SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS

Similar documents
VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

GIS Disconnector Switching Operation VFTO Study

A Simple Simulation Model for Analyzing Very Fast Transient Overvoltage in Gas Insulated Switchgear

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Analysis of Very Fast Transient over Voltages of Transformer in Gas Insulated Substation (GIS) using Wavelet Technique

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

How to Conduct the Lightning Impulse Withstand Test of. Three Gorges Right Bank Substation 550kV GIS

Research Article A Simplified High Frequency Model of Interleaved Transformer Winding

Research Article Survey of Induced Voltage and Current Phenomena in GIS Substation

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

Analysis of MOV Surge Arrester Models by using Alternative Transient Program ATP/EMTP

PREVENTING FLASHOVER NEAR A SUBSTATION BY INSTALLING LINE SURGE ARRESTERS

Tab 2 Voltage Stresses Switching Transients

The various factors influencing the VFTO levels in 500kV and. 750kV GIS have been discussed by developing the simulink models which

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

A Study on Ferroresonance Mitigation Techniques for Power Transformer

Effect of Shielded Distribution Cables on Lightning-Induced Overvoltages in a Distribution System

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Categorized by the type of core on which inductors are wound:

Electric Stresses on Surge Arrester Insulation under Standard and

Transmission Line Transient Overvoltages (Travelling Waves on Power Systems)

Controlling Input Ripple and Noise in Buck Converters

Research on Lightning Over-voltage and Lightning Protection of 500kV. HGIS Substation

Hybrid Simulation of ±500 kv HVDC Power Transmission Project Based on Advanced Digital Power System Simulator

In power system, transients have bad impact on its

Do Capacitor Switching Transients Still Cause Problems?

Accurate Modeling of Core-Type Distribution Transformers for Electromagnetic Transient Studies

Ferroresonance Experience in UK: Simulations and Measurements

SWITCHING OVERVOLTAGES IN A 400-KV CABLE SYSTEM

Simulation Study on Transient Performance of Lightning Over-voltage of Transmission Lines

Research Article Resistive Ferroresonance Limiter for Potential Transformers

Final Exam Fall 2018

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Distribution Transformer Random Transient Suppression using Diode Bridge T-type LC Reactor

Pre-insertion Resistor of Switching Shunt Capacitor Banks

Weidong Zhang, May.9, 2016 Development of Pre-Insertion Resistor for an 800kV GIS Circuit Breaker. ABB Group May 11, 2016 Slide 1

EXPERIMENTAL INVESTIGATION OF A TRANSIENT INDUCED VOLTAGE TO AN OVERHEAD CONTROL CABLE FROM A GROUNDING CIRCUIT

DEPARTMENT OF EEE QUESTION BANK

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

EP A1 (19) (11) EP A1 (12) EUROPEAN PATENT APPLICATION. (43) Date of publication: Bulletin 2011/48

The Fault Level Reduction in Distribution System Using an Active Type SFCL

CHAPTER 7. Response of First-Order RL and RC Circuits

SIDDHARTH GROUP OF INSTITUTIONS :: PUTTUR (AUTONOMOUS) Siddharth Nagar, Narayanavanam Road QUESTION BANK (DESCRIPTIVE) UNIT I INTRODUCTION

Modeling insulation in high-voltage substations

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

The Analysis Results of Lightning Overvoltages by EMTP for Lightning Protection Design of 500 kv Substation

Switching and Fault Transient Analysis of 765 kv Transmission Systems

Capacitive Voltage Substations Ferroresonance Prevention Using Power Electronic Devices

Design and Simulation of 15 KV, 15 Stage Solid State Bipolar Marx Generator

Investigation into Transient SFO, FFO, VFTO Overvoltage Characteristics for Typical Gas Insulated Substations

DC VACUUM CIRCUIT BREAKER

Differential-Mode Emissions

FERRORESONANCE SIMULATION STUDIES USING EMTP

CHAPTER 2. v-t CHARACTERISTICS FOR STANDARD IMPULSE VOLTAGES

GIS Instrument Transformers: EMC Conformity Tests for a Reliable Operation in an Upgraded Substation

Electrical Theory. Power Principles and Phase Angle. PJM State & Member Training Dept. PJM /22/2018

New Modeling of Metal Oxide Surge Arresters

A Special Ferro-resonance Phenomena on 3-phase 66kV VT-generation of 20Hz zero sequence continuous voltage

Department of Electrical and Computer Engineering Lab 6: Transformers

Single Line Diagram of Substations

RC and RL Circuits. Figure 1: Capacitor charging circuit.

Question Paper Profile

Sirindhorn International Institute of Technology Thammasat University

Resonance Analysis Focusing on Stray Inductance and Capacitance of Laminated Bus Bars

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Adi Mulawarman, P.E Xcel Energy Minneapolis, MN. Pratap G. Mysore, P.E Pratap Consulting Services, LLC Plymouth, MN

Designing and Application of -type Miniaturized Lumped Equalizer

Chapter 30 Inductance, Electromagnetic. Copyright 2009 Pearson Education, Inc.

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

Metal-Oxide Surge Arresters Integrated in High-Voltage AIS Disconnectors An Economical Solution for Overvoltage Protection in Substations

Generation of Sub-nanosecond Pulses

INTERNATIONAL JOURNAL OF ENGINEERING SCIENCES & RESEARCH TECHNOLOGY. Approach for Fault Detection in GIS.

High Current Amplifier

Fixed Series Compensation

Lightning test in lab. Symmetrical fault and protection. Olof Samuelsson

Physics Class 12 th NCERT Solutions

CONTENTS. 1. Introduction Generating Stations 9 40

Resonant Controller to Minimize THD for PWM Inverter

G. KOEPPL Koeppl Power Experts Switzerland

Filters And Waveform Shaping

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

Power Frequency Withstand Voltage On-site testing of 400 kv GIS

Comparison of switching surges and basic lightning impulse surges at transformer in MV cable grids

Current limiting characteristic of saturated iron core SFCLs

2. Current interruption transients

Electronics and Instrumentation ENGR-4300 Spring 2004 Section Experiment 5 Introduction to AC Steady State

DIFFERENCE BETWEEN SWITCHING OF MOTORS & GENERATORS WITH VACUUM TECHNOLOGY

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Power Control Scheme of D-Statcom

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

Solving Customer Power Quality Problems Due to Voltage Magnification

Application Note 0009

Prevention of transformers damage in HPP with double generating units connected to GIS via HV cables

Electromagnetic Disturbances of the Secondary Circuits in Gas Insulated Substation due to Disconnector Switching

Transcription:

SUPPRESSION METHODS FOR VERY FAST TRANSIENT OVER- VOLTAGES ON EQUIPMENT OF GIS A.Raghu Ram 1, P.Swaraj 2 1,2 Associate Professor, PG Scholar, Department of Electrical and Electronics Engineering, JNTUH college of engineering, AP, India, raghuram_a@yahoo.co.in, swaraj.panjala@gmail.com Abstract Gas Insulated Substations (GIS) have found a broad range of applications in power systems because of their high reliability, easy maintenance, small ground space requirements etc. In a Gas insulated substations, the operation of disconnector switches and circuit breakers can cause Very Fast Transient Overvoltages (VFTOs), which will bring an instantaneous change in voltage with a very short rise time and it is normally followed by oscillation having high frequencies. For designing the insulation level of a substation, it is essential to know the maximum value of VFTO. Fast operating disconnector switches are usually used to reduce time of the breakdown; however, it cannot eliminate fully the effect of the VFTO. Very Fast Transient Overvoltages caused by disconnector switch operation of 1000 kv GIS is simulated and calculated in this paper using MATLAB. The various protection measures on equipment of GIS have been compared and analyzed by adding ferrite rings, opening and closing of resistor, metal oxide arrester and R-C absorber. Index Terms: Gas Insulated Substation, Very Fast Transient Overvoltage s, Matlab/Simulink, Disconnector switch. -----------------------------------------------------------------------***----------------------------------------------------------------------- 1. INTRODUCTION Gas Insulated Substations (GIS) have found a broad range of applications in power systems because of their high reliability, easy maintenance, small ground space requirements etc. In a Gas insulated substations Operation of disconnector switches and breakers can cause very fast transient overvoltages (VFTO), tip of which is very steep accompanied with high frequency oscillation [1]. VFTO generated in a GIS should be considered as an important factor in the insulation design. Very Fast Transients overvoltages (VFTO) belong to the highest frequency range of transients in power systems. When Disconnector Switch [DS] is opened or closed in GIS, it will bring an instantaneous change in voltage with a very short rise time in range from 4 to 100 ns, and it is normally followed by oscillation having frequencies in the range of 1 to 50 MHz. For designing a substation it is essential to know the maximum value of VFTO. Several inhabitation methods are available in the literature, which can provide the reference for the protection against VFTO. In this paper a 1000KV GIS is considered to build the simulation model. The equivalent diagram is shown in Figure.3. During the operation of disconnector VFTO S are observed from 1 s to 3 s ( i.e. operating condition of circuit breaker) across potential is showed in figure 4 & 5. Since the main Objective of this article is to inhibit the protection measures to the equipments in GIS a simple simulation model is considered that consists of current (CT) and potential (PT) connected through the disconnectors[2][3]. After the tripping action takes place at the circuit breaker (CB) the VFTO s across CT s a nd PT s are analyzed and the same is done after imparting the opted protection method. The reduction in the VFTO tells that the equipment is safe further after the tripping action. 2. MODELING OF SIMULATION BLOCKS The proposed simulation model of GIS consists of the following blocks. These blocks modeling and connections are explained in detail as follows: A. Source Power B. Source impedance C. Circuit Breaker D. Instrumentation Transformer E. Disconnector switch Since the whole system is three phase symmetry; single phase circuit can be used to simulate it by doing required modifications. 2.1 Source Voltage A 1000KV ac source is assumed for simulation model which resembles the considered 1000KV GIS system. The source is modeled from the following equation 2.2 Source Impedance Source impedance assumed for simulation model is calculated using below equation Volume: 01 Issue: 02 Oct-2012, Available @ http://www.ijret.org 190

Z= 60 ln Capacitance C= Inductance L= H 2.3 Circuit Breaker A circuit breaker is connected in series to protect the equipments in GIS from high voltages, which can damage the equipments. Breaker resistance for 1000kv under on state is 0.001 ohms. 2.4 Instrument Transformer The instrument s (CT, PT) used for measuring are connected across the circuit breaker in the assumed model gives the output by which the analysis of VFTO is done. Hence for the assumed GIS system the current and potential s are modeled as follows 2.4.1 Current Transformer The block of current is modeled as interconnection of resistors, inductors and capacitors which can be observed in figure 1 Fig2: Equivalent circuit of potential This potential is connected in parallel to line after circuit breaker to measure the voltage in the line. 2.5. Disconnector Switch (DS) In the simulation model of GIS, disconnector switch is modeled with a capacitor. The closing and opening actions of the disconnector switch is functioned by assigning different values to the capacitor as given below Disconnector switch in open condition C= 50 pf Disconnector switch in closed condition C= 88 pf Fig1: Equivalent circuit of current This current is connected in series to the line after the circuit breaker to measure the current in the line 2.4.2 Potential Transformer The block of potential is modeled as the interconnection of resistor, inductor and capacitor which can be observed in figure 2 Fig3: Basic simulation diagram of GIS Volume: 01 Issue: 02 Oct-2012, Available @ http://www.ijret.org 191

The closing resistor should be equiped with actuator devices in application, which operate frequently, the probability of failure are great. Therefore, this method needs to combine practical considerations. Fig4: Waveform of VFTO across potential Fig6: VFTO waveform with opening and closing resistor at potential Fig5: Waveform of VFTO across current Fig7: VFTO waveform with opening and closing resistor at current 3. RESULTS 3.1 Installation Of The Opening And Closing Resistor The equivalent circuit is modified by connecting 500Ω opening and closing resistor at disconnector switch and waveform is shown in Fig. 6 & 7. The installation of opening and closing resistor has a certain application in order to inhibit the VFTO in GIS [1]. The amplitude of VFTO decreases obviously, and the steepness is limited. However, from a technical and economical point of view, as the compact structure of the GIS, this method brings difficulty in equipment, more seriously it weakens the system reliability. 3.2 Installation Of The Metal Oxide Surge Arrester Metal oxide surge arrester (MOA) is particularly applicable to protection of GIS equipment from voltage surges.the equivalent circuit of 1000kV GIS is considered with metal oxide surge arrester and simulations are carried out. The volttime characteristic of which is flat. MOA cannot be simulated only by non-linear resistor during passage of high frequency content of VFTO[1]. When MOA is installed at DS, the amplitude decreases is shown Fig 8& 9.However, it is noticed that, MOA only inhibit the amplitude of the VFTO, its steepness basically has no effect, the high frequency components are still present. Volume: 01 Issue: 02 Oct-2012, Available @ http://www.ijret.org 192

ring material have a great impact on VFTO, However this measure would not increase the complexity of the structure of the GIS and it can play a role in the protection of GIS equipment inside the bus bar. Fig8: VFTO waveform with Metal Oxide Surge Arrester at potential Fig10: VFTO waveform with Ferrite Ring at potential Fig9: VFTO waveform with Metal Oxide Surge Arrester at current 3.3 Installation Of The Ferrite Ring Ferrite rings are installed at conductor pole of the disconnector switch in order to inhibiting VFTO. The equivalent circuit of 1000kv GIS is considered with equivalent of ferrite ring and simulation results are obtained. Ferrite material has different characteristics of saturation magnetic conductivity, frequency response and loss. These characteristics influence the VFTO suppression effect [4][5]. The suppressing effect on the VFTO could be improved by the high magnetic strength (H), magnetic conductivity (h) and frequency (f) respectively. The effect of reflected wave and the losses are neglected as parallel combination of resistor and inductance the equivalent resistance of the ferrite ring is equal to the surge impedance of GIS bus bar and the equivalent inductance is 0.02 mh, which the inhibition of the VFTO is the largest. The simulations have been carried out after adding ferrite ring equivalent. Fig 10&11.Shows the VFTO waveform and its frequency spectrum. From above results, we find that the saturation characteristic of the ferrite Fig11: VFTO waveform with Ferrite Ring at current 3.4 Dinstallation Of RC Filter The equivalent circuit of 1000kV GIS is considered with equivalent of RC filter and simulations are carried out. The results are shown in the Fig 12 & 13. RC filters have been widely used in vacuum circuit breakers to suppress the over voltages. RC filter is parallel next to disconnector switch. The values chosen for R=100Ω and C =0.2µF, voltage amplitude and steepness drop faster. The main reason of which is that capacitor absorbs the high frequency component and finally energy is consumed resistor. Volume: 01 Issue: 02 Oct-2012, Available @ http://www.ijret.org 193

A. The amplitude of VFTO only is suppressed by MOA but its steepness and high frequency oscillations. B. By installing a opening and closing resistor not only decreases the amplitude but also the steepness of VFTO. C. The installation of RC filter decreases the amplitude of VFTO as well as steepness of VFTO by absorbing high frequency components energy of VFTO. D. Installing ferrite rings can decreases the amplitude and saturation characteristics of the ferrite ring material have great impact on VFTO. Fig.12 VFTO waveform with RC filter at potential Fig.13 VFTO waveform with RC filter at current Table.1 Comparison of VFTO s Reduction Method proposed At current Using opening and closing resistors 66Kv 4Kv Using metal oxide arrester Using ferrite ring 96Kv At potential 15Kv 60 Kv 2Kv Using R-C filter 64Kv 3Kv CONCLUSIONS By simulating and calculating various measures adopted to suppress VFTO in GIS, We can draw the following conclusions. FUTURE SCOPE The effect of VFTO s in the Gas Insulated Substation can analyzed by using PSPICE and ATP-EMTP. REFERENCES: [1] Lingxia Gan, Lei Li, Yuanyuan Zhou, Yinfeng Xu, Research on Protection Measure for Very Fast Transient over- voltages of GIS, Power and Energy Conference, March 2009. APPEEC 2009. Asia Pacific. [2] WANG ZHuo, WANG Weiquan, WANG Qiang, Research of suppressing VFTO for 500kV GIS substation based, E-Business and E- Government(ICEE), 2011 International Conference. May 2011 [3] YANG Linghui and ZHANG Jiamin, Research on transient over-voltage during operation of 500kV GIS disconnecting switch, East China Electric Power, vol.32, pp.38-41. Jan 2004. [4] GAN Xianggen, Characterstic Parameter Analysis on Suppressing VFTO in GIS by Ferrite, High Voltage Engineering, China, vol. 30, pp. 24-26.sep 2004 [5] GIN Ligun and LIU Weidong, Research on Suppressing VFTO in GIS by Ferrite Ring, High Voltage Engineering, China, vol. 28, pp. 1-3. Jul 2002 BIOGRAPHIES: A.Raghu Ram, is working as an Associate Professor in Jawaharlal Nehru Technological University Hyderabad, College of Engineering since 2003. He obtained Ph.D from JNTUH, Hyderabad, A.P, INDIA. He has published National and International papers in High Voltage Engineering and areas of interest are High Voltage Engineering and Electrical Energy Conversation. P.Swaraj, PG Scholar, Department of Electrical and Electronics Engineering, JNTUH College of engineering, Andhra Pradesh, India, swaraj.panjala@gmail.com Volume: 01 Issue: 02 Oct-2012, Available @ http://www.ijret.org 194