NOT SO SCARY LIGHTING MATH NOT SO SCARY LIGHTING MATH

Similar documents
NOT SO SCARY LIGHTING MATH

NOT SO SCARY LIGHTING MATH

NOT SO SCARY LIGHTING MATH

Energy and Calculating Light. Lighting Needs Power: Electrical Systems. Lighting Needs Power: Wires Distribute Electricity

Lighting for seniors

daylight Spring 2014 College of Architecture, Texas Tech University 1

Physics of Light. Light: electromagnetic radiation that can produce a visual sensation.

Electrical Illumination and Design

Photometric Test Report

Rendering and Documenting Light

AMLED Areamaster LED Flood/High Bay Luminaires For Hazardous Locations. 250 W, 400 W, 750 W HID Light Level Equivalent

Complete Product = Frame-in kit + Light engine + Reflector Order each separately. N Non-IC New construction. Z V Dimming L Lutron.

Report No.: HZ h/R1. Total Luminous Flux (Lumens) Stabilization Time (Light & Power) Table 1: Executive Data Summary CRI

Photometry for Traffic Engineers...

(Lumens) Stabilization Time CRI (K) (Light & Power) Table 1 Executive Data Summary

Electrical Installation LectureNo.10 Dr.Mohammed Tawfeeq Al-Zuhairi. Luminous flux Luminous intensity Illuminance Luminance

Report No.: HZ b. Total Luminous Flux (Lumens) Stabilization Time (Light & Power) Table 1: Executive Data Summary CRI

Report No.: HZ c/R1. Total Luminous Flux (Lumens) Stabilization Time (Light & Power) Table 1: Executive Data Summary CRI

Photometric Test Report

Report No.: HZ b. Total Luminous Flux (Lumens) Stabilization Time (Light & Power) Table 1: Executive Data Summary CRI

Report No.: HZ w. Stabilization Time (Light & Power) CRI. Table 1: Executive Data Summary. Figure 1- Overview of the sample

LM Test Report. for Elec-Tech International Co.,Ltd. LED CEILING LIGHT Model: XX(XX: 01-10)

LM Test Report. for Elec-Tech International Co.,Ltd. LED CEILING LIGHT Model: XX(XX: 61-70)

LM Test Report. for Elec-Tech International Co.,Ltd. LED CEILING LIGHT Model: XX(XX: 01-10)

General Information 11A-1. A. General. B. Industry Outlook. Design Manual Chapter 11 - Street Lighting 11A - General Information

Lumen Method Calculation Assignments Due: Tuesday, November 28, 9:00am

(Lumens) Stabilization Time CRI (K) (Light & Power) Table 1 Executive Data Summary

Photometric Test Report

Report No.: HZ a/R2. Total Luminous Flux (Lumens) Stabilization Time (Light & Power) Table 1: Executive Data Summary CRI

Report No.: HZ a/R2. Total Luminous Flux (Lumens) Stabilization Time (Light & Power) Table 1: Executive Data Summary CRI

Report No.: HZ f. Total Luminous Flux (Lumens) Stabilization Time (Light & Power) Table 1: Executive Data Summary CRI

Rendering and Documenting Light

CHAPTER VII ELECTRIC LIGHTING

Photometry for Traffic Engineers...

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

Lighting Sciences

Electrical Illumination and Design

MAC Quantum Profile Catalog number Lens Option Standard. MAC Quantum Profile_Standard_Minimum.ies

LM Test Report. for Maxlite Inc. LED Canopy Model: MLCAN20LED50

No seasoning was performed in accordance with IESNA LM-79.

Lighting Terminology Wolf Lake Drive, suite 105, Bartlett, TN O F

Basic Lighting Terms Glossary (Terms included in the basic lighting course are italicized and underlined)

Product Tripix 300 Catalog number Lens Option Standard. Tripix300_ ies

Lighting Sciences, Inc.

LM Test Report. for EiKO Global, LLC. 25W Floodlight Model: FLM-2C-N-U

Space #2: Science Room 1

Rendering and Documenting Light. Rendering Light. Light and Air

Report No.: HZ j. Total Luminous Flux (Lumens) Stabilization Time (Light & Power) Table 1: Executive Data Summary CRI

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE MAXLITE Jersey Blvd. Rancho Cucamonga, CA 91730

Photometric Test Report

Report No.: HZ h. Total Luminous Flux (Lumens) Stabilization Time (Light & Power) Table 1: Executive Data Summary CRI

Catalog number Lens Option Very Narrow without diffuser Exterior200LED_VeryNarrow_withoutdiffuser_5600Kelvin.ies

Number Eight Lighting Company MPT2-HI-R-6-BK/15/DIM1-M-1000

LM Test Report. for Elec-Tech International Co., Ltd. BR40 LAMP Model: XX(XX:01-10), WBR40L27S2A

Artificial lighting. Dr Torwong Chenvidyakarn

LM Test Report. for Elec-Tech International Co.,Ltd. LED PAR30 Spot light Model: XX(XX:41-50)

Photometric Indoor Test Report

LM Test Report. for Maxlite SK America Inc. WALLPACK Model: MLSWP30LED50DS

Lumen lm 1 lm= 1cd 1sr The luminous flux emitted into unit solid angle (1 sr) by an isotropic point source having a luminous intensity of 1 candela

LM Test Report. for Maxlite SK America Inc. 2*4 Retrofit Kits Model: RKT4514U5550DV

Lighting Terminologies Introduction

Exterior 400. Balanced white 6500Kelvin. Catalog number Lens Option Standard. Exterior400_Standard_ ies

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

Morris Products 53 Carey Road, Queensbury, NY 12804

Calibration Due Date Chroma Programmable AC Source 61604

Existing Lighting Conditions

INDEPENDENT TEST LABORATORY REPORT No

Evolution LED 3 " Calculite Professional-grade downlighting

INDEPENDENT TEST LABORATORY REPORT No

INDEPENDENT TEST LABORATORY REPORT No

Revolution Lighting Technologies 4139 Guardian Street, Simi Valley, CA No seasoning was performed in accordance with IESNA LM-79.

Revolution Lighting Technologies 4139 Guardian Street, Simi Valley, CA No seasoning was performed in accordance with IESNA LM-79.

INDEPENDENT TEST LABORATORY REPORT No

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

QUANTUM PHOTO-METER LX OPERATING INSTRUCTIONS. ... Three decimal points only displayed Overrange reading. Adjust Range. ( X 1000will light up)

1.4 Rollins Center Performance Hall

INDEPENDENT TEST LABORATORY REPORT No

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE MAXLITE 12 York Ave. West Caldwell, NJ.

ISOFOOTCANDLE LINES OF HORIZONTAL ILLUMINATION

LM Test Report. for. Philips (China) Investment Co., Ltd. InstantFit LEDtube Model:

Project: EIR for Carondelet High School Sports Complex

Revolution Lighting Technologies 4139 Guardian Street, Simi Valley, CA 93063

MAC Viper Profile Catalog number Lens Option Standard. MACViperProfile_Standard_Minimum.ies

Model No Stock No Calibration Due Date Chroma Programmable AC Source PS-AC02

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

Second Floor Circulation

Revolution Lighting 4139 Guardian St. Simi Valley CA 93063

TEST REPORT. Job No SHA Date: Apr 12,2017 REPORT NO SHA-006. TEST OF ONE LED Luminaire MODEL NO.

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE SANDRA STREET, FRANKLIN PARK, IL 60131

NVLAP LAB CODE:

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

BARTCO Lighting 5761 Research Drive, Huntington Beach, CA 92649

NVLAP LAB CODE LM Test Report. For GREEN INOVA LIGHTING TECHNOLOGY (SHENZHEN) LTD. (Brand Name: GI LED LIGHTING)

APPENDIX GLOSSARY OF TERMS

MAC Viper Performance Catalog number Lens Option Standard without beamsmoother. MACViperPerformance_Standard without beamsmoother_minimum.

Catalog Number UPC Number LED Spot Bullet Flood Light 42W 4204 Lumens White

8165 E Kaiser Blvd. Anaheim, CA p f NVLAP LAB CODE

Report No.: EASZE Page 2 of 14

Transcription:

NOT SO SCARY LIGHTING MATH NOT SO SCARY LIGHTING MATH The importance of Lighting Math: Calculations can determine the light levels Calculations can determine the required quantity of fixtures Calculations can verify layout Methods to perform Lighting Math: By Hand By Computer 1

Target Illuminance / Light Levels Who Defines Light Levels? IES of North America Recommended Practices Defines light levels and quality of illumination by task and application Codes and Regulations The Owner Definitions: Task = the work performed Applications = the project type (i.e. School, Commercial etc, IESNA Light Level recommendations are for Footcandles at the work plane (2 6 AFF) They have limited significance to us when we interpret the actual environment. Such factors as lighting walls, brightness accents, shadows, sparkle, and color have a greater influence on emotional reaction. IESNA s recommend light levels are for an age range of 40 55 years old 2

Ages Less than 40 years old Can reduce the light levels up to 1/3! Standard Age Range is 40-55 years old Over 55 years old Can increase the light levels up to 2/3! Babies require 3 times more light than a 20 year old! IESNA Recommended Light Levels 3

Summary Light Level (table 15) Measuring Light Luminance Measures how easy something is to see, or how bight a surface is emitting light energy Examples: backlit signage, a full moon, glowing wall Measured in: Foot-Lamberts (US) or Candelas per meter squared (metric) 1 Foot-Lambert = 3.426 Candelas/m2 Illuminance Measures how much light there is to see by, the light level to perform a task arriving lighting energy Examples: emergency light level on the floor), Measured in: Foot-Candles (US) and Lux (Metric) 4

Light The Foot-candle 1 foot 1 fc Foot-candle is known as a unit of light - direct illumination light level Derived from one candle placed at a distance of one foot from a surface is defined as a foot-candle (abbreviation = fc or FC) Light The Lumen 1 lm The energy of light from a candle falling on a one foot square area is One Lumen (abbreviation = lm) The total amount of light energy coming out of the candle is approximately 13 lumens The total amount of light energy coming out of 100-watt A-lampA is approximately 1650 lumens NOT DEFINED BY DISTANCE 5

Light The Candela 180 deg 270 deg 90 deg Candela 0 deg Distribution Curve Polar Chart Candle Power is the intensity value at any given direction. (unit is Candela, abbreviated as cp) Distribution Curve represents the total light intensity pattern produced by a source CIE Luminaire Types / Distributions Direct Semi-Direct General Diffuse (IES) Direct-Indirect Semi-Indirect Indirect 6

Candlepower Distribution Curve Candlepower distribution curves provides intuitive information on how a luminaire will perform Candela values are used in calculations to predict light levels Candle Power Distribution 300 600 900 1200 1500 0 deg 10 20 30 90 deg 80 70 60 50 40 Distribution angles Asymmetrical Distribution Curve Rectangular Tubular Fluourescent fixture 90 deg Perpendicular 0 deg Parallel Rectangular Tubular Fluourescent fixture Perpendicular 90 degrees Candlepower Distribution Parallel 0 degrees Candlepower Distribution 7

Light Measurement Measures the candlepower distribution of a particular lamp or luminaire. Information is generated in a -- Photometric report Integrating Sphere Gonio-Photometer The Spectro-Radiometer Lumens versus Candelas Lumen is an amount of ENERGY Candela is an amount of INTESITY Light output from lamps and fixtures be measured in Lumens and Candelas. Fixtures alter Lumen and Candela output (Their values can only be found in Photometry Reports) 8

Photometry Reports Plot of candlepower values Summary of candlepower values in different planes Fixture Efficiency Lumen Summary Luminance summary Spacing criteria (SC) or Spacing/Mounting Height (S/MH) for uniformity Coefficient of Utilization Table Guides Photometry Reports: sample 1 Open Downlight 9

Photometry Reports: sample 2 Indirect Pendant Photometry Reports: sample 3 Ceiling Fixture 10

Hand Methods to Calculate Light Mnfrs Guides Direct or Average Illumination from a Fixture or Lamp Recommended spacing or layout Point-by by-point Direct light level from a Fixture or Lamp Lumen Method Average Light Level in a Room from a Fixture Can be used to determine quantity needed Point-by-Point Foot-candle = Candle Power Distance 2 FC = 2651candelas / 9ft 2 FC = 2651 / 81 FC = 32.7 foot-candles Ceiling height = 9ft Light Level at Floor 11

Point-by-Point Foot-candle = Candle Power Foot-candle = Distance 2 Ceiling Fixture Example FC = candelas / ft 2 FC = foot-candles Ceiling height = 9ft Determine the Light Level at Table Point-by-Point Foot-candle = Candle Power Distance 2 Ceiling Fixture Example Ceiling height = 8ft D Eye Level = 5.5ft Determine the Light Level at the Wall Corridor Width = 6 ft 12

Point-by-Point Ceiling Fixture Example Foot-candle = Candle Power Distance 2 Ceiling height = 8ft To solve for D, you can: 1. Scale the Drawing, or 2. Use Trigonometry Eye Level = 5.5ft D Determine the Light Level at the Wall 2.5ft 3ft Distance Corridor Width = 6 ft A 2 + B 2 = C 2 2.5 2 + 3 2 = C 2 C = (6.25 + 9) 6.25 + 9 = C 2 C = 3.9 (approx4ft) Point-by-Point Foot-candle = Candle Power Distance 2 Ceiling Fixture Example Ceiling height = 8ft Eye Level = 5.5ft Corridor Width = 6 ft 4ft Determine the Light Level at the Wall To solve for Angle, you can: 1. Scale the Drawing, or 2. Use Trigonometry? 2.5ft 3ft Tan (Angle) = Opp / Adj Angle = Tan -1 (Opp / Adj) Angle = Tan -1 (3 / 2.5) Angle = 50 degrees 13

Point-by-Point Foot-candle = Candle Power Distance 2 Ceiling Fixture Example Ceiling height = 8ft FC = candelas / ft 2 FC = foot-candles 50deg 4ft Eye Level = 5.5ft Determine the Light Level at the Wall Corridor Width = 6 ft Point-by-Point Factors Calculated Levels are Facing the Light Fixture With the exception of directly below 14

Point-by-Point Factors You need to factor an adjustment if you want levels at other angles (IE Horizontal, Vertical Angles) COSINE Adjusted!! Vertical Horizontal Vertical COSINE Adjustments Foot-candle = Candle Power Distance 2 X COS(Angle of Incidence) Light Source Incidence Reflectance θ θ 15

Point-by-Point with COSINE Adjustment Ceiling Fixture Example Ceiling height = 8ft FC = CP/D 2 x COS(angle) 50deg 4ft What is the Angle of Incidence? Eye Level = 5.5ft Determine the Light Level at the Wall FC = 7.25 x COS ( deg) FC = foot-candles Corridor Width = 6 ft Methods to Calculate Light Point-by by-point Direct Illumination from a Fixture or Lamp You need. Photometry Distances from Fixture or Lamp Lumen Method Average Light Level in a Room from a Fixture You need. Photometry Room Dimensions and Surface Reflectance's 16

Room Reflectance Room comprised of Walls, Ceiling, and Floor. Walls typically have Doors and Windows All surfaces have a reflectance value to bounce light. Light from Light Fixture bounces off of all surfaces. Room Reflectance Surfaces with less reflectance will bounce less light Typical Reflectance Values: 75%-90% White, Off White, Grey, Light tints of Blue or Brown 30%-60% Medium Green, Yellow, Brown, or Grey 10%-20% Dark Grey, Medium Blue 5%-10% Dark Blue, Brown. Dark Green, and many wood finishes 17

Calculations using Lumens Lumen Method Calculation Calculates the Average Illumination for a room. Takes into account the room surface reflectance's but assumes the surfaces are diffuse (not shiny!). Assumes an empty room (without furniture). Can also be used to determine the required Quantity of Fixtures needed for a target light level. Does not determine light fixture layout or location you must following mnfrs spacing criteria. 1. You need Room Dimensions and the Fixture Mounting Height. 2. You need to select a Light fixture 3. Determine the rooms Room Cavity Ratio (RCR). 4. Look-up the fixtures Coefficient of Utilization for the RCR. 5. Calculate! Photometry Reports Plot of candlepower values Summary of candlepower values in different planes Fixture Efficiency Lumen Summary Luminance summary Spacing Criteria (SC) or Spacing/Mounting Height (S/MH) for uniformity Coefficient of Utilization Table Guides 18

Coefficient of Utilization Also known as CU Defines the percentage of light output that is expected from a fixture The value is determined by a CU table For commercial Reflectance of 80/50/20,, the actual CU value is this. Room Cavity Ratio RCR = 5xMHx(L+W) Room Area The RCR can vary depending on the height you want to calculate as shown here with the calculation height at the floor. 19

Room Cavity Ratio RCR = 5xMHx(L+W) Room Area Room Cavity Ratio (aka RCR) is the volume between the Fixture and Height of Calculation Workplane height is typically 30-inches above the floor A rooms RCR will always be between 1 and 10 Room Cavity Ratio RCR = 5xMHx(L+W) Room Area The RCR can vary depending on the height of the fixture.as shown here with Wall Brackets or Sconces. 20

Room Cavity Ratio RCR = 5xMHx(L+W) Room Area The RCR can vary depending on the height of the fixture.as shown here with Pendants. Room Cavity Ratio RCR = 5xMHx(L+W) Room Area Example: Room Width: 12ft Room Length: 15ft Ceiling Height: 10ft RCR = 5 x ( ) x ( + ) ( x ) RCR = 21

Lumen Method Formula To Calculate Foot-candle level: FC = Qty of Fixtures x Number of Lamps per Fixture x Lumens per Lamp x CU Area of the Room To Calculate number of Fixtures: FC = Total Lumens in the Room x CU Area of the Room Qty of Fixtures = FC x Area of the Room Number of Lamps per Fixture x Lumens per Lamp x CU Qty of Fixtures = FC x Area of the Room Total Lumens in the Room x CU Lumen Method Example 1 What is the resulting Foot-candle Level at table height from four downlights? Example: Room Width: 12ft Room Length: 15ft Ceiling Height: 10ft 22

Coefficient of Utilization Also known as CU Defines the percentage of light output that is expected from a fixture The value is determined by a CU table For our example: RCR the CU is For commercial Reflectance of 80/50/20,, the actual CU value is this. Lumen Method Example 2 How many fixtures do I need to achieve 30-foot-candles at table height? 23