EXPERIMENTAL STUDY OF TIMBER-TO-CONCRETE DOWEL TYPE CONNECTIONS USED IN TIMBER PLATFORM FRAME

Similar documents
The Influence of Nails and Plasterboard on the Racking Resistance of Stud Walls

LOAD CARRYING CAPACITY OF METAL DOWEL TYPE CONNECTIONS OF TIMBER STRUCTURES

SCREWS WITH CONTINUOUS THREADS IN TIMBER CONNECTIONS

Dowel-type fasteners. Timber Connections. Academic resources. Introduction. Deferent types of dowel-type fasteners. Version 1

STRUCTURAL TIMBER DESIGN

STRUCTURAL PERFORMANCE OF TIMBER EXTERNAL CLADDING

Connections in CLT Assemblies

The predictive model for strength of inclined screws as shear connection in timber-concrete composite floor

ALUMIDI. Concealed beam hanger with and without holes Aluminum alloy tridimensional perforated plate ALUMIDI - 01 CERTIFIED STEEL-ALUMINUM

Ductility of large-scale dowelled CLT connections under monotonic and cyclic loading

3.1 General Provisions

Engineering Research into Traditional Timber Joints

APA Performance Rated Rim Boards

BauBuche Fasteners and connections

ESR-2648 Reissued May 1, 2012 This report is subject to renewal June 1, 2013.

ESR-2024* Reissued September 1, 2011 This report is subject to renewal September 1, 2013.

Butt Two pieces of wood meeting with flat sides adjoining usually at right angles. Some type of connector is needed to prevent movement.

Powder Actuated Fastening INTRODUCTION

RlGIDITY AND STRENGTH OF WALL FRAMES BRACED WlTH METAL STRAPPING

FASTENERS C O M P AT I B L E W I T H F E R O T I E S Y S T E M S. Which FERO Tie Systems Require Fasteners?

SDWH TIMBER-HEX Screw

optimisation of pre-cast support beams

HOME STRENGTHENING GUIDE HOW TO ECONOMICALLY STRENGTHEN YOUR HOUSE AGAINST EARTHQUAKES AND HURRICANES

Featuring TJ Rim Board and TimberStrand LSL

European Technical Assessment. ETA-14/0426 of 15 December English translation prepared by DIBt - Original version in German language

European Technical Assessment ETA-17/1005 of

Bolt Material Types and Grades 1- Bolts made of carbon steel and alloy steel: 4.6, 4.8, 5.6, 5.8, 6.8, 8.8, 10.9 Nuts made of carbon steel and alloy

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

THE ENGINEERED WOOD ASSOCIATION

CLT Cross Laminated Timber

Design of structural connections for precast concrete buildings

POWDER-ACTUATED FASTENERS IN COLD-FORMED STEEL CONSTRUCTION

European Technical Assessment. ETA-14/0426 of 21 December English translation prepared by DIBt - Original version in German language

GARDEN SHED BRIGHTOLN

Attach Trusses and Rafters Faster

Connection Philosophy. p NDS Chapter-by-chapter description Changes from previous editions Examples. Part 1: Member Design Webinar.

Please direct powder-actuated and screw fastening technical inquiries to your local Hilti Field Engineer or Technical Support at

Joint Evaluation Report

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year.

² TL Beton-StB 07 = German technical conditions for construction materials for concrete road pavements

Verbindungselemente Engel GmbH Weltestraße Weingarten DEUTSCHLAND. Manufacturing plant 74437, , ,

CLT Connections Design Seminar on CLT Design, including Connections, and Resistance to Lateral and Gravity Loads

ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in two years.

Glulam Connection Details

Building for High Wind Resistance in Light-Frame Wood Construction

Cast-in Ferrule Connections Load/Displacement Characteristics in Shear

ESR-1254 * DELETED BY CITY OF LOS ANGELES. Reissued April 1, 2006 This report is subject to re-examination in one year.

Designed for Building Designed for Living

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC AND COMPOSITE FASTENINGS REPORT HOLDER: DEWALT

Connection Design Examples

WITHDRAWAL AND LATERAL STRENGTH OF THREADED NAILS

VERSA-LAM. An Introduction to VERSA-LAM Products

Overdriven Nails in Structural Sheathings. Overview Revised 3/22/2017

Design guide to separating distances during construction

European Technical Assessment ETA-13/0029 of 11/07/2017

Investigations on the Effectiveness of Self-tapping Screws in Reinforcing Bolted Timber Connections

ICC-ES Evaluation Report

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

Connection Solutions for Wood-frame Structures. Copyright Materials. Learning Objectives

Load Tables, Technical Data and Installation Instructions

+ + CFA Guidance Note: Powder Actuated Fixing Systems. Ensuring best fixings practice. Contents. 1.

Umbrella Inserts and Stubby Screens

ICC-ES Evaluation Report

Dowel type joints Influence of moisture changes and dowel surface smoothness. Erik Serrano and Johan Sjödin, Växjö University, Sweden

Load carrying capacity of dowelled connections

Optimast Installation Method Statement. F108.

TEST SERIES TO EVALUATE THE STRUCTURAL BEHAVIOUR OF ISOBOARD OVER RAFTER SYSTEM

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER:

Dowel connections in laminated strand lumber

HUS 6 Screw anchor, Redundant fastening

Tension Perpendicular to Grain Strength of Wood, Laminated Veneer Lumber, and a Wood Plastic Composite.

Shear force transmission in expansion joints

The Wood Products Council is a Registered Provider with. . Credit(s) earned on completion of this program will be

LP SolidStart Laminated Strand Lumber and Laminated Veneer Lumber Louisiana-Pacific Corporation Revised May 6, 2011

Connection and performance of two-way CLT plates

Tensile strength of ASSY plus VG screws wood-wood (softwood)

REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

ESR-2403 Reissued October 1, 2009 This report is subject to re-examination in one year.

ICC-ES Evaluation Report Reissued June 1, 2011 This report is subject to renewal in one year.

SECTION R507 DECKS DECKING LEDGER BOARD BEAM. FOOTING BEAM SPAN CANTILEVER For SI: 1 inch = 25.4 mm FIGURE R507.2 DECK CONSTRUCTION

American Institute of Timber Construction 7012 South Revere Parkway Suite 140 Centennial, CO Phone: 303/ Fax: 303/

European Technical Assessment ETA-04/0038 English translation prepared by DIBt. Page 2 of July 2016

EVALUATION OF SCREWS USED IN LAMINATED VENEER LUMBER ROCKING CONNECTIONS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: WOOD, PLASTIC, AND COMPOSITE FASTENINGS REPORT HOLDER: SCREW PRODUCTS, INC.

HK I. Anchor size (carbon steel) HK6 HK6L HK8 Resistance F Rk [kn] 2,0 5,0 5,0

Canadian li ing device design for Cross Laminated Timber (CLT)

Wood Duck Nest Box Design & Assembly Directions

Independent Containment System (ICS)

Tech Guide. Screw Anchor Performance Why use a screw anchor? Ease in installation

eb^sv=qfj_bo UNIVERSITY OF WISCONSIN - STOUT COLLEGE OF SCIENCE TECHNOLOGY ENGINEERING & MATHEMATICS Architectural Technology AEC 233

DIVISION: CONCRETE SECTION: CONCRETE ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT:

Glued laminated timber beams repair.

ESR-1799 Reissued April 2014 This report is subject to renewal June 1, 2015.

Guidance Document January 2014

GLOSSARY OF TERMS SECTION 8

Ready To Go SimpleSpec tm. Installation Manual. For more information, please visit 3-form.com or call

Load-carrying capacity of timber frame diaphragms with unidirectional support

Available online at ScienceDirect. Procedia Engineering 114 (2015 )

Comparison of behaviour of laterally loaded round and squared timber bolted joints

European Technical Approval ETA-10/0038

Transcription:

EXPERIMENTAL STUDY OF TIMBER-TO-CONCRETE DOWEL TYPE CONNECTIONS USED IN TIMBER PLATFORM FRAME Summary Kenneth Leitch BSc (Hons) Research Assistant Centre for Timber Engineering, Napier University Edinburgh, Scotland Robert Hairstans BEng (Hons), PhD Lecturer School of Engineering and the Built Environment, Napier University Edinburgh, Scotland Derek Abbott Managing Director ETA Fixings (UK) Ltd Stourbridge, England Robin Dodyk Technical Director Oregon Timber Frame Ltd Selkirk, Scotland Scott McAndrew Technical Manager Cullen Building Products Ltd Glenrothes, Scotland Market forces in the U.K are dictating that timber frame houses are built with narrow frontages which contain a large percentage of openings. As a result of this, the number of full height panels which can be classified as offering resistance to racking forces is reduced and the performance requirements of the remaining panels are increased. As part of a wider project aimed at addressing this problem through the development of a hybrid racking panel, this paper considers the importance of a robust soleplate connection and its ability to offer secure anchorage. Specifically, it quantifies the degree of lateral (sliding) resistance offered by a range of commercially available fasteners. The results from an experimental test program show the lateral load-carrying capacity of each of these fasteners when used to connect a C16 or Laminated Strand Lumber (LSL) soleplate to a concrete foundation substrate. It is shown that the currently preferred method is inefficient in terms of both structural and economic performance when compared to other fasteners tested.

1. Introduction Modern Methods of Construction (MMC) are gaining increased popularity in the U.K due to improved quality control, speed of construction and efficient use of materials. One of the most common examples of MMC is timber platform frame which at present accounts for approximately 20% [1] of new homes built in the U.K. Timber platform frame often competes in the low cost, high volume estate market where the cost of land and client desire for detached accommodation leads to narrow properties with openings often concentrated in the shorter walls [2]. This is problematic when designing for overall structural stability as reduced width shear wall panels do not have the ability to provide sufficient resistance to sliding and overturning (racking) forces caused by the applied wind load. In order to offer a solution to this problem, research is currently being carried out into the development of a Hybrid Racking Panel (HRP) which is optimised in terms of performance, cost and installation. When considering the racking performance of a wall panel it is important to understand how the inplane forces acting upon it are resisted and transferred to the foundation (Fig. 1). In order to resist in plane loading a shear wall relies on framing members, sheathing and nail connectors all interacting closely with one another [3]. Improvements in the racking performance can be achieved if each of these variables is optimised for the required conditions and this is central to the development of an HRP. However, the successful implementation of these improvements is dependent on secure anchorage specification which must ensure applied lateral (shear) and overturning forces are transferred safely to the foundations. Compression reaction Shear reaction Applied lateral force Vertical anchor force Fig. 1 Illustration of forces acting upon a shear wall panel At present neither BS 5268 [4] nor the soon to be introduced Eurocode 5 (EC5) [5] offer a method specifically for the calculation of a timber-to-concrete connection s lateral load-carrying capacity. Research by Aicher et al [6] has proved the calculated characteristic shear load capacity of a timberto-concrete joint to be approximately the same as that obtained by using a timber design code for nailed timber-to-thick steel plate connection [7]. However, methods such as this only consider standard smooth or threaded types of fasteners. Detailed in this paper is the experimental investigation of standard and non-standard fixings when used in conditions replicating that of timber sole plate to substrate connection. The purpose of the test program was to determine the feasibility of specifying the connections detailed and these findings are reported on. Further to this, the research program was conducted in a manner which would facilitate further investigation of the fixing types and connection detailing. Research by Blass [8] identified that the three parameters influential to a joints load carrying behaviour are; (i) the bending capacity of the dowel (ii) the embedding capacity of the timber or wood based material (iii) the withdrawal capacity of the dowel. With respect to these, a supplementary test program was carried out and these results are also reported and discussed. 1.1 Site practice and detailing The structural performance as well as the accuracy of a timber platform frame build is reliant on the initial positioning and fixing of the soleplate. Table 1 shows typical soleplate material specification whilst Fig. 2 shows the soleplate in relation to a typical wall footing detail. Applied wind load

Table 1 Soleplate material specification Dimensions Timber type Characteristic density (ρ k) 38x89mm 45x89mm C16 ( * ) Solid sawn timber 310 kg/m 3 ( * ) Structural strength class as per BS EN 338 [9] A desktop study into practices adopted throughout Footing North America (where Timber frame accounts for 90% of low rise builds) showed that Laminated Strand Lumber (LSL) is often used in areas where high Foundation performance is required. Examples of this include shear walls designed to resist hurricane and seismic activity. As well as structural benefits, LSL is also well suited to Fig. 2 Detail of wall footing use as a soleplate material. It is more resistant to moisture and the resultant warping and twisting it causes than sawn timber. Furthermore, it also offers uniform strength properties in each axis and this gives it improved resistance to compressive forces imposed by the vertical stud ends. In the U.K the preferred method for securing the soleplate and providing lateral resistance is the shot fired dowel. This is a smooth type dowel installed via a powder actuated tool (Fig. 3). This method has found favour due to its ease and speed of installation. However, the performance of this fastener must be validated in relation to the increased shear forces which will require to be transferred by the proposed HRP. Therefore, an experimental program to evaluate the lateral resistance offered by it and other fasteners, along with the effect of using LSL as a soleplate material was developed. Fig. 3 KMN45LV tool 2. Experimental program Floor slab Wall Panel Footer Sole Plate To evaluate the performance of the shot fired dowel and provide comparative data from other fastener types an experimental investigation was carried out. Eleven commercially available dowel-type fasteners (supplied by ETA Fixings UK Ltd) which were suitable for fixing the soleplate and providing shear resistance were selected. These were divided into 4 sub categories; Masonry Screws (MSC), All purpose masonry screws (KF), Shot fired dowels (KMN) and a non standard fastener type known as an Express nail (EXPN) (Figure 4 & Tables 2-5). Wall All purpose masonry screw Shot fired dowel Masonry Screw Express Nail Fig. 4 Illustration of tested fastener range

Table 2 Average dimensions of tested Masonry screws Length (mm) Diameter (mm) Overall Thread Shank Thread Root Shank Head MSC36070 69.13 47.97 17.61 5.37 3.65 3.82 9.11 MSC36082 80.74 55.18 20.92 5.42 3.7 3.52 9.09 BTB4C70 69.60 49.01 15.08 6.45 4.21 4.64 11.93 BTB4C82 81.79 51.77 24.84 6.4 4.4 4.68 11.83 Table 3 Average dimensions of tested All purpose masonry screws Length (mm) Diameter (mm) Overall Thread Shank Thread Root Shank Head KF7.5 80 80.64 75.37 N/A 7.46 5.33 N/A 11.15 KF7.5 100 100.66 95.07 N/A 7.28 5.24 N/A 11.49 Table 4 Dimensions of tested Express Nails Length (mm) Diameter (mm) Overall Point Shank Head X section area (mm 2 ) EXPN6 60 60.23 6.04 6.40 12.68 EXPN6 100 99.89 6.12 6.36 12.48 12.54 EXPN8 70 70.04 7.86 8.36 15.18 EXPN8 90 89.82 7.86 8.48 15.28 20.52 Table 5 Dimensions of tested Shot fired dowel Length (mm) Diameter (mm) Overall Root Head Washer KMN72 74.46 3.8 5.48 11.9 The experimental investigation conducted replicated UK in-situ sole plate connection detailing, Dense Aggregate Block (DAB) with a characteristic strength of 7N/mm 2 was used and Damp Proof Coursing (DPC) was placed at the timber/block interface (Fig. 5), and lateral load tests were carried out in accordance with BS EN 1380 [10]. Shear plane Applied load @ Rate 2mm/min 40mm 65mm 45mm DAB 65mm 65mm 45mm 65mm C16 Timber / LSL 40mm Fig. 5 Details of lateral load-carrying capacity set up and specimen under test

Installation methods for each fastener (Table 6) were carried out as per manufactures recommendations. Details of the test methods used for the supplementary program can be found in the standards given (Table 7). Table 6 Installation methods for tested fasteners Fastener type Masonry Screw All purpose masonry screw Express nail Shot fired dowel Installation method Pre-drill timber and substrate as per Manufacturer s specification. Brush and blow debris from hole. Screw into place with cross head drill bit. Pre-drill timber and substrate as per Manufacturer s specification. Brush and blow debris form hole. Screw into place with Torque bit. Pre-drill timber and substrate as per Manufacturer s specification. Brush and blow debris from hole. Drive fastener home with hammer. Install with KM45LV cartridge tool and charges Table 7 Supplementary test program details Test Carried Carried out on out to Point side Based Fasteners tested in 7N block withdrawal upon BS installed at minimum strength EN recommended depth Head side pull through strength Embedment strength 1383[11] BS EN 1382[12] BS 383[13] Fasteners tested in both C16 Solid timber and LSL Fasteners tested in both C16 Solid timber and LSL. Fig. 6 Illustration of head side pull through (l) and point side withdrawal (r) test methods. 4. Results Results from tests determining the lateral load carrying capacity (Fig. 7) of each fastener in both C16 timber and LSL show 2 particularly relevant results: 1. The current method of fixing the soleplate 6000 (KMN72) is proven to give the lowest 5000 lateral resistance of the fasteners on test. 4000 2. By specifying LSL over C16 timber, 3000 lateral resistance can be increased. Characteristic Lateral load carrying capacity (N) 2000 1000 0 MSC36070 MSC36082 BTB4C70 BTB4C82 KF7.5x80 KF7.5x100 C16 Solid timber EXPN6x60 EXPN6x100 LSL EXPN8x70 EXPN8x90 KMN72 Fig. 7 Comparison of fastener lateral load carrying capacity in both LSL and C16 timber. These findings are directly applicable to currently employed practices. Moreover, the results provide a bank of information for the future specification of fasteners based upon requirements. In all test cases the development of at least one plastic hinge in the fastener was observed. In the case of threaded fasteners, ultimate failure was found to occur through combined bending and shear forces. This lead to a sudden failure in the area where the hinge had formed. For smooth types of fastener the development of the hinge caused rotation and withdrawal of the fastener from the substrate. There was no sudden loss in connection strength but rather a predictable failure as the fastener was pulled from the substrate.

The angle to which this hinge developed was found to be dependent on the resistance to embedment offered by the timber member (Fig. 8). Results show the embedment resistance of LSL to be consistently higher than that of C16 timber. In line with these findings, LSL was also found to offer improved resistance to head side pull through (Fig. 9). In this respect, Fastener KF75 80/100 was found to give the highest values from tested fasteners and this was attributed the fastener being threaded over its entire length with no smooth shank. Due to this, the additional threads in the timber offered increased resistance. Since the overall withdrawal strength of the fastener is taken to be the of the lesser of the head side pull through and point side withdrawal the use of LSL and the resultant increase in head side pull through strength can, in cases, be shown to change the withdrawal parameter. In such Strength (N) 9000 8000 7000 6000 5000 4000 3000 2000 1000 0 cases the point side withdrawal strength becomes critical. In determining the performance of each fastener, additional findings were made; namely the importance of the installation of fasteners as per manufacturers recommendations. The point side withdrawal capacity of each fastener was found to be highly dependent on the adherence to specified penetration depths. Furthermore, incorrectly drilled holes and those which had not been properly cleared of debris were found to be detrimental in this respect. 5. Discussion In order to make these results relevant to the fastener s specified on site, additional factors such as cost and method of installation must be 3 MSC36070 taken into account. By using assumed 2.5 MSC36082 values for the amount of lateral BTB4C70 resistance required we can easily see 2 BTB4C82 the economic inefficiency of the current 1.5 KF75X80 methods of fixing (Fig. 10). A direct KF75x100 1 EXPN6x60 result of this finding has been the trial 0.5 EXPN6x100 specification of fastener KF7.5 80 on EXPN8x70 site. Data from the test program has 0 EXPN8x90 5000 7000 9000 11000 13000 15000 indicated that the fastener gives KMN72 Required lateral resistance (N) improved performance in relation to both lateral resistance and holding Fig. 10 Comparison of fastener cost performance down. However, its method of installation has been found to be both Cost of fasteners required (GBP) MSC36070/82 BTB4C70/82 KF7.5x80/100 Pointside withdrawal strength LSL Headside pull through EXPN6x60/100 EXPN8x70/90 KMN72 C16 Headside pull through Fig. 9 Comparison of withdrawal strengths of tested fasteners Embedment strength (N/mm 2 ) 80 70 60 50 40 30 20 10 0 MSC36070/82 BTB4C70/82 KF7.5x80/100 C16 Timber EXPN6x60/100 LSL EXPN8x70/90 KMN72 Fig. 8 Comparison of embedment strength of tested fasteners in both C16 and LSL

labour intensive and time consuming. Therefore, whilst it offers improvements in performance it can not be considered a fully optimised solution. Although the primary aim of this paper was to present the results of a laboratory based test program, through the study of site practices it is understood that increases gained from improved specification will be negated if the recommended installation practice is not adhered too (Fig.11). Therefore, to ensure that the values obtained through test are replicated in live situations it is important to ensure that good practice is maintained throughout. 6. Conclusion The primary purpose of this work was to provide test data on a range of fixings suitable for connecting the soleplate to the foundation substrate. In doing so each fixings performance would be evaluated in relation to the method currently employed. The aim was to improve current fastener specification and also provide data which can be used as part of a long term collaborative research project to develop a hybrid racking panel. Although test data combined with cost analysis highlighted the potential for immediate improvements in specification, site trials of the revised specification demonstrated that it was not an optimal solution as the more onerous installation method impinged upon on-site efficiency. Additionally, the importance of observing the manufacturers specified methods and adhering to good practice throughout the installation procedure has also been highlighted. The performance of each fastener when Laminated Strand Lumber is used in place of C16 timber has also been quantified. It has been shown that connection capacity can be directly increased by specifying LSL. Further investigation is needed to determine if the improved structural performance and construction benefits fully justify the increased costs associated with engineered wood products. 7. Acknowledgements The Author would like to thank Cullen BP, ETA Fixings (UK) Ltd, Napier University and Oregon Timber Frame Ltd. Their on going support is greatly appreciated. Gratitude is also expressed towards The Royal Academy of Engineers for their assistance in attending this conference. 8. References Fig. 11 Incorrectly installed (over penetration) shot fired dowel. [1] UK Timber Frame Association (UKTFA). Timber frame facts and figures, www.timberframe.org, UKTFA, The e-centre, Cooperage Way Business Village, Alloa, 2005 [2] Griffiths B., Enjily V., Blass H., and Kallsner B., A Unified Design Method for the Racking Resistance of Timber Framed Walls for Inclusion in Eurocode 5 CIB-W18, 2006 [3] Prion H.G.L, Shear walls and diaphragms In: Timber engineering Edited by Thelandersson S,. and Larsen H.J, Chichester 2003. ISBN 0-470-84469-8 [4] British Standards Institution (BSI) (2002) BS 5268-6.1: 1996: Structural use of timber. Code of practice for timber frame walls. Dwellings not exceeding 4 stories.

[5] British Standards Institution (BSI) BS EN 1995-1-1: 2004. Eurocode 5 Design of timber structures Part 1-1: General Common rules and rules for buildings [6] Aicher S., Klock W., Dill-Langer G., Radovic B., (2003) Nails and nail plates as shear connectors for Timber-concrete composite constructions. Otto-Graf-Journal, Volume 14, 2003, pp. 189-210. [7] N.N.: E DIN 1052:2000. Entwurf, Berechnung und Bemesung von Holzbauwerken. Beuth- Verlag, Berlin, 2000. [8] Blass H.J, (2003) Joints with Dowel-type Fasteners In: Timber Engineering Edited by Thelandersson S,. and Larsen H.J, Chichester 2003. ISBN 0-470-84469-8 [9] British Standards Institution (BSI) BS EN 338:2003 Structural Timber Strength Classes [10] British Standards Institution (BSI) BS EN 1380:1999 Timber structure- Test methods- Load bearing nailed joints. [11] British Standards Institution (BSI) BS EN 1383:1999 Timber structures Test Methods Pull through resistance of timber fastener. [12] British Standards Institution (BSI) BS EN 1382:1999 Timber structures Test Methods Withdrawal capacity of timber fasteners. [13] British Standards Institution (BSI) BS EN 383 Timber structures Test Methods Determination of embedding strength and foundation values for dowel type fasteners