FAULT CURRENT LIMITERS PRINCIPLES AND APPLICATION

Similar documents
A Pyrotechnic Fault Current Limiter Model for Transient Calculations in Industrial Power Systems

Poornima G P. IJECS Volume 3 Issue 6 June, 2014 Page No Page 6453

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Markus Abplanalp, 7. Braunschweiger Supraleiterseminar, Strombegrenzerkonzepte im Vergleich

Fourth Workshop & Conference on EHV Technology CSIC Auditorium, Indian Institute of Science, Bangalore India.

Design and Simulation of superconducting fault current limiter

Resistive and Inductive Fault Current Limiters: Kinetics of Quenching and Recovery

INCREASING THE POWER SYSTEM SWITCH GEAR CAPACITY BY USING SUPERCONDUCTING FAULT CURRENT LIMITER

Standards Developments for Fault Current Limiters

PERFORMANCE ANALYSIS OF SURGE CURRENT PROTECTION USING SUPERCONDUCTORS

TRANSIENT AND DESIGN OPERATION ASSESSMENT OF RFCL IN BULK POWER SYSTEMS

SERIES ACTIVE power filters have proved to be an interesting

The Fault Level Reduction in Distribution System Using an Active Type SFCL

Past CIGRE and Emerging IEEE Guide Documents on FCLs

FAULT CURRENT LIMITER IN SINGLE PHASE AND THREE PHASE LINES FOR COMPENSATING VOLTAGE SAG

Simulation of HTS saturable core-type FCLs for MV distribution systems

Current limiting characteristic of saturated iron core SFCLs

Short Circuit Current and Voltage Stability Analysis of a Realistic Generation System Using Fault Current Limiter and SVC

High Voltage DC Transmission 2

Performance Analysis of Various Types of Fault Current Limiters Using PSCAD

Superconducting Fault Current Limiter for Energy Storage Protection in a Micro Grid

(2) New Standard IEEE P (3) Core : (4) Windings :

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Fault Current Limiter Selection Considerations for Utility Engineers

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

Analysis of Superconducting Fault Current Limiter in DC System with Renewable Energy Sources

Lumped Network Model of a Resistive Type High T c fault current limiter for transient investigations

FAULT CURRENT LIMITER SURGE PROTECTION DEVICE FOR THE POWER GRID BASED UPON ZERO POWER CONSUMPTION CERAMIC FERRITE PERMANENT MAGNETS

CONTENTS. 1. Introduction Generating Stations 9 40

D2-02_13. Saturable-Core FCL Based on the Normal Conductor Direct Current Coil

Grounding System Theory and Practice

Review on Fault Current Limiters

Development and performance analysis of a saturated core high temperature superconducting fault current limiter

Design and Simulation of Passive Filter

Review on Superconducting Fault Current Limiter

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Thyristor Based Fault Current Limiter to Control Magnitudes of Fault Currents

Saturated Core Fault Current Limiters: successful testing/ service performance

HARMONICS THE BASICS H A R M O N I C M I T I G A T I O N A N D D I S P L A C E M E N T P O W E R F A C T O R C O R R E C T I O N

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

HVDC Transmission. Michael Muhr. Institute of High Voltage Engineering and System Performance Graz University of Technology Austria P A S S I O N

FRIENDS Devices and their Coordination

Recent Development of SFCL in the USA

International Journal of Scientific & Engineering Research, Volume 4, Issue 7, July ISSN

Voltage and Current Waveforms Enhancement using Harmonic Filters

Performance of Superconducting Fault Current Limiter and Fault Current Limiter in Power System

Minimizing of Fault Current Using SFCL Technology

International Journal of Engineering Technology and Scientific Innovation

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

A Silicon Carbide Based Solid-State Fault Current Limiter for Modern Power Distribution Systems

Electromagnetic transient analysis of saturated iron-core superconducting fault current limiter and DVR

REDUCTION OF TRANSFORMER INRUSH CURRENT BY CONTROLLED SWITCHING METHOD. Trivandrum

A Comparative Study of Different Topologies of Multilevel Inverters

2 Grounding of power supply system neutral

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

Principles for Controlling Harmonics

Modeling and Analysis of Superconducting Fault Current Limiters Applied in VSC-HVDC Systems

Conventional Paper-II-2011 Part-1A

Proposed structure of fault current limiter with power quality improvement

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System

Comparison Between two Single-Switch Isolated Flyback and Forward High-Quality Rectifiers for Low Power Applications

Long lasting transients in power filter circuits

COOPERATIVE PATENT CLASSIFICATION

DESIGN AND DEVELOPMENT OF SMES BASED DVR MODEL IN SIMULINK

1% Switchgear and Substations

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

Application Note. Motor Bearing Current Phenomenon. Rev: Doc#: AN.AFD.17 Yaskawa Electric America, Inc August 7, /9

AORC Technical meeting 2014

Evaluating the Response of Surge Arresters

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Ein supraleitender Strombegrenzer für die Energieübertragung

A Thyristor Controlled Three Winding Transformer as a Static Var Compensator

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

DOWNLOAD PDF POWER ELECTRONICS DEVICES DRIVERS AND APPLICATIONS

USING OVER-DAMPING METHOD TO SUPPRESS THE FERRO-RESONANCE OF POTENTIAL TRANSFORMER

FACTS devices in Distributed Generation

DC current interruption tests with HV mechanical DC circuit breaker

ATC s Mackinac Back-to-Back HVDC Project: Planning and Operation Considerations for Michigan s Eastern Upper and Northern Lower Peninsulas

Notes 1: Introduction to Distribution Systems

CHAPTER 4 4-PHASE INTERLEAVED BOOST CONVERTER FOR RIPPLE REDUCTION IN THE HPS

Power Upgrading of Transmission Line by Injecting DC Power in to AC Line with the help of ZIG-ZAG Transformer

THE IMPACT OF NETWORK SPLITTING ON FAULT LEVELS AND OTHER PERFORMANCE MEASURES

Introduction to HVDC VSC HVDC

Development of 13-V, 5000-A DC Power Supply with High-Frequency Transformer Coupling Applied to Electric Furnace

ANALITICAL ANALYSIS OF TRANSFORMER INRUSH CURRENT AND SOME NEW TECHNIQUES FOR ITS REDDUCTION

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Active Smart Wires: An Inverter-less Static Series Compensator. Prof. Deepak Divan Fellow

Power Quality enhancement of a distribution line with DSTATCOM

Basic Principles and Operation of Transformer

ABSTRACT I. INTRODUCTION

Harmonic Solutions. Clean Power Drive Solution to Harmonic Distortion

Reyrolle Protection Devices. 7PG11-18 Alpha Electromechanical Relays. Siemens. Answers for energy.

Arvind Pahade and Nitin Saxena Department of Electrical Engineering, Jabalpur Engineering College, Jabalpur, (MP), India

ISSN: [Singh* et al., 6(6): June, 2017] Impact Factor: 4.116

How to maximize reliability using an alternative distribution system for critical loads

Floating Output DC-DC Converter Using Single Winding Reactor and Its Applications

SIMULATION STUDIES OF HALF-BRIDGE ISOLATED DC/DC BOOST CONVERTER

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Impact Factor: Student, SV University, Tirupati, India.

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Impact of Distributed Generation on Network Voltage Levels

Transcription:

FAULT CURRENT LIMITERS PRINCIPLES AND APPLICATION Georgi GANEV 1, Krastjo HINOV 2, Nikolay KARADZHOV 3 1 TU Sofia, branch Plovdiv, e-mail: gganev@tu-plovdiv.bg 2 TU Sofia, e-mail: k_hinov@yahoo.co.uk 3 TU Sofia, e-mail: n_karadjov@abv.bg Abstract: In this paper a new type electrical devices, designed for use in medium voltage and high voltage grids, has been explained the fault current limiters. Their principals of operation and different structures have been proposed. The comparative analysis and their possibile estimation have been made. Keywords: fault current limiters, power system faults INTRODUCTION The short circuit faults are the most destructive ones among the numerous faults occurring in power distribution systems. Sometimes the short-circuit faults generate over current more than 20 times the rated current. The consequences of inevitable fault current in electrical network usually mean thermal or mechanical stress for the affected equipment. The normal power flow is interrupted by the protection relays. The results are voltage interruption and other power quality problems to the end-users. Power equipment is normally dimensioned for the tremendous stress under fault conditions. The maximal short-circuit current is one of the most important dimensioning parameter and it is directly linked to the price of the equipment. The downsizing of the existing equipment, such as transformers, lines, bus-bars and circuit-breakers is possible by decreasing the maximal fault current [1]. The traditional devices, used for fault current limitation, are: Fuses are simple, reliable and they are usually used in low voltage and in middle voltage distribution grids. The main disadvantages are the single-use and the manually replacement of the fuses; Circuit-breakers are commonly used, reliable protective devices. The circuitbreakers for high current interrupting capabilities are expensive and have huge dimensions. They require periodical maintenance and have limited number of operation cycles; Air-core reactor and transformers with increased leakage reactance increase the impedance of distribution network and consequently limit the short-circuit currents; System reconfiguration and bus-splitting. There have been an increase in the number of studies on the alternative solution to improve the reliability of electrical systems and one of them is the application of a fault current limiter (FCL). The main purpose of the installation of FCL into the distribution system is to suppress the fault current. The FCL is series element which has very small impedance during a normal operation. If the fault occurs the FCL increases its impedance and so prevents over-current stress which results as damaging, degradation, mechanical forces, extra heating of electrical equipment. The main requirements to the FCLs are [2]: to be able to withstand distribution and transmission voltage and currents;

to have low impedance, low voltage drop and low power loss at normal operation; to have large impedance in fault conditions; to have a very short time recovery and to limit the fault current before the first peak; to properly respond to any fault magnitude and/or phase combinations; to withstand the fault conditions for a sufficient time; to have a high temperature rise endurance; to have a high reliability and long life; to have fully automated operation and fast recovery to normal state after fault removal; to have a low cost and low volume. The pyrotechnic FCL (so called explosion faults limiting fuses, I s -limiters) takes special place. Is-limiters are consist of an ultra fast acting switch for nominal loads connected in parallel to a heavy duty fuse. A small explosive charge is used to open the main current path if the fault occurs. The current is transferred to the fuse and its magnitude is limited. A service call is required to replace the fuse after each event [3]. Therefore they are not object of this paper. FAULT CURRENT LIMETER TYPES A numerous classifications of FCLs have been known [3,4,5]. One of them is used by CIGRE WG A3.10 [6]: passive FCL - increase the source impedance at nominal and fault conditions; active FCL - fast increasing circuit electrical parameters after fault detection. At last three decades the modern technologies and new materials have been used to make devices with proper parameters. Therefore the common used FCLs classification is: Non-superconducting FCL The different types FCLs have been designed: saturable core FCLs (fig.1) they exploit the non-lineal characteristics of ferromagnetic materials to realize a high inductance. In normal case, the core is saturated by a bias current; the coil inductance is negligible. If the fault occurs, the magnetic core is taken out of saturation, the coil attain a high inductance and limits the fault current. The designs differ in the core shape, core bias arrangement and magnetic design [5]. solid-state FCLs they use the high power semiconductor devices - SCR, GTO, IGBT to realize a FCL. The solid-state FCL could be classified into three major groups: o The serial types FCLs are composed of bidirectional controlled switch and bypass circuit (fig.2). The bypass circuit contains normal state bypass, fault current bypass, over voltage protection bypass and a snubber. The normal state bypass usually is an electromechanical switch. It is purpose is to reduce the losses and distortion in the normal state. The fault current bypass restricts the fault current some schemes turn off the switches to interrupt the current, other modulate the fault current to keep it within the acceptable limits. The over voltage protection bypass and the snubber are essential, because they limit the voltage and dv/dt across the semiconductor switch and absorb some amount of the energy, stored in the line inductance [5].

o The bridge types FCLs are realized using a current-fed diodes/ thyristors full bridge arrangement (fig.3). The current rating of diodes/ thyristors and the limiting reactor are dictated by the peak fault current. Since the current limiting reactor is on the DC side of the rectifier, during the fault conditions the inductor is subject to high DC voltage which could cause inductor saturation, the current increases very fast and FCL may lose the current limiting capabilities. Another disadvantage of these devices is a significant conduction losses in normal state operation [5]. o The resonance types FCLs use switches to reconfigure their topologies either into the normal state or into the fault condition are composed (fig.4). They employ series resonant circuit tuned to the line frequency and thus present negligible impedance to the line. Under the fault conditions the circuit is switched to the fault state sub-topology and much higher impedance is presented to the line. The resonance FCLs reduce the fault current but they do not have interruption capability [5,7]. Fig.1. Saturable core FCL Fig.2. Serial type solid-state FCL Fig.3. Bridge type solid-state FCL Fig.4. Resonance type solid-state FCL Superconducting FCL Because superconducting materials have a highly non-linear behavior they are very useful FCLs to be build. The low temperature superconductors operating at the temperature of liquid helium (4K) as well as high temperature superconductors, called II -nd generation (2G) superconductors with critical temperature around the boiling point of nitrogen (77K) have been studied. The two most important 2G superconducting ceramics are used industrially as a coated conductor [3]: Yittrium-Barium-Copper-Oxide YBa 2 Cu 3 O 7 (often abbreviated YBCO) and is used for thin film techniques;

Bismut-Strontium-Calcium-Copper-Oxide Bi 2 Sr 2 Ca ncu n-1 O 2n+4+x, (abbreviated as BSCCO and with trade mark of the compound Bi-2212 / Bi-2223) are used for filament. There are three major type superconducting fault current limiters (SFCLs): The resistive type SFCLs is shown in line with the source and load (fig.5). During the normal operation the current is flowing through the superconducting element R SC dissipates low energy. If the current rises above the critical current value the resistance R SC increases rapidly. The dissipated losses heats the superconductor above the critical temperature T c and the superconductor R SC changes its state from superconducting into the resistive state, some resistance is generated and fault current is reduced. This phenomenon is called quench of superconductors. When the fault current has been reduced, the element R SC recovers its superconducting state. The parallel resistance or inductive shunt Z SH is needed to avoid hot spots during quench, to adjust the limiting current and to avoid over-voltages due to the fast current limitations. The resistive SFCLs are much smaller and lighter then the inductive ones. They are vulnerable to excessive heat during the quench state [1,2,4]. The inductive type SFCLs works like transformer with shorted superconducting secondary winding (fig.6). In normal operation the primary winding resistance and leakage inductance determine the impedance of the limiter. If the fault occurs, the resistance of the secondary winding is the superconductor quenches. The value R SC is transferred into the primary side by the k 2 =(w 1 /w 2 ) 2 and the FCL impedance increases [1,3]. Despite of the size and the weight this type FCL led to prototypes of higher power rating the resistive FCL [3]; The bridge type SFLC is shown in fig.7. Under normal operation the combined DC current and AC current remains low enough to allow all of the diodes or thyristors to be biased forward and therefore the AC current bypasses the inductance. In these conditions the FCL impedance is low, the total voltage drop and loss are dominated by the power diodes. If a fault occurs and the magnitude of the AC current exceeds the DC bias current two diodes will switch into a blocking mode for each half cycle and insert the inductor into the circuit. The coil impedance will limit the transient current. If thyristors are used instead of the diodes it is possible to turn off the current within the half-cycle. The main disadvantage of bridge type FCL is the relatively high total losses [8,9,10]. Besides these three basic types there are a variety of other concepts for SFCLs realization but their principles of operation are very close to these major types. As example the DC biased type SFCLs is shown in fig.8. The principal of pre-magnetized iron cores is the same as the saturable core FCLs (fig.1). The superconducting coils reduce the power losses in the bias coils. In normal operation the currents in both iron cores are driven into saturation with direct current. As a result the impedance is low, consisting mainly of the two air coil impedances Z w1 and Z w2. In the case of a fault the large AC current will drive the two coils out of saturation and into the region of high permeability on the magnetization curve resulting in a significant increase of the apparent coil inductance [9]. The main advantage of this type SFCL is the use of DC instead AC for the superconductor and avoiding of AC losses. The major disadvantage is the size of the devise it has to be approximately twice the size of such a transformer [3];

Fig.5. Resistive type SFCL Fig.6. Inductive type SFCL Fig.7. Bridge type SFCL Fig.8. DC bias type SFCL The common part of all these devices is the cryostat, creating the low temperatures for superconductivity hold up. [1,2]: APPLICATION The FCLs applications afford an opportunity to [2,11,12]: avoid equipment damaging; avoid equipment replacement; use lower fault rated equipment; avoid series reactor, split busses, bus-tie breakers; reduce voltage dips on adjacent feeders; enhance power grid transient stability. The FCLs can be installed in three main places in distribution substations (fig.8) incoming feeder position. The FCL protect the feeder and all downstream equipment that are valuable and sometimes is difficult to replace; outgoing feeder position. The FCL only limit the fault current passing through that feeder; bus-tie position. The FCL allows two buses to be tied together without significantly raising fault current on either bus.

Fig.8. FCLs connection points in power grid In the main incoming feeder position the fault current is higher as FCL limit all currents coming from the main breaker and falling into outgoing feeders. The bus-tie position FCL would have lower losses under normal operating position, because it has not continuously carry the full load current as feeder positioned FCLs. The optimal locations for FCL depend on the structure of the power system and other aspects - such as generators location or type of used generators [13] or protection relay scheme [14] etc. CONCLUSIONS By growth of interconnections in electrical systems the short-circuit capacity increases. The maximal over-current is one of the most important dimensioning parameter for the power equipment The development of effective FCLs is becoming very important in relation to rising fault current levels in modern power networks. The benefit of FCLs application in power systems is reduction the current stresses on equipment during faults, transient stability of the power grid enhancement and reduction of voltage dips and sags. There are many possible locations in power systems where FCLs installation offers technical and economical benefits. The bus-tie position appears to be the most economical option among other alternatives. ACKNOWLEDGEMENTS The RDS of Technical University-Sofia is gratefully acknowledged for the financial support of research project N o 122ПД0043-01 / 26.04.012. REFERENCES: [1] J.Kozak, T.Janowski, Application of HTS fault limiters in power network [2] S.Kalsi, A.Malozemoff, HTS fault current limiter concept, IEEE PESM, June 2004. [3] M.Steurer, K.Fröhlich, Current limiters state of the art, 4 th Workshop &Conference on EHV Technology, July 1998.

[4] M.Noe, M.Steurer, High-temperature superconductor fault current limiters: concepts, applications, and development status, Supercond. Sci. Technol. 20 (2007), R15-R29. [5] K.Smedley, A.Abravomitz, Development of fault current controller technology, June, 2011. [6] Fault current limiters, Report on the CIGRE WG A3.10, by CIGRE WG 13.10. [7] M.Tarafdar Hagn, MJafari, S.B.Naderi, New series resonance type fault current limiter, International Conf. on Power Systems Transients (IPST2011), june, Delft, Netherlands, 2011. [8] R.F.Giese, Fault current limiters a second look, Argonne National Laboratory, 1995. [9] S.H.Lim, B.S.Han, H.S.Choi, Bridge type fault current limiter using switching operation of HTSC thin film, Journal of the Korean Physical Sociaty, vo.45, no.3,sept.2004, pp.765-768. [10] M.Noe, C.Schacherer, Status and outlook on superconducting fault current limiter development in Europe, Proc. of ISETS07, pp.529-535. [11] V.Sokolovsky, V.Meerovich, I.Vajda. Transient stability of a power system with superconducting fault current limiters [12] D.Ioka,H.Shimizu, Y.Yokomizu, M.Goto, T.Matsumura, Effect of fault current limiter installed in customer system on suppression of fault current and voltage sag, IEEE2003, Power Tech Conference, Bologna, Italy. [13] E.Muljadi, V.Gevorgian, F.DeLaRosa. Wind power plant enhancement with a faultcurrent limiter, IEEE PES Annual Meeting, Detroit, July, 2011. [14] Fault current limiters application, principles and experience, CIGRE WG A3.16, Tokyo, 2005.