PREDICTING RECLOSER FAILURE RATES FROM FIELD CONDITION ASSESSMENT. A Thesis by. Joseph M. Warner

Similar documents
PLAN... RESPOND... RESTORE! Utility Automation & Information Technology... Automation Rising

4. CONNECTIONS. Make sure all connections to and in your Universal Rectifier are tight.

OPERATING AND MAINTENANCE INSTRUCTIONS FOR CONSTANT CURRENT RECTIFIERS USING SATURABLE CORE REACTORS

The effect of data aggregation interval on voltage results

Partial Discharge Theory, Modeling and Applications To Electrical Machines

The NOVA Recloser shall be designed and tested in accordance with the following standards as applicable:

Comparison of recloser and breaker standards

Electrical Equipment Condition Assessment

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

Modeling Distribution Component Deterioration: An application to Transformer Insulation. A.U. Adoghe 1, a, C.O.A. Awosope 2,b and S.A.

STRESS DETECTION USING GALVANIC SKIN RESPONSE SHAHNAZ SAKINAH BINTI SHAIFUL BAHRI UNIVERSITI MALAYSIA PAHANG

A STUDY ON THE CAUSES OF DESIGN CHANGES EFFECTING THE CONSTRUCTION PROJECT PERFORMANCE NUR ARFAHANEM BT MOHAMAD UMPANDI (AA12204)

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.

Economical Solutions to Meet Harmonic Distortion Limits[4]

No. SSIEC-SEW SHINSUNG. Solid Insulation Eco Load Break Switch (SILO) SILO SERIES 15kV, 27kV 400A, 630A

AN IMPROVED NEURAL NETWORK-BASED DECODER SCHEME FOR SYSTEMATIC CONVOLUTIONAL CODE. A Thesis by. Andrew J. Zerngast

Reliability and Power Quality Indices for Premium Power Contracts

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

TIME- OPTIMAL CONVERGECAST IN SENSOR NETWORKS WITH MULTIPLE CHANNELS

ISO MAINTENANCE STANDARDS

Single Jersey Plain. Single Lacoste. Needle set out. Cam arrangement F K. Needle set out. Cam arrangement F1 F2 F3 F4 K T K K K K K T

Electrical Overcurrent Studies

ARC FLASH HAZARD ANALYSIS AND MITIGATION

Section L5: PRE-ENERGIZATION TEST PROCEDURES FOR LOAD-ONLY ENTITIES AND TRANSMISSION-ONLY ENTITIES

ANALYSIS OF A FLASHOVER OPERATION ON TWO 138KV TRANSMISSION LINES

COURSE PLANNER. Subject: TESTING AND COMMISSIONING OF ELECTRICAL EQUIPMENTS ( ) B.E. Fourth Year (8 th Sem) Branch Electrical Engineering

ARDUINO BASED WATER LEVEL MONITOR- ING AND CONTROL VIA CAN BUS TUAN ABU BAKAR BIN TUAN ISMAIL UNIVERSITI MALAYSIA PAHANG

WIRELESS THREE PHASE LINE FAULT MONITORING

Although shunt capacitors

Phase earthing system - method for faulty phase selection with phase-to-earth faults. Ari Nikander Tampere University of Technology

Advanced Monitoring Tools to Improve Distribution System Visibility and Reduce Faults and Outages

How to maximize reliability using an alternative distribution system for critical loads

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

ABB Power Products Service

Human System Modeling for Optimum Labor Utilization and Man-Machine Configuration

A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

No. SSIEC-PRC SHINSUNG. Polymer Recloser SIREC SERIES 15kV, 27kV, 38kV 400A, 630A, 800A

A SEMINAR REPORT PRESENT ON AIR BLAST CIRCUIT BREAKER

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

The CAD Technician s Role in Office Practice and Procedure

PARTIAL DISCHARGE MEASUREMENT

Automated Power System Waveform Analytics for Improved Visibility, Situational Awareness, and Operational Efficiency

Leslie J. Anderson Supervising Attorney Public Service Commission of West Virginia 201 Brooks St. PO Box 812 Charleston, WV Dear Ms.

Novel Simulation Method to Quantify Induced Voltage & Current between Parallel or Partially Parallel Proximity AC Transmission Circuits

Power Transformer Condition Assessment Based on Standard Diagnosis

Transmission Availability Data Systems Frequently Asked Questions

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

ATCO ELECTRIC LTD. (Transmission System) SERVICE QUALITY AND RELIABILITY PERFORMANCE, MEASURES AND INDICES Revision 0

THE DEVELOPMENT OF INTENSITY DURATION FREQUENCY CURVES FITTING CONSTANT AT KUANTAN RIVER BASIN

[Note to PSC: Include these sections in the Contract Documents, even though some are not included in the U of I Facilities Standards]

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

Optimizing Public Transit

Using Administrative Records for Imputation in the Decennial Census 1

Loss prophet. Predicting stray losses in power transformers and optimization of tank shielding using FEM

A New Use for Fault Indicators SEL Revolutionizes Distribution System Protection. Steve T. Watt, Shankar V. Achanta, and Peter Selejan

Development of Explosion-proof Autonomous Plant Operation Robot for Petrochemical Plants

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Distance Protection for Distribution Feeders. Presented By: Yordan Kyosev, P.Eng. & Curtis Ruff, P.Eng.

Improving High Voltage Power System Performance. Using Arc Suppression Coils

EE030: Circuit Breaker & Switchgears Inspection, Maintenance, Design, Repair & Troubleshooting

IMPORTANCE OF INSULATION RESISTANCE

Self Healing Single Phase Looped Network AUTOMATED RECONFIGURATION FOR POWER OUTAGE MANAGEMENT. Team Members

OPTIMIZING MAINS IMPEDANCE: REAL WORLD EXAMPLES by Judith M. Russell Consulting Electrical Engineer PowerLines

LV/MV/HV CIRCUIT BREAKERS (SWITCH GEAR) DESIGN, INSPECTION, MAINTENANCE, REPAIR & TROUBLESHOOTING

ECE 528 Understanding Power Quality

ENHANCING AND EVALUATING SMART POWER DISTRIBUTION SYSTEM RELIABILITY: A DISTRIBUTED SENSOR MONITORING NETWORK APPROACH.

ABSTRACT ADAPTIVE SPACE-TIME PROCESSING FOR WIRELESS COMMUNICATIONS. by Xiao Cheng Bernstein

DG Allocation and Sizing Based on Reliability Improvement by Means of Monte Carlo Simulation

Notes 1: Introduction to Distribution Systems

STANDARD SPECIFICATIONS SECTION SUBMITTAL PROCEDURES

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Distribution/Substation Transformer

WORLDSKILLS STANDARD SPECIFICATION

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

RECOMMENDATION ITU-R P Acquisition, presentation and analysis of data in studies of tropospheric propagation

ECE 528 Understanding Power Quality

Real Time Monitoring of SF6 Gas Pressure for Optimization Point on Wave Switching of SF6 Circuit Breaker

Life Cycle Management of Station Equipment & Apparatus Interest Group (LCMSEA) Getting Started with an Asset Management Program (Continued)

Detection System of Faulty Ground Wires from Aerial Video of Transmission Lines with Consideration of Influence of Devices on Ground Wires

A Guide to Establish an Arc Flash Safety Program for Electric Utilities

LIFE SAFETY DIVISION GUIDELINE. Subject: BDA Radio Amplification Checklist Date initiated: Date revised:

Keywords- Fuzzy Logic, Fuzzy Variables, Traffic Control, Membership Functions and Fuzzy Rule Base.

Application of DFA Technology for Improved Reliability and Operations

INCIDENTS CLASSIFICATION SCALE METHODOLOGY

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING

Verifying Transformer Differential Compensation Settings

MV, HV AND EHV SWITCHGEAR TESTING & COMMISSIONING

VI 3 - i TABLE OF CONTENTS

The Effects of Optimized Thermal Characteristics In Resistance Welding Transformers

Reliability Analysis of Power Distribution System in Nigeria: A Case Study of Ekpoma Network, Edo State

ISSN: Page 298

2018 Consultant s Handbook Division 26 Electrical ARC Flash Hazard Analysis

Harmonic impact of photovoltaic inverter systems on low and medium voltage distribution systems

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

AN EFFICIENT APPROACH FOR VISION INSPECTION OF IC CHIPS LIEW KOK WAH

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Transcription:

PREDICTING RECLOSER FAILURE RATES FROM FIELD CONDITION ASSESSMENT A Thesis by Joseph M. Warner Bachelor of Science, Wichita State University, 2004 Submitted to the College of Engineering and the faculty of the Graduate School of Wichita State University in partial fulfillment of the requirements for the degree of Master of Science December 2005

PREDICTING RECLOSER FAILURE RATES FROM FIELD CONDITION ASSESSMENT I have examined the final copy of this Thesis for form and content and recommend that it be accepted in partial fulfillment of the requirement for the degree of Master of Science in Electrical Engineering. Dr. Ward Jewell, Committee Chair We have read this Thesis and recommend its acceptance: Dr. Asrat Teshome, Committee Member Dr. Scott Miller, Committee Member ii

DEDICATION To my parents Bob and Louise Warner iii

ACKNOWLEDGMENTS I would like to thank my advisor, Dr. Ward Jewell, for all the time, effort, and patience while I pursued this research. Also, I want to thank PSERC for funding, and providing ways for students to network with industry while still in graduate school. Also, I would like to thank Pioneer Electric for all the practical and monetary assistance provided me through my college education. Much thanks to all the support from my friends and family, namely, my parents who, among many others, have always supported me in my endeavors and generally set a bar nearly unattainable.nearly. Thanks to all for pushing me so far, and expecting so much. I could not have done it without you. iv

ABSTRACT This research develops a technique to predict the failure rate of a power distribution system recloser. The prediction is based on suggested criterion given and defined within this paper. Because inspection practices differ among utilities, the technique will apply to whatever data is available, and make the best prediction from that data. Examples of using the technique are provided. Predicted failure rates can then be used in system simulations to predict system reliability indices, and the effect routine maintenance has on them. v

CONTENTS Chapter Page INTRODUCTION...1 METHODS AND PROCEDURES...2 Condition Assessment...2 Scoring...3 Weighting...3 Criterion Definitions...4 Age of Oil...4 Duty Cycle Rate...4 Environment Factor...5 Oil Dielectric Strength...5 Condition of Contacts...6 Age of Recloser...6 Experience with this Recloser Type...6 Condition of Tank...6 FAILURE RATE CALCULATION...7 EXAMPLE...10 CONCLUSION...13 Optimization...13 Future Research...13 LIST OF REFERENCES...15 vi

LIST OF TABLES Figure Page Table 1 - Recloser Score Sheet...2 Table 2 - Low Scoring Recloser...11 Table 3 - Average Scoring Recloser...12 Table 4 - High Scoring Recloser...12 vii

LIST OF FIGURES Figure Page Figure 1 Recloser Life Cycle..1 Figure 2 NEMA Standard Duty Cycle...4 Figure 3 Score/Failure Rate Relationship.11 viii

LIST OF ABBREVIATIONS NEMA SAIFI λ(x) x 0 x 1 x cs x fs National Electrical Manufacturers Association System Average Interruption Frequency Index Failure Rate Function defined with lambda The Best Condition Score Recorded The Worst Condition Score Recorded Recloser Sheet Condition Score Failure Rate Function Score ix

CHAPTER I INTRODUCTION There are approximately 1 million reclosers active on the U.S. power grid. As with all devices, mechanical and electrical, reclosers need routine maintenance to maintain performance relatively close to original specifications. Maintenance budgets are limited, requiring utilities to make decisions on which units to maintain each year. The repercussions of uneducated decisions either show up in the budget or the system reliability indices. These decisions must be made more frequently, due to an aging power utility system. A method is being developed to determine an optimal annual preventive maintenance routine based on available budget and personnel resources. Presently, failure rates of individual components are used in a system reliability model to estimate system reliability indices. However, a method to estimate the failure rate of a specific recloser has not been instituted. Therefore, this paper discusses a suggested methodology for estimating the failure rate of a recloser that is in service on the system. This research is part of a larger project where maintenance tasks are selected and scheduled based on the improvements to reliability indices due to the effect routine maintenance has on the parameters of interest. 1

CHAPTER 2 METHODS AND PROCEDURES In Figure 1, we see a simplified life-cycle of a recloser. Quantifying condition assessment and the improvement maintenance has on the condition are the two steps that are addressed in this paper. We are interested Reconditioned New Recloser In Service Condition Assessment Scrapped in the maintenance routine loop. Figure 1 - Recloser Life Cycle Condition Assessment The methodology begins by assessing the condition of the recloser. A scoring sheet that itemizes Age of Oil Criterion Weight Score (0-1) Pre- Maintenance relevant failure causes is shown in Table 1. Duty Cycle Rate The criteria on the score sheet have been Environmental Factor chosen carefully. They are all items that contribute to Oil Dielectric Strength Condition of Contacts the reliability of a recloser, and most of them can be Age of Recloser improved by routine maintenance. Those that cannot be improved are still quite relevant in determining the recloser s condition. These include the age of the recloser, the duty cycle rate and environmental factor, which are a function of placement on a distribution Experience with this Recloser Type Condition of Tank Sum Weighted Average Table 1 - Recloser Score Sheet system rather than maintenance. 2

Scoring Scoring a recloser begins with first deciding on which criteria from Table 2 to score for that recloser. Different types and models of reclosers, for example, will use different criteria. The score for each recloser assessed will then be normalized by dividing its score by its maximum possible score for the scored criteria. For example, to check the contacts and the oil dielectric strength, the recloser must be taken out of service; however, the cost to do this outweighs the benefit, unless removing the device is going to be done regardless. Therefore, these will not be included in the assessment or maximum possible score. The score for each item is a percentage of the state of the recloser criterion. For example, if the contacts are 60% of their original size, their score would be 0.60. A recloser that has completed 75% of its recommended duty cycle would have a duty cycle score of 0.25, indicating the remaining 25% of its duty cycle. The resulting condition score, between 0 and 1, is denoted as x cs. Weighting The weight column in Figure 2 represents the influence a particular condition actually has on the failure rate of a recloser. As this directly influences the actual score, much consideration should be made to determine the specific weights applied to the scoring sheet. The weights of most inspection items are determined by the combined opinion of manufacturers and experienced field personnel. However, certain items are utility dependent, such as the environment factor inspection item. 3

Criterion Definitions The following are explanations of why the criteria were selected, their importance to the condition of a recloser, and a suggested method of scoring. When scoring a recloser, not all of these criterions have to be scored to return an estimated failure rate. Age of Oil The oil in a recloser is the most important dielectric in the unit, especially if the contacts are not in a vacuum. The oil helps extinguish arcs as contacts open and close, keeps arcs from occurring between other electrical conductors within the recloser, lubricates most of the moving parts, and is used to raise the trip piston after the set operations. Expected oil life is generally 3 years. Oil age thus provides an estimate of the oil s dielectric strength without having to remove the recloser from service. Duty Cycle Rate Duty cycle is a measure of the level of use a recloser has experienced since its last maintenance, and is one of the most important issues for determining when maintenance Figure 2 - NEMA Standard Duty Cycle should be done again. Duty cycle is a combination of the number of interruptions the recloser has performed and either the percent of rated interrupting current or the circuit X/R value. The National Electrical Manufacturers Association (NEMA) has defined a standard duty cycle for distribution class reclosers, shown in Figure 2 [2]. Constant monitoring of every recloser s duty cycle is impractical, so an alternate criterion, duty cycle rate, is defined. 4

To calculate the duty cycle rate, the number of faults a recloser will see per year in a certain location is determined from the historical data used to calculate the utility s System Average Interruption Frequency Index (SAIFI), which is easily obtainable with automated outage systems described in [4]. The value of system X/R at the recloser location is determined from system data. Then the NEMA standard duty cycle definitions of Figure 2 give the number of operations per duty cycle for that location. Dividing the operations/cycle by expected operations/year gives the duty cycle in years/cycle for a recloser at that location. This is compared to expected oil life: Duty cycle rate = expected duty cycle/expected oil life This score is high for high expected remaining duty cycle. If the score is greater than one, then the expected duty cycle is longer than the expected oil life, and the score is entered as one. This score is a function of recloser location on the system, and not of actual recloser condition. Environment Factor This criterion is for reclosers in locations that require special consideration for more frequent maintenance. This is a combination of recloser placement and environmental effects on the physical condition of the recloser. For example, a recloser bank protecting a feeder along the coastline will experience air with a much higher salt content than those located farther inland. The salt may cause the dielectric strength of the recloser oil to fall below standards much sooner than normal. This criterion addresses such conditions. Oil Dielectric Strength This score is important if the maintenance routine includes filtering the oil instead of replacing it. The score should be given as the difference between the new oil dielectric strength 5

and the post-maintenance oil dielectric strength divided by the difference between the new and minimum oil dielectric strengths. i.e. d new d new d now d min = score Condition of Contacts This score is given as a percentage of remaining useful contact life. Age of Recloser The age of a recloser is important because, as with all machines, reclosers become less reliable with age, and will fail at some point. However, reclosers have proven to last for many years, and age is not a reliable predictor of failure. Recloser age should still be monitored, though, to help determine where new reclosers should be placed to increase reliability. Experience with this Recloser Type This criterion is used to differentiate among failure rates for different recloser manufacturers or models, types, and sizes of reclosers. Condition of Tank If a tank has excessive damage, either from nature or handling, it could need maintenance before it is justified by the other factors. The score sheet is suggested, and does not have to permanently be the above. However, it is a guide that includes what is most important to a recloser s sure operation for an extended period of time. That being said, all criterions need not be scored to obtain a condition score either. Next, the score failure rate relationship is defined followed by examples. 6

CHAPTER 3 FAILURE RATE CALCULATION The relationship between a recloser s condition score to its actual numerical failure rate is presented in [1]. Historical failure rate data from a number of systems were compiled for various power system components, including reclosers. From this data the best, worst, and average failure rates for each component were calculated. The resulting values for reclosers are: λ ( 0 ) = 0. 0025 (Best) ( 1 / 2) = 0. 015 λ (Average) λ () 1 = 0. 060 (Worst) If no historical data exists for the system to be modeled, then these values can be used. If, however, historical data is available for the system, then that data can be used to determine recloser failure rate statistics for that system. Equation 1, given in [3], demonstrates how a system-wide average recloser failure rate can be calculated: ( ) λ 1/2 = Total no. recloser failures ( No. reclosers ) x ( No. years ) (1) The historical failure rate is determined by dividing the total number of documented recloser failures by the product of the number of reclosers on the system at the time of the failures and the period of time the data is recorded. Obviously, the longer the period of time information over which is collected, the more accurate the failure rate calculation. Even though the calculation is simple, realizing it proves difficult for a few simple but noteworthy reasons. The first is that detailed records of the relevant information must be kept. For example, the number of reclosers on a system should be known constantly to ensure calculation accuracy. For this to take place, a utility must develop and implement a strategy to effectively collect and store the pertinent data. 7

Even when such a strategy is in place, reclosers inherently rarely fail, which is the second obstacle. A lengthy period of diligent record keeping thus precedes accurate rate calculate for a specific system. Although most utilities do keep records, they may not include the correct data needed to calculate recloser failure rates. Thus the main complication in calculating accurate failure rates is the tedious, never-ending process of accumulating specific data. However, once implemented, this process becomes routine and proves beneficial in many ways. A growing number of utilities have implemented automated systems to accurately keep track of their reliability indices, as stated in [4]. These systems are an example of how accumulating component data and calculating their effective failure rates can be done; however, time is still needed to attain an acceptable level of accuracy. Once the best, worst, and average failure rates for reclosers on a system are determined, either from historical or published [1] data, A, B, and C parameters are calculated using equation 2 [1]: 2 [ (1/ 2) λ(0) ] () 1 2λ( 1/ 2) + λ( 0) λ (2) A = λ λ(1/ 2) + A λ(0) B = 2ln A C = λ(0) A The parameters should be recalculated periodically as more historical failure rate data is collected. These parameters are then used in equation 3 to estimate the failure rate for a recloser [1]: B* x ( x) = Ae + C λ (3) In equation 3, λ(x) is the failure rate calculated from x, the relative condition score for the recloser. A high value of x cs represents a low failure rate, and a low value represents a high failure rate. Scores and failure rates must be directly related, so a new score is calculated: 8

x = 1 - x cs (4) However, using the condition score calculated in equation 4 to determine a failure rate using equation 3 will skew the resulting failure rates. A recloser would need a score of x cs = 1 to be assigned the worst failure rate on the system. But to get such a score of x cs = 1, a recloser would have to completely fail every condition with a score of zero, which is not practical. To correct this, the best and worst scores on the system should relate to the best and worst historical failure rates. This is done in equation 5, which modifies equation 4: x fs = 1 x cs x 1 x 0 x 1 = x 0 x cs x 0 x 1 (5) In this equation, x 1 is the worst recloser condition score recorded on the system, and x 0 is the best. With failure scores set this way, the lowest condition score recorded on the system will result in that recloser being assigned the lowest recorded failure rate. If any of the failure scores from equation 5 are negative, or greater than one, then the condition score x cs would replace the appropriate best or worst historical score, respectively. The high and low condition scores should be updated as appropriate: if x fs < 0, x cs is the updated x 0 if x fs > 1, x cs is the updated x 1 (6) (7) 9

CHAPTER 4 EXAMPLE Six years of outage data was obtained from a utility, and is used to illustrate the method developed in this paper. From the data, recloser failure rates are calculated. There were 23 recloser failures out of a total of 341 reclosers on the system over a span of 6.44 years. Equation 1 produces an average failure rate, λ(1/2) of: 23 λ (1/2) = 0.010473 341 * 6.44 = The best and worst failure rates, λ(0) and λ(1), are then calculated. Each recloser on the system failed either zero or one time during the six year period. This gives failure rates of: λ(0) = 0 failure / 6.44 years = 0.00000 λ(1) = 1 failure / 6.44 years = 0.15528 These are too low and too high, respectively, to be practical, so published failure rates [1] are used for the best and worst values: λ(0) = 0.0025 λ(1/2) = 0.010478021 λ(1) = 0.060 Next, the A, B, and C parameters are calculated using equation 2 to be: A = 0.0015321 B = 3.6514524 C = 0.0009679 10

The resulting equation is: λ ( x) := 0.0015321 e 3.6514524 x + 0.0009679 and the relationship of assessment score to failure rate is shown in Figure 3. It is next assumed that the worst (x 1 ) and best (x 0 ) historical scores for reclosers are 0.31 and 0.95, respectively. λ( x) 0.06 0.05 0.04 0.03 0.02 0.01 0 0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1 Figure 3 - Score/Failure Rate Relationship x The scores for a recloser that has been left in service until it fails are shown in Table 2. The recloser was considerable past its expected duty cycle. It was removed from service and scored. The resulting condition score x cs is 0.392. Equation 5 corrects this to 0.95 0.392 x fs := 0.95 0.31 x fs = 0.872 which results in a failure rate, equation 3, of λ( 0.872) = 0.038 Criterion Weight Score (0-1) Pre- Maintenance Age of Oil 20 0 Duty Cycle Rate 20 0.5 Environmental Factor 20 N/A Oil Dielectric Strength 15 N/A Condition of Contacts 15 N/A Age of Recloser 10 0.65 Experience with this Recloser Type 10 0.7 Condition of Tank 5 0.4 Sum 65 25.5 Weighted Average 0.392307692 Table 2 - Low Scoring Recloser The low condition score, 0.392, as expected, produced a higher than average failure rate. 11

Next, a recloser is scored, Table 3, with approximately the average failure rate. This score produces the estimated failure rate: λ 0.95 0.667 0.95 0.31 = 0.00867 This is close to the system average of 0.01048. Once again, notice that a score had been determined even though three of the criterions have not been scored. The score sheet demonstrates that we do not have any environmental issues on our system, and we did not Criterion Weight Score (0-1) Pre- Maintenance Age of Oil 20 0.33 Duty Cycle Rate 20 0.9 Environmental Factor 20 N/A Oil Dielectric Strength 15 N/A Condition of Contacts 15 N/A Age of Recloser 10 0.65 Experience with this Recloser Type 10 0.9 Condition of Tank 5 0.65 Sum 65 43.35 Weighted Average 0.666923077 Table 3 - Average Scoring Recloser remove the recloser from service to check the oil dielectric strength or the contacts. Finally, Table 4 scores a relatively new recloser, one that underwent scheduled maintenance about a year before it was scored. This is indicated by the age of the oil in the recloser. The recloser is not expected to complete a duty cycle before the oil is due to be changed again. The estimated failure rate for this recloser is: Criterion Weight Score (0-1) Pre- Maintenance Age of Oil 20 0.66 Duty Cycle Rate 20 1 Environmental Factor 20 N/A Oil Dielectric Strength 15 N/A Condition of Contacts 15 N/A λ 0.95.861 0.95 0.31 = 0.00351 Age of Recloser 10 0.95 Experience with this Recloser Type 10 0.9 Condition of Tank 5 0.85 This failure rate is close to 0.0025, the best failure rate previously found on the system. Sum 65 55.95 Weighted Average 0.860769231 Table 4 - High Scoring Recloser 12

CHAPTER 5 CONCLUSION This methodology allows quantifiable assessment of the condition of a recloser. The assessment can be done either in the field, without removing the recloser from service, or in the shop, after removal from service. The methodology then converts the assessment score to a predicted failure rate, which is based on historical data. The assessment criteria are directly related to maintenance tasks that may be performed on the recloser. Each maintenance task will increase the score for the associated criteria, resulting in a lower calculated failure rate. A similar method can be applied to other power distribution system electro-mechanical devices. The method will be used to schedule preventive maintenance to optimize system reliability indices. Optimization This thesis is part of a larger project that focuses on optimizing the distribution system routine maintenance to minimize the system indices. The maintenance tasks associated with each criterion will increase the affected criteria score; this may be 1, or something less than 1. The cost of each maintenance task will be defined, along with all labor and overhead costs involved with taking a recloser from service. Once all this information is gathered, optimization software will determine which reclosers and other equipment will be removed from service for maintenance, and in what order, to optimize system reliability indices. Future Research There are a few areas of this paper that need to be tested and researched more. First, actual system data needs to be used to determine the difficulty of gathering the data, and 13

integrating all the ideas to perform the analysis. Second, calculating failure rates generally provides indices for a system model that do not calculate indices that are similar to historical data [1]. To remedy this issue, calibration has been used to correct the difference between the two. The least squares approach using the method of gradient descent is suggested in [1]. This method adjusts the failure rates until the predicted reliability indices match historical values. Other non-invasive measures that are being used utilize sensors of various types to monitor abnormalities in sound, temperature, etc. to determine whether a failure is imminent. 14

LIST OF REFERENCES 15

LIST OF REFERENCES 1. Brown, Richard E., Failure Rate Modeling Using Equipment Inspection Data, IEEE Transactions on Power Systems, vol. 2, pp 782-787, May 2000. 2. Cooper Power Systems, Type H Single Phase Maintenance Instructions, Service Information number S280-10-1, January 1970, pg. 3 3. Horton, W.F.; Goldberg, S.; Volkman, C.A., The failure rates of overhead distribution system components, Transmission and Distribution Conference, 1991., Proceedings of the 1991 IEEE Power Engineering Society, 22-27 Sept. 1991 pp 713 717 4. Musser, Phil, The Many Routes of Reliability, Transmission and Distribution World, vol. 56. No. 6, June 2004 pg. 32. 16