Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

Similar documents
Position Indicator model MFC-300/IP. Technical Manual. Licht

ma/bcd Converter Model MFC-201 ma/bcd The MFC-201 ma/bcd Converter is a device designed to convert a DC current signal into BCD (8421) signals.

Modbus communication module for TCX2: AEX-MOD

PROCESS & TEMPERATURE CONTROLLERS

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

Fault indicator. Application. SPEF 3A2 C 1MRS MBG Issued: April 1999 Status: Updated Version: B/ Data subject to change without notice

Improve asset protection and utilization

GS1 Parameter Summary Detailed Parameter Listings...4 9

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

Advanced, accurate and intelligent monitoring for your transformer

WIRELESS MODBUS GATEWAY WGW410

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

VersaPoint I/O Module

M1 Series. Humidity - Temperature Transmitter INSTRUCTION MANUAL

ENGLISH. General features 2. Technical features 3. Installation 10. Preliminary operations 12. Front panel description 13.

K3P ENG.qxd 23/10/ Pagina 1

DPF-MAC Auto power factor controller

RCMS460 and RCMS490 Series

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES

PD300. Transformer, generator and motor protection Data sheet

Supercal 531 Multi function Integrator that lives up to Your highest expectations

Industrial Modbus I/O Modules

7 Function description 7.1 Digital filter Alarm output

Characteristics and functioning

isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw

B850 Boiler House Energy Monitor

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

Installation, Operation and Maintenance Manual

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

ioselect Z-NET Z-4RTD 4 Channel RTD Input Module

REF 610 Feeder Protection Relay. Technical Reference Manual

Selection guide. Communication accessories. Communication accessory selection guide. Characteristics

Measuring Transducer MT4xx series Programmable AC Current Transducer MT418

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

Programmable AC Current Transducer MT418

High Performance Process & Temperature Controllers

User s instructions. Page 1 sur 20 AXD-C / AAD-C / DVX-C / DVS-C : User s instructions B

DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters DSCL, DSCP, SCTP. Industrial Loop Isolators and Transmitters

R24 DISPLAY MODULE WITH ACTIVE OUTPUT AND RELAY

NX Series Inverters. HVAC Pocket Programming Guide

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

S11 Adjustable Speed Drive Engineering Specification

- SMART TUNE- PID CONTROL - UNIVERSAL, 3 WIRE- TC, RTD AND LINEAR INPUT - AUX- REMOTE SET POINT/ TRIM INPUT - 2x ISOLATED CONTROL AND RETRANSMISSION

SVM F22. Calculator for heating or cooling applications. Data sheet

B850 Boiler House Energy Monitor

presentation contents application advantages

OVEN INDUSTRIES, INC. Model 5C7-362

General Specifications

POWER DELEGATOR SERIES 7200A POWER DISTRIBUTION UNIT WITH POWER CONDITIONING GENERAL SPECIFICATIONS

Operation. Displayed channel. Measuring range. Status indication/ remote control Key lock Measuring mode/ time constant. Scale.

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

BAS Integration Manual

Programmable AC Voltage Transducer MT416

ISOMETER IRDH575. Approvals

Monitoring Electric Network Via Internet

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

VI 3 - i TABLE OF CONTENTS

CONTROL MANUAL. Dry-Pic 09PE - 09VE

FCR 06, FCR 12. Power factor correction controller. User and service manual

IDA 4 XM V 1.X. Installation and configuration of IDA 4 XM User Manual

CHAPTER 8 SUMMARY OF PARAMETER SETTINGS

TECO F510 Inverter. Quick Start Guide. Step 1. Supply & Motor connection

General Specifications

[u] u in. Case, polycarbonate IP20 Figure 1. Measured voltage and frequency pulse Wire connectors max 4 mm 2. output

Excellent low-cost Process & Temperature Controllers

ADJUSTABLE SPEED DRIVES FS1

General Specifications

Power Processor - Series 700F 10KVA to 150KVA

RETROFITTING. Motor Protection Relay. Two mountings are available, Flush Rear Connection (EDPAR) or Projecting Rear Connection (SDPAR).

Operating Instructions

E3 Adjustable Speed Drive Engineering Specification

ONE CALIBRATOR ONLY MAIN FEATURES:

Characteristics and functioning

Jacket heater, etc Mounting bracket for Pipe wrapping. (Optional) Temperature sensor. Output (To heater) (Optional)

TOSVERT TM VF-nC3 Parameter List

269 Troubleshooting Guide 11/4/98 1

S O P H I S T I C A T E D A U T O M A T I O N

General Specifications

Data Acquisition Modules/ Distributed IO Modules

Installation and Operating Instructions

T1 4-Channel transmitter

isolr275 / AGH-LR Digital Ground Fault Monitor / Ground Detector For Low-Resistance Ungrounded (Floating) AC/DC Systems

current transformers or VAC secondary voltage from our SIGNAL CONVERTERS Selection Chart

INSTRUCTION MANUAL Redox sensor M 1322 C

±50V Isolated, 3.0V to 5.5V, 250kbps, 2 Tx/2 Rx, RS-232 Transceiver MAX3250

NPRG860 NPRG870 REGULATION. Automatic Synchronizer for Generator

KNX Powerline PL 110. KNX Association

MICRO-CONTROLLER X (48 48 mm)

R&D TECHNICAL SPECIFI

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

GPRS-A. Universal monitoring module. Firmware version 1.00 gprs-a_en 04/18

Portable Appliance Testers. OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver Code No

PID CONTROLLERS LT SERIES

N1040i Indicator. UNIVERSAL INDICATOR INSTRUCTIONS MANUAL V1.0x D PRESENTATION FEATURES

ENGLISH ENGLISH ENGLISH ENGLISH. Installation and User Manual version 1.03 TLB4 2014/30/UE EN55022:2010 EN :2005 EN :2007

SRA 2250/6 RESISTOR ARS-01 RESISTOR AUTOMATICS

Shaft Absolute Vibration Monitor Specifications

Transcription:

Temperature Controller model MFC-301/T-Dry Version for Dry Transformers and Motors Technical Manual Licht

Contents 1 Introduction 2 2 Operating principle 3 2.1 General principle 3 2.2 RTD operation 3 3 Front panel indication 5 4 Configuration 6 4.1 Parameter reset 6 5 Programmable parameters 7 5.1 Current outputs (option) 8 5.2 MODBUS protocol 9 5.3 DNP3 protocol (option) 9 5.4 Clock 10 A Specifications 11 B Housing diagrams 12 C Connection diagrams 13 D MODBUS registers 16 Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 1

Licht 1 Introduction The MFC-301/T-Dry is a precise, highly reliable and versatile microcontrolled protection system for dry transformers and motors. It is designed to read, infer, display and transmit the temperatures of up to 6 RTDs (resistance temperature detectors), and to activate alarm, cooling and shutdown systems whenever necessary. Among its features, we highlight: up to 6 compensated and auto-calibrated RTD inputs for temperature measurement, 1 isolated RS-485 line, independent relays for cooling, alarm, trip and failure, independent set-points for cooling, alarm and trip and a current loop output (optional). Versions with up to 5 relays may be supplied on special order. The temperature acquisition is performed with 16-bit resolution. All DC signals are sampled after a 50/60 Hz filter with a rejection band attenuation greater than 100 db. The MFC-301/T-Dry presents pairwise galvanic isolation between signal inputs, power supply, current outputs and the RS-485 port. It features a universal 80-260 Vdc/Vac power supply. All signals that enter and exit the controller are pairwise galvanically isolated, preventing potentially damaging noise and transients from being transferred between subcircuits or retransmitted to other devices. Figure 1.1 MFC-301/T-Dry Controller Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 2

2 Operating principle 2.1 General principle The MFC-301/T-Dry s main purpose is to monitor transformer temperatures and activate cooling systems or protection systems whenever necessary. It features up to 6 RTD inputs, which are automatically compensated for cable length and linearized for each sensor s standardized temperature response. The standard MFC-301/T-Dry configuration for dry transformers and motors features 4 relays, associated with cooling, alarm, trip and failure events. Each RTD has associated cooling, alarm and trip set points. For instance, if the cooling set point associated with RTD 2 is configured to 80 C and this RTD s temperature exceeds this value, the MFC- 301/T-Dry activates the forced cooling relay, regardless of the states of the other RTDs. Each relay features a hysteresis, whose purpose is to prevent intermittent activations whenever the temperature oscilates around a configured set point. For example, if the cooling hysteresis is configured to 2 C, then in the example above the cooling relay will only be deativated once RTD 2 s temperature drops below 80 2 = 78 C. Relays dedicated to cooling functions may also be activated once per day at a configurable time and remain active for a configurable duration. The daily activation of cooling pumps or fans is desirable in cold climates in order to keep mechanical parts well lubricated and to prevent the accumulation of dirt. During normal operation, the temperature maximum for each RTD is registered in nonvolatile memory. These values may be reset with a user command. The MFC-301/T-Dry can may also feature a current loop output with 16-bit resolution (maximum measured temperature among all the RTDs), and with scales configurable to 0-1, 0-5, 0-10, 0-20 or 4-20 ma. 2.2 RTD operation The MFC-301/T-Dry continuously monitors the state of each RTD and its connection, and automatically ignores sensors which are absent or which present abnormal behavior. If the user wishes to install less RTDs than the maximum allowed by the equipment, the parameter Qty. of Active RTDs should be set. The following events are identified as RTD faults: Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 3

Measured temperature below 0 C or above 255 C. Temperature variation rate exceeding 20 C/s. Detection of inconsistencies in the measurement circuit. Any of the events above triggers the activation of the RTD fault relay, the activation of the cooling relay and the inhibition of future relay operations associated with the faulty RTD. Once the originating fault is resolved (for example, by replacing a damaged RTD), the system returns to normal operation after a 30 second delay. Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 4

3 Front panel indication During normal operation, the MFC-301/T-Dry alternates between displaying each channel s value. The type of indication can be chosen between Temperature and Resistance. In the Temperature display, the presented values are those measured by the RTDs, compensated for each sensor s intrinsic nonlinearity and cable resistances. The Resistance option presents the physical RTD resistances read by the MFC-301/T-Dry in Ω, (without the cable resistances). The indication type can be temporarily altered by pressing the and keys. Licht www.licht-labs.com MULTI FUNCTION CONTROLLER MFC-301 P RTD 1: RTD 2: VF AL TR F Re 63.0 C 86.4 C C Figure 3.1 Front Panel Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 5

4 Configuration The MFC-301/T-Dry features 4 keys to access its functions. The procedure to configure any parameter is as follows: 1. Press the P key to enter the parameters menu. 2. Enter the currently configured 4 letter password one letter at a time, using the and keys to select each letter and P to advance between letters. The default password is AAAA. 3. Using the and keys, choose the desired parameter. 4. Press P to confirm the parameter s selection. 5. Choose the desired value with the and keys. 6. Confirm pressing P. By holding down the or keys it is possible to advance through the options faster. The configuration sequence can be cancelled at any time by pressing C. 4.1 Parameter reset The MFC-301/T-Dry can be reset to factory settings. This procedure also resets its password to AAAA. To do so, power up the device while pressing C. Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 6

5 Programmable parameters The MFC-301/T-Dry was developed to provide the user with the greatest possible flexiblity, such that all supervision and configuration can be executed on-site through the keyboard or remotely via the RS-485 link. We define all user-configurable parameters as follows. Parameter: Fan Set Point [1-6] Options: 0 to 255 C, in increments of 1 C. Description: Temperature set point for activating the cooling relay associated with each RTD. Parameter: Alarm Set Point [1-6] Options: 0 to 255 C, in increments of 1 C. Description: Temperature set point for activating the alarm relay associated with each RTD. Parameter: Trip Set Point [1-6] Options: 0 to 255 C, in increments of 1 C. Description: Temperature set point for activating the trip relay associated with each RTD. Parameter: Indication Type Options: Temperature, Resistance. Description: Type of values indicated on the MFC-301/T-Dry s front panel. Parameter: Number of Active RTDs Options: 1 to 6. Description: Quantity of installed RTDs. Parameter: Fan Hysteresis Options: 1 to 255 C, in increments of 1 C. Description: Temperature hysteresis for the deactivation of the cooling relay. Parameter: Alarm Hysteresis Options: 1 to 255 C, in increments of 1 C. Description: Temperature hysteresis for the deactivation of the alarm relay. Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 7

Parameter: Trip Hysteresis Options: 1 to 255 C, in increments of 1 C. Description: Temperature hysteresis for the deactivation of the trip relay. Parameter: Fan Delay Options: 0.1 to 25.5 minutes, in increments of 0.1 minute. Description: Delay for the activation of the cooling relay. Parameter: Alarm Delay Options: 0.1 to 25.5 minutes, in increments of 0.1 minute. Description: Delay for the activation of the alarm relay. Parameter: Trip Delay Options: 0.1 to 25.5 minutes, in increments of 0.1 minute. Description: Delay for the activation of the trip relay. Parameter: Daily Cooling (Start) Options: 00:00 to 23:59, in increments of 1 minute. Description: Time of day at which all cooling relays are forcefully activated. Use this option to ensure the adequate lubrication of fans and pumps in cold climates. Parameter: Daily Cooling (Duration) Options: Disabled, or 1 to 999 minutes, in increments of 1 minute. Description: Duration of the forced cooling cycle. 5.1 Current outputs (option) Parameter: Output Scale Options: 0-1, 0-5, 0-10, 0-20, 4-20 ma Description: Refers to the various configurable current loop scales. Parameter: T FS Options: 0 to 255 C, in increments of 1 C. Description: Full scale for the maximum of the RTD temperatures. For example, if T FS = 150 C and Output Scale = 4-20 ma, the displayed temperature will be 0 C for 4.0 ma and 150 C for 20.0 ma. Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 8

5.2 MODBUS protocol Parameter: Baud Rate Options: 9600, 19200, 38400, 57600, 115200 bps. Description: baud rate for the RS-485 link. Parameter: Format Options: 8N1, 8E1, 8O1, 8N2. Description: symbol transmission format, where: 8N1: 8 data bits, no parity, 1 stop bit. 8E1: 8 data bits, even parity, 1 stop bit. 8O1: 8 data bits, odd parity, 1 stop bit. 8N2: 8 data bits, no parity, 2 stop bits. Parameter: Address Options: 1 to 247. Description: MODBUS address for the MFC-301/T-Dry. 5.3 DNP3 protocol (option) Parameter: Baud Rate Options: 9600, 19200, 38400, 57600, 115200 bps. Description: baud rate for the RS-485 link. Parameter: Format Options: 8N1, 8E1, 8O1, 8N2. Description: symbol transmission format, where: 8N1: 8 data bits, no parity, 1 stop bit. 8E1: 8 data bits, even parity, 1 stop bit. 8O1: 8 data bits, odd parity, 1 stop bit. 8N2: 8 data bits, no parity, 2 stop bits. Parameter: Address Options: 0x0000 to 0xFFEF. Description: DNP3 outstation address in hexadecimal notation. Parameter: Application Layer Confirmation Options: Only when transmitting events or multi-fragment responses, Always. Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 9

Description: Selects when the MFC-301/T-Dry outstation should request application layer confirmations. Parameter: Maximum Inter-Octet Gap Options: 2 to 100 ms. Description: The DNP3 specification states that frames should not have inter-octet gaps. In accordance, the MFC-301/T-Dry never inserts inter-octet gaps when transmitting data. However, we allow the option to tolerate gaps in incoming transmissions. Frames featuring inter-octet gaps larger than the Maximum Inter-Octet Gap will be quietly dropped. Parameter: Backoff Delay (Fixed) Options: 1 to 100 ms. Description: See description for Backoff Delay (Random). Parameter: Backoff Delay (Random) Options: 1 to 100 ms. Description: The MFC-301/T-Dry is designed for multi-drop scenarios where more than one outstation may transmit over the same line. To handle collision avoidance, a backoff scheme is implemented. Before transmitting, the MFC-301/T-Dry always waits for the line to become idle. Once that happens, it waits for T delay = T fixed + T random ms, where T fixed is the fixed backoff delay and T random is a random value, uniformly distributed between 0 and the random backoff delay parameter. If after T delay ms the line is still idle, then the MFC-301/T-Dry begins transmission. Parameter: Insert Inter-frame Gap Options: Never, Always. Description: The DNP3 specification states that no inter-frame gaps are required. However, some masters have been observed to drop frames when no inter-frame gaps are provided. This option allows communicating with such non-compliant devices. We discourage its use, given that the forced inter-frame gap implies a forced backoff-delay. 5.4 Clock Parameter: Date/Time Options: HH:MM:SS DD/MM/YYYY Description: sets the local date and time. Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 10

A Specifications Power Supply Power Consumption Operating Temperature Enclosure Rating Mounting Options Dimensions Weight DC Inputs Current Outputs Galvanic Isolation (60 Hz, 1 min.) Communication Displays Relays Isolated, 80-260 Vac/Vdc. 3 W -10 to 70 C (LCD display) -40 to 70 C (VFD display) IP20 Panel-mounted 96 x 48 x 135 mm 320 g Types: RTD, current loop, voltage Error/Non-linearity: 0.2% + 0.1% / 10 C Scales: 0-1, 0-5, 0-10, 0-20, 4-20 ma Error/Non-linearity: 0.2% + 0.1% / 10 C Ground 2.0 kv Auxiliary Power 2.0 kv PT100 entries 2.0 kv RS-485 2.0 kv Current outputs 2.0 kv Relays 3.0 kv RS-485 - MODBUS RTU or DNP3 9600, 19200, 38400, 57600, 115200 bps 8N1, 8E1, 8O1, 8N2 2 lines, 16 characters each (5 mm). LCD with backlight or VFD. 10 A @ 250 Vac, 0.5 A @ 125 Vdc Galvanic Isolation: 3.0 kv, 60 Hz, 1 min. Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 11

B Housing diagrams Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 12

C Connection diagrams Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 13

Important considerations The installation of electronic devices in substations should conform with the recommendations given by recent international standards. The most recent and detailed guide for installations is IEC 61000-5-2:1997, which was based on decades of laboratory and field research. We summarize below some of the guidelines contained in IEC 61000-5-2:1997. For further reading, we recommend the articles and application notes available on our web site. a. Shielded cables must be used for connecting RTDs, current loop outputs, RS-485 links and the auxiliary supply. b. Cables must be segregated in trays, ducts or conduits according to their functions. In particular, power cables must never be routed in the proximity of signal cables, even if these are shielded. The minimum distances which must be observed are described in IEC 61000-5-2:1997 and in articles available on-line at this product s web page. c. The electrical continuity of cables, ducts, trays and conduits must be preserved up to frequencies in the order of MHz, over all their extension, including curves and junctions. In order to guarantee this continuity, joints and bonds should present electrical contact along each cable, duct or tray s transversal section. In particular, trays should be bonded with seam-welded joints (best), U-brackets with multiple fixings (ok) and never with wires. d. Shielded cables should present no gaps in their screens along their lengths. 360 bonding should be performed instead. e. Should there be unshielded sections (for example, near terminal block connections), these should be short as possible. f. Trays, ducts and conduits must be electrically continuous, and must be grounded at both ends. In this configuration, trays, ducts and conduits provide shielding and also perform as parallel earth conductors. g. Shielded cables should also have their screens bonded at both ends. It is extremely important that the tray, duct or conduit which contains each cable is also grounded at both ends, allowing it to perform as a parallel earth conductor. In the absence of a parallel earth condutor, the cable screens will be exposed to extremely high currents which will severely compromise their operation. h. RS-485 pairs must be terminated at both ends by 120 Ω resistors. Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 14

i. RS-485 devices must be connected in a bus topology. No other network topology (tree, star, ring, etc.) is acceptable. j. Dry contact inputs (if applicable) must free of potentials. Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 15

D MODBUS registers The MFC-301 implements the Read Holding Register (0x03), Write Single Register (0x06) and Write Multiple Register (0x10) MODBUS RTU functions. A frame referring to any other function will be answered with an "unsupported function code" exception. We present below the table of remotely accessible registers. Register Description Values Multiplier 1-6 Fan Set Point [1-6] 0 to 255 C 1 21-26 Alarm Set Point [1-6] 0 to 255 C 1 41-46 Trip Set Point [1-6] 0 to 255 C 1 201 Indication Type 0: temperature 1: resistance 202 Number of Active RTDs 1 to 6 1 203 Fan Hysteresis 1 to 255 C 1 204 Alarm Hysteresis 1 to 255 C 1 205 Trip Hysteresis 1 to 255 C 1 206 Fan Delay 0.1 to 25.5 minutes 1 207 Alarm Delay 0.1 to 25.5 minutes 1 208 Trip Delay 0.1 to 25.5 minutes 1 209 Daily Cooling (Start) 0 to 1439 (in minutes from 00:00) 210 Daily Cooling (Duration) 0 to 999 1 1 1 301 Current Loop - Output Scale 0: 0-1 ma 1: 0-5 ma 2: 0-10 ma 3: 0-20 ma 4: 0-20 ma 302 T FS 0 to 255 C 1 1 401 Local Hour 0 to 23 1 402 Local Minute 0 to 59 1 403 Local Second 0 to 59 1 404 Local Day 1 to 31 1 405 Local Month 1 to 12 1 406 Local Year (2000-2099) 0 to 99 1 Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 16

Register Description Values Multiplier 501 RTD1 Temperature 0.0 to 255.0 C 10 502 RTD1 Resistance 0.0 to 255.0 Ω 10 503 RTD2 Temperature 0.0 to 255.0 C 10 504 RTD2 Resistance 0.0 to 255.0 Ω 10 505 RTD3 Temperature 0.0 to 255.0 C 10 506 RTD3 Resistance 0.0 to 255.0 Ω 10 507 RTD4 Temperature 0.0 to 255.0 C 10 508 RTD4 Resistance 0.0 to 255.0 Ω 10 509 RTD5 Temperature 0.0 to 255.0 C 10 510 RTD5 Resistance 0.0 to 255.0 Ω 10 511 RTD6 Temperature 0.0 to 255.0 C 10 512 RTD6 Resistance 0.0 to 255.0 Ω 10 521-526 RTD State[1-6] bit 0: enabled bit 1: activated fan bit 2: activated alarm bit 3: activated trip bit 4: RTD failure 1 541-546 Maximum Temperature[1-6] 0.0 to 255.0 C Write to reset 10 Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 17

Rev. A0 (30 05 12) MFC-301/T-Dry Technical Manual 18