Compensation of Dead Time in PID Controllers

Similar documents
DeltaV v11 PID Enhancements for

Procidia Control Solutions Dead Time Compensation

CHBE320 LECTURE XI CONTROLLER DESIGN AND PID CONTOLLER TUNING. Professor Dae Ryook Yang

Feedforward and Ratio Control

Getting the Best Performance from Challenging Control Loops

Different Controller Terms

-binary sensors and actuators (such as an on/off controller) are generally more reliable and less expensive

STANDARD TUNING PROCEDURE AND THE BECK DRIVE: A COMPARATIVE OVERVIEW AND GUIDE

Think About Control Fundamentals Training. Terminology Control. Eko Harsono Control Fundamental - Con't

Various Controller Design and Tuning Methods for a First Order Plus Dead Time Process

International Journal of Research in Advent Technology Available Online at:

Class 5. Competency Exam Round 1. The Process Designer s Process. Process Control Preliminaries. On/Off Control The Simplest Controller

6.4 Adjusting PID Manually

Logic Developer Process Edition Function Blocks

Nonlinear Control Lecture

MM7 Practical Issues Using PID Controllers

Automatic Controller Dynamic Specification (Summary of Version 1.0, 11/93)

PROCESS DYNAMICS AND CONTROL

PROCESS DYNAMICS AND CONTROL

PID control. since Similarly, modern industrial

Experiment 9. PID Controller

A M E M B E R O F T H E K E N D A L L G R O U P

CHAPTER 4 PID CONTROLLER BASED SPEED CONTROL OF THREE PHASE INDUCTION MOTOR

Find, read or write documentation which describes work of the control loop: Process Control Philosophy. Where the next information can be found:

Enhance operational efficiency with Advanced Process Control (APC) Integration of APC in SIMATIC PCS 7 SIMATIC PCS 7. Answers for industry.

Effective Use of PID Features for Loop Performance and Optimization. Greg McMillan CDI Process & Industrial Hector Torres Solutia Inc.

InstrumentationTools.com

Switch Mode Power Conversion Prof. L. Umanand Department of Electronics System Engineering Indian Institute of Science, Bangalore

F. Greg Shinskey. "PID Control." Copyright 2000 CRC Press LLC. <

PID Control Technical Notes

Modified ultimate cycle method relay auto-tuning

Chapter 4 PID Design Example

PROCESS CONTROL DIAGNOSTICS. F. Greg Shinskey Process Control Consultant North Sandwich, NH 03259

Controller Algorithms and Tuning

LESSON 2: ELECTRONIC CONTROL

Paul Schafbuch. Senior Research Engineer Fisher Controls International, Inc.

Level control drain valve tuning. Walter Bischoff PE Brunswick Nuclear Plant

Optimize Your Process Using Normal Operation Data

Application Note. Renu Electronics Private Limited. PID Instruction In IEC. Page 1

2.1 PID controller enhancements

Effective Use of PID Controllers ISA New Orleans Standards Certification Education & Training Publishing Conferences & Exhibits

QuickBuilder PID Reference

CHAPTER. delta-sigma modulators 1.0

The PID controller. Summary. Introduction to Control Systems

GLOSSARY OF TERMS FOR PROCESS CONTROL

6545(Print), ISSN (Online) Volume 4, Issue 1, January- February (2013), IAEME & TECHNOLOGY (IJEET)

Chapter 6 Controller Design Using Design Tools

PID control of dead-time processes: robustness, dead-time compensation and constraints handling

Introduction To Temperature Controllers

Andrea Zanchettin Automatic Control 1 AUTOMATIC CONTROL. Andrea M. Zanchettin, PhD Spring Semester, Linear control systems design

Process controls in food processing

SECTION 6: ROOT LOCUS DESIGN

Understanding PID Control

Non Linear Tank Level Control using LabVIEW Jagatis Kumaar B 1 Vinoth K 2 Vivek Vijayan C 3 P Aravind 4

ELT 215 Operational Amplifiers (LECTURE) Chapter 5

Relay Based Auto Tuner for Calibration of SCR Pump Controller Parameters in Diesel after Treatment Systems

DESIGN AND ANALYSIS OF TUNING TECHNIQUES USING DIFFERENT CONTROLLERS OF A SECOND ORDER PROCESS

Loop Design. Chapter Introduction

Instrumentation and Process Control. Process Control. Pressure, Flow, and Level. Courseware Sample F0

BINARY DISTILLATION COLUMN CONTROL TECHNIQUES: A COMPARATIVE STUDY

Cohen-coon PID Tuning Method; A Better Option to Ziegler Nichols-PID Tuning Method

Model Based Predictive Peak Observer Method in Parameter Tuning of PI Controllers

CHAPTER 11: DIGITAL CONTROL

Position Control of DC Motor by Compensating Strategies

Introduction to Servo Control & PID Tuning

PID Tuning Guide. For the Allen-Bradley Family of PLCs. A Best-Practices Approach to Understanding and Tuning PID Controllers

Advanced Control Foundation: Tools, Techniques and Applications. Terrence Blevins Willy K. Wojsznis Mark Nixon

Glossary of terms. Short explanation

Embedded Control Project -Iterative learning control for

Performance Monitor Raises Service Factor Of MPC

Tuning interacting PID loops. The end of an era for the trial and error approach

IMC based Smith Predictor Design with PI+CI Structure: Control of Delayed MIMO Systems

DESIGN OF PID CONTROLLERS INTEGRATOR SYSTEM WITH TIME DELAY AND DOUBLE INTEGRATING PROCESSES

Application Note (A13)

Bulletin 1402 Line Synchronization Module (LSM)

CHAPTER 4 AN EFFICIENT ANFIS BASED SELF TUNING OF PI CONTROLLER FOR CURRENT HARMONIC MITIGATION

I/A Series Software. Extended Proportional-Integral-Derivative (PIDX) Controller PSS 21S-3F3 B4 OVERVIEW PRODUCT SPECIFICATIONS

CSE 3215 Embedded Systems Laboratory Lab 5 Digital Control System

SxWEB PID algorithm experimental tuning

Linearity Improvement Techniques for Wireless Transmitters: Part 1

Control Theory. This course will examine the control functions found in HVAC systems and explain the different applications where they are applied.

1. Consider the closed loop system shown in the figure below. Select the appropriate option to implement the system shown in dotted lines using

Closed-Loop Position Control, Proportional Mode

Configuration Example of Temperature Control

ChE 4162 Control Laboratory Methodologies Fall Control Laboratory Methodologies

Designing PID for Disturbance Rejection

Fundamentals of Servo Motion Control

Controller Tuning for Disturbance Rejection Associated with Delayed Double Integrating processes, Part IV: PID Plus First-Order Lag Controller

The issue of saturation in control systems using a model function with delay

Anti Windup Implementation on Different PID Structures

AVR221: Discrete PID Controller on tinyavr and megaavr devices. Introduction. AVR 8-bit Microcontrollers APPLICATION NOTE

LAMBDA TUNING TECHNIQUE BASED CONTROLLER DESIGN FOR AN INDUSTRIAL BLENDING PROCESS

2. Basic Control Concepts

Process Control Laboratory Using Honeywell PlantScape

TTH300. Temperature transmitter. Additional Information. FOUNDATION Fieldbus. Measurement made easy

Series Resistance Compensation

CHAPTER 4 LOAD FREQUENCY CONTROL OF INTERCONNECTED HYDRO-THERMAL SYSTEM

Closed-Loop Transportation Simulation. Outlines

PID Tuner (ver. 1.0)

Simulation and Analysis of Cascaded PID Controller Design for Boiler Pressure Control System

Transcription:

2006-12-06 Page 1 of 25 Compensation of Dead Time in PID Controllers Advanced Application Note

2006-12-06 Page 2 of 25 Table of Contents: 1 OVERVIEW...3 2 RECOMMENDATIONS...6 3 CONFIGURATION...7 4 TEST RESULTS...11 5 REFERENCES...25

2006-12-06 Page 3 of 25 1 Overview PID controllers with dead time compensation are reported to eliminate dead time in terms of a controller seeing the effect of changes in its controller output. For set point changes where all the controller needs to be concerned with is how its output responds to a new set point, the results are impressive for an exact knowledge of the process dead time. However, for unmeasured load disturbances at the process input, the ultimate performance is set by the total dead time from the process equipment, piping, control valves, instrumentation, and digital devices. This application note shows that a dead time compensator can offer some improvement in load rejection by facilitating more aggressive tuning of the PID but with a considerable risk of oscillations from an inaccurate dead time. The ultimate performance achievable in terms of load disturbance rejection depends upon the dead time. In the Theory section of Chapter 2 of Advanced Control Unleashed equations are developed that show the minimum peak error is proportional to the dead time and the minimum integrated error is proportional to the dead time squared for unmeasured load upsets. How close the actual performance of a control loop comes to this ultimate performance depends upon PID structure, tuning, and enhancements. This blog focuses on the effect of variations in dead time on the performance and robustness of dead time compensation as an enhancement and Lambda as a tuning rule for disturbance rejection. The two predominant methods of dead time compensation studied here are the Smith Predictor PID and the PID with a delayed external reset. The Smith Predictor was extensively documented in the 1970s. It provides a new controlled variable that is the response of the process variable to its controller output without dead time. It requires entry of three parameters commonly known as process gain, dead time, and time constant. The Smith Predictor uses these parameters to create models of the process from the controller output. In its most documented form, the Smith predictor subtracts a model of the process with dead time from a model of the process without dead time and adds the net result to the measured process variable to create a new controlled variable. If the model is perfect, the new controlled variable has zero dead time in terms of the controller seeing the effect of its own controller output. Since the maximum allowable controller gain is inversely proportional to dead time, the controller gain can theoretically increased without limit for a perfect model provided you ignore extenuating circumstances, such as loop interaction, measurement noise, and final element dead band and resolution. One of the practical issues with the Smith Predictor is that the new controlled variable of the PID is no longer the actual process variable. The original process variable must be restored for the operator interface to the PID. Also, performance monitoring or trending must look at the original process variable rather than the new controlled variable used by the PID. Terry Blevins proposed in the 1979 ISA paper Modifying the Smith Predictor for an Application Software Package a multiplicative and additive correction of the process variable to deal with changes in the slope (gain) and intercept (bias), respectively in the process model. The PID with a delayed external reset was informally presented in the 1980s and published in the early 1990s. It simply consists of putting a dead time (DT) block in the external reset. This method only requires that a single parameter commonly known as process dead time be entered as the dead time in the DT block. Terry Blevins documented in the early 1990s how the Smith Predictor for a particular Lambda tuning reduces to this PID with a delayed external reset. The delayed external reset method of dead time compensation has several advantages readily evident. The user is not required to identify or estimate the process gain or process time constant. Also, the actual process variable is left intact. Other possibilities also exist for a more informative external reset signal than just the Analog Output (AO) block BKCAL_OUT, such as the use of read back actual valve position from a Digital Valve Controller (DVC) or a secondary loop s process variable for a cascade control loop. These alternative external reset (ER) signals may potentially be able to compensate for dynamics and disturbances of control valves or secondary loops. These ER signals can additionally protect the primary controller from outrunning the slewing rate of the control valve or the response of the secondary loop and prevent the walk off of override controllers. However, if a feedforward multiplier or split range block is

2006-12-06 Page 4 of 25 used, the signal used for external reset must be converted back to its original basis as the controller output (e.g. divided by feedforward multiplier). For more details on the value and use of external reset, see the article The Power of External Reset Feedback in the May 2006 issue of Control magazine. The results presented here show that for a perfect model and the same controller tuning the PID with a delayed external reset performed better for processes with a small dead time to time constant ratio (time constant dominant), whereas the Smith Predictor performed better for processes with a large dead time to time constant ratio (dead time dominant). The Smith Predictor did not do as well for small dead time to time constant ratios because the control error seen in the controlled variable by the PID is much smaller than the actual control error in the process variable. In both cases, the improvement was not as impressive as the improvement gained from setting Lambda equal to the dead time rather than the time constant. Surprisingly the improvement in load disturbance rejection from dead time compensation was greater for processes with small dead time to time constant ratios. This goes against the conventional wisdom that the best opportunity for dead time compensation is for dead time dominant loops. The results can be explained in terms of the ultimate limit for performance of dead time dominant loops being lower. The reduction in the peak excursion from more aggressive tuning settings is negligible for dead time dominant processes because the peak error is essentially the open loop error. Another startling result was how quickly a Smith Predictor erupted into rapidly growing oscillations in the controller output when the model dead time was more than twice the actual process dead time. The fast full scale oscillations in the controller output resembled on-off control. While it is relatively well known that dead time compensators are sensitive to model mismatch, the effect was expected to be gradual and thought to be more in terms of a model dead time being too small. The concern for rapid deterioration for a model dead time being too large was raised in Good Tuning a Pocket Guide and was documented for model predictive control in Models Unleashed. While a PID with delayed external reset is also adversely affected by a dead time mismatch in both directions, this PID develops a small amplitude high frequency dither rather than a full scale oscillation in controller output for an excessively high model dead time. The consequence is less severe and may be adequately handled by the addition of a small dither filter inserted in the PID controller output, but this was not tested. Another major point here is that PID controller tuning for self-regulating processes without extenuating circumstances can only initiate oscillations for an identified (modeled) process dead time or gain that is too small or an identified time constant that is too large. For PID controllers with dead time compensation or model predictive controllers, high and low identified (model) values can cause oscillations. In order to get the performance benefit from dead time compensation, the PID must be tuned more aggressively. In other words, a PID with dead time compensation will perform the same as a PID without dead time compensation if they are tuned the same. While the improvement in integrated absolute error (IAE) for load upsets from more aggressive tuning (higher controller gain and lower reset time) can be accurately estimated for a regular PID, the equation does not work well for a dead time compensator. Furthermore, a dead time compensator soon reaches a point of diminishing returns. For example, the improvement in load rejection of a Smith Predictor from a controller gain that is quadrupled may not be noticeable whereas for a regular PID, it normally results in a four fold reduction in IAE. It is important to remember there is a tradeoff between performance and robustness for any feedback controller in that as you make controller tuning more aggressive to improve load rejection you make the controller more sensitive to changes in the process gain, dead time, or time constant. A nonlinear gain from the installed characteristic of a control valve has been widely discussed. However, the nonlinearity of the process gain of the temperature or composition response is the inverse and consequently the combined effect is less than documented when these loops directly manipulate a control valve. The variability of dead time is often larger than the variability of the process gain or time constant because the dead time is inversely proportional to a rate (e.g. flow rate or pumping rate or rate of change of a signal) and has many different sources (e.g. valve deadband or resolution, piping transportation delay, mixing delay, process lags in series, sensor lags, signal filters, and discrete communication or scan intervals). Thus, it is problematic to compute the dead time accurately enough to get the benefit of a dead time compensator.

2006-12-06 Page 5 of 25 The calculation of process dead times and the role of PID structure will be addressed will be detailed in Advanced Application Notes 004 and 005, respectively. Only a small portion of the test results are included here as figures. A more complete compilation of test results is posted on the web site under the category of Continuous Control. Information on disturbances, dead time, and controller tuning is also posted on the this website under the categories of Plant Design and Tuning and Control System Performance. http://modelingandcontrol.com

2006-12-06 Page 6 of 25 2 Recommendations To improve the performance of a PID controller for load disturbances at the process input: (1) First improve the PID controller tuning before even considering dead time compensation. Setting Lambda equal to the maximum dead time (Lambda factor equal to the maximum dead time to time constant ratio) is effective for load disturbances at the process input if there are no extenuating circumstances. (2) Add feedforward control whenever it is possible to measure or infer load disturbances at the process input. (3) If there is economic justification for further improvement and the dead time can be updated within 25% accuracy for varying operating conditions, trial test and closely monitor a PID with delayed external reset for low dead time to time constant ratios. (4) For loops with high dead time to time constant ratios, multiple manipulated variables, interactions, or constraints, consider model predictive control.

2006-12-06 Page 7 of 25 3 Configuration A DeltaV library module template titled PID_DEADTIME is available for implementing the Smith Predictor in DeltaV. It provides additional features such as a bias or process gain correction to the process model for major load disturbances. This study used a simple Smith Predictor of the form commonly documented in the literature. Figure 3-1a shows the module used for testing the PID with a Smith Predictor. It includes a simple process simulation that consists of an actuator and a first order plus dead time process. The three process parameters are PROCESS_GAIN, PROCESS_DELAY, and PROCESS_LAG. The actuator can simulate stroking lags, delay, deadband, and stick-slip but these were all set to zero or negligible values for this study. The module also includes noise added to the AT2 block output and a periodic load upset added to the process input. The load upset goes through a filter block whose filter time is the upset lag (UPSET_LAG). If the upset lag is zero, the upset is a step change at the process input. The Smith Predictor is a composite block shown in Figure 3-1a. The output of the AV2 block is the input signal to the Smith Predictor. The three parameters provided to the Smith Predictor are MODEL_GAIN, MODEL_DELAY, and MODEL_LAG. For a perfect model, these parameter values are equal to their corresponding process parameter values. A DITHER_FILTER block was inserted between the OUT and the AV2 block CAS_IN but it did nothing in these tests (filter time constant was kept at zero). Note that in control literature, different nomenclature is often used for the three dynamic parameters of a first order plus dead process or model. For each parameter below, the first name is the most common and the last name is most specific. process gain = plant gain = open loop gain process dead time = plant delay = total loop dead time process time constant = plant lag = open loop time constant Figure 3-1b shows the drill down into the composite block. The Smith Predictor input signal is multiplied by the model gain in the MLTY1 block and then goes through a filtered with a process lag in the FLTR1 block. The output of FILTR1 block is delayed via the DT1 block and subtracted in the SUB1 block from its undelayed output. The Smith Predictor output is added in the main module via the SUM2 block to the output of the PV2 block, which has added noise to the AT2 block output. If the model is perfect and there are no disturbances or noise, the model with the delay cancels out the measured process variable from the AI block. What is left is the process model without any dead time (delay). Any loop without dead time and extenuating circumstances can have its controller gain increased without limit and still be stable. A common mistake is to forget that the process variable used by PID as the controlled variable is no longer the actual process variable but a model of the process response without dead time based solely on the controller output. Trends of the PID PV will show a much smaller deviation from the set point and a false sense of actual control loop performance.

2006-12-06 Page 8 of 25 Smith Predictor Output Figure 3-1a Test Module with Embedded Smith Predictor Composite Block Smith Predictor Embedded Composite Figure 3-1b Drill Down of Embedded Smith Predictor Composite Block

2006-12-06 Page 9 of 25 Figure 3-2a shows the test module for PID with delayed external reset. A dead time block DELAY_COMP was inserted between the BKCAL_OUT of the AV2 block and the BKCAL_IN of the block. This method of dead time compensation requires just one parameter, which is the model dead time (MODEL_DELAY). A DITHER_FILTER block was inserted between the OUT and the AV2 block CAS_IN but it did nothing in these tests (filter time constant was kept at zero). This test module employs the same type of process simulation used in the test module for the Smith Predictor. Figure 3-2b shows that in order for external reset signal to be used, the Dynamic Reset Limit box must be checked in FRSPID_OPTS for the PID. This method dead time compensation has several advantages readily evident. The user is not required to identify or estimate the process gain or process time constant. Also, the actual process variable is left intact. Other possibilities also exist for a more informative external reset signal than just the Analog Output (AO) block BKCAL_OUT, such as the use of read back actual valve position from a Digital Valve Controller (DVC) or a secondary loop s process variable for a cascade control loop. These alternative external reset (ER) signals may potentially be able to compensate for dynamics and disturbances of control valves or secondary loops. These ER signals can additionally protect the primary controller from outrunning the slewing rate of the control valve or the response of the secondary loop and prevent the walk off of override controllers. However, if a feedforward multiplier or split range block is used, the signal used for external reset must be converted back to the original basis of the controller output (e.g. divided by feedforward multiplier).

2006-12-06 Page 10 of 25 Delayed External Reset Figure 3-2a Test Model for PID with Delayed External Reset Figure 3-2b Enabling of Dynamic Reset Limit in FRSPID_OPTS for PID with Delayed External Reset

2006-12-06 Page 11 of 25 4 Test Results In all of the test results the used for comparison purposes is always an uncompensated PID with Lambda equal to the process time constant (lag), which is equivalent to a Lambda factor of one. All tests have an unmeasured load disturbance at the process input. The first upset in each figure is for a step disturbance. The second upset in each figure is for a disturbance that has been slowed down by a time constant (upset lag) that is twice the original process dead time. The first set of test results in Figure 4-1a through 4-1f illustrates the effect of different tuning for different model accuracies for a low and high dead time to time constant ratio. Here is an uncompensated PID with Lambda equal plant delay (process dead time) which is equivalent to a Lambda factor set equal to the delay/lag ratio (dead time to time constant ratio). Figures 4-1a through Figure 4-1c is for a control loop with a 0.2 delay/lag (dead time to time constant) ratio. This ratio of 0.2 is seen in concentration and temperature control of columns and vessels where there is a low degree of back mixing. Single large gas pressure volumes and highly agitated vessels with a low turnover time can have a much lower delay/lag ratio if there is no significant additional dead time associated with an analyzer, sensor, or wireless communication time. The improvement in the integrated absolute error (IAE) is about 66% from setting the Lambda equal to the process dead time instead of the process time constant and matches well the improvement predicted by Equations 2-2a and 2-2b in the book New Directions in Bioprocess Modeling and Control. This IAE improvement holds up even for the 50% increase in plant delay in Figure 4-1b. For the 50% decrease in plant delay in Figure 4-1c, the IAE is slightly less for both and but the per cent improvement is basically the same. Figure 4-1d through Figure 4-1f is for a control loop with a 4.0 delay/lag (dead time to time constant) ratio. This ratio of 4.0 is seen in concentration and temperature control of plug flow pipelines and exchanger volumes where there is essentially no back mixing. This high ratio also occurs when chromatographs with a cycle time and sample transportation delay much larger than the residence time of an agitated volume. Even higher ratios occur for sheet thickness control. The improvement in the IAE is negligible but the controller is less oscillatory for the original plant delay and a 50% increase in plant delay (process dead time). An upset lag makes both loops less oscillatory. For a decrease in plant delay both controllers have a very smooth responses but the return to set point is noticeably faster for.

2006-12-06 Page 12 of 25 Load Upset IAE Improvement (%) Original Plant Delay Original Delay/Lag Ratio = 0.2 = standard PI = standard PI ) Figure 4-1a Uncompensated PID for 0.2 Delay/Lag Ratio and Original Plant Delay Load Upset IAE Improvement (%) 50% Increase in Plant Delay Original Delay/Lag Ratio = 0.2 = standard PI = standard PI ) Figure 4-1b Uncompensated PID for 0.2 Delay/Lag Ratio and 50% Increase in Plant Delay

2006-12-06 Page 13 of 25 Load Upset IAE Improvement (%) 50% Decrease in Plant Delay Original Delay/Lag Ratio = 0.2 = standard PI = standard PI ) Figure 4-1c Uncompensated PID for 0.2 Delay/Lag Ratio and 50% Decrease in Plant Delay Original Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI = standard PI ) Figure 4-1d Uncompensated PID for 4.0 Delay/Lag Ratio and Original Plant Delay

2006-12-06 Page 14 of 25 50% Increase in Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI = standard PI ) Figure 4-1e Uncompensated PID for 4.0 Delay/Lag Ratio and 50% Increase in Plant Delay 50% Decrease in Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI = standard PI ) Figure 4-1f Uncompensated PID for 4.0 Delay/Lag Ratio and 50% Decrease in Plant Delay

2006-12-06 Page 15 of 25 The second set of test results shows how well a Smith Predictor can do. Here is a Smith Predictor PID with the gain doubled and the reset time halved after Lambda has again been set equal to the plant delay (process dead time). In other words, this has twice the proportional and integral action of the uncompensated in the first set of test results. Figures 4-2a through Figure 4-2d is for a control loop with a 0.2 delay/lag ratio. The improvement in the integrated absolute error (IAE) in Figure 4-2a is about 76% over the uncompensated conservatively tuned, which is about 10% better than an uncompensated more aggressively tuned in the first set of test results. This improvement holds up for 50% changes in the plant delay as illustrated by Figure 4-2b and Figure 4-2c. However, if the model delay is more than 100% higher than the plant delay, the Smith Predictor breaks out into growing oscillations in the controller output as shown in Figure 4-2d. The risk of essentially on-off control from a high model dead time may be an unacceptable risk. Figures 4-2e through Figure 4-2h is for a control loop with a 4.0 delay/lag ratio. The Smith Predictor is less oscillatory than the uncompensated conservatively tuned for the original plant delay and a increase in plant delay shown in Figures 4-2e and Figure 4-2f. However, for an decrease in plant delay shown in Figure 4-2g, which is normally thought of as a more stable condition, high frequency oscillations start to appear. If the model delay is more than 100% higher than the plant delay, the Smith Predictor breaks out into growing oscillations in the controller output as shown in Figure 4-2h.

2006-12-06 Page 16 of 25 Load Upset IAE Improvement (%) Original Plant Delay Original Delay/Lag Ratio = 0.2 = standard PI (AT2/PV)= Smith Predictor PI Figure 4-2a Smith Predictor PID for 0.2 Delay/Lag Ratio and Original Plant Delay Load Upset IAE Improvement (%) 50% Increase in Plant Delay Original Delay/Lag Ratio = 0.2 = standard PI (AT2/PV)= Smith Predictor PI Figure 4-2b Smith Predictor PID for 0.2 Delay/Lag Ratio and 50% Increase in Plant Delay

2006-12-06 Page 17 of 25 Figure 4-2c Smith Predictor PID for 0.2 Delay/Lag Ratio and 50% Decrease in Plant Delay 110% Increase in Model Delay Original Plant Delay Original Delay/Lag Ratio = 0.2 = standard PI (AT2/PV)= Smith Predictor PI Figure 4-2d Smith Predictor PID for 0.2 Delay/Lag Ratio and 110% Increase in Model Delay

2006-12-06 Page 18 of 25 Original Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI (AT2/PV)= Smith Predictor PI Figure 4-2e Smith Predictor PID for 4.0 Delay/Lag Ratio and Original Plant Delay 50% Increase in Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI (AT2/PV)= Smith Predictor PI Figure 4-2f Smith Predictor PID for 4.0 Delay/Lag Ratio and 50% Increase in Plant Delay

2006-12-06 Page 19 of 25 50% Decrease in Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI (AT2/PV)= Smith Predictor PI Figure 4-2g Smith Predictor PID for 4.0 Delay/Lag Ratio and 50% Decrease in Plant Delay 110% Increase in Model Delay Original Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI (AT2/PV)= Smith Predictor PI Figure 4-2h Smith Predictor PID for 4.0 Delay/Lag Ratio and 110% Increase in Model Delay

2006-12-06 Page 20 of 25 The third set of test results shows how well a simpler type of dead time compensated PID reset can do. Here is a PID with a delayed external reset. Like the Smith Predictor the gain is doubled and the reset time halved after Lambda has again been set equal to the plant delay (process dead time). In other words, this like the Smith predictor has twice the proportional and integral action of the uncompensated in the first set of test results. Figures 4-3a through Figure 4-3d is for a control loop with a 0.2 delay/lag ratio. The improvement in the integrated absolute error (IAE) in Figure 4-3a is about 88% over the uncompensated conservatively tuned, which is about 22% better than an uncompensated more aggressively tuned in the first set of test results. It is anticipated that the improvement increases as the delay/lag ratio decreases. The improvement is large enough for this dead time compensator to be considered for low delay/lag applications where the plant delay is accurately known. The improvement deteriorates and the response becomes oscillatory for a 50% increase in the plant delay as illustrated by Figure 4-3b. A decrease in plant delay has little as shown in Figure 4-3c. However, if the model delay is more than 100% higher than the plant delay, the PID with a delayed external reset exhibits some decaying oscillations in the controller output as shown in Figure 4-3d. Figures 4-3e through Figure 4-3h is for a control loop with a 4.0 delay/lag ratio. The PID with a delayed external reset does not have the slow oscillations seen in the uncompensated conservatively tuned for the original plant delay and 50% changes plant delay shown in Figures 4-3f through Figure 4-3g. However, there is a persistent high frequency dither in the controller output. The a time constant could have been set in the DITHER_FILTER block to help smooth this out. Control valve dead band and resolution limits in the control valve may help prevent these oscillations from affecting the process. If the model delay is more than 100% higher than the actual plant delay, the dither amplitude gets larger and slower as shown in Figure 4-3h.

2006-12-06 Page 21 of 25 Load Upset IAE Improvement (%) Original Plant Delay Original Delay/Lag Ratio = 0.2 = standard PI = dead time compensated PI Figure 4-3a PID with Delayed External Reset for 0.2 Delay/Lag Ratio and Original Plant Delay Load Upset IAE Improvement (%) 50% Increase in Plant Delay Original Delay/Lag Ratio = 0.2 = standard PI = dead time compensated PI Figure 4-3b PID with Delayed External Reset for 0.2 Delay/Lag Ratio and 50% Increase in Plant Delay

2006-12-06 Page 22 of 25 Load Upset IAE Improvement (%) 50% Decrease in Plant Delay Original Delay/Lag Ratio = 0.2 = standard PI = dead time compensated PI Figure 4-3c PID with Delayed External Reset for 0.2 Delay/Lag Ratio and 50% Decrease in Plant Delay 110% Increase in Model Delay Original Plant Delay Original Delay/Lag Ratio = 0.2 = standard PI = dead time compensated PI Figure 4-3d PID with Delayed External Reset for 0.2 Delay/Lag Ratio and 110% Increase in Model Delay

2006-12-06 Page 23 of 25 Original Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI = dead time compensated PI Figure 4-3e PID with Delayed External Reset for 4.0 Delay/Lag Ratio and Original Model Delay 50% Increase in Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI = dead time compensated PI Figure 4-3f PID with Delayed External Reset for 4.0 Delay/Lag Ratio and 50% Increase in Plant Delay

2006-12-06 Page 24 of 25 50% Decrease in Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI = dead time compensated PI Figure 4-3g PID with Delayed External Reset for 4.0 Delay/Lag Ratio and 50% Decrease in Plant Delay 110% Increase in Model Delay Original Plant Delay Original Delay/Lag Ratio = 4.0 = standard PI = dead time compensated PI Figure 4-3h PID with Delayed External Reset for 4.0 Delay/Lag Ratio and 110% Increase in Model Delay

2006-12-06 Page 25 of 25 5 References 1-1 Boudreau, Michael, A. and McMillan, Gregory K., New Directions in Bioprocess Modeling and Control Maximizing Process Analytical technology Benefits, Instrumentation, Automations, and Systems (ISA), 2006. 1-2 McMillan, Gregory, Good Tuning a Pocket Guide, 2 nd edition, Instrumentation, Automations, and Systems (ISA), 2005. 1-3 McMillan, Gregory and Cameron, Robert, Models Unleashed Virtual Plant and Model Predictive Control Applications, Instrumentation, Automations, and Systems (ISA), 2004. 1-4 Blevins, Terrence L., McMillan, Gregory K., Wojsznis, Willy K., and Brown, Michael W., Advanced Control Unleashed Plant Performance Management for Optimum Benefits, Instrumentation, Automations, and Systems (ISA), 2003.