Protection of low power mains against pulse power of natural lightning using spark gap arresters. Abstract

Similar documents
ABSTRACTS of SESSION 6

EE 1402 HIGH VOLTAGE ENGINEERING

VBS TBS KTS BSS LFS UFS

BASIC PROBLEMS AND SOLUTION OF THE ENCAPSULATION OF A LOW VOLTAGE SPARK GAP WITH ARC SPLITTER CHAMBER

2007 DEHN + SÖHNE / protected by ISO EXFS / 5392

7P Series - Surge Protection Device (SPD) Features 7P P P

U.S. Government work not protected by U.S. copyright

Technical Specification

Spark Gap Surge Protectors For Lv Mains

MEDIUM VOLTAGE COMPACT STARTER TYPE KAE

Equipment Rack Grounding. Technical Note

Use of application-optimised type 1 combined arresters in low-voltage installations

Secondary Arresters. Figure 1. Type L secondary surge arrester rated 175 Vac, 125 Vdc.

Precautions to be considered for use of surge arresters tested according to Class 1 of IEC

RESULTS OF EXPERIMENTAL HIGH CURRENT IMPULSE 4/10 s OF METAL OXIDE VARISTORS ZINC IN THE HIGH VOLTAGE 220KV SURGE ARRESTER

Energy Division. Bowthorpe LV/MV Surge Arresters

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

MODIFICATION OF THE ARRESTER ARRANGEMENT WHEN CONVERTING THE METHOD OF NEUTRAL TREATMENT

In order to minimise distribution (11 and 22 kv) feeder breaker

Problems of the Processing Accuracy for Electro-erosion erosion and Electrochemical Machining Processes

A Low Impedance Marx Generator as a Test bed for Vacuum Diodes

Table 1: Results with standard impluse current 8/20 s applied to check for the residual voltage of V-MOV-ZnO

Vacuum Interrupters for Medium Voltage

02/11/2015

08/07/2015

PANIMALAR ENGINEERING COLLEGE Department of Electrical and Electronics Engineering

Technical Specification

Insulation Test System

FUNCTIONS OF CIRCUIT BREAKERS

22/10/2012

Shunt Reactor Switching

Modeling insulation in high-voltage substations

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

VACUTAP VVS COMPACT ON-LOAD TAP-CHANGER FOR GRID APPLICATIONS.

Analysis of lightning performance of 132KV transmission line by application of surge arresters

Capacitive voltage transformers

A SIMPLIFIED LIGHTNING MODEL FOR METAL OXIDE SURGE ARRESTER. K. P. Mardira and T. K. Saha s: and

Tab 8 Surge Arresters

The Testing Of High Voltage Silicon Carbide Lightning Arresters

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

02/11/2015

P331-2 set ESD generator (IEC )

High voltage engineering

Electric Stresses on Surge Arrester Insulation under Standard and

Overvoltage Protection of Light Railway Transportation Systems

High Voltage Generation

Testing 320 kv HVDC XLPE Cable System

Tab 2 Voltage Stresses Switching Transients

APPLICATION OF LONG FLASHOVER ARRESTERS FOR IMPROVEMENT OF LIGHTNING PROTECTION AND OPERATING VOLTAGE RELIABILITY OF DISTRIBUTION LINES

HIGH VOLTAGE Insulation Coordination

OVERVOLTAGE PROTECTION. Dimensioning, testing and application of metal oxide surge arresters in low-voltage power distribution systems

PMT/UMT(275) Power Gap Description and Use Application Note

Pulse Generator with Diodes D2601NH 90T at company Phoenix Contact Introduction Application D2601N90T

SIOV metal oxide varistors

24/07/2012

When surge arres t ers are installed close to a power transformer, overvoltage TRANSFORMER IN GRID ABSTRACT KEYWORDS

Insulation Test System

MINI-PS AC/24DC/1.3

GIS Disconnector Switching Operation VFTO Study

WIRELESS INSULATOR POLLUTION MONITORING SYSTEM

Electronic timer CT-TGD.22

Type CP-S, CP-C & CP-A Switch mode

Philosophies for the best method

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Lightning performance of a HV/MV substation

02/11/2015

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

Protection against unacceptable voltages in railway systems

02/11/2015

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

Design and Implementation of 8 - Stage Marx Generator Used for Gas Lasers

Investigation of skin effect on coaxial cables

Capacitive voltage transformers

The Study of TVS Trigger Geometry and Triggered Vacuum. Conditions

The relationship between operating maintenance and lightning overvoltage in distribution networks based on PSCAD/EMTDC

DEPARTMENT OF ELECTRICAL AND ELECTRONICS ENGINEERING QUESTION BANK SUBJECT CODE & NAME : EE 1402 HIGH VOLTAGE ENGINEERING UNIT I

High Voltage Engineering

SG A. Impulse Voltage Test System, kv / kj APPLICATION

IEC Electrical fast transient / Burst immunity test

08/07/2015

Resistive capacitive voltage divider

RE11RMMU time delay relay 10 functions - 1 s..100 h V AC - 1 OC

ROEVER ENGINEERING COLLEGE ELAMBALUR, PERAMBALUR DEPARTMENT OF ELECTRICAL & ELECTRONICS ENGINEERING

Power Electronics Power semiconductor devices. Dr. Firas Obeidat

Over-voltage Trigger Device for Marx Generators

Simulation and Analysis of Lightning on 345-kV Arrester Platform Ground-Leading Line Models

ANALYSIS OF FAULTS INTERRUPTED BY GENERATOR

Lightning transient analysis in wind turbine blades

9. How is an electric field is measured?

PAM31DOAB Series 1500 WATT TVS COMPONENT APPLICATIONS DO-214AB PACKAGE MECHANICAL CHARACTERISTICS FEATURES PIN CONFIGURATIONS.

UNIT 4 PRINCIPLES OF CIRCUIT BREAKERS SVCET

Parameters Affecting the Back Flashover across the Overhead Transmission Line Insulator Caused by Lightning

PHV RO. High impedance passive probe. Features: CeramCore TM Hybrid Probe. Modular Construction. Coaxial Design

International Journal of Advance Engineering and Research Development. Analysis of Surge Arrester using FEM

QUINT-PS/ 3AC/24DC/10

Chip Varistor LVS B DESCRIPTION APPLICATIONS FEATURES ORDERING INFORMATION. Capacitance 030 = 3pF 300 = 30pF 301 = 300pF

Visualization of the Ionization Phenomenon in Porous Materials under Lightning Impulse

XR1 Rotor Earth Fault Relay. Manual XR1 (Revision C)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

Transcription:

Protection of low power mains against pulse power of natural lightning using spark gap arresters. J Meppelink*, E.G. Jordan.**, J.Trinkwald*** *University of Paderborn,* BET Blitzschutz-und EMV Technologiezentrum GmbH, Menden, Germany *** OBO Bettermann GmbH, Menden, Germany. *übecker Ring 2 59494 Soest Germany Tel.: (49)-2921-378-272, Fax.: (49)-2921-378-271, e-mail: Meppelink@t-online.de Abstract The present state of lightning arresters with spark gaps for protection of low voltage installations will be analysed. Requirements for such devices must follow the actual knowledge of lightning physics, especially the lightning parameters. 1 Introduction ightning arresters are used for transient potential equalisation in low voltage networks to protect the equipment from over voltages [1]. They are designed to handle large currents, which occur in case of a lightning stroke into the external lightning protection equipment. Different solutions are already on the market, e.g. [2,3]. ightning current arresters are designed for impulse currents up to some 50 ka with a wave shape of 10/350µs. Metal oxide arresters, designed for the same values would require a large volume. Therefore the volume of metal oxide would be extreme compared to the volume of a gap arrester. This results from the higher residual voltage of a metal oxide arrester compared to a gap arrester. However, in some cases metal oxide arresters of compact design are used as lighting arrester but only for impulse currents up to some ka with 10/350µs wave shape. ightning current arresters for highest currents are therefore still gap arresters. There are many solutions on the market which use the arc of an open gap for follow current interruption. In this paper a new carbon technology will be shown. The application of carbon technology avoids some disadvantages of the existing gaps and shows therefore a better performance. A key for success is the application of new materials and arc interruption principles. The paper summarises the impact of lightning parameters and follow currents on a spark gap and describes a new technology. The following parameters have to be taken into consideration: ightning parameters Current distribution into the low voltage installation in case of lighting flash to a building Electrical spark-over characteristics of the gap, even under multiple lightning currents. Pressure in a spark gap due to the arc energy Erosion of electrode material Interruption of follow current Transient overvoltages Testing of spark-over voltage during service All the above-mentioned parameters were used as the basic engineering parameters for a new technology for lightning arresters with spark gap. 2 Behaviour of a conventional spark gap arrester Fig. 1 shows a group of lightning current arresters in a TT-Net. Fig. 2 shows a model to simulate the behaviour. The new lightning current arrester MC 50-B is represented using a macro model. Fig.3 shows the network behaviour. The gap triggers at 2 kv. The lightning - 1 -

current of 50 ka with a shape of 10/350µs follows but contains a power frequency follow current. Due to the properties of the lightning current arrester the arcing voltage reduces the current. The prospective current would appear if a short replaces the arrester. It is the property of the lighting current arrester to reduce the prospective current due to the development of an arc in the gap. In conventional gap arresters the plasma of the arc is blown out e.g. [2]. Others use closed chambers but there is a limited follow current interruption capability [3]. Fig. 4 shows the performance of an open gap arrester. It is a disadvantage to blow out hot plasma and such solutions require special housings with pressure release. 3. New solutions with a closed gap arrester To avoid the disadvantages of existing solutions, the main focus was concentrated on a closed gap with reduced aging and high follow current interruption capability. Fig. 5 shows a principal cross section drawing of a multiple gap arrester. The arcing voltage U arc is generated using the anode- and cathode drop in each closed pressure chamber. The total arcing voltage is therefore given by Uarc = n [ UAnode + U Cathode ] (1). The length of an arc in each chamber is negligible and therefore there is low energy dissipation. Fig. 6 shows the active parts of a phase arrester for 50 ka and fig. 7 shows an N-PE arrester for 125 ka both 10/350µs. Fig. 8 shows a complete phase arrester. The material of the electrodes defines the anode- and cathode drop. All metals vaporise at the footing points of arcs and result in a deviation of the spark-over voltage with the cumulative charge. To realise a constant sparkover voltage of each gap a solution without metal electrodes had to be found. Graphite as electrode material provides excellent properties for anode and cathode drop, heat conduction and vaporisation behaviour. Experiences from application of graphite for electrodes in high power spark gaps have shown excellent results [7]. The surface of graphite electrodes remains smooth even after some 10000 shots of 100 ka 10/350µs in crow bar generator spark gaps [4]. Therefore graphite electrodes can handle large lightning impulse currents. 3.1 Performance under combined stress As shown in fig.3, the power supply voltage drives follow current after the lightning current has passed the gap. The gap has to extinguish the follow current. The arcing voltage acts as a counter voltage and therefore the actual follow current in the gap is less than the prospective current. The behaviour of the multiple gaps under follow current was tested according to fig.9 [5] and the results are shown in fig. 10. In this test the gap was triggered using an 8/20µs surge current of 10 ka at a defined phase angle of 30 degrees of the power supply voltage. At this angle the voltage at the gap remains nearly constant at 285 Volt. When the arcing voltage is equal to the actual value of the power supply voltage, the gap extinguishes and does not reignite. Under test conditions of 25 ka prospective peak current [5] the actual follow current in the gap is only 6,3 ka peak. During the tests no plasma was visible from outside. From this test one can conclude that the arcing voltage in a multiple gap is sufficient to reduce the follow current and to extinguish the plasma in the chambers. 3.2 V-t curves of lightning arresters The series connection of spark gaps requires special measures for triggering at 1,2/50µs [5]. As shown in fig 5 the first upper gap triggers first, followed by the next due to capacitive voltage grading. Fig. 11 shows the measured voltage time characteristic of a multiple gap arrester. Compared to the spark gap arrester [2] (one gap only) the multiple gap arrester shows a lower spark-over voltage of 2 kv. The time to breakdown is lower due to the better provision of initial electrons from the parallel plate graphite electrode in the multiple gaps, compare fig.6. Fig.11 shows also the successive trigger of all gaps of the multiple spark gap arrester. Also the arcing voltage can be compared in fig.11. The spark gap arrester with one - 2 -

gap only shows a few 10 volts of arcing voltage and the multiple spark gaps shows some 100 volts. Fig.12 shows the voltage-time curve. Since the multiple spark gap arrester starts with the breakdown of the first gap and ends with the final breakdown after triggering of all gaps, the time dependence of the voltage curve in fig. 12 shows both the first and the final breakdown. 3.3 Performance under multiple lightning impulses Multiple lightning occurs in the negative downward flash. As shown in [6] multiple lightning impulses can be generated as hybrid impulses in laboratory. Each impulse starts with a 1,2/50µs voltage impulse. When the gap has triggered, the generator produces an 8/20µs current impulse. Fig. 11 shows the performance of the multiple gap arrester under four impulses. The gap triggers finally below the desired protection level of 2 kv. This test shows how fast the gap recovers from the ionisation from the previous impulse. The small gap distance provides fast recombination of ions into the electrodes. 3.4 EMC design of new arresters As required in [6] the connection of the new lightning current arrester to the net is realised using a double clamp for V-connection. Fig. 1 shows the details of the connection in case of a TT-net. Fig.14a shows the recommended connection according to [6]. Fig. 14b shows the di equivalent circuit. The voltage drop in this case is: U= 2 + U R dt The better solution is the V-shape connection as shown in fig. 14c with the equivalent circuit in fig. 14d. The voltage drop in this case is given by (3) were the inductance of leads has no effect. The voltage drop in this case is: U= U R 4. REFERENCES [1] IEC 60364-5-534, Part 5, selection and erection of electrical equipment Section 534: Devices for protection against over voltages. [2] K.Scheibe, J.Schimanski, Practical experiences with surge protection devices, Proceedings of 24th International Conference on ightning Protection (ICE.), pp.801-807, Birmingham, 1998. [3] J.Pospiech, F.Noack, R.Brocke, P.Hasse, P.Zahlmann, Self blast spark gaps: A new solution for lightning current arresters in low-voltage mains,proceedings of 24th International Conference on ightning Protection (ICP), pp.746-751, Birmingham,1998. [4] C.Drilling, M.Droldner, E.G.Jordan, J.Meppelink, A new generator for testing of SPD s using multiple lightning current impulses for combined tests with follow currents, Proceedings of 24th International Conference on ightning Protection (ICP), pp.905-912, Birmingham,1998. [5] IEC 61643-1 Surge protective devices connected to low-voltage power distribution systems Part 1 performance requirements and testing methods. [6] Kallweit, J.; udewig, S.; Meppelink, J.; Schoene, J.: Development of a 10-stage multiple lightning surge hybrid generator with variable time interval and peak value. [7] Drilling,C.;Droldner,M.;Jordan,E.G.; Meppelink,J.: A new combined crow bar generator for complex testing of lightning protection equipment using multiple lightning currents. 13th International Zurich Symposium on Electromagnetic Compatibility, 1999 Zurich, Switzerland. - 3 -

Prospective current Current in arrester MC 50-B Fig. 3b Currents calculated in fig.2. Fig. 1 Class I lightning arresters in a TTnet. Approved by VDE, KEMA, and ÖVE. 1 V1 N PE Fig.2 Circuit for simulation of basic, principal behaviour of one lighting arrester in a 1-phase network. Transformer of 650 kva, and 100 m cable 70 mm 2 Station ground R= 5 ohm; transformer ground 2 ohm Fig. 4 Conventional spark-gap arrester with blow off chamber during test with impulse 10/350µs impulse of 60 ka in laboratory [7] using a crow bar generator. 1:conventional arrester, 2,3: spark gaps of lightning current generator. 3 4 1 6 Voltage across arrester MC 50-B 5 Voltage of mains 2 Fig.3a Voltages calculated in fig.2 Fig. 5 Multiple spark gap with capacitive grading.1, 2: Connections; 3: Capacitive grading; 4: Graphite electrodes; 5 Sparks in sealed chamber between electrodes. 6 Teflon insulation disc. - 4 -

AC Ip=25 ka 50 Hz Z Arrester 8/20µs Impulse 10kA Shunt for follow current Shunt for impulse current Fig. 6 Phase arrester with multiple spark gaps with capacitive grading. 1,2: Connections; 3: Capacitive grading; 4: Graphite electrodes; 5 plug in active part, 6 Teflon insulation disc. Fig. 9 Principal test arrangement for combined testing of gap arresters with surge current and follow current. Current in spark gap 6,3 12 ms Current with trigger point 30 degrees Fig. 7 Twin spark gap arrester as N-PE arrester. 285 V 12 ms Voltage across spark gap Fig. 8 Phase arrester with housing Fig10 Results of combined test with the multiple gap lightning arrester. The arrester was triggered using a surge current 8/20µs with 10 ka peak. The AC source was set to a prospective peak current of I P =25 ka. The trigger point was set to 30 degrees. The voltage across the gap and the current in the gap were measured. Please note: Only the follow current of the AC source is shown in the above oscillogramms. - 5 -

Breakdown of first gap Breakdown of all gaps 1,24 kv 0,88 µs A) Performance of the 9-stage multiple gap arrester Fig. 13 Performance of the multiple gaps in a multiple hybrid generator with 1,2/50 µs open circuit voltage and 8/20µs impulse current after triggering. Breakdown: 3 kv <0,5 m di/dt U R UA <0,5 m 4,24 µs di/dt B) Performance of a conventional one gap arrester Fig.11 Performance of the 9-gap arrester compared with a spark gap arrester with one gap only under the same lightning impulse voltage 3/50µs with the same prospective peak value. N or PE-bar Fig. 14 V-shape connection of lightning current arresters according to [6] U R UB 4000 V 3500 Breakdown voltage (Volt) Breakdown of a arrrester with one gap only 3000 2500 2000 1500 Breakdown of all gaps 1000 500 Breakdown of first gap only 0 100 1000 Time ns 10000 Fig.12 Voltage-time-characteristic of the multiple gap arrester with 9 gaps compared with a conventional spark gap arrester with one gap only. - 6 -