Protecting Large Machines for Arcing Faults

Similar documents
Catastrophic Relay Misoperations and Successful Relay Operation

Minnesota Power Systems Conference 2015 Improving System Protection Reliability and Security

The InterNational Electrical Testing Association Journal. BY STEVE TURNER, Beckwith Electric Company, Inc.

Generator Protection GENERATOR CONTROL AND PROTECTION

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology

System Protection and Control Subcommittee

COPYRIGHTED MATERIAL. Index

BUS2000 Busbar Differential Protection System

Advanced Applications of Multifunction Digital Generator Protection

The Importance of the Neutral-Grounding Resistor. Presented by: Jeff Glenney, P.Eng. and Don Selkirk, E.I.T.

Power Plant and Transmission System Protection Coordination Fundamentals

Section 6: System Grounding Bill Brown, P.E., Square D Engineering Services

889 Advanced Generator Protection Technical Note

thepower to protect the power to protect i-gard LITERATURE Low and medium voltage

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

NERC Protection Coordination Webinar Series July 15, Jon Gardell

Transformer Protection

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Babak Enayati National Grid Thursday, April 17

ENGINEERING DATA SUBMITTAL For the Interconnection of Generation System

Distance Relay Response to Transformer Energization: Problems and Solutions

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

Table 6.1 Fault Code List Code indication (Note 3)

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

PROTECTION SIGNALLING

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Impact of Incipient Faults on Sensitive Protection

Overcurrent Elements

O V E R V I E W O F T H E

Static Breaker Back-up Relay Type SBC Relay SBC231B

> the power to protect. Ground Fault Protection on Ungrounded and High Resistance Grounded Systems. Application Guide.

Upgrading Your Electrical Distribution System To Resistance Grounding

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

Issued: September 2, 2014 Effective: October 3, 2014 WN U-60 Attachment C to Schedule 152, Page 1 PUGET SOUND ENERGY

Generator Advanced Concepts

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

Grounding System Theory and Practice

Detecting and Managing Geomagnetically Induced Currents With Relays

Transformer Protection Principles

Summary of the Impacts of Grounding on System Protection

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Substation applications

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

NORTH CAROLINA INTERCONNECTION REQUEST. Utility: Designated Contact Person: Address: Telephone Number: Address:

ENHANCE SWITCHING POWER SUPPLY SPECIFICATION 250 WATT MODEL NO:V525

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

PART 1 OWNER/APPLICANT INFORMATION

How Transformer DC Winding Resistance Testing Can Cause Generator Relays to Operate

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

Overcurrent and Overload Protection of AC Machines and Power Transformers

Power Quality Basics. Presented by. Scott Peele PE

Modern transformer relays include a comprehensive set of protective elements to protect transformers from faults and abnormal operating conditions

Overvoltage and undervoltage. Dr Audih 1

13. Before making a service call Trip information and remedies

GPM. Field and Stator Ground Fault Protection Modules. Instruction Manual AF1. GE Grid Solutions

TN, TT & IT Earthing Arrangements

www. ElectricalPartManuals. com Generator Differential Relay MD32G Rotating Machine Differential Relay

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

CONTENTS. 1. Introduction Generating Stations 9 40

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation

INSTRUCTIONS. SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays. GE Power Management

Webinar: An Effective Arc Flash Safety Program

Industrial Electrician Level 3

Setting Generic Distance Relay UTP-100#WPSC1. in the. Computer-Aided Protection Engineering System (CAPE)

Unit Auxiliary Transformer (UAT) Relay Loadability Report

NOVEL PROTECTION SYSTEMS FOR ARC FURNACE TRANSFORMERS

IDAHO PURPA GENERATOR INTERCONNECTION REQUEST (Application Form)

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide

New Methods for Monitoring Neutral Grounding Resistors

Optimizing HV Capacitor Bank Design, Protection, and Testing Benton Vandiver III ABB Inc.

INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)

Protection Issues Related to Pumped Storage Hydro (PSH) Units

State of North Dakota Engineering data submittal Page 1 For interconnection of distributed generation to Otter Tail Power Company

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

System Protection and Control Subcommittee

Transformer Protection

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

NERC Protection Coordination Webinar Series June 16, Phil Tatro Jon Gardell

Generator Protection M 3420

POWER SYSTEMS QUALITY Topic 5: Principles for Controlling Harmonics

SHUNT CAPACITOR BANK DESIGN AND PROTECTION BASICS

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

o9oo INSTRUCTIONS SGC 21A, 21B, 21C Negative-Sequence Time Overcurrent Relays GE Power Management

Effective System Grounding

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection

TEST PROCEDURE FOR THE RMS-2012AF PROGRAMMABLE LOGIC CONTROLLER USING AN AMPTECTOR SECONDARY TEST SET.

Improving Transformer Protection

APPENDIX B: Generation Interconnection Application Form

1C.6.1 Voltage Disturbances

A1-101 INFLUENCE OF SPECIAL SHORT CIRCUIT ON ELECTRICAL GENERATOR DESIGN. Ding Zhong MENG (HONG KONG, CHINA)

Three Phase Transformers

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

PD300. Transformer, generator and motor protection Data sheet

Problems connected with Commissioning of Power Transformers

2015 Relay School Bus Protection Mike Kockott March, 2015

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

Transcription:

Protecting Large Machines for Arcing Faults March 2, 2010 INTRODUCTION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating along with catastrophic electrical failure. These events typically require extensive repairs with an extended shutdown of the machine. It is highly desirable to detect such faults at an early or incipient stage so that remedial action can be taken before a complete failure occurs. A common practice for large synchronous machines is to limit the ground fault current through the generator stator windings by grounding the neutral through a distribution transformer with a resistor connected across the secondary winding. The neutral resistor is reflected to the primary and provides high resistance grounding during single phaseto-ground faults and is typically sized to limit the ground fault current from 3 to 25 amps primary. The ohmic value of the grounding resistor is selected to avoid high transient voltage due to ferro-resonance. FIGURE 1. High Impedance Grounded Machine It is not possible to reliably detect these faults using overcurrent protection. Neutral overvoltage protection is suitable since the voltage drop across the grounding resistor is proportional to the fault location along the stator winding. The neutral voltage is equal to the nominal secondary voltage of the grounding bank for a fault located at the generator terminals and is then a percentage of that as the fault location moves towards the neutral. FIGURE 2. Neutral Voltage as Function of Fault Location along Stator Windings Conventional protection methods are not reliable since due to the intermittent nature of an arcing fault any single arc may not last long enough to operate time delayed neutral Page 1 of 8

voltage protection. Figure 3 shows the neutral voltage for a large machine with a persistent arcing fault at the generator terminals. Note that the neutral current is negligible. FIGURE 3. Typical Arcing Fault Measured at Generator Terminals This paper presents a new protection method to detect arcing faults along the entire winding and up to the terminals of the step-up transformer. This protection can trip the unit before extensive damage occurs. This paper also shows the protection engineer how to properly identify the faulted phase. Faulted phase identification is important since it will greatly aid locating the source of an intermittent arcing fault. CONVENTIONAL STATOR GROUND FAULT PROTECTION Neutral Overvoltage (59N) A time delayed neutral voltage level detector operates on the fundamental frequency zero-sequence voltage dropped across the neutral resistor. Typically 59N has a minimum pickup of 5 volts secondary. 59N is reliable and provides protection for up to 90 95 percent of the stator windings. Ground faults in the last 5 10 percent of the stator windings near the neutral do not provide enough fundamental frequency zerosequence voltage to assert 59N. Third Harmonic Undervoltage (27TN) A time delayed neutral voltage level detector operates on the third harmonic zerosequence voltage dropped across the neutral resistor. Third harmonic zero-sequence voltage at the neutral is present in nearly every machine to varying degrees. Monitor this third harmonic voltage to detect ground faults in the last 5 10 percent of the stator windings near the neutral. The combined scheme is illustrated in Figure 4A. Figure 4B shows how 59N and 27TN overlap to provide conventional 100 percent stator winding protection. Page 2 of 8

FIGURE 4A. 100% Stator Ground Fault Protection Scheme FIGURE 4B. Overlap of 59N with 27TN Figures 5A and 5B illustrate how to set 27TN and 59N. These are arbitrarily chosen example settings. You need to calculate the settings for your own particular application. Page 3 of 8

59N Minimum pickup 5 volts secondary Time delay on pickup 30 cycles FIGURE 5A. 59N Settings 27TN Minimum pickup 1 volt secondary Time delay on pickup 30 cycles FIGURE 5B. 27TN Settings Note that both protection elements have the same time delay on pickup and they both trip via the same contact output. Page 4 of 8

CASE STUDY #1 Figure 6 is an oscillographic recording of a numerical generator relay trip. This was an arcing fault on A-Phase external to the generator stator windings. The nominal line-toneutral voltage is 66.4 volts secondary and the neutral voltage rose as high as 120 volts secondary during the arcing fault. Note that the potentials were clean again after the breaker opened since the arc was external. The voltage across the neutral grounding transformer is 180 degrees from A-Phase voltage (see Figure 7) when A-Phase is grounded: V A + V N = 0 V N = -V A Also note that the voltage on the unfaulted phases rise to the nominal line-to-line value. FIGURE 6. 1 st Case Study Oscillographic Record FIGURE 7. Faulted Phase Identification Page 5 of 8

CASE STUDY #2 Figure 8 is another oscillographic recording of a numerical generator relay trip. The arcing fault occurred on B-Phase. The phase angle of V N is 180 degrees from the B- Phase voltage (V BC leads V B by 30 degrees). This fault was also external to the generator stator windings and was due to a dirty insulator. This was an arcing fault on B-Phase external to the generator stator windings. The nominal line-to-neutral voltage is 66.4 volts secondary and the neutral voltage rose as high as 120 volts. FIGURE 8. 2 nd Case Study Oscillographic Record Page 6 of 8

New Arc Fault Protection Method An arcing fault is intermittent and if the duration of each arc is shorter than the conventional 100 percent stator ground fault protection time delay on pickup then no trip occurs. Figure 9 illustrates the logic. The reset timer (T R ) has memory and stalls the delay on pickup timer (t p ) when the initiating function pickup drops out intermittently as is the case for an arcing fault. The initiating function that drives this logic is 59N. You can also use 27TN in parallel logic to cover grounds close to the neutral. For the purpose of this example the time delay on pickup is equal to 18 cycles and the reset timer is equal to 30 cycles. Set the reset timer greater than the period when the arcing fault is off otherwise the pickup timer will reset prior to a trip. FIGURE 9. Arc Detector Logic Figure 10 shows the timing sequence for a trip during an arcing ground fault. FIGURE 10. Timing Sequence to Trip during Arcing Fault CONCLUSION Arcing faults occur due to dirty insulators or broken strands in the stator windings. Such faults if undetected can lead to overheating along with catastrophic electrical failure. These events typically require extensive repairs with an extended shutdown of the machine. It is highly desirable to detect such faults at an early or incipient stage so that remedial action can be taken before a complete failure occurs. It is not possible to reliably detect these faults using overcurrent protection. Neutral overvoltage protection is suitable since the voltage drop across the grounding resistor is proportional to the fault location along the stator winding. The neutral voltage is equal to the nominal secondary voltage of the grounding bank for a fault located at the generator terminals and is then a percentage of that as the fault location moves towards the neutral. Page 7 of 8

Conventional protection methods are not reliable since due to the intermittent nature of an arcing fault any single arc may not last long enough to operate time delayed neutral voltage protection. This paper presents a new protection method to detect arcing faults along the entire winding and up to the terminals of the step-up transformer. This protection can trip the unit before extensive damage occurs. REFERENCE Upgrading Generator Protection Using Digital Technology by Charles J. Mozina, pp. 3 5 Page 8 of 8