Functions module / Gateways Application Description Product Page KNX-GW-DMX-xxx DMX Gateway. KNX-GW-DMX Product Group 1

Similar documents
Application Description

» Minimal and maximal levels can be set on site. The bus coupling unit enables to use the values in the KNX-Bus.

EIB/KNX, Indoor / Outdoor, IP65 Document: 3400_ex_SK08-GLBS.pdf Article No.

EIB/KNX, Indoor / Outdoor, IP65 Document: 3500_ex_SK08-BFT.pdf Article No.

EIB/KNX, Indoor / Outdoor, IP65 Document: 3600_ex_SK08-BFTLFT.pdf Article No. 6.1 Application Description Product Page 20

For monitoring and control of the water quality in aquariums, swimming pools, ponds and service water systems.

Arcus-EDS. Application Description. SK0x-Txxx

KNX manual 1-channel flush-mounted switch actuator SU 1

1. Function. Universal dimming actuator REG-K/2x230/ 300 W. Universal dimming actuator REG-K/230/ 500 W. Universal dimming actuator REG-K/230/ 1000 W

Product Manual. ABB i-bus EIB / KNX. Universal Interface US/U Intelligent Installation Systems

Binary Inputs. Ref.-No. KNX universal binary input, 8-gang. ETS-product family: Series embodiment (SE-) device (2 units) Ref.-No.

Width (W): 44 mm. bus connecting and branching terminal External supply --- Inputs: Number: up to 2 (depending on parameterization: channel 1 to 2)

Thorsten Reibel, Training & Qualification Global Application and Solution Team

instabus EIB product documentation

Installer manual inputs/outputs interface for led KNX

Instruction manual. art Installation manual

Rev ABB i-bus KNX 6151/11 U-500. Power and productivity for a better world TM

KNX manual High-performance switch actuators RM 4 H FIX1 RM 8 H FIX2

KNX Room temperature controller

CU-DIN DIM 6-CH 0 10V KNX

Technical data: Instabus EIB supply Voltage: YY 6 x 0.6 mm; red: bus (+) / black: bus (-)

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

MDT Switch Actuator/FanCoil

Time Switch, 2-channel, MDRC SW/S 2.5, GH Q R0001

animeo KNX 4 AC Motor Controller 31. March 2016 WM/DRM V AC

HG G B. Gyroscope. Gyro for AGV. Device Description HG G B. Innovation through Guidance. Autonomous Vehicles

Rev Product Manual ABB i-bus KNX. Heating actuator 1gang with 6164/11 U-500. Power and productivity for a better world TM

MV110-8AS. Analog input module 8 channel. User guide

EIB/KNX Switch Actuators. User manual

animeo KNX/EIB 4 AC Motor Controller WM/DRM V AC

Air Quality Sensor KNX AQS

series dimmer actuators, DMG 2 S, Upgrade Module DME 2 S and Booster DMB 2

USER MANUAL CU-DIN DIM 4-CH 1.5A KNX EC MA

EVDP610 IXDP610 Digital PWM Controller IC Evaluation Board

animeo KNX 4 DC 2 A Motor Controller WM 24 V DC Installation manual

KNX ENO 620/622 (32-channel AP)

The universal input/output device is a DIN rail mounted device. It is connected to the EIB via a bus connecting terminal.

User Manual 3X300 DIMMER MODULE DM03B02KNX

1. Use of the application program

KNX PY. Global Irradiance Sensor. Installation and Adjustment

Integrations GW Programming manual

animeo KNX 4 DCE Motor Controller WM/DRM V AC Instructions

animeo KNX/EIB 4 DC/E Motor Controller WM V AC Installation manual

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 7.X August 2015 USER MANUAL. metaphase-tech.com. pg. 1

IP 251 Universal Signal Converter SSI parallel RS232 parallel SSI RS232

Data Acquisition Modules/ Distributed IO Modules

INSTRUCTION MANUAL. IBRit - rf1 - usb PC - Station for wireless Data transmission. M e s s t e c h n i k. Messtechnik GmbH & Co.

Metaphase ULC-2. Technologies ULC. Metaphase. Technologies Version 6.2 June 12, 2013 USER MANUAL. metaphase-tech.com. pg. 1

Compact KNX Line Coupler TP/TP User manual

16-Channel Yearly Time Switch TR 648 S DCF

AL-DALI-010v 0-10v Dimmer 3-Way switch with DALI

K-BUS Switch Actuator

SonoLab Echo-I User Manual

RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation

NOVA series Ceiling lights with tuneable white Colour temperature 2700 to 6500 K. Detailed operating instructions

Technical Manual MDT LED-Indicator

Universal Radio Cord Dimmer Order No.: Function

Revision 1. March 21, ADC Operation Manual N 11 th St San Jose CA

TECHNICAL DATASHEET #TDAX ISOLATED DUAL CHANNEL UNIVERSAL SIGNAL CONVERTER

User manual. KNX MultiController DALI. Article number: 5410x / 5411x. function Technology AS

I-2533CS series User Manual

STC-KNX (32-channel AP)

User Manual. KNX MultiLight Dali. Article number: function Technology AS. Picture: KNX MultiLight products

TECHNICAL DATASHEET #TDAX INPUTS, 5 OUTPUTS VALVE CONTROLLER

HDL KNX / EIB BUS. Dimmer Actuator. 1/43. Light Technology Nederland ditributor of HDL

MU110-16R(K) Digital output module 16 channel. User guide

Technical manual GS 4x.00 knx application description air quality sensor

ABB i-bus KNX DALI Light Controller DLR/S M Product Manual

Universal dimmer 6.3.1

dmx2pwm 9 channel dimmer setup manual

Answering frequently asked Questions (Firmware V.107)

GPS Evaluation Kit EVA1035-H

Technical Manual MDT Room Temperature Controller

Series Dimmer Actuator DMG 2, Upgrade Module DME 2 and Booster DMB 2 DMG DME DMB

User Manual EnOcean V 0.1

KNX ON/OFF controller 4 contacts 16A

KNX ENO 634 (32-channel AP)

Unidirectional Gateway EnOcean - KNX/BUS

INTERACT3. User manual Wireless adaptor plug switch IP 20/IP 44, wireless adaptor plug dimmer German/English

theben 4-/8-/12-Channel Switch Module Switch Actuator Modular with Basic Device RMG 4 - EIB and Additional Device RME 4 EIB

isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw

Manual RF-Gateway RS485 Typ APG03B-RS485 RS485 Gateway bidirektional Typ APG03B-RS485-Eno Art-Nr Manual

MK110-8D.4R. Digital I/O-Module 12 channel 8 DI, 4 DO. User guide

Current Module, 3-channel, MDRC SM/S , GH Q R0111

HURRICANE Radio Modem. FULL DUPLEX Radio MODEM

AUDIO MODE SELECTOR MODEL AMS-6000

EULAMBIA ADVANCED TECHNOLOGIES LTD. User Manual EAT-EOM-CTL-2. Alexandros Fragkos

The specifications are classified as follows: Characterization, type and order-number. Mode of functioning. Technical data.

ABB i-bus KNX Valve Drive Actuator VAA/S x Product Manual

Modbus communication module for TCX2: AEX-MOD

Weather Station for KNX

ABB i-bus KNX DALI-Light Controller DLR/A Product Manual

Electrical devices may only be mounted and connected by electrically skilled persons.

ScaleRCHelis.com Light Controller Users Manual

AG FB-CAN. Absolute encoder viva CAN. Product Manual E-V0204.doc

Electronic Circuit Breaker BASIC FIX

MU110-8R(K) Digital output module 8 channel. User guide

Product documentation

Operation/Reference Guide NXP-CPI16. NetLinx Custom Panel Interface. Custom Panel Interfaces

RUDAT The Big Deal. Applications

Transcription:

Seite 1 KNX---xxx Gateway KNX-- Product Group 1 Document: 4200_ex_KNX--.pdf KNX-- The KNX-- is a gateway between the KNX-Bus and the 512-Bus used by a wide range of devices for lighting applications. Article No. 40120186 Parametrization is done by the dedicated program -Configurator. KNX-- -2TE Free download at www.arcus-eds.com 40120182 2.1 1 2.2 Initial Operation 5 2.3 Technical Data 6 Imprint 2.1 Active Principle and Application Area The KNX- Gateway is an Interface between the KNX bus and the 512 bus. It combines elements of building automation with a multitude of lighting and special effects devices for every need. Application and Functionality The KNX- Gateway is unidirectional, receives data telegrams on the KNX bus and transmits the data onto the 512 bus. The interface allows the 512 actuators to communicate via the KNX bus using the full range of the channel. The KNX- Gateway contains 8 adjustable sequence positions within the whole channel range. Individual scenes with all 512 channels can be saved and retrieved using KNX group addresses. This function allows all channels to be connected simultaneously to one single object without causing any undo load on the KNX bus. The sequences are saved internally and can be retrieved even after a power outage. ( A sequence can only be saved 10000 times during the lifetime of the device. The automatic save function should not be set for short intervals ). The set value in sequence 8 is also on for all channels when using 1 bit objects. The KNX- Gateway is ready to use and can be positioned to the main group addresses with an S1 rotary switch. It is not necessary to project via the ETS. Page 1

Seite 2 KNX---xxx Gateway The KNX- Gateway has 1556 objects with three types of telegrams available: DPT 1.001 ( 1-bit switch ) single channel DPT 1.001 ( 1-bit switch ) save sequence and retrieve DPT 3.007 ( 4-bit relative dimming ) single channel DPT 5.001 ( 1byte show value ) single channel The S2 rotary switch adjusts the transition period from one preset brightness to the next, 15 (F) being immediate, 0 a time period of 1 second from 0% to 100%. The S3 rotary switch automatically sets the dimming function ( s.u. ) parameters, 0 is no automatic dimming, otherwise dimming time = 1.5 sec * switch value ( S3 = 1.. 15 (F) ) in increments of 1% ( dimming value 0111b or 1111b ). The rotary switch settings will be prompted when starting and can be readjusted during operation by using the T1 button. Necessary requirements are a KNX bus, 512 bus and a power supply. The KNX- Gateway in REG casing IP20 is available in sizes of 6 units. Firmware upgrades can be done with ArcSuite via USB port. Automatic Dimming Function Automatic dimming function can be switched on or off for all channels using an object, or can be parameterized by S3 when booting up. Thereby the properties are controlled when a dimming telegram ( DPT 3.007 ) appears. Automatic function Off ( S3 = 0 ) Automatic function On ( S3 <> 0 ) A dimming object ( 4 bit ) value range +7.. -7 singularly reduces or increases the value percentagewise. Appropriate for MicroVis dimming function ( Standard 6% per rotary click ) or similar rotary device. A uniquely transmitted dimming setting is repeated during a time period ( dimmer repetition ) until it reaches a value of 0 or 100% or until it is manually stopped. When 100% is transmitted, the preset value in dimming curve is used ( basic setting 1% ). This function allows the integration of the KNX-Gateway for an installation with standard key buttons. A standard key button transmits a 100% upward or downward command in dimming function when pushed and held and a stop command when let go. A dimming setting can thus be set. The dimming time period can be adjusted separately using either the parameter repetition or the dimmer curve. The basic setting after booting up is 1% dimming. The repetition rate is controlled by the rotary switch S3 and gives a dimming time result of circa 1.5 sec * switching value ( S3 = 1.. 15 (F) ). Address Diagram The KNX- Gateway is a master device in the bus. It possesses an internal data memory and constantly transmits the data at a rate of 250k baud to all 512 channels. When receiving valid KNX telegrams the values in the memory are changed. The transfer of the KNX telegram is preconfigured so that individual programming is not necessary. The KNX data points are managed in 3 address rooms. That means that switching or dimming can be accessed on every channel. The group addresses diagram must be set up using the S1 rotary switch before initial operation ( voltage supply ). Changes become effective after a reboot. The main group addresses from 0 15 are set up with the 16 stage rotary switch. The middle and lower group addresses are set by the predetermined address rooms ( see table 1 ). The DPT 5.001 allocates the first 512 address on the KNX bus. After that the DPT 1.001 and DPT 3.007. Finally, the sequence commands, a test function and dimming parameters are coded. Page 2

Seite 3 KNX---xxx Gateway Group Address Allocation Lower Group ( bi-level KNX Address Room ) Set Channel Value with DPT 5.001 1 byte value ( 0.. 100% ) Addresses 0-511 To set a 1 byte value, use the lower group addresses 0-511 which correspond to the channels 1-512 on the bus. Switch Channel Value with DPT 1.001 1 bit value ( switch ) Addresses 512-1023 Using a switch, this function can be used to switch every channel separately. When the value is 0 the channel is switched off (0), when it is 1 the saved value in sequence 8 is accessed and transmitted to the 512 bus. Every channel can be independently switched. Before the values are transmitted, there must be defined values saved in Sequence 8. This is the case for default settings at the time of delivery ( 255 for all channels ). To reset the default settings use either the defined value with DPT 5.001 ( group address x/0-511 ) or the function Central On ( group address x/1552 ) all values to 255. Then save this to Sequence 8 ( group address x/1551 ). This establishes a maximum value for every channel. Dimming Channel with DPT 3.007: 4 bit Value ( Dimming ) Addresses 1024-1535 Table 1 Possible Dimming Value as 4 bit Object: 0 = Stop 1 = 100% down 2 = 50% down 3 = 25% down 4 = 12% down 5 = 6% down 6 = 3% down 7 = 1% down 8 = Stop 9 = 100% up 10 = 50% up 11 = 25% up 12 = 12% up 13 = 6% up 14 = 3% up 15 = 1% up Using the automatic dimming function affects the performance when a dimming telgram is received. Choose Sequence with DPT 1.001 1 bit Value Addresses 1536-1543 A complete sequence with 512 channels can be output via the bus. All previously saved values are displayed on channels 1-512. There is a choice of 8 sequences at the addresses 1536-1543. The default value at the time of delivery is 255 for sequence 8 and 0 for sequences 1-7. Save Sequence with DPT 1.001 1 bit Value Addresses 1544-1551 Here the current values can be saved in one of the 8 sequences. The current brightness will be saved. There is a choice of 8 sequences at the addresses 1544-1551. Central On with DPT 1.001 1 bit Value Address: 1552 All 512 channels display 100% when a 1 is transmitted and 0% when a 0 is transmitted. Page 3

Seite 4 KNX---xxx Gateway Dimmer Repetition Rate with DPT 5.001 1 byte Value ( 0.. 250 ) Address: 1553 Set repetition rate parameters The repetition rate affects the dimming time. At increments of 1%, a dimming time of 1.5 sec * is achieved. Standard settings can be set using S3 (1.. 15 (F) ). Suggested values are 2-40. Downwards Dimming Curve with DPT 3.007 4 bit Value ( Dimming ) Address: 1554 Set dimming down to 100%. When the automatic dimming function is chosen, the command 0001b (100% dim down) is received and the programmed dimming setting will be repeated (see Repetition Rate Object 1553) until 0 has been reached or until it is manually stopped. Standard setting 0111b = -1% Possible dimming values as 4 bit object, see table 1 Upwards Dimming Curve with DPT 3.007 4 bit Value ( Dimming ) Address: 1555 Set dimming up to 100%. When the automatic dimming function is chosen, the command 1001h (100% dim up)is received and the programmed dimming setting will be repeated (see Repetition Rate Object 1553) until 255 has been reached, or until it is manually stopped. Standard setting 1111b =+1% Possible dimming values as 4 bit object, see table 1 Activate Automatic Dimming with DPT 1.001 1 bit Value ( Switching ) Address: 1556 Automatic Dimming Standard setting 0 if S3=0, otherwise 1 0 = automatic dimming switches off, no repetition of dimming. 1= automatic dimming switches on, repetition of dimming. Page 4

Seite 5 KNX---xxx Gateway 2.2 Initial Operation Connection Pin Assignment Clamp RS485 / Clamp DC IN ( 9.. 30V ) Clamp KNX-Bus Ground D - D + minus plus GND ( 0V ) Data - ( B ) Data + ( A ) 0V VDC 9.. 30V VDC Screw clamp are included Screw clamp are included Clamp block KNX are included Switch on the voltage supply. The group addresses are coded by S1 when the DC voltage in KNX- Gateway is switched on. Soft-start ( slow start-up to protect lights ) can be adjusted using S2 and S3 sets the dimming function. Turning the rotary switch afterwards has no Effect unless restarting the device or pushing the T1-Button. When pushing the T1-Button you can switch all -Channels simultaneously on/off. The prog-button on the mainboard inputs the physical addresses via a dummy application into the ETS. The Jumper J1 ( 120R TERM ) times the RS485 Bus with 120 Ohm load resistance in its initial state. The KNX bus is galvanically separated from the 512 bus! The power supply is galvanically separated from the 512 bus and the KNX bus! KNX Terminal Block RS485 Programming Button LED S1 S2 S3 KNX Terminal Block DC IN 9-30 VDC RS485 KNX---xxx View Connections Page 5

Seite 6 KNX---xxx Gateway 2.3 Technical Data Dimensions KNX-- 107 x 75 x 31 mm Rail Mounted Device ( 6 TE ) Dimensions KNX---2TE 35 x 90 x 63 mm Rail Mounted Device ( 2 TE ) Protection Class IP20 Temperature Range -5 C.. 45 C Controls 3 16-level Rotary Switch 1 Button User 2 LED User 1 EIB Button+LED KNX-Connection KNX Terminal Block KNX-Supply 20.. 32VDC / ca. 150mW -Connector 3x Screw clamp 0,8mm 2 Terminating Resistor RS485 120 Ohm via Jumper Forth - Programmierung USB-Slot with PC-Software Arcsuite ( Only Forth-User, for additional tools ) Power Supply 9.. 30VDC, 100mA, internal galvanically separated, polarized, defect-proof 512 Bus RS485-250 Kbaud, incl. galvanic separation 512 log Please note the 512 specific connecting configurations ( bus connection, number of receiving slaves, bus topology ). Page 6

Seite 7 KNX---xxx Gateway KNX 3 Level Structure Group Addresses Diagram ( three stages ) 512 Sequence KNX- Gateway Main Groups MG UG Value Channel No. No. Function Details 0 0-255 0.. 255 001-256 - DPT 5.001 transmit 1byte value ( Absolute Value ) 1 0-255 0.. 255 257-512 - DPT 5.001 transmit 1byte value ( Absolute Value ) 2 0-255 0 / 1 001-256 - DPT 1.001 3 0-255 0 / 1 257-512 - DPT 1.001 1 byte value is stored into the corresponding -Channel directly. When a 1 is received the value stored in scene Nr. 8 is sent to the corresponding - Channel. When a 0 is received the -Channel is turned off. 4 0-255 -7.. +7 001-256 - DPT 3.007 ( Dimming ) 5 0-255 -7.. +7 257-512 - DPT 3.007 ( Dimming ) 6 0 / 1 All Channel 0-7 DPT 1.001 access saved scene 6 8-15 0 / 1 All Channel 0-7 DPT 1.001 save new scene 6 16 0 / 1 All Channel - DPT 1.001 (Switch) all channels central on 6 17 0.. 255 All Channel - DPT 5.001, repetition rate parameters Relatively lighter or darker dimming than the current level. See description below. The selected scene values of all 512 channels are transmitted on the 512 bus. All current - values in channels 1-512 are stored in the selected scene position All 512 channels display 100% when 1 is transmitted, 0% when 0 is transmitted. Repetition rate of 10msec is multiplied with this value default 3. 6 18 0.. 7 All Channel - DPT 3.007, set downward dimming curve Dim down repetition value. default 15=1% 6 19 0.. 7 All Channel - DPT 3.007, set upward dimming curve 6 20 0 / 1 All Channel - DPT 1.001 deactivate automatic dimming Dim up repetition value. Default 15=1% Disables automatic dimming when value=0. Page 7

Seite 8 KNX---xxx Gateway Group Addresses Diagram KNX 2 Level Structure Group Addresses Diagram ( two stages ) 512 Sequence KNX- Gateway Main Groups Sub Groups Value Channel No. No. Function Details 000-511 0.. 255 001-512 - DPT 5.001 1 byte ( Absolute Value ) 511-1023 0.. 255 001-512 - DPT 1.001 1 byte value is stored into the corresponding -Channel directly. When a 1 is received the value stored in sequence No. 8 is sent to the corresponding Channel. When a 0 is received the Channel is turned off. 1024-1535 -7.. +7 001-512 - DPT 3.007 ( Dimming ) 1536-1543 0 / 1 All Channel 0-7 DPT 1.001 access saved scene 1544-1551 0 / 1 All Channel 0-7 DPT 1.001 save new scene 1552 0 / 1 All Channel DPT 1.001 all channels central on 1553 0.. 255 All Channel DPT 5.001, repetition rate parameters Relatively lighter or darker dimming than the current level. See description below. The selected scene values of all 512 channels are transmitted on the 512 bus. All current values in channels 1-512 are stored in the selected scene position All 512 channels display 100% when 1 is transmitted, 0% when 0 is transmitted. Repetition rate of 10msec is multiplied with this value default 3. 1554 0.. 7 All Channel DPT 3.007, set downward dimming curve Dim down repetition value. Default 15=1%, 1555 0.. 7 All Channel DPT 3.007, set upward dimming curve 1556 0 / 1 All Channel DPT 1.001 deactivate automatic dimming Dim up repetition value. Default 15=1% Disables automatic dimming when value=0. 2 Adress Space, 32-Channel and Group-Dimming-Function The Firmware 0.12, which can be uploaded to the gateway, is an extension of the firmware 0.10. The firmware supports 32 Channels, 64 Scenes and 4 Sequences. Upload of the firmware and setup of the gateway with scenes and sequences is done by the Program --Configurator. With this program, you can also mask the channels, that are to be used inside the scene. With this Firmware one Middle-group ( Set up by S1 and S2 ) is occupied. S2=8.. 15 equals S2=0.. 7 with an additional switching-ramp of about 3 Seconds. Page 8

Seite 9 KNX---xxx Gateway KNX 3 Level Structure Group Addresses Diagram ( three stages ) 512 Sequence KNX- Gateway Main Groups MG UG Value Channel No. No. Function Details 0-31 0.. 255 001-32 - DPT 5.010 1byte value 32-63 0 / 1 001-32 - DPT 1.001 1 Byte value is stored into the corresponding -Channel directly. When a 1 is received the value stored in sequence Nr. 64 is sent to to the corresponding -Channel. When a 0 is received the -Channel is turned off. 64-95 -7.. +7 001-32 - DPT 3.007 ( Dimming ) Relatively lighter or darker dimming than the current level. See description below. 96-159 0 / 1 All Channel 1-64 DPT 1.001 access saved scene The selected scene values of all 32 channels are transmitted on the -bus. 160-223 0 / 1 All Channel 1-64 DPT 1.001 save new scene All current - values in channels 1-32 are stored in the selected scene position. 224 0 / 1 All Channel - DPT 1.001 all channels central on/off All 32 channels display 100% when 1 is transmitted, 0% when 0 is transmitted. 225 0.. 63 All Channel 1-64 DPT 5.010 1byte access saved scene The selected scene values of all 32 channels are transmitted on the bus. 226 0.. 63 All Channel 1-64 DPT 5.010 1byte save new scene All current - values in channels 1-32 are stored in the selected scene position. 227 0.. 4 All Channel 1-64 DPT 5.010 1byte Playback sequence The sequences 1 to 4 are played back. On 0 all sequences are stopped. 228 0.. 255 All Channel - DPT 5.010, repetition rate parameters Repetition rate of 10msec is multiplied with this value. default 3 229 0.. 7 All Channel - DPT 3.007, set downward dimming curve Dim down repitition value. Default 15=1% 230 0.. 7 All Channel - DPT 3.007, set upward dimming curve Dim up repitition value. Default 15=1% 231 0 / 1 All Channel - DPT 1.001 activate automatic dimming Disables automatic dimming if value=0 232-247 -7.. +7 All Channel - DPT 3.007 ( Dimming ) Relative lighter or darker dimming for a group defined by the scenes 1 to 16. All active channels in the scene are dimmed. Page 9

Seite 10 Imprint Editor: Arcus-EDS GmbH, Rigaer Str. 88, 10247 Berlin Responsible for the contents: Hjalmar Hevers, Reinhard Pegelow Reprinting in part or in whole is only permitted with the prior permission of Arcus-EDS GmbH. All information is supplied without liability. Technical specifications and prices can be subject to change. Liability The choice of the devices and the assessment of their suitability for a specified purpose lie solely in the responsability of the buyer. Arcus-EDS does not take any liability or warranty for their suitability. Product specifications in catalogues and data sheets do not represent the assurance of certain properties, but derive from experience values and measurements. A liability of Arcus- EDS for damages caused by incorrect operation/projecting or malfunction of devices is excluded. The operator/project developer has to make sure that incorrect operation, planning errors and malfunctions cannot cause subsequent damages. Safety Regulations Attention! Installation and mounting must be carried out by a qualified electrician. The buyer/operator of the facility has to make sure that all relevant safety regulations, issued by VDE, TÜV and the responsible energy suppliers are respected. There is no warranty for defects and damages caused by improper use of the devices or by noncompliance with the operating manuals. Warranty We take over guarantees as required by law. Please contact us if malfunctions occur. In this case, please send the device including a description of the error to the company's address named below. Manufacturer Registered Trademarks The CE trademark is a curb market sign that exclusively directs to autorities and does not include any assurance of product properties. Registered trademark of the Konnex Association. www.arcus-eds.de x sales@arcus-eds.de Fax.: +49 / (0)30 / 2593 3915