The Synthesis and Analysis of Partial Discharges from Stator Winding Insulation of Hydro Generators

Similar documents
Finite Element Analysis of a Single-Phase Alternating Current Meter

Online Monitoring of the Air Gap for Large Synchronous Hydrogenerators with the Purpose to Prevent some Operating Troubles

Modulated Field Synchronous Generator for Wind Turbines

CONTINUOUS ON-LINE SYSTEM FOR PARTIAL DISCHARGE MONITORING FOR HA1 AT CHE ROBEŞTI

Researches Regarding the Pollution with Harmonics by the Frequency Converters

PARTIAL DISCHARGE MEASUREMENT ON ROTATING MACHINES

IRIS POWER TGA-B. Periodic Online Partial Discharge Monitoring Instrument for Turbine Generators and Motors

A1-209 EXPERIENCES IN IDENTIFICATION OF PARTIAL DISCHARGE PATTERNS IN LARGE HYDROGENERATORS

PARTIAL DISCHARGE MEASUREMENT

Extended analysis versus frequency of partial discharges phenomena, in support of quality assessment of insulating systems

Intelligent Infrastructures Systems for Sustainable Urban Environment

International Journal of Advance Engineering and Research Development. Comparison of Partial Discharge Detection Techniques of Transformer

CHAPTER 5 CONCEPT OF PD SIGNAL AND PRPD PATTERN

Analysis of Partial Discharge Patterns for Generator Stator Windings

Simulation Model of Partial Discharge in Power Equipment

Software System for Finding the Incipient Faults in Power Transformers

Dielectric response and partial discharge measurements on stator insulation at varied low frequency. Nathaniel Taylor

High Frequency Voltage Stress. Presented by: Flore Chiang Date: March 30, 2012

Partial Discharge Theory, Modeling and Applications To Electrical Machines

Measurement Of Partial Discharge (PD) In High Voltage Power Equipment

Knowledge Is Power SM Apparatus Maintenance and Power Management for Energy Delivery. Application of EMI Diagnostics to Hydro Generators

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.

Basics of Partial Discharge. Prepared for 2015 Phenix RSM Meeting January 2015

Type 297, High-Voltage Mica Capacitors Corona-free Mica Coupling Capacitors for Medium-Voltage PDA s

IRIS POWER PDTracII. Continuous On-line Partial Discharge Monitoring for Motors, Generators, Dry Type Transformers, and Air-Insulated Switchgear.

High-Voltage Test and

VIBRATIONS LEVEL ANALYSIS DURING THE OPERATION OF A HIGH HEAD HYDROPOWER PLANT

Objective Methods to Interpret Partial-Discharge Data on Rotating-Machine Stator Windings

Instruction Manual. For Type E Plasma Tube Electrodes

EFFECT OF INTEGRATION ERROR ON PARTIAL DISCHARGE MEASUREMENTS ON CAST RESIN TRANSFORMERS. C. Ceretta, R. Gobbo, G. Pesavento

Researches Concerning to Minimize Vibrations when Processing Normal Lathe

PARTIAL DISCHARGE MEASUREMENT AS A DIAGNOSTIC TOOL FOR CURRENT TRANSFORMER

PARTIAL DISCHARGE DETECTION - AN OVERVIEW

Digital Speed Cascade Control, using Scilab / Xcos Environment

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Preface...x Chapter 1 Electrical Fundamentals

EFA Loudspeakers. Proc. ESA Annual Meeting on Electrostatics 2008, Paper A2 1

CHARACTERIZATION OF PARTIAL DISCHARGE PULSES OF POWER GENERATOR

Condition Assessment of High Voltage Insulation in Power System Equipment. R.E. James and Q. Su. The Institution of Engineering and Technology

Life Prediction of Mold Transformer for Urban Rail

PARTIAL DISCHARGE MEASUREMENT ANALYSIS ON RING MAIN UNIT

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

Analysis of Off-Line and On-Line Partial Discharge in High Voltage Motor Stator Windings

2006 2nd International Conference on Power Electronics Systems and Applications

PATTERN CLASSIFICATION OF PARTIAL DISCHARGE IN LV WINDING OF 1- TRANSFORMER USING PCA

Review of Partial Discharge and Dielectric Loss Tests for Hydropower Generator Bars

Relative Ability of UHF Antenna and VHF Capacitor Methods to Detect Partial Discharge in Turbine Generator Stator Windings

Ramp Testing in Identifying and Preventing Insulation Failure

EXPERIENCE WITH ON-LINE PARTIAL DISCHARGE MEASUREMENT IN HIGH VOLTAGE INVERTER FED MOTORS

Module-3: ADVANCED MATERIAL REMOVAL PROCESSES

Open Access Application of Partial Discharge Online Monitoring Technology in ± 660kV Converter Transformer

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

IEEE Guide for the Measurement of Partial Discharges in AC Electric Machinery

Stator Winding Partial Discharge Activity for Air- Cooled Generators

RESIDUAL LIFE ASSESSMENT OF GENERATOR TRANSFORMERS IN OLD HYDRO POWER PLANTS

Partial Discharge Analysis of a Solid Dielectric Using MATLAB Simulink

nical catalogue Tech

Current state of surge testing induction machines

Evaluation of Distribution Line Spacers Located Near the Coast

ELECTRIC CURRENT VERY SHORT ANSWER QUESTIONS

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

THE PROPAGATION OF PARTIAL DISCHARGE PULSES IN A HIGH VOLTAGE CABLE

Innovative Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

Field Measurement of Transmission Cable Dissipation Factor

Effective maintenance test techniques for power transformers

vacon 100 industrial vacon 100 flow vacon 100 hvac vacon 100 x ac drives du/dt filter technical guide

Effective Maintenance Test Techniques and Diagnostic Measurements to Improve the Performance and Reliability of Power System Transformers

PORTABLE PARTIAL DISCHARGE MONITORING INSTRUMENT

Computer Aided Design of Kaplan Turbine Piston with SolidWorks

Characteristics of Insulation Diagnosis and Failure in Gas Turbine Generator Stator Windings

Radiation Detection Instrumentation

TRANSFORMER OPERATIONAL PRINCIPLES, SELECTION & TROUBLESHOOTING

Fault Indicators of Partial Discharges in Medium-Voltage Systems

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Lifetime Consumption and Degradation Analysis of the Winding Insulation of Electrical Machines

process has few stages and is highly repeatable. Excellent mechanic properties and electro-magnetic compatibility. Planar design gives the height lowe

Power transformer maintenance. Field Testing.

Partial Discharge Monitoring and Diagnosis of Power Generator

PARTIAL discharge testing has been used for nearly

High Voltage Engineering

Glossary of Common Magnetic Terms

SIMULATION OF HEAT FLOW IN TVS DIODES. Simona Zajkoska 1, Peter Bokes 1

Application Note. Detection of Partial Discharge Using Ultrasound. Detection of Partial Discharge Using Ultrasound. Problem. iriss.

Aspects of PD interpretation in HV power cables. by Edward Gulski, Piotr Cichecki, Rogier Jongen

Chip Resistors Pulse Withstanding

Logic Level Signal Isolation Technology Review. MARK CANTRELL Senior Applications Engineer

Specialists in HV and MV test and diagnostics. Testing in Substations

LOW VOLTAGE PWM INVERTER-FED MOTOR INSULATION ISSUES

THE CONDUCTIVE ADHESIVE JOINS UNDER THERMAL SHOCKS. Ivana BESHAJOVA PELIKANOVA a

This is an author-deposited version published in : Eprints ID : 18192

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

Health indexes for power transformers: A case study

Rotary Machine Prognostic Based on Gamma Process

Application of Polarisation Depolarisation Current (PDC) technique on fault and trouble analysis of stator insulation

Control of Induction Thermal Plasmas by Coil Current Modulation in Arbitrary-waveform

Insulation State On-Line Monitoring and Running Management of Large Generator

Frequency Spectrum Analysis of Electromagnetic Waves Radiated by

Partial Discharge Characteristics and Insulation Life with Voltage Waveform

Transcription:

ANALELE UNIVERSITĂłII EFTIMIE MURGU REŞIłA ANUL XIV, NR. 1, 2007, ISSN 1453-7397 Mihaela Răduca, Ana-Maria Pittner, Eugen Răduca, Iancu Tătucu The Synthesis and Analysis of Partial Discharges from Stator Winding Insulation of Hydro Generators In this paper to perform the partial discharges which appear in stator winding insulation, the main characteristic measures of these, measurement and the results of partial discharges test. 1. Introduction During exploitation the electrical equipment insulation may be required at supplementary solicitations of voltage, according by commutation over voltages, atmospherically over voltages or accidentally over voltages inducing by defects appeared in using time. The over voltages can generated in insulation, according with existing conditions, to different electrical phenomenon s, sometimes attend on sonorous and light effects, known over the name: discharges; pierces; arc-over; sparks; primers; effluences; Corona effects. 2. Partial discharges or ionizations The insulations not be considerate perfectly homogenous. In this, always will find small dimensions goals filled with gas. This gas result from contraction of insulation different constituents or from technological executed process. Below action of electric field, these goals are ionized and when voltage between opposed faces touch the destructive gradient of closed gas, appear the partial discharges (ionizations). These partial discharges (PD) depend in number and amplitude by voltage gradient, superficially resistance of goal walls and goal dimensions, by nature and pressure of closed gas. The energy transmitted to the electrons from electric field is used in the following processes: the shocks which going to heating the gas from goal; 149

the excitation of gas atoms which produced a emanation of radiations; the ionization which multiply the number of atoms; electrodes bombardment (goal walls) which determinate the chemical and structure modifications of insulated materials; The discharge energy transfer on the goal walls in which to develop the partial discharges are made is in two ways: through local transfer on one chemical structure, which can determined, in case of high molecular mass substances, a rupture of some connections, or, in another conditions, appear of supplementary connections; through heating transfer; the time of exchange being extremely short, this transfer is applied to a little volume of substance and for that the increase of temperature in impact points may induce melting and evaporation of it, or to some components of her. The apparition and development of these inner partial discharges have a harmful effect on the insulation because these goals became bigger with time, formatted the channels by union of many goals, going out with formation of craters. In this manner, the insulation is loosening and can be appear the pierces which going out at destruction of insulation. Measurement of partial discharges let us observed from time the increasing of their level, therefore apparition of some evolution defects in insulation mass or general aging of insulation. 3. Characteristic measures of partial discharges The characteristic measures of partial discharges are the followings: the apparent charge of one partial discharge q, is the charge which instantaneous injection to the terminals of tested object, will instantaneous modified the terminals voltage with same quantity like partial discharge it self. the medium discharge current I, is the ratio between absolute value sum of apparent charges of partial discharges, on the one time period T: v( t + T ) 1 I = q v T v( t), (1) the square flow of apparent charges D, is ratio between square sum of apparent charges of partial discharges, on the one time period T: 150

v( t + T ) 1 2 D = q v T v( t), (2) the dissipated power through partial discharges P, is average power supplied at terminals owing to partial discharges on the one time period T: v( t + T ) 1 P = q v U v T v( t), (3) where U v is instantaneous values by v rage of voltage at terminals, corresponding at q charges. average ionization current I m : I m = 2Df i, (4) where f i is attempt voltage frequency the reduction square of apparent charges d: D d = C, (5) where C is capacity of insulation. reduced ionization medium current i m : I i = m m C, (6) 4. Measurement of partial discharge level The measurement of partial discharges is a estimation method of insulation quality, especially, looking over insulation homogenous (presence of goals and impurities in insulation, so also). In the same time the periodically measurements make at exploitation equipments permit us to observe, in time, the aging process of insulation. Through the measurement of partial discharges level are understanding the measurement of the following measures: apparent charge; medium discharge current; square flow of apparent charges; losses in dielectric owning to discharges. The choosing of apparent charge, q, as characteristics fundamentally measure of partial discharge permit to measure the individually discharge intensity which are produce in particular points of insulation, in- 151

dependent circuit and measurement apparatus. The apparent charge can determinate the highest discharge (being easy interpretation). This charge are easy measured, and can be follow the discontinuities which going out at release of discharge in other points than in which already exists. The choosing of medium discharge current, I, reflect the combination effect a lot of discharges. To use in practice of this measure is very difficult. The measurement of square flow of apparent charges, D, have the advantage that the meters are very simple. This measure depends of discharges with low and high intensity, in the same time. The measurement of dissipation power through partial discharges, P, is used especially for insulation sample. It have the advantage that if it is known the dielectric constant and loss tangent, tgδ, can be separated the losses produced by discharges to the another losses. 5. The measurements of partial discharges The partial discharges test in PDA-IV technology it is used to indicate the following causes for deterioration of stator winding: The coils and bars which not sufficiently impregnated with epoxi resin Insulation mass which was exfoliated (separation of mica band layers) own to overheating and/or thermal cycles. The deterioration of semiconductor covering in slot and/or in frontal heads Loosen wedges and slot filling owning to manufacturing Conductive contaminations at frontal heads which going at phasemass or phase-phase arc-over In case of partial discharges test, for each phase are determinate two type of graphs. The first graph is two-dimensional (2D) where is present the impulse numbers (PD/sec) in function of partial discharges (PD) amplitude. The second graph is tri-dimensional (3D). The each graph resumes two types of measures: Peak amplitude, ±Q m Total activity of partial discharges, ±NQN (Normalized Quantity Number). where: ± Q m is peak amplitude of positive or negative partial discharges corresponding a repetitive rate of 10 pulses per second; ±NQN is proportionally measure with graph surface below analysed line of positive or negative impulses amplitude and it is the total transfer of charge owning to partial discharges. 152

The Q m measure is one rate amplitude of 10 impulses/seconds partial discharges and shows the deterioration in the winding grave point. The NQN measure is proportionally with total value of deterioration caused by partial discharges activity. The positive values of +NQN si + Qm measures indicate the presence of partial discharges activity at surface between coil and slot or on the frontal parts surface. The negative values of -NQN si - Q m indicate the presence of partial discharges activity at surface between copper and insulation or in insulation between coils. 6. The measurements prosecution For the partial discharge test, the coils were tested on the stand and the partial discharges test does at phase voltage: U = 0.6 f U n, (7) During function of generator the phase winding insulation is applied at phase voltage. Because the coils insulation is imposed at different voltages, so the coils towards null are imposed at low voltages and the coils towards the main terminal are imposed at phase voltage. For analyse the insulation state in PDA-IV technology each phase supplied separately at outside phase voltage so that the insulation of all coils which compose the one phase is imposed at phase voltage. In this way, the partial discharge activity is high than which appear in generator functioning time. But through this measurement are obtain an exactly appreciation of all phase insulation. 7. The results of partial discharges test After the tests, are obtained the followings results for characteristics measures ±NQN and ±Q m. These measures were determinate, with help of couplers,for each phase and obtained results are presented in table 1. Table 1 Couplers U=0.6xUn Phase R +NQN -NQN -NQN/+NQN +Qm -Qm -Qm/+Qm R - C1 62 80 1.29 38 39 1.02 Couplers U=0.6xUn Phase S +NQN -NQN -NQN/+NQN +Qm -Qm -Qm/+Qm S - C1 53 73 1.37 37 48 1.29 153

Couplers U=0.6xUn Phase T +NQN -NQN +NQN/-NQN +Qm -Qm +Qm/-Qm T - C1 67 56 1.19 38 36 1.05 R phase The two-dimensional (2D) and tri-dimensional (3D) analysis of partial discharges is presented in figure 1 and figure 2. Figure 1. The two-dimensional (2D) partial discharges analysis Figure 2. The tri-dimensional (3D) partial discharges analysis S phase The two-dimensional (2D) and tri-dimensional (3D) analysis of partial discharges is presented in figure 3 and figure 4. 154

Figure 3. The two-dimensional (2D) partial discharges analysis Figure 4. The tri-dimensional (3D) partial discharges analysis T phase The two-dimensional (2D) and tri-dimensional (3D) analysis of partial discharges is presented in figure 5 and figure 6. Figure 5. The two-dimensional (2D) partial discharges analysis Figure 6. The tri-dimensional (3D) partial discharges analysis 155

8. Conclusions Measurement of partial discharges permits understanding of their level, in time, therefore apparition of evolution defects in mass of insulation or general aging of insulation. Through characteristic measures of partial discharges can be appreciate the insulation state. From graph analysis, in stator coils insulation, on the all phases are obtain an intense activity of partial discharges in winding, being at admissible limit in generator functioning. For generator safety function impose replacement of winding insulation in maximum 1 2 years. References [1] Emery F.T. Partial discharge, dissipation factor, and corona aspects for high voltage electric generator stator bars and windings. IEEE Transactions on Dielectrics and Electrical Insulation, 12(2): pp.347 361, 2005. [2] IEC 270. Measurement methods for partial discharges. [3] Răduca Mihaela, ContribuŃii la identificarea, modelarea şi simularea sistemelor de izolańie ale hidrogeneratoarelor, Teză de Doctorat, ISBN 978-973-652-467-3, Editura Politehnica, Timişoara, 2007 Addresses: Lector eng. Mihaela Răduca, Eftimie Murgu University of Romania, PiaŃa Traian Vuia, nr. 1-4, ReşiŃa, raducamiha@yahoo.com Ass. eng. Ana-Maria Pittner, Eftimie Murgu University of Romania, PiaŃa Traian Vuia, nr. 1-4, ReşiŃa, pittneram@yahoo.com Prof. dr. eng. Eugen Răduca, Eftimie Murgu University of Romania, PiaŃa Traian Vuia, nr. 1-4, ReşiŃa, e.raduca@uem.ro Conf. dr. eng. Iancu Tătucu, Eftimie Murgu University of Romania, PiaŃa Traian Vuia, nr. 1-4, ReşiŃa, i.tatucu@uem.ro 156