CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER

Similar documents
An Overview of Diagnostic Testing of Medium Voltage Power Cables John Densley

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation

Partial discharge diagnostics on very long and branched cable circuits

Investigation of PD Detection on XLPE Cables

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

Return to Session BREAKDOWN CAUSED BY ABRUPT DC-VOLTAGE GROUNDING OF XLPE CABLE INSULATION ABSTRACT KEYWORDS INTRODUCTION

ON-LINE PARTIAL DISCHARGE TESTING OF SOME OF THE WORST PERFORMING CIRCUITS ON A UTILITY DISTRIBUTION SYSTEM

Partial Discharge Patterns in High Voltage Insulation

USING DAMPED AC VOLTAGES

HVA SERIES VLF TEST SETS. Hipot Testers HVA Series for VLF (0.1 Hz) testing of MV and HV cables.

Cable testing and diagnostics

IDAX 300 Insulation Diagnostic Analyzer. Dielectric Frequency Response Also known as: Frequency Domain Spectroscopy

PHG 70 TD PD / PHG 80 TD PD

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

PD Testing Considerations for MV Plant Cables

NEW MV CABLE ACCESSORY WITH EMBEDDED SENSOR TO CHECK PARTIAL DISCHARGE ACTIVITY

DIELECTRIC HEATING IN INSULATING MATERIALS AT HIGH DC AND AC VOLTAGES SUPERIMPOSED BY HIGH FREQUENCY HIGH VOLTAGES

Field Measurement of Transmission Cable Dissipation Factor

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Non-intrusive Measurement of Partial Discharge and its Extraction Using Short Time Fourier Transform

Investigations on a Combined Resonance/VLF HV Test System Partial Discharge (PD) characteristics at VLF and DAC voltages

Testing 320 kv HVDC XLPE Cable System

Field Experiences. Partial Discharge Diagnosis on MV Cables. Philipp Legler. XVI. Szigetelésdiagnosztikai Konferencia (

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

INSULATION DIAGNOSIS OF HIGH VOLTAGE POWER CABLES

Discipline Electrical Testing Issue Date Certificate Number T-2837 Valid Until Last Amended on - Page 1 of 6 LOCATION 1

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

Specialists in HV and MV test and diagnostics. Testing in Substations

INVESTIGATION ON THE TECHNOLOGIES FOR DEFECT LOCALIZATION AND CHARACTERIZATION ON MEDIUM VOLTAGE UNDERGROUND LINES

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

A Study on the Effect of Performing VLF Withstand Tests on Field Aged Degraded Joints

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Cable diagnostic in MV underground cable networks

A New Approach for Transformer Bushing Monitoring. Emilio Morales Technical Application Specialist Qualitrol

Partial Discharge Inception and Propagation Characteristics of Magnet Wire for Inverter-fed Motor under Surge Voltage Application

Design of HV Switching for Polarization & Depolarization Current Measurement

Matz Ohlen Director Transformer Test Systems. Megger Sweden

Harmonic Components Analysis of Leakage Current for Standard and Anti-Fog Suspension Insulators under Humidity Conditions

VLF. DAC tandelta. Partial Discharge. Experience the world of Megger electrical testing

Why is water killing power transformer insulation? Water is a slow but deadly poison for power transformers

Statistical Characteristics of Partial Discharge Caused by Typical Defects in Cable Joint under Oscillating Voltage

Simultaneous Partial Discharge and Tan Delta Measurements: New Technology in Cable Diagnostics

Extending the Functionality of On-line PD Monitoring Equipment for MV Power Cables

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

High Voltage Engineering

H V T E S T S O L U T I O N S PA RT N E RS F O R H V & E M C

BEST PRACTICES FOR OFFLINE DIAGNOSIS OF MV CABLES

Electrical Power Engineering Group, School of Electronics and Computer Science, University of Southampton, Highfield, Southampton, SO17 1BJ, UK 2

SENSITIVITY ASPECTS OF ON-LINE PD DIAGNOSIS OF MV POWER CABLES

Off-Line Field Diagnostics for MV and HV Oil-Paper Insulated Cables

PERMANENT ON-LINE MONITORING OF MV POWER CABLES BASED ON PARTIAL DISCHARGE DETECTION AND LOCALISATION AN UPDATE

Dielectric analysis of high-voltage power transformers DIAGNOSIS ABSTRACT KEYWORDS. 1. Introduction

A6.6 9 th International Conference on Insulated Power Cables A6.6

ECE2019 Sensors, Signals, and Systems A Lab #6: Electromagnetic Field Sensing

Experiment 4: Grounding and Shielding

MV Power Cable Testing Training

Long lengths transmission power cables on-site testing up to 500 kv by damped AC voltages

High Voltage Diagnostics Sarl 4, Rue de Lac CH 1897 Le Bouveret Switzerland

Experiment 5: Grounding and Shielding

Strathprints Institutional Repository

ELEC-E8409 High Voltage Engineering. Condition Monitoring of Power Cables

3 THE REVIEW OF DISSERTATION

EE273 Lecture 3 More about Wires Lossy Wires, Multi-Drop Buses, and Balanced Lines. Today s Assignment

HV AC TESTING OF SUPER-LONG CABLES

Online Localisation of Partial Discharge Using Pulse Propagation Parameters in Medium Voltage Cable Network

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Cable fault location in power cables. Systematics for cable testing, diagnosis and cable fault location

PARTIAL DISCHARGE LOCATION Selected Topics

5. Transducers Definition and General Concept of Transducer Classification of Transducers

Variation in SFRA plot due to design and external parameter

Impact of Contact Pressure on Breakdown Strength of Solid-Solid Interfaces

Evaluation of Distribution Line Spacers Located Near the Coast

Practical aspects of PD localization for long length Power Cables

EI HIGH VOLTAGE INSULATION TESTING POLICY

NOVEL METHOD FOR ON-SITE TESTING AND DIAGNOSIS OF TRANSMISSION CABELS UP TO 250KV

CIGRE- AORC Technical Meeting 2016 and International Conference on Global Trends in the Development of Power T&D System including Smart Grid

Be on guard for effective testing: Introduction

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Jean Carlos Hernández Mejía International Conference of Doble Clients Boston, MA, USA March 25 - March 30, GTRI/DoE Disclaimer

INVENTION DISCLOSURE- ELECTRONICS SUBJECT MATTER IMPEDANCE MATCHING ANTENNA-INTEGRATED HIGH-EFFICIENCY ENERGY HARVESTING CIRCUIT

Maximum Lightning Overvoltage along a Cable due to Shielding Failure

ONLINE OFFLINE B Y WIL L IAM H IG INBOT H AM,

Prognostic Modeling for Electrical Treeing in Solid Insulation using Pulse Sequence Analysis

ECP HV INSULATION TESTING

Abstract. 1 Introduction

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

Experimental Challenges when Measuring Partial Discharges under Combined DC and High Frequency AC Voltage

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

ICC PES Spring 2011 Meeting, Educational Session Luigi Testa, Alfred Mendelsohn

Coherence and time-frequency analysis of impulse voltage and current measurements

6 - Stage Marx Generator

IN HOUSE CALIBRATION OF PD DETECTOR SYSTEM FOR FIELD TEST RESULT RELIABILITY

Breakdown in short rod-plane air gaps under positive lightning impulse stress

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

CIGRE General Session, Paris 2014 Group Meeting SC B1 Insulated Cables, 27th August, 2014 Results of CAG Questionnaire

Transcription:

CONDITION ASSESSMENT OF XLPE MV CABLE JOINTS BY USING AN INSULATION TESTER Henrik ENOKSEN Espen EBERG Sverre HVIDSTEN SINTEF Energy Research - Norway SINTEF Energy Research - Norway SINTEF Energy Research - Norway henrik.enoksen@sintef.no espen.eberg@sintef.no sverre.hvidsten@sintef.no Ole Johan HATLEN BKK - Norway ole-johan.hatlen@bkk.no Eva A. ROGNSVAAG BKK - Norway Eva.Rognsvag@bkk.no ABSTRACT Condition assessment of water treeing in medium voltage XLPE cable insulations by tan δ measurements is well established. If a measured cable section has one or more joints with low insulation resistance, the assessment of the complete cable link can be difficult as the tan δ is significantly higher for the joints than for the cable insulation. This paper describes a simple method based on using an insulation tester to reveal if joints with low resistance are present in the cable link. Measurements have been performed on cable samples taken from service after more than 20 years due to high tan δ values and partial discharges located in the cable. The joints were characterized in the laboratory by time domain dielectric response and dielectric spectroscopy. It has been shown that both the polarization and depolarization currents should be used during the assessment to provide robust evaluation criteria to distinguish the response of a low resistance joint from heavily water treed cable insulations avoiding misinterpretation of the cable condition. This method should be used before applying any other diagnostic equipment. INTRODUCTION In Norway it has been observed that many medium voltage (12 and 24 kv) cable sections with one or several heat shrink joints have a very low insulation resistance. This is especially observed for XLPE cables installed in the 80s, which constitutes a significant amount of the installed cables in the network. The low resistance values can typically be in the range of 0.1 10 GΩ making condition assessment of the cable sections not feasible by using very low frequency (VLF) tan δ testing at 0.1 Hz [1]. Moreover, the presence of low resistance joints can likely lead to misinterpretation of the cable condition. Even though the cable itself is in good condition, the assessment based on the on-site diagnostic testing can conclude that the cable is severely water tree degraded. The diagnostic criteria enclosed with the diagnostic equipment do likely not take the challenge of joints into account. The main purpose of this paper is to propose a methodology to be able to distinguish the response of a severely water tree degraded cable from a cable with no water trees but with a heat shrink joint with low resistance. This work includes measurements on cable joints removed from service. The methodology is mainly based on measurements using a simple DC insulation tester. THEORY When applying a DC voltage across the cable insulation, the conductivity of the insulation and the dielectric displacement will contribute to the displacement (polarization) current, expressed by J(t) = σe(t) + dd(t) (1) dd where σ is the conductivity, E is the electric field, and D is the electric displacement field of the insulation [2]. After some time, all the molecules are polarized and thus the dielectric displacement current vanishes. At this point, there is only a steady state conductive current flowing through the insulation. When the cable insulation is short-circuited, the polarized molecules will relax to their original orientation/position. Consequently, a new current will flow in the opposite direction of that of the polarization current. However, as the applied voltage is zero during this period, there is no contribution from the conductivity. This current is called the depolarization current. A typical behavior of the polarization and depolarization currents is shown in Figure 1. Figure 1: Illustration of polarization (I ppp ) and depolarization (I ddddd ) currents as a function of time. CIRED 2015 1/5

Expressing Eq. (1) in frequency domain, and assuming that the permittivity is complex, yields J(ω) = (σ + ωε )E(ω) + jjj E(ω) (2) where ω is the frequency, and ε and ε are the real and imaginary parts of the permittivity, respectively. The loss tangent is defined as tan δ = C (ω) σ + ωε (3) C = (ω) ωω where C and C are the real and imaginary part of the test object's capacitance [2]. It is essentially the ratio between the resistive part and the capacitive part of the cable. If the test object is a long cable with a joint, the resulting loss tangent can be calculated as tan δ = C ccccc + C jjjjj (4) C ccccc + C jjjjj If the cable is much longer than the joint, then C jjjjj C ccccc, and if the cable insulation is XLPE, then C ccccc C jjjjj. Consequently, Eq. (4) can be approximated as tan δ C jjjjj (5) C ccccc EXPERIMENTAL WORK Test object This work includes on-site measurements on a 469 m long 24 kv three-phase wet designed XLPE insulated power cable (U 0 =12 kv) that was installed in 1985. After the on-site measurements, a 30 m long section was removed for further on-site measurements and characterisation in the laboratory. It was important to not mechanically strain the cable section during the removal and therefore a mechanical support was carefully attached to the cable during the handling. At the centre of the removed cable a heat-shrink joint was present. Each of the joints was immediately covered with aluminium and plastic foils to prevent any moisture to escape from or diffuse into the joint materials. For practical reasons, the cable section used in the laboratory was reduced to 2.5 m with the joint positioned at the centre of the section. Diagnostic testing in service Partial discharges (PDs) and the dielectric loss tangent were measured at voltages from 6 kv to 25 kv using commercially available VLF equipment (0.1 Hz). After testing in service, the 30 m long cable was removed from service. Then, additional on-site PD measurements were performed on the removed section. Diagnostic testing in the laboratory Water tree examination Ten 20 cm long cable sections with removed strippable insulation screens were immersed in 90 C water for one month. Afterwards, the pieces were visually checked for very long (bridging) vented water trees. Dielectric spectroscopy The loss tangent was measured at RMS voltages 2.5/ 2, 5/ 2, 6, and 12 kv. The first two magnitudes were chosen in order to make direct comparisons with the results with the DC polarization and depolarization current measurements. The latter two voltages were selected to compare the results from the laboratory and service measurements. The voltage frequencies range from 0.01 to 100 Hz. After the measurements at 5/ 2 kv, a second measurement at 2.5/ 2 kv was performed to examine the reproducibility of the measurements (hysteresis). The same was done at 6 kv after 12 kv. PD free terminations and guard electrodes were installed prior to the laboratory measurements. Time domain dielectric response measurements Two different measurement setups were used to perform time domain dielectric response measurements. First, a conventional DC insulation tester was used. Here, the polarization and depolarization currents were measured at 0.5, 1, 2.5, and 5 kv for 10 and 5 minutes, respectively. Another measurement was performed at 2.5 kv after 5 kv to check for hysteresis. A guard electrode was used to remove spurious surface currents. Then, the measurements were repeated with a more sensitive experimental setup including a stable high voltage DC source and a picoamperemeter. The purpose of these measurements was to examine the accuracy of the currents measured with the insulation tester. Figure 2 shows the measurement circuit for the latter setup. The measurement circuit of the insulation tester is principally the same. During these measurements, the joint was placed inside a plastic tube covered with aluminium foil connected to ground which shields the measurement electrode from outside noise. Figure 2: Illustration of experimental setup. (1) FUG 65 kv HVDC source, (2) 70 kv HV switch, (3) cable joint, (4) Keithley 6485 picoamperemeter, (5) 6 kv HV switch, and (6) aluminium covered tube connected to ground. The resistors, R, are 50 MΩ. RESULTS AND DISCUSSION Diagnostic testing in service The measurements in service were performed at 0.1 Hz and are summarized in Table 1 and Table 2. CIRED 2015 2/5

Table 1: PD results before and after removing the cable from service. The cable length before removal is 469 m, while it is 30 m after removal. U 0 = 12 kv. Note that the phases are labelled differently before and after removal. Phase PD before [pc] PD after [pc] U 0 2U 0 U 0 2U 0 F1 0 0 100-200 1000-2000 F2 0 500-1200 500-1600 3000-9000 F3 150-300 200-700 0 0 Table 2: Loss tangent results before removing the 469 m long cable from service. Results are taken from measurements at 0.1 Hz. Phase tan δ [10 3 ], 6 kv tan δ [10 3 ], 12 kv F1 18.9 27.1 F2 11.4 17.8 F3 12.7 20.7 High numbers and magnitudes of partial discharges were measured for the 469 m long cable. The loss tangent measurements were stopped at 12 kv (U 0 ) due to very high values. Due to the partial discharges and the high loss tangents, a 30 meter long cable section was removed with the discharge site at the centre of this section. Partial discharges were re-measured on the 30 m section. Again, the PDs were located at the centre of the cable where it was observed that a joint was positioned. The magnitudes were even higher than before removal. The lower magnitudes before removal are likely due to the attenuation and dispersion of the much longer cable. According to the procedure issued by the manufacturer of the equipment, the tan δ results indicated that all phases were severely water-treed. However, the presence of a low resistance joint can also cause very high loss tangents [1], and thus lead to wrong conclusions about the complete cable. The joint could likely be the cause of both the partial discharges and the high dielectric loss tangents. Note that the phases were not labelled when the cable was removed from service. Hence, it is not possible to compare directly the results obtained from service with the results obtained in the laboratory. Diagnostic testing in the laboratory When removing the outer sheath of the cable, it was observed that the joints had likely experienced overheating as visible deformations were seen on the joint body surfaces. Table 3: Loss tangent results from the laboratory. Results are taken from measurements at 12 kv and 0.1 Hz. Phase tan δ [10 3 ] Corrected tan δ [10 3 ] L1 99.6 30.3 L2 472 144 L3 256 77.9 Water tree examination The visual examination of the cable sections showed no visible large bridging water trees. Consequently, this indicates that the cable was most likely not severely water tree degraded. Dielectric spectroscopy The loss tangent values measured in the laboratory are even higher than those measured in service. Table 3 shows the loss tangent for all phases measured at 12 kv at 0.1 Hz. Note that these measurements are performed on the joints only. Hence, a corrected value is calculated with Eq. (5) to account for the cable length (469 m) present when measuring in service. When calculating this value it is assumed that the cable has low losses, as expected for moderately service aged XLPE cables of this design [2, 3]. Figure 3 shows the loss tangent as a function of frequency for different voltages for phase L2. The other two phases show similar frequency and voltage dependencies, although with lower magnitudes as observed in Table 3. The great increase in the loss tangents at low frequencies indicates that the conductivity of the joint is large, see Eq. (3). This is most likely caused by high water content in the joint [4]. One possible reason for obtaining much higher loss tangents in the laboratory than in service, even after correcting for the cable length, could be presence of condensed water at interfaces in the joint. In any case, these results strongly indicate that the joint is the cause of the high loss tangents measured in service. Hence, there is no indication of severe water tree degrading in the cable. The dotted lines of Figure 3 show the second measurements of 2.5/ 2 kv and 6 kv performed after 5/ 2 kv and 12 kv, respectively. These results indicate slight hysteresis in the loss tangent. In the case of bridging water trees, the hysteresis should be significantly larger [3]. Figure 3: Loss tangent as a function of frequency for different voltages for phase L2 measured in the lab. CIRED 2015 3/5

Time domain dielectric response measurements Figure 4 and Figure 5 show the polarization and depolarization currents, respectively, for phase L1 at 500 V and 5 kv measured with the insulation tester and the laboratory setup. Results for voltages 1 kv and 2.5 kv, and the other two phases are not shown, though the measurements at these voltages show similar magnitudes. As instrumental current transients from the insulation tester disturb the measurements during the first 30 seconds, these are omitted. It is observed that the difference between the currents measured by the two setups is very small and can for practical purposes be neglected in this range. reason can be an increase in the conductivity induced by overheating causing material oxidation. Moreover, the currents at 5 kv display an unstable oscillatory behavior for L2, and for L1 and L3 the currents increase with time as shown in Figure 6. This may be caused by movement of condensed water located at the interfaces between the different parts of the joint. Figure 6: Polarization currents measured with the insulation tester for all phases at 5 kv shown at a linear scale. Figure 4: Polarization currents measured with a picoamperemeter (solid lines with downwards triangles) and the insulation tester (dashed lines with circles) for phase L1 at 0.5 kv and 5 kv. Figure 7 shows that the polarization currents have a significant voltage dependence. It has previously been shown that high water content in the joint materials will make the conductivity voltage dependent [4] as indicated in Figure 4. Hence, it is likely that this joint has absorbed a significant amount of moisture during its service. Figure 5: Depolarization currents measured with a picoamperemeter (solid lines with downwards triangles) and the insulation tester (dashed lines with circles) for phase L1 at 0.5 kv and 5 kv. According to theory, the polarization current should relax to a steady conductive current after the polarization processes are diminished, see Eq. (1). The measured polarization current magnitudes are however very large compared to the depolarization currents even after short times and low voltages. This indicates a large contribution from the conductivity of the joint. The origin of the low resistance (high conductivity) could be increased moisture content of the joints [4]. Another Figure 7: Polarization currents as a function of applied voltage for all three phases (L1 downwards triangles, L2 circles, and L3 upwards triangles). The currents are normalized with respect to the applied voltage and each data point is the average value of the data taken from the last two minutes of measuring. The dashed and solid lines denote insulation tester and picoamperemeter, respectively. Figure 8 shows that the depolarization current is much less dependent on voltage than the polarization current. If a high number of long vented water trees were present, the depolarization current would likely be voltage dependent [5]. CIRED 2015 4/5

CONCLUSION This paper indicates that a simple insulation tester provides useful information when assessing the condition of a MV XLPE cable system with joints. It is an easy and efficient method of separating heavily water tree degraded cables from cable systems where a joint is causing high loss tangents. This method should be used before applying any other diagnostic equipment. Figure 8: Depolarization currents after 100 seconds as a function of applied voltage for all three phases (L1 downwards triangles, L2 circles, and L3 upwards triangles). The currents are normalized with respect to the applied voltage. The dashed and solid lines denote insulation tester and picoamperemeter, respectively. The initial measurements of the loss tangent indicated that the cable was heavily water-treed due to the high values shown in Table 2. Figure 9 shows the polarization and depolarization currents measured at 2.5 kv, then 5 kv, and then at 2.5 kv again for phase L2. The other phases show the same behavior. Note that only 0.5 m of the cable on each side of the joint is included in these measurements. Still, if the cable had been severely water tree degraded, this cable length should have contained enough water trees to yield a significant hysteretic effect as expected from heavily water tree degraded cables [3]. However, only a slight hysteresis is observed. This corresponds to the slight hysteresis observed in Figure 3. Hence, the cable is probably not severely water tree degraded. It is more likely that the low resistance joints are the cause of the large loss tangents, rather than water trees bridging the insulation. Figure 9: Polarization and depolarization currents for phase L2 at 2.5 kv first run, 5 kv, and 2.5 kv second run, denoted by dashed, solid, and dotted lines, respectively. Polarization and depolarization currents are denoted by circles and squares, respectively. From the results in this work it can be concluded that: - The insulation tester provides sufficient accuracy and resolution to be used in MV XLPE cable links. - By using reliable evaluation criteria, an insulation tester can e.g. reveal if a joint is the cause for high tan δ values of the complete cable link avoiding misinterpretation of the condition. - Example of such a criterion could be the non-linear (voltage dependent) polarisation currents, and linear depolarisation currents as measured for the joint. - The results can also be used to decide if more advanced diagnostic methods (PD or tan δ) should be applied afterwards. - More work must be performed to establish robust and reliable evaluation criteria for the insulation tester that can be used during the condition assessment. Acknowledgements The work has been performed as a R&D-project in the framework of Norwegian Federation of Utilities (Energy Norway). Both Norwegian utilities and cable industry have contributed to and sponsored the work. The authors would like to express gratitude for their support and permission to publish the work. REFERENCES [1] S. Hvidsten, and J. T. Benjaminsen, 2002, "Diagnostic Testing of MV XLPE Cables with Low Density of Water Trees", Conference Record of the 2002 IEEE International Symposium on Electrical Insulation, pp.108-111. [2] A. K. Jonscher, 1983, Dielectric Relaxation in Solids, Chelsea Dielectrics Press, London, United Kingdom, 45. [3] CIGRE Working group D1/B1.20, "Non- Destructive Water-Tree Detection in XLPE Cable Insulation" TB-493, April 2012. [4] F. Mauseth, K. D. Hammervoll, and S. Hvidsten. "Dielectric properties of service aged medium voltage XLPE cable joints", Solid Dielectrics (ICSD), 2010 10th IEEE International Conference on, pp. 1-4. [5] T. Heizmann, and W.S. Zaengl, "Influence of ageing on depolarization currents in polymerinsulated medium-voltage cables", Electrical Insulation and Dielectric Phenomena (CEIDP). 1991 Annual Report. Conference on, pp. 324-329 CIRED 2015 5/5