SEPARATOR P20G TYPE USER S MANUAL

Similar documents
PROGRAMMABLE TRANSDUCER OF DC CURRENT AND DC VOLTAGE SIGNALS P20H TYPE

TRANSDUCER of TEMPERATURE and STANDARD SIGNALS P20 type

DIGITAL PANEL METER N24 AND N25 METER SERIES

POWER TRANSDUCERS FOR SINGLE-PHASE AND THREE-PHASE NETWORK ISO P11P, P13P and P13B mm SERVICE MANUAL

RAIL MOUNTED NETWORK METER TYPE N27D USER S MANUAL

N24, N25 DIGITAL PANEL METER

TEMPERATURE CONTROLLER RE21 TYPE

DIGITAL SYNCHRONIZING UNIT KS3.2 SERVICE MANUAL. 144 x 144 x 77 mm C E R T I F I E D

EA16, EB16, EA17, EA19, EA12 MOVING-IRON METERS Ammeters and Voltmeters

new! nd30 - METER OF POWER NETWORk PARAMETERS EXAMPlE OF APPliCATiON MEASUREMENT AND ViSUAliZATiON OF POWER NETWORk PARAMETERS

TEMPERATURE CONTROLLER. MOUNTED ON A 35 mm RAIL RE60 TYPE USER S MANUAL

N100. example of application Ethernet www/ ftp. Ethernet TCP IP RS X MeaSUreMent of power network parameters.

High power radio transmission module MR03 type

a * example of application MeaSUreMent and ViSUalization of power network parameters Ethernet TCP IP RS-485 USB HOST /SD CARD

nd30 EXAMPlE OF APPliCATiON MEASUREMENT AND ViSUAliZATiON OF POWER NETWORk PARAMETERS Ethernet www/ ftp Modbus TCP Modbus RS-485

THREE-PHASE POWER CONTROLLER RP3 Type

4-CHANNEL MODULE OF ANALOG INPUTS SM2 TYPE

nd30pnet - METER Of POwER NETwORk PARAMETERS with profinet EXAMPlE Of APPlICATION MEASUREMENT ANd VISUAlIZATION Of POwER NETwORk PARAMETERS

POWER CONTROLLER RP1 type

N E W functions! Modbus. Wireless transmission - SM ma TCP IP ma. NA5 meter with bargraph. k *

TEMPERATURE CONTROLLER RE55 TYPE USER S MANUAL

ND40 V V. Ethernet www/ ftp / smtp. Ethernet TCP IP RS-485 USB HOST /SD CARD.

TRANSDUCER OF NETWORK PARAMETERS P43 TYPE

USER S MANUAL POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER ZSP 41 POWER SUPPLY - ISOLATOR - SIGNAL CONVERTER SIGNAL MULTIPLIER ZSP 41/2

RE92. CHECKMATE. Dual loop controller for industry purpose.

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

TVA 080 / 100 / 120 / 180 / 200 / 220 Isolation amplifier active

N30P DIGITAL PANEL METER

Precipition Sensor with analogue Intensity Output ,

Installation and Operating Instructions for Phase Demodulator Type _.2

DT1100 xx xx xx PS. Isolators, Isolator / Power Supplies. Operating Instructions

Precipitation Monitor ,

USER S MANUAL. Rail-mounted temperature transmitter ATL

Installation and Operational Instructions for ROBA -multiswitch Type 019._00.2

POWER NETWORK MEASUREMENTS Analysers, Multimeters & Transducers

new! nd40 example of application MeaSUreMent and ViSUalization of power network parameters Ethernet www/ ftp / smtp Ethernet TCP IP RS-485

DT1100 E xx xx (PS) Galvanic Isolators. Operating Instructions

Installation and Operational Instructions for ROBA -switch Type 017._00.2

USER MANUAL. WBP314P71 active power transducer. (3-phase 4-wired)

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO-E

Operating Manual MU2000K

MCR-SL-CUC Universal current transducer. Data sheet _en_05. 1 Description

SINEAX U 553 Transducer for AC Voltage

Data Sheet 066.8e. Transducers for Active and Reactive Power EW+B 2.2 DGW+B 2.2 VGW+B 2.2 DUW+B 2.2 VUW+B 2.2

OPERATION MANUAL ELECTRONIC FREQUENCY CONVERTER HFO E

OPTITEMP TT 20 Technical Datasheet

Thermocouple - Transducer

POWER NETWORK PARAMETER METER N13 SERVICE MANUAL

Section 1, General information Introduction... 3 Description... 3 Specifications... 4 Wiring connections... 5

MODEL: M2DYS SEN TRONIC AG

PIR6WT-1Z interface - time relays

PEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

ND40 - POWER NETWORK ANALYZER /RECORDER

MCR-VAC-UI-0-DC. Voltage transducer for AC voltages. INTERFACE Data sheet _en_02. 1 Description

Notes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 400VAC

Notes: Note1: Efficiency is tested at nominal input and full load at +25 C ambient. Output Voltage 400VAC 320VAC 360VAC 400VAC 400VAC

TE200S Solid State Relays. Two-phase control of three-phase loads. User manual

MOVING-IRON METERS EA16, EB16, EA17, EA19, EA12 TYPES

MD-45 AC MD-45 LV/HV INSTALLATION MANUAL

K1 K2. User's manual AC/DC CURRENT PROBE C H A U V IN A R N O U X AC/DC CURRENT PROBE. 1 mv/ma OFF 300V CAT II

Operating Instruction

English. Operating manual. Temperature measuring transducer MU125. Save for later reference. Company / brands of GHM

LOW VOLTAGE CONVERTER WITH THREE POINT GALVANIC INSULATION

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL:

MODEL: W2DYS SEN TRONIC AG. Mini-MW Series

MODEL: M2SES SEN TRONIC AG [3] OUTPUT

HAWK5000 Operators Manual

AC/DC Current Oscilloscope Probe Model SL261

MINI MCR-SL-UI-f(-SP)

OPTITEMP TT 10 C/R Technical Datasheet

Dawson DDM190. Digital Multimeter User s Manual

Level Switch NRS 2-50 NRS Original Installation Instructions English

IGS IGS-M-EL-22(1) Contactors APPROVED. Iranian Gas Standards

Digital Meters With A Multicolour Bargraph LEL-NA3 one-channel LEL-NA5 one-channel LEL-NA6 two-channel

TEMPERATURE CONTROLLER 48 x 48 mm RE70 TYPE USER S MANUAL

Wind Transmitter - with analogue output xxx

BENNING. CM7 Electrical Tester. Service Information

MODEL AT-10 ANALOG TRANSMITTER

Installation and Operational Instructions for ROBA -switch Type 017._00.2

SINEAX TV 808, 1 channel Isolating Amplifier unipolar/bipolar

DS10000ULFS-10V/10kA

Series BDF for Process

High Performance Current Transducer IT 200-S ULTRASTAB = A. ε L

IDEAL INDUSTRIES, INC. TECHNICAL MANUAL MODEL: MODEL: Multimeter Service Information

400,440Vac Vdc V, A, W, VA, var, Hz, V, Avg. A cos phi, sin phi and phi measurement kwh, kvarh (via Pulse Output)

AMM-1022 Digital Multimeter USER`S MANUAL

Operating Instructions for Pressure Sensor with Ceramic Sensor Element. Model: SEN-9601

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

INSTALLATION MANUAL. Model: Smart Analyzer Manufacturer: Smart Impulse. Power meter with consumption breakdown by use 03/12/13

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

n True RMS measurement n Fully onsite programmable input voltage range (for CIP-V)

LDC480 Series is a single phase, extremely compact Power Supply with active PFC specially designed for space sensitive and demanding applications.

Theta 20A / 20V. Technical Data Sheet. Special Features

SINEAX I 552 Transducer for AC current

RMO500 M I C R O O H M M E T E R

3 PHASE ENERGY ELECTRONIC METERS MKT & MKT2. (Code to ) INSTRUCTION MANUAL ( M / 00 A ) (c) CIRCUTOR S.A.

10/2 Product overview. 10/3 4AC3 0, 4AC3 1 bell transformers. 10/5 4AC AC3 6 transformers for permanent loads. 10/8 4AC2 4 power supply units

TETRIS 1000 High Impedance Active Probe. Instruction Manual

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302

Transcription:

SEPARATOR P20G TYPE USER S MANUAL 1

2

Contents 1. APPLICATION... 5 2. SEPARATOR SET... 5 3. OPERATIONAL SAFETY... 6 4. FITTING... 7 4.1. Fixing Way... 7 4.2. External Connection Diagrams... 8 5. SERVICE... 9 6. TECHNICAL DATA OF THE P20G SEPARATOR... 10 7. EXECUTION CODES... 12 8. SERVICE AND MAINTENANCE... 14 3

4

1. APPLICATION The P20G separator is destined to realize the galvanic separation of current and voltage analog signals. The output signal is galvanically isolated from the input signal and the supply. One can also obtain in the separator the linear conversion of one kind of signal led to its input into a standard output signal of another kind. The separator is fully configurable through the PD14 programmer. By means of this programmer, one can change the input type, output type, measurement averaging time and recalibrate the analog output according to the output individual characteristic, and also read out the measured value. 2. SEPARATOR SET The set of the P20G separator is composed of: 1. P20G separator... 1 pc. 2. User s manual... 1 pc. 3. Guarantee card... 1 pc 4. Plug with screw terminals... 2 pcs. 5. Hole plug of the programmer socket... 1 pc When unpacking the transducer, please check whether the type and execution code on the data plate correspond to the order. 5

3. OPERATIONAL SAFETY In the safety service scope, the transducer meets to requirements of the EN 61010-1 standard. Observations Concerning the Operational Safety All operations concerning transport, installation, and commissioning as well as maintenance, must be carried out by qualified, skilled personnel, and national regulations for the prevention of accidents must be observed. Before switching the separator on, one must check the correctness of connections to the network. When connecting the supply, one must remember that a switch or a circuit-breaker should be installed in the building. This switch should be located near the device, easy accessible by the operator, and suitably marked as an element switching the separator off. Do not connect the separator to the network through an autotransformer. Before removing the separator casing, one must switch the supply off and disconnect measuring circuits. The removal of the separator casing during the guarantee contract period may cause its cancellation. The programmer socket is only use to connect the PD14 programmer. After the separator programming, one must insert the hole plug. Non-authorized removal of the housing, inappropriate use, incorrect installation or operation, creates the risk of injury to personnel or the separator damage. For more detailed information, please study the User s Manual. 6

4. INSTALLATION 4.1. Fitting Way P20G transducers are designed to be mounted on a 35 mm rail according to EN 60715. Overall dimensions and fitting way are shown on the fig. 1. Fig. 1 Overall dimensions and the separator fitting way. Separators should be mounted on the rail in direct contact with another devices that emit heat (eg transducer P20G). You must keep a minimum 5 mm distance between the devices to allow emit heat from the housings to the ambient. Otherwise, the in rated operating temperature of transducer which is in direct contact with the other transducer may exceed the rated operating temperature stated operating conditions. 7

4.2. External Connection Diagrams The separator has two terminal strip sockets, which two plugs with terminal screws are connected to and enable the connection of external wires with 2.5 mm 2 cross-section (terminals 6-9) and 1.5 mm 2 crosssection (terminals 1-5). For the connection of signal terminals, one must use shielded wires. The way to connect external signals is shown on the fig.2 The electrical connection diagram is also situated on the separator casing. Fig. 2. Electrical connection diagrams of the P20G separator 8

5. SERVICE After switching the separator on, the work state diode should light in red for a moment, next it should light in green. supply analog output P20 Diode of the separator work state: - the state diode lights in green normal work, - the state diode lights in red improper work parameters; one must configure the transducer again, - the state diode pulsates in red lack of calibration or the non-volatile memory is damaged; one must return the transducer to the manufacturer. Fig. 3. View of the P20G separator. Confirmation of the separator s communication with PD14 programmer is indicated by the status diode which turns off for short period of time. To configure P20G separator is designed LPCon software available on the web site: www.lumel.com.pl/. 9

6. TECHNICAL DATA Basic parameters: analog output galvanicaly isolated: - current (max. range) -20...20 ma - voltage (max. range) -10...10 V - load resistance of the current output 500 W - load resistance of the voltage output ³ 500 W conversion class 1) 0.2 averaging time of the measurement ³ 0.1 s power input < 2 VA warm-up time of the separator 10 min response time of the separator ³ 0.1 s Rated operating conditions: supply depending on the version code 10 85...253 V a.c./d.c. 20...85 V d.c., 20...65 V a.c. frequency of the supply a.c. voltage 45...65 Hz ambient temperature -20...23...55 C storage temperature -25...85 C related air humidity < 95% (inadmissible condensation of water vapour) operating position any Additional errors: from temperature changes 50% of class/10 K Input parameters: resistance of voltage input [V] > 1 M W resistance of current input [ma] 12 W ±1% Sustained overload: - voltage 1.2 X n - current 1.1 X n

Short duration overload 5 X n /3 s Ensured protection grade acc. to EN 60529: - casing IP 40 - from terminal side IP 20 Dimensions Weight Fitting 22.5 100 120 mm 0.125 kg on a 35 mm DIN rail, acc.to EN 60715 Electromagnetic Compatibility: - noise immunity EN 61000-6-2 - noise emissions EN 61000-6-4 Safety Requirements acc. to EN 61010-1 standard: - isolation between circuits BASIC - installation category III - pollution degree 2 - phase-to-earth operating voltage: - supply 300 V 2) - input 50 V - output 50 V - altitude above see level < 2000 m 1) Guaranteed for a minimal width of output ranges: 16 ma or 5 V (see table 3) 2) Execution for 230 V supply voltage Current standard editions are in the conformity declaration. 11

7. ORDER CODES Order codes of the P20G separator Table 2 SEPARATOR P20G - XX XX X XX X X Kind of programmed input: see table 3... XX Kind of programmed output: see table 3... XX Supply: 85...253 V a.c./d.c....1 20...85 V d.c., 20...65 V a.c....2 Version: standard... 00 non-standard settngs...ns custom-made*... XX Language: Polish...P English...E other*... X Acceptance Tests: without extra quality requirements...0 with an extra quality inspection certificate...1 acc. to customer s requirements*... X * after agreeing with the Manufacturer 12

Coding of input and output of the P20G separator Table 3 Range Input code Output code 0...1 V 01 01 1) 0...5 V 02 02 0...10 V 03 03 ± 1 V 04 04 1) ± 5 V 05 05 ± 10 V 06 06 0...5 ma 07 07 1) 0...20 ma 08 08 ± 5 ma 09 09 1) ± 20 ma 10 10 4...20 ma 11 11 Custom-made execution XX XX 1) Conversion class > 0,2 When ordering, please respect successive code numbers. Example of Order: The code: P20G - 06 06 1 00 E 1 means: P20G Separator of P20G type in standard execution, 06 Kind of programmed input voltage (-10...10 V), 06 Kind of programmed output voltage (-10...10 V), 1 Supply: 85...253 V a.c./d.c., 00 standard version E English language 1 with an extra quality inspection certificate 13

8. MAINTENANCE AND GUARANTEE The P20G separator does not require any periodical maintenance. In case of some incorrect operations: From the Shipping During the Period Given in the Annexed Guarantee Card: One should return the separator to the Manufacturer s Quality Inspection Dept. If the instrument has been used in compliance with the instructions, we guarantee to repair it free of charge. The disassembling of the casing may cause the cancellation of the granted guarantee. After the Guarantee Period: One should turn over the separator to repair it in a certified service workshop. Spare parts are available for the period of five years from the date of purchase. Our policy is one of continuous improvement and we reserve the right to make changes in design and specifications of any products as engineering advances or necessity requires and revise the above specifications without notice. 14

15

P20G-09A LUMEL S.A. ul. Słubicka 1 65-127 Zielona Góra - Poland Tel.: (48-68) 45 75 100 (exchange) Fax: (48-68) 45 75 508 e-mail: lumel@lumel.com.pl http://www.lumel.com.pl Export Department: Tel.: (48-68) 45 75 139 or 305 Fax: (48-68) 325 40 91 e-mail: export@lumel.com.pl 16