Solid-State Soft Starters

Similar documents
SIRIUS/SIKOSTART Soft Starters For Standard Applications

Type 3RW RW40 7. Control electronics Rated values. Terminal. external DC supply (to DIN 19240) through terminals and IN Relay outputs

Subject to changes 11/2003 Page 1/7

Output of three-phase motors at 50 Hz and 400 V

Controls Contactors and Contactor Assemblies Special Applications

3RA13, 3RA14 Contactor Assemblies

Switching Devices Contactors and Contactor Assemblies for Switching Motors

3RF A A 0 2. Switching function. Control voltage Operating voltage with heat sink 10 = 10.5 A. A = Zero-point switching

Solid-State Relays Zero-point switching, without heatsink

ATS01N112FT soft starter for asynchronous motor - ATS01-12 A V KW

ATS01N125FT soft starter for asynchronous motor - ATS01-25 A V KW

General data 4/5. Overview. You can find further information on the Internet at:

Controls Solid-State Switching Devices

Type: DILM80(110V50HZ,120V60HZ) Article No.: Sales text Contactor,37kW/400V,AC operated. Ordering information

Type: DILM95(230V50HZ,240V60HZ) Article No.: Sales text Contactor,45kW/400V,AC operated. Ordering information

References 1 for asynchronous motors 1

For non-electrical quantities

ATS01N103FT soft starter for asynchronous motor - ATS01-3 A V KW

ATSU01N232LT soft starter for asynchronous motor - ATSU01-32 A V KW

Solid State Relay, 1-phase

ATS01N206QN soft starter for asynchronous motor - ATS01-6 A V KW

Industrial Controls. SIRIUS 3R_1* in sizes S00/S0 to S12. Catalog Add-On IC 10 AO 2012 SIRIUS. Answers for industry.

ATSU01N222LT soft starter for asynchronous motor - ATSU01-22 A V KW

hp

Soft starters with internal by-pass

ATS01N206QN soft starter for asynchronous motor - ATS01-6 A V KW

ATS01N222LU soft starter for asynchronous motor - ATS01-22 A V KW

Solid-State Switching Devices

CP-T range Product group picture

QUINT-PS-24DC/24DC/10

Power supply CP-D 24/4.2 Primary switch mode power supply

Contactors and Contactor Assemblies

CP-T range Benefits and advantages

QUINT-PS AC/24DC/40

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

QUINT-PS/ 1AC/24DC/20

PHOENIX CONTACT - 06/2008. Features. DANGER OF EXPLOSION! Only remove equipment when it is disconnected and not in the potentially explosive area.

Primary switch mode power supplies Product group picture

3 - Protection components Circuit-breakers

ATSU01N209LT soft starter for asynchronous motor - ATSU01-9 A V KW

Price groups PG 41B, 41C, 41E, 41F, 41H, 41J, 42G, 42H, 42J, 401

Multi-function (MI, ME, M2, M1) 2 NO (2 SPST-NO) 12 / / 400 3,000 1, / 0.3 / (5 / 5) AgNi

Three-phase monitoring relays CM-PFE and CM-PFE.2

STEP-UPS/24DC/24DC/3. Uninterruptible power supply. Data sheet. 1 Description. Features

SIRIUS 3RW Soft Starters 4/5 General data 3RW30, 3RW40 for Standard Applications 4/8 3RW30 4/18 3RW40 3RW44 for High-Feature Applications 4/34 3RW44

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

QUINT-PS/ 3AC/24DC/10

The CWC0 compact contactors are offered as a complete solution for switching and controlling motors.

Industrial Controls. Catalog IC SIRIUS. Answers for industry.

ATS01N106FT soft starter for asynchronous motor - ATS01-6 A V KW

Thermistor motor protection relays

UNO-PS/1AC/24DC/150W. Primary-switched power supply unit. Data sheet. 1 Description

CI-tronic Soft start motor controller

Power supply CP-E 24/20.0

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Inverter MICROMASTER 410

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

MINI-PS AC/24DC/1.3

Capacitor Switching Contactors

Type CP-S, CP-C & CP-A Switch mode

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

PHOENIX CONTACT - 05/2008. DANGER OF EXPLOSION! Remove an item only when it is not connected to power or if it is located in the non-explosive area.

QUINT-PS/ 3AC/24DC/40

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

Type: EASY719 DA RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 12 V DC. Description

CP-E range Benefits and advantages

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

MINI-PS AC/2X15DC/1

Power supply CP-T 24/40.0 Primary switch mode power supply

Power supply CP-D 12/2.1

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

Switching power supplies CP range, Linear power supplies CP-L range. Content

Power supply CP-T 48/20.0 Primary switch mode power supply

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

Miniature circuit-breakers S 280 UC series. System pro M. Technical data

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

Power supply CP-T 24/20.0 Primary switch mode power supply

Three-phase monitoring relay CM-PFS

Insulation monitoring relay CM-IWS.1 For unearthed AC, DC and mixed AC/DC systems up to U n = 250 V AC and 300 V DC

Power supply CP-D 24/1.3

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Three-phase monitoring relays

Transformers, Power Supply Units and Socket Outlets

Power supply CP-E 24/2.5

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

Type: EASY719 AC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 115/230 V AC. Description

Electronic timer CT-SDD.22

Siemens AG Allows easy and consistent configuration with one series of overload relays (for small to large loads)

77 Series - Modular Solid State Relay 5 A. Features. Timers and Monitoring relays

Approved Standards. Ordering Information. Mini Contactor Relays 4-pole J7KNA-AR. Model Number Legend. Main contactor. Accessories

NS..S contactor relays - with spring terminals AC operated

Power supply CP-T 24/10.0 Primary switch mode power supply

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

Solid State Relay. Zero Switching Types RGC Solid State Contactor 'U' Connection. Product Description RGC 1 A 60 A 40 K G U _.

Modular equipment. Presentation, standards. Standard contactors TeSys GC

Overcurrent Protection / 7SJ45

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Transcription:

Selection and ordering data Rated operational voltage U e V Soft starters for three-phase asynchronous motors 3RW30 25-1B14 3RW30 35-1B14 t ambient temperature 40 C Size Order No. Price Weight Pack. Rated operational current I e Rated outputs of three-phase motors at rated operational voltage U e 230 V 400 V 500 V kw kw kw 1 Unit kg Unit 200 to 460 6 0.55 1.1 S00 3RW30 14-1CB@4 0.26 1 6 0.75 1.5 S00 3RW30 14-1CB@4 6 1.1 2.2 S00 3RW30 14-1CB@4 6 1.5 3 S00 3RW30 14-1CB@4 9 2.2 4 S00 3RW30 16-1CB@4 12.5 3 5.5 S0 3RW30 24-1B@4 0.44 1 16 4 7.5 S0 3RW30 25-1B@4 25 5.5 11 S0 3RW30 26-1B@4 32 7.5 15 S2 3RW30 34-1B@4 0.75 1 38 11 18.5 S2 3RW30 35-1B@4 45 15 22 S2 3RW30 36-1B@4 63 18.5 30 S3 3RW30 44-1B@4 1.85 1 75 22 37 S3 3RW30 45-1B@4 100 30 45 S3 3RW30 46-1B@4 100 55 S3 3RW30 46-1B@4 460 to 575 12.5 1.5 S0 3RW30 24-1B@5 0.44 1 12.5 2.2 S0 3RW30 24-1B@5 12.5 3 S0 3RW30 24-1B@5 12.5 4 S0 3RW30 24-1B@5 12.5 5.5 S0 3RW30 24-1B@5 12.5 7.5 S0 3RW30 24-1B@5 16 7.5 S0 3RW30 25-1B@5 25 15 S0 3RW30 26-1B@5 32 18.5 S2 3RW30 34-1B@5 0.75 1 38 22 S2 3RW30 35-1B@5 45 30 S2 3RW30 36-1B@5 63 37 S3 3RW30 44-1B@5 1.85 1 75 45 S3 3RW30 45-1B@5 75 55 S3 3RW30 45-1B@5 100 70 S3 3RW30 46-1B@5 Order No. suffix Rated control supply voltage UC 24 V............................................................... 0 UC 110 V to 230 V....................................................... 1 Soft starters with two-ramp control for three-phase motors with two speeds (double pole-reversing) 200 to 460 12.5 3 5.5 S0 3RW31 24-1CB14 0.44 1 16 4 7.5 S0 3RW31 25-1CB14 25 5.5 11 S0 3RW31 26-1CB14 460 to 575 12.5 7.5 S0 3RW31 24-1CB15 0.44 1 16 11 S0 3RW31 25-1CB15 25 15 S0 3RW31 26-1CB15 Rated operational voltage U e t ambient temperature 40 C Size Order No. Price Weight Pack. Rated operational current I e Rated outputs of three-phase motors at rated operational voltage U e 115 V 230 V kw kw 1 Unit kg Unit V Soft starters for single-phase motors (please inquire about delivery launch) N 115 to 240 25 2.2 4 S0 3RW30 26-112 0.42 1 38 3 5.5 S2 3RW30 35-112 0.72 75 5.5 11 S3 3RW30 45-112 0.80 The W3 sold-state soft starters are designed for simple starting conditions. In the event of deviating conditions or increased switching frequency, it may be necessary to choose a larger unit. See technical data for information about rated currents for ambient temperatures >40 C. Selection of the soft starter depends on the motor s rated current. 5/50 Only supplied in packs.

ccessories Fans 3RW39 26-8 3RW39 36-8 For devices Design Order No. Price Weight Pack. Type 1 Unit kg Unit To increase switching frequency and for unit mounting in positions different from the normal position. The fan is snapped into the housing from below. 3RW3. 2. 3RW39 26-8 0.008 1 3RW30 3. and 3RW39 36-8 0.018 1 3RW30 4. Covers 3RT19 36-4E2 For devices Design Order No. Price Weight Pack. Type kg Pack. Terminal cover for box terminals dditional touch guard to be fitted at the box terminals (2 units required per device, = 10 Units) 3RW30 3. 3RT19 36-4E2 2.70 0.012 1 3RW30 4. 3RT19 46-4E2 3.20 3RT19 46-4E1 Teminal cover for cable lug and busbar connection For meeting the clearance and as protection against accidental fingertouch with distant box terminals (2 units required per device, = 1 Unit) 3RW30 4. 3RT19 46-4E1 5.20 0.028 1 Link module 3R19 11-1 3R19 21-1 Electrical and mechanical link between circuitbreaker and soft starter. Note: For fuseless load feeders with soft starter of size SO, the link module has an integrated conductor routing. No. of units per packg. 3RW30 1.. 10 3R19 11-1 25.90 0.15 3RW30 2.. 10 3R19 21-1 38.20 0.21 3RW30 3.. 5 3R19 31-1 38.20 0.1 3RW30 4.. 5 3R19 41-1 43.30 0.3 3R19 31-1 Note: The covers and connection modules listed here are also used for load feeders (circuit-breaker 3RV + contactor 3RT). Further technical data in Part 3. Only supplied in packs. 5/51

ccessories For devices Design Order No. Price Weight Type Preferred type 1 Unit kg S-Interface load feeder modules 3RK1 400-1KG01-01 3RK1 400-1MG01-01 Support with mounted power plug coupling S-Interface load feeder module For snapping onto standard mounting rail For sizes S00 and S0 For mounting onto 40 mm or 60 mm busbar systems and SIRIUS busbar adapters the fitting support is required. The S-Interface connector for data and auxiliary supply cables (yellow and black) SP4 must be ordered separately. Pack. 2 inputs / 1 output / DC 24 V 3RK1 400-1KG01-01 0.08 1 Unit 4 inputs / 2 outputs / DC 24 V 3RK1 400-1MG01-01 0.08 1 Unit 2 inputs / 1 relay output / 3RK1 402-3KG02-01 0.08 1 Unit C 120/230 V 3 inputs / 2 relay outputs / C 120/230 V 3RK1 402-3LG02-01 0.08 1 Unit Manual for S-Interface load feeder module German, English Italian, French 3RK1 701-2GB00-00 3RK1 701-2HB00-00 1 Unit 1 Unit Support for S-Interface load feder module for mounting onto 3R19 22-1 SIRIUS standard mounting rail adapter 45 mm 3RK1 901-3G00 0.04 1 Unit 3RK1 901-0E00 Power connector set 5-pole, 2.5 mm 2 ( = 5 plugs and 5 couplings) 3RK1 901-0E00 0.02 S-Interface connector for data and auxiliary supply cables with overlapping terminals for 2 x (0.5 to 0.75 mm 2 ) flexible lead ( = 5 Units) yellow black 3RK1 901-0N00 3RK1 901-0P00 0.01 0.01 3RK1 901-0N00 3RK1 901-0P00 3RK1 091-0Q0 dapters for rail mounting 3R19 22 For mechanical fixing of circuit-breaker and soft starter; suitable for snap-on fitting on standard mounting rail or for screw fitting 3RW30.1 ( = 5 Units) 3R19 22-1 0.35 Surge suppressor of RC network for PLC control 3TX7 462-3. RC element for snapping onto 35 mm standard mounting rail C 127 V to 240 V 3TX7 462-3T 0.075 10 See Part 1 for further accessories and technical data for communication devices. See Part 3 for technical data for adapters for rail mounting and surge suppressors. See page 5/57 for details of the RC network for PLC control when using the surge suppressor. 5/52 Only supplied in packs.

Technical data Control electronics Type 3RW3...-1.B0. 3RW3...-1.B1. 3RW30..- 114 Rated control supply voltage V UC 24 UC 110 to 230 Rated control supply current m 50 25 to 20 Rated frequency for C Hz 50/60 ± 10 % Power electronics Type 3RW3...-1.B.4 3RW3...-1.B.5 3RW30..- 114 Operating range voltage V C 200 to 460 3-phase (± 10 %) Rated frequency Hz 50/60 ± 10 % Permissible installation altitude Reduction of I E up to 1000 m above sea level up to 2000 m above sea level up to 3000 m above sea level up to 4000 m above sea lev. 1 ) 100 % 92 % 85 % 78 % C 460 to 575 3-phase (± 10 %) C 115 to 240 1-phase (±10 %) Type 3RW30 1. 3RW3. 2. 3RW30 3. 3RW30 4. Size S00 S0 S2 S3 Uninterrupted operation (% of I e ) % 100 Minimum load 2 ) (% of I e ); at 40 C % 4 Permissible ambient temperature C 25 to +60 (derating from 40 C; see below) Making/breaking capacity of the auxiliary contacts 230 V/C-15 230 V/DC-13 24 V/DC-13 3 0.1 1 Type 3RW30 14 3RW30 16 3RW30 24 3RW30 25 3RW30 26 Load ratings Rated operational current I e acc. to IEC at 40/50/60 C, C-53b 6/5/4 9/8/7 12.5/11/9 16/14/12 25/21/18 Rated operational current I e acc. to UL/CS at 40/50/60 C, C-53b 4.8/4.8/4 7.8/7.8/7 11/11/9 17.5/14/12 25/21/18 Power loss at rated operational current (40 C) W 5 7 7 9 13 Permissible starts per hour when not using a fan intermittent duty S4, T u = 40 C 1/h 60 40 30 12 ON-period = 30 %; single installation % 250 x I e, 2 s 300 x I e, 2 s Permissible starts per hour when using a fan intermittent duty S4, T u = 40 C 1/h 3 ) 54 21 ON-period = 30 %; single installation Pause intervals after continuous duty s 0 200 with I e before a new start Degree of protection acc. to IEC 60 529 IP 20 (terminal compartment IP 00) Conductor cross-sections Screw connection uxiliary conductors: (1 or 2 conductors connections solid mm 2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5) according to IEC 60 947; max. 2 x (0.75 to 4) possible) finely stranded with mm 2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5) for screw driver end sleeve Size 2 and Pozidriv 2 WG conductor connections, solid or stranded WG 2 x (18 to 14) - Terminal screws M 3, PZ2 - Tightening torque Nm lb.in 0.8 to 1.0 7.1 to 8.9 0.8 to 1.0 7.1 to 8.9 Main conductor: solid mm 2 2 x (0.5 to 1.5) 2 x (1 to 2.5) Please inquire about technical data of soft starters for single-phase motors. 2 x (0.75 to 2.5) 2 x (2.5 to 6) mm 2 2 x (0.5 to 2.5) 2 x (1 to 2.5) 2 x (2.5 to 6) finely stranded with end sleeve stranded mm 2 WG conductor connections, solid or stranded WG 2 x (18 to 14) 2 x (14 to 10) - Terminal screws M 3, PZ2 M 4, PZ2 - Tightening torque Nm lb.in 0.8 to 1.2 7 on 10.3 2 to 2.2 18 to 22 1) Please inquire about more than 4000 m. 2) The motor's rated current (specified on the motor's rating plate) should at least amount to the specified percentage of the SIRIUS soft starter's rated current I e. 3) Installation of the fan, which is available as an accessory, is not possible for size S00. 5/53

Technical data Power electronics Type 3RW30 34 3RW30 35 3RW30 36 3RW30 44 3RW30 45 3RW30 46 Load ratings Rated operational current I e acc. to IEC at 40/50/60 C, C-53b 32/27/23 38/32/27 45/38/32 63/54/46 75/64/54 100/85/72 Rated operational current I e acc. to UL/CS at 40/50/60 C, C-53b 27/27/23 34/32/27 42/38/32 62/54/46 68/64/54 99/85/72 Power loss at rated operational current (40 C) W 10 13 17 13 16 26 Permissible starts per hour intermittent duty S4, T u = 40 C 1/h 20 15 5 20 30 15 ON-period = 30 % % 300 x I e, 3 s 300 x I e, 4s Permissible starts per hour when using a fan intermittent duty S4, T u = 40 C 1/h 44 27 9 32 48 24 ON-period 30 %; single installation Pause times after continuous duty s 0 400 0 with I e before a new start Degree of protection acc. to IEC 60 529 IP 20 (terminal compartment IP 00) IP 20 1 ) Conductor cross-sections Screw connection uxiliary conductor: (1 or 2 conductor connections solid mm 2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5) acc. to IEC 60 947; max. 2 x (0.75 to 4) possible) finely stranded with mm 2 2 x (0.5 to 1.5); 2 x (0.75 to 2.5) for screw driver end sleeve Size 2 and Pozidriv 2 WG conductor connections, solid or stranded WG 2 x (18 to 14) - Terminal screws M 3 - Tightening torque Nm lb.in 0.8 to 1.0 7.1 to 8.9 Main conductor: General data solid mm 2 2 x (0.75 to 16) finely stranded with end sleeve mm 2 2 x (0.75 to 16) 1 x (0.75 to 25) stranded mm 2 2 x (0.75 to 25) 1 x (0.75 to 35) WG conductor connections, solid or stranded WG 2 x (18 to 3) 1 x (18 to 2) 2 x (10 to 50) 1 x (10 to 70) 2 x (10 to 1/0) 1 x (10 to 2/0) - Terminal screws M 6, box terminal, PZ2 M6 (socket-head cap screw) - Tightening torque Nm lb.in 3 to 4.5 27 to 40 4 to 6 35 to 53 Noise immunity Standard Parameters Electrostatic discharge (ESD) IEC 61 000-4-2, IEC 60 801-2: 1991 IEC 60 947-4-2 SN-ICS Pulse shape: 1/60 ns Test severity 6 kv or 8 kv 4 kv charging voltage in the event of contact discharge 8 kv charging voltage in the event of air discharge Electromagnetic RF fields IEC 61 000-4-3 Frequency range: 80 to 1000 MHz with 80 % @ 1 khz EN 60 947-4-2, SN-ICS Field strength 10 V/m Conducted low-frequency interference (harmonics) IEC 60 945: 1996 Frequency range: 50 Hz to 10 khz IEC 60 947-4-2 SN-ICS DC supply: 3 V off 50 Hz supply: 50 to 750 Hz: 10 % U vers 0.75 to 5 khz: 10 to 1 % U vers 5 to 6 khz: 1 % U vers RF voltages and RF currents on conductors IEC 61 000-4-6 Frequency range: 80 to 1000 MHz with 80 % @ 1 khz IEC 60 947-4-2 SN-ICS 10 V at 0.15 to 80 MHz 3 V at 10 khz to 80 MHz Burst IEC 61 000-4-4 Test severity: 2 kv or 1 kv Surge IEC 61 000-4-5 Test severity: 2 kv or 1 kv Emitted interferences Radio interference field strength CISPR 11/09.1990 H field: 150 khz to 30 MHz E field: 30 MHz to 1000 MHz EN 60 947-4-2 Class B limit at 30 to 1000 MHz SN-ICS Limit acc. to Section 19.2 for Power distribution location Radio interference voltage CISPR 11/09.1990 Frequency range: 9 khz to 30 MHz IEC 60 947-4-2 (0.15 to 30 MHz): Unit class (industry) and unit class B (public networks) SN-ICS (9 khz to 30 MHz): Limits acc. Section 19.2 for Power distribution or bridge and open deck location Unit class B (public networks) is only met in the case of versions 3RW3,-1B0. with UC 24 V control voltage. For versions 3RW3,-1.1. with UC 110 V to 230 V control voltage, the units must be preceded by single-stage filters (e.g. type B84143-...). 1) IP 20 only with installed box terminal ('as-delivered'). IP 00 without box terminal. 5/54

Fuse coordination Fuseless version Fused version Technical data Soft starter Circuit breaker 1 ) Link module 2 ) Soft starter Line fuse Overload relay Contactor Order No. Order No. Order No. Order No. Order No. Rated current Type of coordination 1: I q = 50 k at 400 V thermal electronic Size Order No. Order No. Order No. 3RW30 14 3RV10 11 3 ) 3R19 11-1 3RW30 14 3N38 10 25 00 3RU11 16 3 ) 4 ) 3RB10 16 3 ) 4 ) 3RT10 15 3RW30 16 3RV10 11 3 ) 3R19 11-1 3RW30 16 3N38 10 25 00 3RU11 16 3 ) 4 ) 3RB10 16 3 ) 4 ) 3RT10 16 3RW30 24 / 3RW31 24 3RV10 21 3R19 21-1 3RW30 24 / 3RW31 24 3N38 22 63 00 3RU11 26 5 ) 3RB10 26 5 ) 3RT10 24 3RW30 25 / 3RW31 25 3RV10 21 3R19 21-1 3RW30 25 / 3RW31 25 3N38 22 63 00 3RU11 26 5 ) 3RB10 26 5 ) 3RT10 25 3RW30 26 / 3RW31 26 3RV10 21 3R19 21-1 3RW30 26 / 3RW31 26 3N38 24 80 00 3RU11 26 5 ) 3RB10 26 5 ) 3RT10 26 3RW30 34 3RV10 31 3R19 31-1 3RW30 34 3N38 30 100 00 3RU11 36 5 ) 3RT10 34 3RW30 35 3RV10 31 3R19 31-1 3RW30 35 3N38 30 100 00 3RU11 36 5 ) 3RT10 35 3RW30 36 3RV10 31 3R19 31-1 3RW30 36 3N38 30 100 00 3RU11 36 5 ) 3RT10 36 3RW30 44 3RV10 41 3R19 41-1 3RW30 44 3N38 44 250 1 3RU11 46 5 ) 3RT10 44 3RW30 45 3RV10 41 3R19 41-1 3RW30 45 3N38 44 250 1 3RU11 46 5 ) 3RT10 45 3RW30 46 3RV10 41 3R19 41-1 3RW30 46 3N38 44 250 1 3RU11 46 5 ) 3RT10 46 Fused version with SITOR fuses 3NE1 (Semiconductor and lead protection) Fused version with SITOR fuses 3NE8 (Semiconductor protection by fuse, lead and overload protection by circuit-breaker) Soft starter ll-range fuse Soft starter Semiconductor protection fuse 6 ) Circuit-breaker 1 ) Link module 2 ) Order No. Order No. Rated current Type of coordination 2: I q = 50 k at 400 V / 500 V Size Order No. Order No. Rated current Size Order No. Order No. Type of coordination 2: I q = 50 k at 400 V 3RW30 14 3NE18 14-0 7 ) 20 000 3RW30 14 3NE80 03 35 00 3RV10 11 3R19 11-1 3RW30 16 3NE18 15-0 7 ) 25 000 3RW30 16 3NE80 03 35 00 3RV10 11 3R19 11-1 3RW30 24 / 3RW31 24 3NE18 15-0 8 ) 25 000 3RW30 24 / 3RW31 24 3NE80 03 35 00 3RV10 21 3R19 21-1 3RW30 25 / 3RW31 25 3NE18 15-0 8 ) 25 000 3RW30 25 / 3RW31 25 3NE80 03 35 00 3RV10 21 3R19 21-1 3RW30 26 / 3RW31 26 3NE18 02-0 8 ) 40 000 3RW30 26 / 3RW31 26 10 ) 3RW30 34 3NE18 18-0 8 ) 63 000 3RW30 34 3NE80 22 125 00 3RV10 31 3R19 31-1 3RW30 35 3NE18 20-0 8 ) 80 000 3RW30 35 3NE80 24 160 00 3RV10 31 3R19 31-1 3RW30 36 3NE18 20-0 8 ) 80 000 3RW30 36 3NE80 24 160 00 3RV10 31 3R19 31-1 3RW30 44 3NE18 20-0 8 ) 80 000 3RW30 44 3NE80 24 160 00 3RV10 41 3R19 41-1 3RW30 45 3NE10 21-0 8 ) 100 00 3RW30 45 3NE80 24 160 00 3RV10 41 3R19 41-1 3RW30 46 9 ) 3RW30 46 3NE80 24 160 00 3RV10 41 3R19 41-1 The coordination types are explained in detail on page 5/25. 1) The motor s rated current defines the selection of units. 2) Pay attention to quantity units. 3) 50 mm distance required at the top and bottom from earthed parts. 4) I q = 50 k up to max. 400 V. 5) I q = 50 k up to max. 500 V. 6) If the motor feeder is to be assembled in accordance with UL regulations, -1 must be added to the order number of the fuse (example: 3NE80 24-1) 7) Fuse coordination for up to max. 400 V. 8) Fuse coordination for up to max. 500 V. 9) Fuse coordination with all-range fuse not possible; it may be necessary to take recourse to pure semiconductor protection fuses plus circuitbreakers. 10) Fuse coordination with semiconductor protection fuses not possible; it may be necessary to take recourse to pure all-range fuses 3NE1..-0 or the next highest soft starters. 5/55

Description pplication The SIRIUS solid-state soft starters are suitable for soft starting and stopping of threephase asynchronous machines. Thanks to two-phase control, the current is kept at minimum values in all three phases throughout the entire starting time. Thanks to continuous voltage influencing, current and torque peaks, which are unavoidable in the case of stardelta starters, for instance, do not occur. Service range Pumps, compressors, conveyor belts. Features Soft starting with voltage ramp; the adjustment range of the starting voltage U s ranges from 40 % to 100 % and the ramp time t R can be set from 0 s to 20 s. Soft running down with voltage ramp; the running down ramp time t off can be varied in the range from 0 s to 20s. t the same time, the switching-off voltage U off is dependent on the chosen starting voltage U s. Setting by means of three potentiometers Simple installation and commissioning Mains voltages at 50/60 Hz 200 V to 575 V Two control voltage outputs C/DC 24 V and C/DC 110 V to 230 V Wide temperature range from 25 C to +60 C Integrated bypass contacts to minimize dissipated power. dvice The 3RW solid-state soft starters are designed for simple starting conditions. In the event of deviating conditions or increased switching frequency, a larger unit must be selected. For an exact dimensioning, the special starting conditions must be observed. If necessary, an overload relay for heavy-starting must be selected where long starting times are involved. PTC thermistor detectors are recommended. This must be also observed with smooth running down. In this case an additional current load is effective compared with a free running down. No capacitive elements (e.g. correction equipment) may be contained in the motor feeder between SIRIUS soft starter 3RW3 and the motor. ll elements of the main circuit (e. g. fuses, switching devices and overload relays) should be dimensioned for direct starting, following the load short-circuit conditions. Fuses, switching devices and overload relays must be ordered separately. Equivalent circuit diagram: Power electronics 1 ) Soft starter in the Internet: http://www.ad.siemens.de/ sanftstarter Connection examples For control with switches or auxiliary contacts Control by switch Control via auxiliary contacts Control by switch in versions for pole-changing motors (for 3RW31 soft starters only) Control by contactor relays in versions for pole-changing motors (for 3RW31 soft starters only) 1) Equivalent circuit diagram applies only to 3RW30 1/2/3. In the case of 3RW30 4, the second phase is jumpered. 5/56

For control with pushbuttons Main circuit 1 ) State diagrams nschlußbeispiele uxiliary contacts (Sizes S0 to S3 only) S-Interface load feeder with SIRIUS soft starter Main circuit Control circuit Q1 = Circuit-breaker G1 = 3RW30 1. SIRIUS soft starter. X5 = Power connector Control with PLC When a 3RW3 is operated with a triac or a thyristor output, the leakage current at the PLC output should be < 1 m as otherwise the 3RW3 will interpret the resulting voltage drop at the input as an "On command". In the case of PLC outputs with a large leakage current, a remedy can be found in an RC network with > 100 nf and 220 Ω in series between "1N1" and terminal "2" of the 3RW30 (order No.: 3TX7 462-3T, see accessories). 1) s an alternative, the motor feeder can also be installed as a fuseless or as a fused version. See page 5/55 for details of fuse and switching device coordination. 5/57