Construction Standard No:

Similar documents
SECTION TRACER WIRE FOR NONMETALLIC PIPE

Sewer/Water Utility - Trace Wire Specification

1. TRACER WIRE. I. Application. Material Specification. Page 1 of 16

Sewer/Water Utility - Trace Wire Specification

Risk Assessment & Safe Working Practice

Construction Specification for Watermain and Water Service Tracer Wire

A. Product Description: Stranded conductor insulated wire.

BRASELTON WATER AND WASTEWATER DEPARTMENT CONSTRUCTION PLAN REVIEW CHECKLIST May 2006

Wiring Techniques for Wiring a Lamp

N5PUV s 4 Band Fan Dipole Experiment. Using the New SRI (Stanford Research Institute) Method

Electrical Wiring Projects

Stargrip series 3000 Mechanical Joint Wedge Action Restraint for Ductile Iron Pipe

TRANSACTION RECORD TR

Piping & Equipment Identification

HOW TO BUILD A THREE LEG TERMINATED DIPOLE T3FD COVERING

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

Big Oz. Rocket. User Guide V0313

Shannon s CCR Spiral Tree

Article 250 Grounding & Bonding

American Electrical Institute

SECTION ELECTRICAL IDENTIFICATION

4-8 HSF 250 Patriot. Line Stop Fitting Installation Instructions. Installation Instructions and Best Practices continued on back

THE W3FF HOMEBREW BUDDIPOLE

Appendix C Construction Details

ROVs in a Bucket Building an Underwater Robot. 5.0 Building the Tether

SECTION 7. SAFETYING

Wiring Repair WIRING REPAIR

ELECTRIC GROUNDING AND WIRING REQUIREMENTS BOOTHS-METAL

PART 4 STANDARD DRAWINGS FOR CONSTRUCTION

Water Level Meter: Op Instructions

PRODUCT CATALOG Meadowview Rd Junction City, OR fax

PIPE/CONDUIT SUPPORTS

Underground Pipe, Cable, and Leak Locating. Mark Beatty, Principal Owner/CEO

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents.

Connecting a Warp Feed to an Intelliframe

Page Electric Utility Service Specifications

HANDLEY CATHODIC TEST STATIONS

Easy-to-Build Homebrew Portable Vertical Antenna-4th Version

High-Tensile Coated Wire Fence Installation Guide

Repair Instructions. Replacing a La Z Time Mechanism Side Subassembly. Remove the Back(s): Remove the Mechanism Assembly: CAUTION.

CONTINUING EDUC ATION

Home Electrical Wiring. Types of Receptacles and Wiring them for 120v 15Amp/20Amp

Lucky Dog Sports Club.com 300 S. Central Blvd., Jupiter, FL

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33

Array Solutions OCF Series Dipoles

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

Heat Exchanger Coil: Build Instructions

A. Product Data: For each electrical identification product indicated.

Installation Instructions. Materials Needed. Parts Included. Tools You Will Need

RANGER Class Preview Product Demonstration Inner Space: Rigs to Reefs

Major 5001 Wire Stripper

Spiderbeam Balun Construction Guide

PureFlow PEX Crimp Zero Lead Fittings for Use with Viega PureFlow Tubing. Potable Water. Other

Omarshauntedtrail.com. Obtained from. Merlin's Wall Sconce.

1. ASME A Scheme for the Identification of Piping Systems.

Caution: Installation and Operation Instructions. Locking Mechanism (if supplied) Set Screws Backed Out. Mounting Orientation

INSTALLATION AND OPERATION MANUAL. Multiple-Radio Interface Module 41021G P-26 (11-12) 2012 David Clark Company Incorporated

How to Build a Fold- Down Greenhouse

Installation Instructions

installation guide 1 GUIDE#: pwb-assault-001

STANDARD RTD's INDEX

Electrical Wiring: Commercial, Seventh Canadian Edition

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

Instructions for Preparing AFL OPTICAL GROUND WIRE CABLE (ALUMACORE CABLE DESIGNS) FOR BPA

Storage Master. Shed Row. Poly Buildings

Instructions for Preparing OPTICAL GROUND WIRE IN AN ISOLATOR

SECTION COMMON WORK RESULTS FOR HVAC

Cable Hanging Instruction Manual

SECTION COMMUNICATIONS COPPER BACKBONE CABLING

SECTION III SUBMITTALS AND APPROVALS

PAC-12 Kit Contents. Tools Needed Soldering iron Phillips screwdriver Wire stripper Wrenches, 7/16 and 1/2 Terminal crimp tool Pliers Solder

Hardware Store 40m Magnetic Loop Antenna for Regional and EMCOM Use. Richard Bono NO5V. QST Antenna Design Competition 80 through 10 meter entry

SECTION III STANDARD DRAWINGS ROYSE CITY GENERAL CONSTRUCTION NOTES & DETAILS

Installation & Operation Manual

Installation Instructions Hustler 6-BTV Trap Vertical

American Morse Equipment

NEW OR UPGRADED ELECTRICAL SERVICE

Designs for Generating the Jeff Cook Effect

SECTION IDENTIFICATION FOR HVAC PIPING, DUCTWORK AND EQUIPMENT

ELECTRICAL PANEL SYSTEM

Universal End of Period (EOP) Segment Installation Manual

Aluminum HF Vertical Travel Antenna

SUT-1000CLC ASSEMBLY REQUIREMENTS

Installation Instructions Hustler 6-BTV Trap Vertical

TYPHOON ASSEMBLY AND INSTALLATION INSTRUCTIONS

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing).

DETAIL SPECIFICATION SHEET FITTINGS - INSTALLATION OF FLARED TUBE, STRAIGHT, THREADED CONNECTORS, DESIGN STANDARD FOR

Wind Pump Construction

The W3FF Portable Dipole

Wind Turbine Experimenter s Kit User Guide

THE ROGUE TM FUNSLIDE TM

Low/High Tunnel Greenhouse Plans

& ' (wire, inches) 16 black Tef-Flex 16 Black Lex 32 Red Lex 48 Blue Tef-Flex 32 White Tef-Flex

SECTION CHAIN LINK FENCING AND GATES AND SOFTBALL BACKSTOP

Industrial Pipe Marking

Instruction Manual for MHE Products DeepWater2 PushPoint Sampler Ver. 2.0 November 21, 2016

Rough Country JK Modular Winch Mount Bumper With Light End Caps

HQ Hideaway. Installation and Operation Version 2.2, April 2015 Part # QT40100

PORTABLE PULL TESTER

Hoop House Construction Plans

Transcription:

Page: 1 of 5 GENERAL * This Construction Standard governs trace wire installation on water mains. A 14 gauge or larger trace wire shall be installed on all water mains. Exception: Water mains as part of a relocation project shall have trace wire installed: - If the length of the relocated section is 600 or greater - The length of the relocated section is between 200 and 600 and includes a valve (including hydrant branch valves) - The main being relocated currently has trace wire on it - All relocated PVC and HDPE water mains - Where called for on project drawings Typical hydrant branches, that are perpendicular to the water main, do not require trace wire. Trace wire shall be installed on non-typical hydrant branches (i.e. dog-legged hydrant branch). * Take care to protect the wire insulation and repair it with electrical tape if the coating is damaged. Always attach the wire to the lead end of the pipe when boring or plowing and avoid kinking or tangling the wire during installation. Because of the tremendous strain on trace wire when using directional boring equipment, three 10 or 12 gauge wires should be pulled with the main in case one or two wires break. * APPROVED TRACE WIRE MATERIAL - Trace wire for direct bury installations shall be #14 AWG Copper Clad Steel wire as manufactured by Copperhead Industries, LLC #14 AWG solid Copper wire with 30 mil high molecular weight polyethylene insulation as manufactured by Agave Wire LTD, or approved equal. * - Trace wire for water mains installed by directional boring shall be #12 or #10 AWG copper clad steel wire as manufactured by Copperhead Industries, or approved equal. - Blue tri-view plastic markers by Rhino w/test Screws - 4 ft U-channel posts - Valve Box Top Sections - Direct Bury Wire Nuts (Dryconn Direct Bury Wire Nut (10444) manufactured by King Innovation, DBY-6 or DBR-6 as manufactured by 3M or approved equal). - Direct Bury Lug (Dryconn Direct Bury Lug as manufactured by King Innovation or approved equal). * Revised Text TRACE WIRE CONNECTIONS Joining Ends of Trace Wire: Connections into existing trace wire, connections into trace wire used during water main bores, connections between one spool of trace wire to another, and other similar connections shall be made using a direct bury wire nut.

Page: 2 of 5 When connecting trace wire ends together, strip 5/8 of insulation from the end of each wire. Insert the two ends firmly into the direct bury wire nut. Twist the wire nut clockwise while pushing the wires firmly into the nut. Do not over torque. Tie the wires in a knot as shown in Fig 1. Joining Trace Wire - Branch to Main: Connections of trace wire at tees, crosses, and at locations where the trace wire will be brought to the surface shall be conducted using a direct bury lug. Refer to Fig 2 for this connection style.

Page: 3 of 5 INSTALLATION Trace wire shall be installed in a continuous fashion. Install trace wire on top of water main and secure to main every five (5) feet with tape as shown in Fig 3. Bring trace wire to surface at every cc box, vault, blue plastic marker with trace wire connectors, dead end hydrants, and as called out in the drawings. Trace wire shall be brought to the surface at least every one thousand (1,000) feet. Take care not to damage the wire coating. Repair damaged coating with electrical tape. Trace Wire in a Vault Trace wire shall be brought up in all vaults. Trace wire shall be brought to the surface according to Fig 4. Do not wrap the trace wire around the steps or any other place where a person entering the vault could trip on the wire.

Page: 4 of 5 Trace Wire in Blue Plastic Pipe Line Marker When bringing the trace wire up in a blue plastic pipe line marker, install the trace wire according to Fig 5. Bury a four foot u-channel post two feet in the ground. Run the trace wire up through the marker and slide the blue plastic marker over the post. Bury the bottom six inches of the marker. Connect the trace wire to the brass connecting screws and label the screws with a permanent marker as shown in Fig 5. Note location of trace wire pipeline marker on as-built drawings. Note: If a marker is used only to mark the main location and not bring up the trace wire, use the blue markers without the trace wire connectors. Trace Wire in a CC Valve Box Trace wire shall be brought up in all cc valve boxes. The trace wire shall be brought to the surface according to Fig 6.

Page: 5 of 5 Trace Wire in PVC Conduit at Hydrant Trace wire shall be brought up in a PVC conduit at all dead end/end of main fire hydrants without a valve and at hydrants of a non-typical hydrant branch (i.e. dog-legged hydrant branch). Trace wire shall be brought to the surface according to Fig 7. Note location of PVC conduit in relation to the hydrant (i.e. north, east, south or west) on as-built drawings.