Introduction. AC or DC? Insulation Current Flow (AC) 1. TECHNICAL BULLETIN 012a Principles of Insulation Testing. Page 1 of 10 January 9, 2002

Similar documents
Insulation resistance testing

IMPORTANCE OF INSULATION RESISTANCE

Insulation Resistance Testing

Power Factor Insulation Diagnosis: Demystifying Standard Practices

The Basics of Insulation Testing

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

(2) New Standard IEEE P (3) Core : (4) Windings :

Insulation Testing Preventing Equipment Breakdown and Plant Shutdowns

USING DAMPED AC VOLTAGES

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

Megohmmeter Model 1060

Insulation Resistance Testing Guide

Radar. Radio. Electronics. Television. .104f 4E011 UNITED ELECTRONICS LABORATORIES LOUISVILLE

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

Specialists in HV and MV test and diagnostics. Testing in Substations

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Preface...x Chapter 1 Electrical Fundamentals

ENGINEERING COMMITTEE Interface Practices Subcommittee AMERICAN NATIONAL STANDARD ANSI/SCTE

Basic electronics Prof. T.S. Natarajan Department of Physics Indian Institute of Technology, Madras Lecture- 17. Frequency Analysis

RESONANT TRANSFORMER

700 Series AC Dielectric Test Sets

Notes 1: Introduction to Distribution Systems

A Guide to the DC Decay of Fault Current and X/R Ratios

In-Service Testing and Diagnosis of Gapless Metal Oxide Surge Arresters According to IEC

7. INSPECTION AND TEST PROCEDURES

THE ELECTROM itig II MOTOR TESTER AND WINDING ANALYZER

An Introduction to Power Quality

Tab 2 Voltage Stresses Switching Transients

Exercise 9. Electromagnetism and Inductors EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Magnetism, magnets, and magnetic field

what is a multiplier? how does a multiplier work? common multiplier applications II. Assembly Type III. Other Design Concerns

Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems

Demagnetization of Power Transformers Following a DC Resistance Testing

UNIVERSITY OF NORTH CAROLINA AT CHARLOTTE Department of Electrical and Computer Engineering

Partial Discharge Theory, Modeling and Applications To Electrical Machines

US $9.95 GBP 5.95 A Stitch in Time... The Complete Guide to Electrical Insulation Testing

Methods of secondary short circuit current control in single phase transformers

MIT510/2, MIT520/2 and MIT1020/2

Insulation Testing. Distributor Training Program

Appendix B to Working on Exposed Energized Parts

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

CHAPTER 10 HIGH VOLTAGE TESTING OF ELECTRICAL APPARATUS

Effects of Harmonic Distortion I

Electrical Equipment Condition Assessment

Definitions of Technical Terms

Table of Contents. Introduction...2 Conductors and Insulators...3 Current, Voltage, and Resistance...6

Testing Potential Transformers

Instruction Manual AVTM670600a for Resonating Inductor Catalog No High-Voltage Equipment Read the entire manual before operating.

Be on guard for effective testing: Introduction

Company Directive STANDARD TECHNIQUE: SD7F/2. Determination of Short Circuit Duty for Switchgear on the WPD Distribution System

WIRE AND CABLE ENGINEERING GUIDE

700 Series AC Dielectric Test Sets

4. Classification E: High capacity. 3. Terminal Form Blank: Tab terminals (#250 terminals) Tab terminals #250 SPST-NO

Transformers handling and transport

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

Doble Test Procedures

THE ELECTROM itig II MOTOR TESTER AND WINDING ANALYZER

Generator Advanced Concepts

Chapter 25 Alternating Currents

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

Transformer & Induction M/C

Grounding System Theory and Practice

EI HIGH VOLTAGE INSULATION TESTING POLICY

Voltage Probe Manual and Data North Star High Voltage, Inc. Rev January 2016

TRANSISTOR SWITCHING WITH A REACTIVE LOAD

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

Capacitive Voltage Transformer (CVT) Commissioning Test

Transformer Testing & Maintenance Fundamentals. AVO Training Institute, Inc. 2018

MV Power Cable Diagnostics by Frequency Domain Spectroscopy. Peter Werelius Programma Electric AB

05e28 Di-electric Strength (High Voltage) Test and Leakage Current Test Proficiency Testing Program

Switching Induced Transients:

Exploring the Necessity of the Hot Hipot Test

BY JASON SOUCHAK, Megger

OFFLINE PD DIAGNOSTICS USING SEVERAL EXCITATION VOLTAGES

DM-45 Digital Multimeter

CHAPTER 2 ELECTRICAL POWER SYSTEM OVERCURRENTS

NEO TELE-TRONIX PVT. LTD. 6/7 Bijoygarh, Kolkata , Tel : ; Fax :

Correlation between time and frequency domain polarisation measurements for transformer moisture assessment

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

DC current interruption tests with HV mechanical DC circuit breaker

AC Dielectric Test Sets

Effects of Phase-Shifting Transformers, and Synchronous Condensers on Breaker Transient Recovery Voltages

Power Quality Monitoring and Power Metering Tutorial

Testing and PD Diagnosis of MV Cable Systems with DAC Voltage Educational Session May St Pete Beach, Fl

Substation Preventive Maintenance

Operating Instructions / Voltage Tester per IEC with Phase and Polarity Tester and Phase Sequence Indicator

Comparison of recloser and breaker standards

MS8268 HANDHELD DIGITAL MULTIMETER OPERATOR S INSTRUCTION MANUAL

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

Importance of Transformer Demagnetization

KNOW MORE ABOUT THE TRANSFORMERS. Glossary Transformers

Module 1. Introduction. Version 2 EE IIT, Kharagpur

Transformer Protection

PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering

Harmonic filter design for IEC compliance

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

5-kV and 10-kV Insulation Resistance Testers. n CAT IV 600 V safety rating. n Line supply or battery operated

Industrial Electrician Level 3

Transcription:

Page 1 of 10 January 9, 2002 TECHNICAL BULLETIN 012a Principles of Insulation Testing Introduction Probably 80% of all testing performed in electrical power systems is related to the verification of insulation quality. This Cadick Corporation Technical Bulletin briefly describes the fundamental concepts of insulation testing including insulation behavior, types of tests, and some test procedures. For more detailed information, refer to the bibliography at the end of the paper. AC or DC? Most electrical equipment in utility, industrial, and commercial power systems uses either 50 or 60 Hz alternating current. Because of this,, the use of It an alternating current source to test insulation would appear to be the logical choice. However, as will be described a little later, insulation systems are extremely capacitive. For this and other reasons, DC has found a large niche in the technology. Figure 1 Insulation with an AC voltage applied Ic Ir 2 Ic( θ) Ir( θ) Before we can really evaluate the value of one system as opposed to the other (e.g. AC vs DC), let us examine how each type of voltage affects insulation. Insulation Current Flow (AC) 1 Insulation may be simply modeled as a capacitor in parallel with a resistor as shown in Figure 1. The current flow that results will comprise two components: the capacitive current (I c ) and the resistive current (I r ). Figure 2 shows the time domain graph of the two currents. For good insulation: Ic $ 100 x Ir Ic leads Ir by close to 90 2 0 Ic Ir For marginal insulation: Ic $ 50 x Ir Ic leads Ir by # 80 2 2 0 90 180 270 360 450 540 630 720 0 θ Figure 2 Insulation current with AC voltage applied 720 1 Note that the currents discussed in this paper are the insulation currents NOT load currents.

Insulation Current Flow (DC) Page 2 of 10 When DC current is involved, insulation may be modeled in a slightly different way. Consider Figure 3. When switch S1 is closed, the DC supply is connected to the insulation system. In the DC It model an extra capacitor has been added (dashed lines). The current that flows through this new capacitor is called the dielectric S1 absorption current (Ida) and will be explained later. Figure 4 show the time relationship for these three currents. The following paragraphs explain each of the three currents. DC Ic Ida Ir Capacitive Current (Ic) The capacitive current charge the capacitance Figure 3 Insulation with DC voltage applied in the system. It normally stops flowing a few seconds (at most) after the DC voltage is applied. The short burst of capacitive current flow may put a rather substantial stress on any test equipment that is applied to very large insulation systems such as cables or large rotating machine. Milliamperes.1 Ic() x 0.08 Ida() x 0.06 Ir() x It() x 0.04 0.02 Ic Ir Ida It=Ic+Ida+Ir Dielectric Absorption Current (Ida) The applied insulation voltage puts a stress on the molecules of the insulation. The positive side of the molecules are attracted to the negative conductor and the negative side of the molecules are attracted to the positive conductor. The result is an energy that is supplied to realign the molecules much like force will realign a network of rubber bands. 0 0 0 2 4 6 8 10 110 3 x Time (seconds) Figure 4 DC current flow in good insulation 10 Like Ic, Ida usually dies off fairly quickly as the molecules realign to their maximum extent. Resistive (Leakage) Current (Ir) This is the electron current flow that actually passes through the insulation. In good insulation the resistive current flow will be relatively small and constant. In bad insulation the leakage current may be fairly large and it may actually increase with time.

Testing Insulation Quality with AC (See Appendix for Test Voltages) Page 3 of 10 Limitations Testing with AC has two significant problems 1. Since a large percentage of insulation current in both good and marginal insulation is capacitive, good insulation will have close to the same amount of AC current flow as marginal insulation. It is, therefore, not possible to evaluate the quality of insulation by simply measuring the magnitude of current flow. (For an exception to this see the Power Factor Testing discussion below). Of course we note that if the insulation is extremely bad or if it fails the current drawn will be high enough to clearly identify the problem. 2. The high amount of current flow drawn by the insulation requires a large test instrument to supply it. This causes AC test sets to be heavier and mor difficult to transport than equivalent capability DC test sets. In spite of these limitations many manufacturers specify that AC be used to test their equipment, and AC testing has a large following. At least four basic approaches are used for testing insulation with AC. AC High Potential Testing (Also called an Over-potential Test) In this test a high voltage AC is applied to the insulation. Usually two or more times the rated insulation current will be used. The concept here is somewhat equivalent to overloading the dam with too much water. If the insulation is good, it will not fail during the test. Note that failure during an AC high potential test is usually very rapid and the insulation is completely destroyed. Because of this, the AC Over-potential test isclassed as a go-no go type of test. Power Factor Testing This approach evaluates the ratio of the resistive current to the total current ratio of the resistive current to the capacitive current I I r c I I r t (power factor) or the (dissipation factor). Since the resistive current is very small, their ratio should be very small. (Note that ideally the ratio would be zero since ideally Ir = 0). To perform this test the test equipment must have relatively sophisticated circuitry that is able to distinguish among the three different current types (resistive, capacitive, and total). Bad insulation will have a relatively high power or dissipation factor. Tables and references are available to compare the measured values against other insulation of the same type. 0.1 Hertz Test Set This type of test set uses a very low frequency test signal. Because capacitors act like very high impedances to very low frequencies, the insulation system draws relatively low current and much of it will be the resistive or leakage current. Proponents of the 0.1 Hertz test set identify at least two significant advantages over other types:

Page 4 of 10 1. Since the insulation draws relatively low current the 0.1 Hertz test set is much smaller than its 60 Hz counterparts. 2. The 0.1 Hertz signal tends to be less destructive than improperly applied DC test voltages. For this reason many test personnel have moved away from DC over-potential testing (described later) in favor of the 0.1 Hz test. Capacitive Canceling (Resonant) System This method is normally applied on very high voltage systems of 230 kv and higher. The test set adjusts its own internal inductance to effectively cancel the insulation capacitance. This leaves only the resistive (leakage) current to be read. The last three test systems (Power Factor, 0.1 Hertz, and Capacitive Cancelling) are relatively specialized systems and may require special training for test personnel. Also, sometimes the results are more complex to analyze. Because of these factors DC test equipment still remains the odds-on favorite for the majority of insulation testing applications. Testing Insulation Quality with DC (See Appendix for Test Voltages) Limitations The principle concerns to be observed when testing with DC is the possibility of damaging otherwise good insulation. Some studies have indicated that DC testing at very high voltages may cause insulation damage for one of two reasons: 1. Sudden application or removal of the voltage (creating a very large ) causes an abnormal dt amount of stress. Whenever possible the test voltages should be gradually applied and removed. 2. If a large over-voltage (on the order of 2 or more times normal) is applied to some insulation systems, the small air voids in the insulation will become charged. If the insulation is then suddenly re-connected to the power system, it may fail due to the addition of the system voltage to the still charged voids. Even if the insulation does not immediately fail, it will be stressed and may lose life. To avoid this problem insulation should always be drained of DC test voltage for 1 to 5 times the length of time that the test voltage was applied before it is re-energized. Effects of Humidity and Temperature Temperature will change the measured insulation resistance. When the temperature goes up the resistance of insulation will go down and vice versa. Tables of correction factors are available from industry publications to correct for temperature variations (See Appendix). If no table is available the field rule of thumb may be used that the insulation resistance will double of each 10 C drop in temperature and will halve for each 10 C rise in temperature. Humidity will not generally have much effect on insulation resistance unless the temperature is very dv

Page 5 of 10 close to the dew point and condensation forms on or in the insulation. Despite this, good practice calls for making measurements when insulation is clean and dry whenever possible. Insulation Quality Tests There are three commonly used methods to evaluate the quality of insulation using DC voltage the socalled spot check, the polarization index test, and the step voltage test. Spot Check Table 1 The insulation resistance Spot Check Step # Description Comments 1 Apply the DC Voltage Usually applied with a megohmmeter or high potential test set 2 3 Wait one minute for the Ic and Ida to decay At one (1) minute read the meter current (Ir) or the insulation resistance in megohms If using a high voltage test set, monitor current closely for indications of insulation failure Compare to previous values or industry standards such as International Electrical Testing Association (NETA) Since Ic and Ida disappear in time, a true insulation resistance value, called a spot check, can be read by applying the DC and then simply waiting long enough for only Ir to remain. Unfortunately the time required for the decay may be several minutes or more for very large insulation systems. To simplify the wait, and since comparison is the main purpose of such a test, general industry practice has established the waiting time as one (1) minute. Table 1 summarizes the method. Table 2 The Polarization Index Test Step # Description Comments 1 Apply the DC Voltage Usually applied with a megohmmeter or high potential test set 2 3 Wait one minute for the Ic and Ida to decay. Read and record the insulation resistance (R 1 ) Wait nine (9) additional minutes (10 minutes total) and read the insulation resistance again. (R 10 ) If using a high voltage test set, monitor current closely for indications of insulation failure If using a high voltage test set, monitor current closely for indications of insulation failure 4 Calculate the polarization index (P.I.) PI.. = R R 10 1

Page 6 of 10 Polarization Index To avoid the uncertainties introduced by temperature correction, and to provide an even more diagnostic result, the polarization index may be Table 3 -- Evaluation of the polarization index test calculated for an insulation system. Table 2 lists the steps for performing the polarization index test. Table 3 shows 10 Value P.I. Insulation Evaluation how to evaluate the results of the polarization index test. R R 1 <1 Dangerous <1.5 Poor <2 Fair 3 to 4 Good > 4 Excellent Step Voltage Test Electrical resistance is a physical characteristic of a material and, therefore, should not be changed by the voltage level that is used to measure it. If P.I. is 5 or greater, insulation may be dry and brittle. At higher voltages, however, cracks and other such insulation faults will be stressed more. This means that ionization may occur, causing an increased, disproportionate current flow. In other words, bad insulation will tend to display a lower resistance when a higher voltage is applied. The step voltage test is accomplished by performing a spot check test at two or more voltages. Usually the voltages are separated by at least 500 Volts and the last step should be five (5) times the lowest voltage. For example the first spot check is performed at 500 Volts with additional one minute checks at 1000, 1500, 2000, and 2500 Volts. 2 If R HV < 0.60 R ± 15%, the insulation should be investigated for possible failure. LV Summary The effective electrical maintenance program must include periodic evaluation of the insulation quality. Technical Bulletin only scratches the surface of the subject. For more information you can consult these resources: AVO, International: Doble Engineering: AEMC: http://www.avointl.com http://www.doble.com http://www.aemc.com If you have any questions or comments about this technical bulletin, please contact us at info@cadickcorp.com. 2 Although a megohmmeter is a low energy device, avoid applying more than 3 to 4 times the insulation rated voltage.

Appendix Test Values and Temperature Tables Page 7 of 10 The following three tables are taken from the International Testing Association s standard NETA MTS- 2001.For more detail you should obtain a copy of this standard directly from NETA (http://www.netaworld.org).

Page 8 of 10 Table 4 Temperature correction factors (NETA Table 10-4) Temperature C F Apparatus Containing Immersed Oil Insulations Multiplier Apparatus Containing Solid Insulations 0 32 0.25 0.40 5 41 0.36 0.45 10 50 0.50 0.50 15 59 0.75 0.75 20 68 1.00 1.00 25 77 1.40 1.30 30 86 1.98 1.60 35 95 2.80 2.05 40 104 3.95 2.50 45 113 5.60 3.25 50 122 7.85 4.00 55 131 11.20 5.20 60 140 15.85 6.40 65 149 22.40 8.70 70 158 31.75 10.00 75 167 44.70 13.00 80 176 63.50 16.00

Page 9 of 10 Table 5 Minimum test values for electrical apparatus (NETA Table 10-1). To be used for Megohmmeter type tests Maximum Rating of Equipment in Volts Minimum Test Voltage, dc Recommended Minimum Insulation Resistance in MegOhms 250 500 25 600 1,000 100 5,000 2,500 1,000 8,000 2,500 2,000 15,000 2,500 5,000 25,000 5,000 20,000 35,000 15,000 100,000 46,000 15,000 100,000 69,000 15,000 100,000

Page 10 of 10 Table 6 Maximum withstand voltage for testing electrical apparatus (NETA Table 10-2) For High-Potential Testing Type of Switchgear Low-Voltage Power Circuit Breaker Switchgear Metal-Clad Switchgear Station Type Cubicle Switchgear Metal Enclosed Interrupter Switchgear Rated Maximum Voltage (kv) (rms) ac Maximum Test Voltage (kv).254/.508/.635 1.6 2.3 4.76 14 20 8.25 27 37 15.0 27 37 27.0 45 Consult Manufacturer 38.0 60 Consult Manufacturer 15.5 37 Consult Manufacturer 38.0 60 Consult Manufacturer 72.5 120 Consult Manufacturer 4.76 14 20 8.25 19 27 15.0 27 37 15.5 37 52 25.8 45 Consult Manufacturer dc