of the "AST" time, following the On/Off. FiLL OFF; 1 99 Monitoring of filling time Setting in minutes Restart lockout after power reset off = Restart lockout not active on = Restart lockout active Following a power reset, the control system stays turned OFF, to start with. EMO OFF on Display "Info". "EMO" message flashing. LED in the "O"-key flashes. All other displays except for Power LED are OFF. The control system can be turned ON with the following sequence. ENTER the "EMO"-message with the "O"-key. LED in "O"-key is now permanently alight. The EMO -message must then be deleted. Now the control system can be turned ON with the I -key. OF1 OFF, -100 100 Temperature correction of the internal temperature probe in C OF4 OFF, -100 100 Temperature correction of the probe for inlet temperature in C Duty cycle offset info for system output cooling. OF6 OFF, 1 100 Use of the parameter: To equalize unsteadiness of a cooling valve, an offset (OFF-Set) can be entered here in %. P.Fi OFF, 0,1 60 Filter for stabilization of the actual-value display Setting of the various interface protocols OFF = interface mode turned OFF. Parameter Adr, b and For are without any significance A = Arburg-protocol active Pro OFF St A = Krauss Maffei-protocol active b = Dr. Boy-protocol active E = Engel-protocol active CП = Krauss Maffei-protocol active St = SINGLE Standard-protocol active Pb = Profibus active only at SBC with Profibus interface

Parameter Set-values range Signifying b OFF, 0.3 19.2 This is where the transmission speed baud rate of the interface is being programmed. Possible settings are as follows: OFF = no baud rate set 0.3 = 0.3 kbaud 0.6 = 0.6 kbaud 1.2 = 1.2 kbaud 2.4 = 2.4 kbaud 4.8 = 4.8 kbaud 9.6 = 9.6 kbaud 19.2 = 19.2 kbaud For 7E1 8n2 Here the Interface s data format is being programmed. The data-format is comprised of: Data-bits, parity bit, stop bit. Possible settings are: 7E1, 7o1, 7E2, 7o2, 7n2, 8E1, 8o1, 8n1, 8n2 dn1 0 999 Here the first 3 digits of the equipment No. are programmed. dn2 0 999 Here the last 3 digits of the equipment No. are programmed. C.OFF c.off c.gr Programming c.off After switch-off via the pump run-on control, 100% cooling is effective until cooling temperature is reached. Programming c.gr After switch-off via the pump run-on control, the default cooling gradient is effective until the cooling temperature is reached. C.A2 Compare with parameter C.AL ConF 3P 2PC Control response configuration 3P 3-point controller heating/cooling 2PC 2-point controller cooling PSI -

2.4 Setting the control parameter 2.4.1 Determining the parameters with closed control circuit If the time response of the controlled system is unknown and if the control circuit can be made instable for short periods, then the controller is operated with xp = 0 (on-off, without time response). The control parameters are calculated from the resulting waveform as follows: X ( C) Δx T Δx = oscillation period = oscillation amplitude of the actual value t (sec.) Delay time: 1 Tu = T 4 Lead time: 4 Tv = Tu 10 Reset time: Tn = 5 Tv Proportional range: x 2 xp = 100% Meßbereichsumfang Span SC: 430 K We recommend setting the proportional range cooling to two times the value.

2.4.2 Self-optimisation The optimisation algorithm with closed control circuit ascertains the characteristics of the controlled system and calculates the feedback parameters (Xp, Tv, Tn) and the switching cycle time (C = 0.3 x Tv) for a PD/I controller valid over a wide range. If the controller is operated as a heating-off-cooling controller then the parameter values determined under heating are used for cooling. The optimisation is carried out during start-up shortly before the setpoint. This must be at least 5 % of the span. During the optimisation to a setpoint that has already been reached, the temperature is reduced by approx. 5% of the span in order to accurately determine the controlled system gain. The optimisation algorithm can be triggered at any time by selecting Self-optimisation = ON and confirming with the Enter button. During the optimisation process Opt. Activ is shown in the display. With 3-point controllers (heating-off-cooling) the temperature reduction is accelerated via short-term activation of the cooling. After the feedback parameters have been calculated the controller maintains the actual value at the current setpoint. X w X w OPT on t y OPT on t Optimisation during heating Optimisation to setpoint of the controlled system already "attained y By selecting Self-optimisation = OFF and pressing the Enter button, the optimisation process can be interrupted.

3 Connecting diagram Interface optional! St3 PIN 0/20 ma TTY Profibus DP GND 85 TTY 20 ma- RxTxP 86 RxTxN 87 TTY 20 ma+ Vp +5V 88 St1 PIN draining 17 18 leak-stop system closing 15 16 pilot contact heating pump 13 14 filling heating 11 12 cooling motor protection 9 10 flow watchdog level min. 7 8 level max. Pt 100 control 5 6 Pt 100 temperature 3 4 monitoring 0 V 1 2 24 V St2 PIN group alarm 3 normally open contact 2 opener 1 two-way contact 4 Technical data Power supply 24V DC 0,1A Actual value monitoring Inputs Outputs Relay Pt 100 2-two-wire lead Resolution 0,1 K Data sampling 0,1s Measuring range -30 400 C Sensor break and short circuit monitoring are present Sensor voltage 1mA Calibration accuracy 0,2% Linearity and indication error 0,2% +/-1digit Ambient temperature influence on the span 0,02% / K Switching voltage 24V DC Input current 1mA Suitable for the connection of external, floating contacts 24V DC 0,5A 2A max. SMD fuse 4A Short circuit proof, suitable for inductive loads 1 two-way contact 250V AC 3A cos phi 1