Voltage-Mode Grid-Tie Inverter with Active Power Factor Correction

Similar documents
Oscillators. An oscillator may be described as a source of alternating voltage. It is different than amplifier.

CHAPTER 5 MODIFIED SINUSOIDAL PULSE WIDTH MODULATION (SPWM) TECHNIQUE BASED CONTROLLER

Chapter 2 Shunt Active Power Filter

CHAPTER 3. SINGLE-STAGE PFC TOPOLOGY GENERALIZATION AND VARIATIONS

Chapter 6. Small signal analysis and control design of LLC converter

CHAPTER 2 GENERAL STUDY OF INTEGRATED SINGLE-STAGE POWER FACTOR CORRECTION CONVERTERS

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

Lecture 6 ECEN 4517/5517

Minimizing Input Filter Requirements In Military Power Supply Designs

Lecture 19 - Single-phase square-wave inverter

Lecture 4 ECEN 4517/5517

Testing Power Sources for Stability

DESIGN AND ANALYSIS OF FEEDBACK CONTROLLERS FOR A DC BUCK-BOOST CONVERTER

ATYPICAL high-power gate-turn-off (GTO) currentsource

Lecture Note. DC-AC PWM Inverters. Prepared by Dr. Oday A Ahmed Website:

Grid-Tied Home Energy Production Using a Solar or Wind Power Inverter without DC-to-DC Converter

Figure 1: Closed Loop System

Parallel-Connected Converters with Maximum Power Tracking

Pulse width modulated (PWM) inverters are mostly used power electronic circuits in

ELEC387 Power electronics

A Fuzzy Controlled PWM Current Source Inverter for Wind Energy Conversion System

A Novel Control Method for Input Output Harmonic Elimination of the PWM Boost Type Rectifier Under Unbalanced Operating Conditions

Chapter 13 Oscillators and Data Converters

CHAPTER 9. Sinusoidal Steady-State Analysis

A New Small-Signal Model for Current-Mode Control Raymond B. Ridley

CHAPTER 2 A SERIES PARALLEL RESONANT CONVERTER WITH OPEN LOOP CONTROL

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

Positive Feedback and Oscillators

SHUNT ACTIVE POWER FILTER

Module 5. DC to AC Converters. Version 2 EE IIT, Kharagpur 1

DUAL BRIDGE LLC RESONANT CONVERTER WITH FREQUENCY ADAPTIVE PHASE-SHIFT MODULATION CONTROL FOR WIDE VOLTAGE GAIN RANGE

CHAPTER 6 ANALYSIS OF THREE PHASE HYBRID SCHEME WITH VIENNA RECTIFIER USING PV ARRAY AND WIND DRIVEN INDUCTION GENERATORS

=. This will typically be less

EE 560 Electric Machines and Drives. Autumn 2014 Final Project. Contents

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Power Factor Pre-regulator Using Constant Tolerance Band Control Scheme

Field Programmable Gate Array-Based Pulse-Width Modulation for Single Phase Active Power Filter

Table of Contents Lesson One Lesson Two Lesson Three Lesson Four Lesson Five PREVIEW COPY

ANALYSIS OF EFFECTS OF VECTOR CONTROL ON TOTAL CURRENT HARMONIC DISTORTION OF ADJUSTABLE SPEED AC DRIVE

Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter)

LC Resonant Circuits Dr. Roger King June Introduction

EE362L, Power Electronics, Powering the Grid with Renewable Energy Version Feb. 21, 2009

Experiment 1: Amplifier Characterization Spring 2019

3. Discrete and Continuous-Time Analysis of Current-Mode Cell

Renewable Energy Systems

Lecture 18 Stability of Feedback Control Systems

Lecture 41 SIMPLE AVERAGING OVER T SW to ACHIEVE LOW FREQUENCY MODELS

Sample Question Paper

ELG4139: DC to AC Converters

Testing Power Factor Correction Circuits For Stability

Bidirectional Ac/Dc Converter with Reduced Switching Losses using Feed Forward Control

Applied Electronics II

P. Sivakumar* 1 and V. Rajasekaran 2

Filter Considerations for the IBC

The steeper the phase shift as a function of frequency φ(ω) the more stable the frequency of oscillation

PV System Components: Inverters and Charge Controllers. EE 495/695 Spring 2011

Advances in Averaged Switch Modeling

POWER FACTOR CORRECTION AND HARMONIC CURRENT REDUCTION IN DUAL FEEDBACK PWM CONTROLLED AC/DC DRIVES.

Chapter 33. Alternating Current Circuits

Power supplies are one of the last holdouts of true. The Purpose of Loop Gain DESIGNER SERIES

Module 4. AC to AC Voltage Converters. Version 2 EE IIT, Kharagpur 1

INVESTIGATION AND DESIGN OF HIGH CURRENT SOURCES FOR B-H LOOP MEASUREMENTS

A Novel Control Method to Minimize Distortion in AC Inverters. Dennis Gyma

Solar-based Single-stage High-efficiency Gridconnected

Micro-controller Based Three-phase Voltage Source Inverter for Alternative Energy Source. Abstract

Investigations on Reactive Power and Dead Time Compensation for a Double Active Bridge with a Planar Transformer. Javier Gómez-Aleixandre Tiemblo

Dr.Arkan A.Hussein Power Electronics Fourth Class. 3-Phase Voltage Source Inverter With Square Wave Output

High Voltage DC Transmission 2

Specify Gain and Phase Margins on All Your Loops

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

Investigation of negative sequence injection capability in H-bridge Multilevel STATCOM

SINGLE STAGE LOW FREQUENCY ELECTRONIC BALLAST FOR HID LAMPS

2020 P a g e. Figure.2: Line diagram of series active power filter.

Grid Connected photovoltaic system based on Chain cell converter Using Simulink

Exercise 9: inductor-resistor-capacitor (LRC) circuits

Harmonics White Paper

IMPORTANCE OF VSC IN HVDC

Lab 4: Transmission Line

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

CHAPTER 4 MODIFIED H- BRIDGE MULTILEVEL INVERTER USING MPD-SPWM TECHNIQUE

EMT212 Analog Electronic II. Chapter 4. Oscillator

CHAPTER 4 A NEW CARRIER BASED PULSE WIDTH MODULATION STRATEGY FOR VSI

Electronics II. Previous Lecture

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

CHAPTER 7 MAXIMUM POWER POINT TRACKING USING HILL CLIMBING ALGORITHM

Current Rebuilding Concept Applied to Boost CCM for PF Correction

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Matrix Drives Boost Power Quality and Energy Savings

B.Tech II SEM Question Bank. Electronics & Electrical Engg UNIT-1

Background (What Do Line and Load Transients Tell Us about a Power Supply?)

Type of loads Active load torque: - Passive load torque :-

The measurement of loop gain in feedback seismometers Brett M. Nordgren April 9, 1999 Rev.

Tutorial 5 - Isolated DC-DC Converters and Inverters

Source Transformation

HVDC CAPACITOR COMMUTATED CONVERTERS IN WEAK NETWORKS GUNNAR PERSSON, VICTOR F LESCALE, ALF PERSSON ABB AB, HVDC SWEDEN

Power Quality improvement of a three phase four wire system using UPQC

Highly-Reliable Fly-back-based PV Micro-inverter Applying Power Decoupling Capability without Additional Components

APPLICATION NOTE 6609 HOW TO OPTIMIZE USE OF CONTROL ALGORITHMS IN SWITCHING REGULATORS

Transcription:

Voltage-Mode Grid-Tie Inverter with Active Power Factor Correction Kasemsan Siri Electronics and Power Systems Department, Engineering and Technology Group, The Aerospace Corporation, Tel: 310-336-2931 he Aerospace Corporation 2009 Patent-Pending

Motivation for Voltage-Mode Grid-Tie Inverter Conventional grid-tie inverter operates in a current-source mode: Require fast response of the innermost control loop that regulates the waveform of the inverter s output current, Not easy to compensate the current-mode control loop to be stable, Be susceptible to interactions with the back-end EMI filter and the grid s non-ideal voltage source characteristics. Conventional grid-tie inverter for solar array does not provide active power factor correction (APFC): Only allowed to operate during sunlight periods, Deliver the in-phase output current with respect to the grid voltage, Not fully utilized the capability of active power factor correction particularly during the periods of no sunlight. Voltage-Mode grid-tie inverter for solar array potentially offers APFC function without increasing the power component count. Page 2 Patent-Pending

Motivation for Active Power Factor Correction Conventional grid-tie inverter only works during sunlight (day time): Only designed for power transfer from the solar array to a utility grid, Controlled to deliver an in-phase current into the grid, Controlled to provide 0-A reactive current, No active power correction for a reactive load across the grid voltage. Grid-tie inverters should be fully utilized during both day time and night time: Optionally providing active power factor correction which maximizes the power factor for a given set of AC loads sharing the same utilitygrid voltage across the inverter s output. Page 3 Patent-Pending

Difficulties of Conventional Current-Mode Inverter (1) Distortion of current waveform, particularly when the utility grid voltage crosses 0-V. (2) As inverter current increases, the system performance decreases toward an instability of the innermost control loop. localized bursts of high frequency oscillation superimposed on the AC current waveform of the utility frequency. (3) Difficult to design the back-end EMI filter that minimizes or avoids undesirable interactions with the inverter response. Higher control crossover frequency is needed for the fidelity of the sinusoidal waveform of the inverter output current, resulting in a potential interaction with the resonant frequency of the EMI filter. Page 4 Patent-Pending

INVERTER SYSTEM BLOCK DIAGRAM Convert DC power from solar array to an AC inverter output current, Provide a proper phase control of the inverter output voltage to remove the reactive component from the utility grid current, Track peak power delivered by the solar array at night, Maintain 0-a reactive component in the utility grid current during both daytime and night-time periods. Page 5 Patent-Pending

INVERTER SYSTEM CONTROL CONCEPT Six basic blocks work together for reliable DC-to-AC power conversion: 1. SINE-WAVE Regulation Controller with PWM Output 2. Active Power Factor Correction and Harmonic Cancellation Controller 3. 0-ADC Regulation Controller 4. Maximum Power Tacking (MPT) & Input Voltage Regulation Controller 5. Non-MPT Mode Controller 6. Protection Controller Page 6 Patent-Pending

Phase-Shift Control & Sinusoidal Profile Regulation Active power factor correction is achieved by the phaseshift control. Being equivalent to Independent MPT Sharing only one common MPT controller Actively performing an MPT control for one power source at a time while holding the most recently tracked source voltages of the remaining power sources After proper phase-shifting of the sinusoidal reference signal, it is multiplied with the DC command signal V CON Forming a sinusoidal profile for production of the inverter output voltage through a voltage-mode PWM scheme, Fulfilling other control objectives such as Maximum Power Tracking and/or Inverter Input Voltage Regulation Page 7 Patent-Pending

Harmonic Cancellation Method To achieve the AC grid current having 0-A harmonic or negligible harmonic content, a harmonic cancellation term, v INac (t)/v IN (t), is inserted and the dutyratio can be expressed as d PWM ( t ) = 0. 5 B + k sin( w t + f ) 1 - v V INac IN ( t ) ( t ) where v INac (t) is all of the AC components that are superimposed on the DC component V INdc of the inverter input voltage, V IN (t), and V IN (t) = V INdc + v INac (t). Block 210 shown in Fig. 1 also accepts the inverter input voltage V IN (t) from which the harmonic cancellation term is derived and superimposed onto the ideal sinusoidal reference waveform such that the composite reference signal SINE_AC leads to the duty-ratio signal that satisfies the equation above. Page 8 Patent-Pending

0-ADC Regulation Controller The 0-ADC regulation controller 260 ensures the 0-ADC average value of the inverter output current during steady state. providing an integral-lead compensation to the feedback inverter output current signal I O and delivering the counter balance signal V OFF to be added to the composite sinusoidal signal within the controller block 200. Page 9 Patent-Pending

VOLTAGE-MODE SINE-WAVE REGULATION CONTROLLER WITH PWM OUTPUT Each of the three source voltages: V1, V2, and V3 is actively controlled by the common MPT controller one voltage at a time, while holding their most recently tracked source voltages of the remaining sources. Page 10 Patent-Pending

PWM CONTROL FOR SINE-WAVE VOLTAGE V GS1 = VGS 4 = PWM SD V where GS 2 d PWM = VGS 3 = PWM SD d ( t) = 0.5 + k sin( wt) PWM Ton = + and k 0.5 T Page 11 Patent-Pending

SIMULATED INVERTER RESPONSE Amplitude of the capacitive load current (60-degree lead) was varied from 10 ma to 14 A while the inverter output power is kept constant at 200 W. When the load current, I LOAD, is zero or small (i.e. 10 ma), nearly all of the inverter output power is transferred to the utility grid and the amplitude of grid current I AC is around 3.6 A at time = 4s. As I LOAD increases, I AC is decreased as more inverter power is transferred to the load and less inverter power to the grid while the inverter transferred power P IN of 200 W is sustained. Five following plots of the detailed responses from top to bottom (in the lower plot area) are revealed: V IN : the inverter input voltage, I IN : the inverter input current, P IN : the inverter input power (its moving-average), I LOAD : the load current, and I AC : the grid current being paired with V AC The bottom left plot: I AC and V AC are in-phase, signifying that the excess inverter power above the load demand is absorbed by the utility grid. The bottom right plot: I AC and V AC are out-of-phase, signifying that the grid provides an extra power above the inverter 200-W output power to fulfill the heavy load demand. Page 12 Patent-Pending

Inverter Response (Inductive Load) without Harmonic Cancellation V LOAD, I LOAD, P IN, P LOAD, and I AC are simulated at around time t = 11s for an inductive load (60-degree lag). For 10.95s < t < 11.05s, the inductive load consumes the same power as that delivered by the inverter output P IN, consequently causing I AC at the utility frequency to be reduced to nearly 0 A. Due to distributed imperfections in the inverter power stage and control, the grid current exhibits the third harmonic frequency (180-Hz) with respect to the grid frequency (without the harmonic cancellation). Page 13 Patent-Pending

Inverter Response (Capacitive Load) without harmonic Cancellation V LOAD, I LOAD, P IN, P LOAD, and I AC are simulated at around time t = 11s for a capacitive load (60-degree lead). For 11.15s < t < 11.25s, the capacitive load consumes the same power as that delivered by the inverter output P IN, consequently causing I AC at the utility frequency to be reduced to nearly 0 A. Due to distributed imperfections in the inverter power stage and control, the grid current exhibits the third harmonic frequency (180-Hz) with respect to the grid frequency (without the harmonic cancellation). Page 14 Patent-Pending

Inverter Response Before and After Harmonic Cancellation Before After Before the harmonic cancellation is included, the peak-to-peak grid current is 317.3 ma which mostly contains the third harmonic frequency (180 Hz) as shown on the bottom left plot. After the harmonic cancellation term is included as shown in chart #6, the third harmonic content is almost totally eliminated, leaving only the less than 100-mA peak-topeak current which occurs at the fundamental frequency (60 Hz) as shown on the bottom right plot of the figure. Page 15 Patent-Pending

Maximum Power Tracking Controller Two Major Operational Modes (MPT and Non-MPT): In MPT mode, Input Voltage Regulation (IVR) regulates the inverter input voltage at the solar array peak power voltage. In Non-MPT mode, the inverter input voltage is above the solar array peak power voltage to reduce the solar array power as needed. Page 16 Patent-Pending

Change in Peak Power Voltage (Between 20 V and 30 V) Inductive load of 5.656 A (RMS) or 8A (amplitude), utility grid absorbs excess array power, i.e. I AC and V AC are in-phase. Inductive load of slightly below 200 W, leaving about 100 W of the excess inverter output power to be absorbed by the utility grid. The array peak power of 300 W is continuously tracked despite the change in the peak power voltage between 20V and 30V. Page 17 Patent-Pending

Change in Peak Power Voltage (Between 20 V and 30 V) Inductive load 14A, utility grid fulfills the load demand while the array peak power (300 W) is tracked and delivered to the load. Grid voltage and current are out of phase, revealing that the utility grid provides extra power to fulfill the load demand which exceeds the 300-W solar array peak power. Page 18 Patent-Pending

Simulation of the Grid-Tie Inverter Power System With MPT Control and Active Power Factor Correction PSPICE simulation verifies that the following novel features of the inverter system control: The proper phase-shift method that results in the unity power factor regardless of the load type being terminated across the inverter output (resistive, inductive, or capacitive). The harmonic cancellation method that effectively eliminates or significantly reduces harmonic content from the inverter output voltage and current, particularly at the third or higher harmonic frequencies. The 0-ADC regulation control which ensures that the inverter output current possesses no DC component, thus preventing magnetic saturation from occurring in the inverter isolation transformer. Page 19 Patent-Pending

CONCLUSION PSPICE simulation has validated the novel system controller for a voltagemode grid-tie inverter with active power factor correction (APFC). APFC between the grid voltage and current was achieved by a proper phase-shift control method regardless of the inverter load type The harmonic cancellation circuit has demonstrated the control ability to eliminate or significantly reduce harmonic content from the grid voltage and current, particularly at the third or higher harmonic frequencies. Under the non-linear characteristics of the input power source and the non-ideal impedance characteristics of the utility grid, The voltage-mode inverter is much easier to be implemented than the current-mode inverter, particularly for obtaining the unity power factor being observed by the utility grid. Finally, the 0-ADC regulation controller was also validated, preventing magnetic saturation from occurring at the inverter isolation transformer. Page 20 Patent-Pending

Maximum Power Tracking Controller Two Major Operational Modes (MPT and Non-MPT): In MPT mode, Input Voltage Regulation (IVR) regulates the inverter input voltage at the solar array peak power voltage. In Non-MPT mode, the inverter input voltage is above the solar array peak power voltage to reduce the solar array power as needed. Page 21 Patent-Pending ISIE 2015

TYPICAL I-V & P-V CHARACTERISTICS OF SOLAR ARRAY Page 22 Patent-Pending

THREE MAJOR STATES OF SOLAR ARRAY POWER Page 23 Patent-Pending

APPENDIX B: MPT Controller Page 24 Patent-Pending ISIE 2015

AC ARRAY VOTLAGE AND POWER RIPPLE WITH RESPECT TO UTILITY FREQUENCY Page 25 Patent-Pending

MPT CONCEPTUAL BLOCK DIAGRAM Page 26 Patent-Pending

MPT IMPLEMENTATION DIAGRAM BASED ON DISCRETE LOGIC Page 27 Patent-Pending

Change in Peak Power Voltage (Between 20 V and 30 V) Inductive load of 5.656 A (RMS) or 8A (amplitude), utility grid absorbs excess array power, i.e. I AC and V AC are in-phase. Inductive load of slightly below 200 W, leaving about 100 W of the excess inverter output power to be absorbed by the utility grid. The array peak power of 300 W is continuously tracked despite the change in the peak power voltage between 20V and 30V. Page 28 Patent-Pending ISIE 2015

Change in Peak Power Voltage (Between 20 V and 30 V) Inductive load 14A, utility grid fulfills the load demand while the array peak power (300 W) is tracked and delivered to the load. Grid voltage and current are out of phase, revealing that the utility grid provides extra power to fulfill the load demand which exceeds the 300-W solar array peak power. Page 29 Patent-Pending ISIE 2015

Page 30 Patent-Pending

Simplified Concept of Inverter Model Page 31 Patent-Pending

The Simplest System of Closed-Loop Controlled Inverter Page 32 Patent-Pending

Simplified Phasor Diagram with Inductive Load Page 33 Patent-Pending

Simplified Phasor Diagram with Capacitive Load Page 34 Patent-Pending

Model of Strong-Power Inverter and Utility Grid Simplified equivalent circuit consisting of an inverter, load, and a utility grid with two phasor diagrams of AC voltages and currents when excess inverter power above the load demand is absorbed by the utility grid; the lower-left phasor diagram for an inductive load and the lowerright phasor diagram for a capacitive load. Page 35 Patent-Pending

Model of Weak-Power Inverter and Utility Grid Simplified equivalent circuit consisting of an inverter, load, and a utility grid with two phasor diagrams of AC voltages and currents when extra power is provided by the utility grid to fulfill the load demand above the inverter output power; the lower-left phasor diagram for an inductive load and the lower-right phasor diagram for a capacitive load. Page 36 Patent-Pending

PHASE-SHIFT CONTROL Page 37 Patent-Pending

Extraction of Harmonic Cancellation Term Page 38 Patent-Pending

Average Model of the Bridge Switching Network Q1 and Q4 are concurrently switched with their identical ON time, T ON, which is proportionally to the modulation duty ratio D = T ON /T, whereas Q2 and Q3 are always switched in a complementary fashion with Q1 and Q4. <V(VOP)> = D*V IN <V(VON)> = (1-D)*V IN <V(VOP) V(VON)> = (2*D 1)*V IN Page 39 Patent-Pending

Large-Signal Average Model of the Bridge Switching Ckt. Page 40 Patent-Pending

Average Model of BI-POLAR PWM Modulator d(t) = 0.5 + V CPWM / VR d(t) = T ON (t) / T Where V CPWM = V CON sin(wt) *( 1 - v inac (t) / V IN (t) ) Page 41 Patent-Pending

Average Model of SINGLE POLAR PWM Modulator d(t) = V CPWM / VR d(t) = T ON (t) / T Where V CPWM = V CON sin(wt) *( 1 - v inac (t) / V IN (t) ) Page 42 Patent-Pending

Homework: (1) Prove that V(VOP, VON) contains no product term sin(wt)*sin(2wt) with harmonic cancellation. (2) Prove that sin(wt)*sin(2wt) contains two frequencies (w 1 and w 2 ) and (3) What are the values of w 1 and w 2? where v inac (t) = V m sin(2wt) V IN (t) = V INDC + V m sin(2wt) V CPWM = V CON * V(SINE_AC) V(SINE_AC) = sin(wt) *( 1 - V m sin(2wt)/ V IN (t) ) Page 43 Patent-Pending

PWM SWITCHING SIGNAL BASED ON BI-POLAR MODULATION V GS1 = VGS 4 = PWM SD V where GS 2 d PWM = VGS 3 = PWM SD d ( t) = 0.5 + k sin( wt) PWM Ton = + and k 0.5 T Page 44 Patent-Pending ISIE 2015

Large Signal Average Model of Power Switching Bridge (Bi-Polar Modulation Scheme) Page 45 Patent-Pending

PWM SWITCHING SIGNAL BASED ON SINGLE POLAR MODULATION V GS 1 V GS 2 = ( PWM * SQW) SD = PWM + SQW SD V GS 3 V GS 4 = ( PWM * SQW) SD = PWM + SQW SD d PWM ( t) = k sin( w t) Page 46 Patent-Pending ISIE 2015 where d PWM Ton = + and k T 1.0

ALTERNATIVE PWM SWITCHING SIGNAL BASED ON SINGLE POLAR MODULATION Page 47 Patent-Pending ISIE 2015 PWM A = PWM + SQ2T PWM B = PWM + SQ2T PWM 1 = PWM A SQ _ 60 PWM 2 = PWM B SQ _ 60 V V where = PWM SD V = PWM 1 GS1 1, d PWM GS 2 SD = PWM 2 SD and VGS 4 = PWM 2 GS3, Ton = + and k T SD 1.0

Large Signal Average Model of Power Switching Bridge Single Polar Modulation Page 48 Patent-Pending