EN50160 Individual Report Summary

Similar documents
Voltage characteristics of electricity supplied by public distribution networks

Power Quality - 1. Introduction to Power Quality. Content. Course. Ljubljana, Slovenia 2013/14. Prof. dr. Igor Papič

EN 50160:2010 IMPROVEMENTS OF THE REVISED VERSION. TC8X System Aspects of Electricity Supply

EN50160 Report: Station 28 Puidoux Accepted Week 12 20/03/ /03/2017

Quality of supply regulation in Norway c

POWER QUALITY REPORT

Draft Kenya Standard for Balloting Not to be Cited as Kenya Standard

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Power Analysis Summary

APPLICATION NOTE STANDARD EN VOLTAGE CHARACTERISTICS OF ELECTRICITY SUPPLIED BY PUBLIC ELECTRICITY NETWORKS

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

Power quality report. A Manufacturing Plant

C.A Complete electrical network analysis at the tips of your fingers! Power Quality Monitor. Keeping up with the standards

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

MEASUREMENT METHODS OF THE CHARACTERISTICS AND TARGET VALUES OF THE VOLTAGE QUALITY SUPPLIED BY HYDRO-QUEBEC SYSTEM

PowerMonitor 5000 Family Advanced Metering Functionality

An Introduction to Power Quality

Southern Company Power Quality Policy

Power Quality Report. A Manufacturing Plant

Power Quality Requirements for Connection to the Transmission System

POWER QUALITY AND SAFETY

Roadmap For Power Quality Standards Development

Fundamentals of Power Quality

Harmonic Distortion Evaluations

INTERNATIONAL STANDARD

A Guide to Power Quality Testing

A Power Quality Interface for Low and Medium Voltage Smart Grids

Norwegian Water Resources and Energy Directorate (NVE)

Power Simulator MI 2891 Instruction manual Version 1.1.1, Code No

POWER QUALITY AND ENERGY EFFICIENCY IN LOW VOLTAGE ELECTRICAL POWER SYSTEM OF THE TECHNICAL UNIVERSITY OF GABROVO

1C.6.1 Voltage Disturbances

IEEE sion/1547revision_index.html

Emerging Standards for EMC Emissions & Immunity

PQ Monitoring Standards

RS232. DC POWER SUPPLY 20kW 3 RANGES

Generator Protection GENERATOR CONTROL AND PROTECTION

PQ for Industrial Benchmarking with various methods to improve. Tushar Mogre.

POWER CORPORATION. Power Quality. Specifications and Guidelines for Customers. Phone: Fax:

Monitoring power quality beyond EN and IEC

ZITARES NCD FX-30 Non-SELV (isolated), constant current control gear, 1-channel, dimmable

Contents. All Rights Reserved

Page 1 of 28. Ingo Röhr. Frank Hesmer

Rapid Voltage Changes Defintion and Minimum Requirements

Single Phase Soft Starters

G59/3 TYPE TEST VERIFICATION REPORT

Power quality Harmonics up to 40th harmonic Unbalance, rotary field indication Distortion factor THD-U / THD-I

Power Quality Basics. Presented by. Scott Peele PE

Section 11: Power Quality Considerations Bill Brown, P.E., Square D Engineering Services

MEASURING INSTRUMENTS AND TESTERS

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Voltage Relays. Ensuring Reliable Protection for Electrical Systems against Voltage Faults. ISO 9001:2008 Certified.

DSA150 Series. xxx Series. 150 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details 3.92 (99.8) 2.18 (55.5) 4.92 (125.

Power Quality and Digital Protection Relays

PQube 3 Specifications

Voltage dips short interruptions with PFS and Netwave

ECE 528 Understanding Power Quality

UMG 103. UMG 103 Universal measurement device for DIN rails. GridVis Analysis software. Harmonics. Measurement accuracy 0.5.

Power Quality and Circuit Imbalances Northwest Electric Meter School Presented by: Chris Lindsay-Smith McAvoy & Markham Engineering/Itron

Side view View from below Rear view

It includes the Generating Units supplier declaration of compliance with the requirements of Engineering Recommendation G59/3

1. Introduction to Power Quality

G59/3 TYPE TEST VERIFICATION REPORT

TECHNICAL DATASHEET MDS Medical AC-DC Open Frame 065APS18 B Highlights & Features Safety Standards Model Number: Unit Weight Dimensions (W x L x H):

Power Quality Monitoring and Power Metering Tutorial

PQ-Box 100 Network Analyzer for Low-, Medium- and High-Voltage Networks

E N G I N E E R I N G M A N U A L

Power Quality Evaluation of Electrical Distribution Networks

ZITARES NCD FX-30 Non-SELV (isolated), constant current control gear, 1-channel, dimmable

Reliability and Power Quality Indices for Premium Power Contracts

The University of New South Wales. School of Electrical Engineering and Telecommunications. Industrial and Commercial Power Systems Topic 9

Smart Energy & Power Quality Solutions. Portable energy measurement devices COMPACT FLEXIBLE PRECISE

POWER QUALITY MONITORING - PLANT INVESTIGATIONS

POWER QUALITY SPECIFICATIONS AND GUIDELINES FOR CUSTOMERS ENGINEERING STANDARDS CITY OF LETHBRIDGE ELECTRIC

DSR120 Series. xxx Series. 120 Watts. AC-DC Power Supplies. Models & Ratings. Mechanical Details

TABLE OF CONTENTS. 1. General Description of EUT General Information of Test Conducted Emission Tests 7-10

Fluke 3540 FC Three-Phase Power Monitor

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

Interruptions: Voltage event where the effective value is below 10 % (or 1 % according to criteria used) of the declared nominal voltage.

AC CURRENT GENERATOR POC-6000 (current from 0 to 1000 ARMS)

Fluke 3540 FC Three-Phase Power Monitor

Table 6.1 Fault Code List Code indication (Note 3)

Constant current LED Drivers For outdoor use

Overvoltage and undervoltage. Dr Audih 1

Voltage Sags Evaluating Methods, Power Quality and Voltage Sags Assessment regarding Voltage Dip Immunity of Equipment

Capacitor overvoltage protection function

Microgrid Protection

Power quality Harmonics up to 40th harmonic Rotary field components Distortion factor THD-U / THD-I

TEST SUMMARY. Prüfbericht - Nr.: Test Report No.: Seite 2 von 27. Page 2 of 27

LED Driver Compact fixed output 4,5 83,5 93. Ordering data. Type

OPERATING MANUAL POWER QUALITY ANALYZER PQM-707

TEST REPORT DIN V VDE V :2006 Automatic disconnecting device

Introduction to Harmonics and Power Quality

Minimizing Plant Interruption Caused by Line Disturbances Using Active Voltage Conditioners

Suppliers' Information Note. BT Metallic Path Facility. Interface Description

SAFETY ASPECTS AND NOVEL TECHNICAL SOLUTIONS FOR EARTH FAULT MANAGEMENT IN MV ELECTRICITY DISTRIBUTION NETWORKS

UNDERSTANDING POWER QUALITY

LB115S 115W Single Output

Medical Safety Approvals (-M versions) Industrial Heavy Duty Terminals. Output Power up to 1500 W. High Power Density - 18W/in 3

Company Directive STANDARD TECHNIQUE: SD1E/2. Technical Requirements for Customer Export Limiting Schemes

Power Quality Analyzer / High Frequency Recorder

Transcription:

EN50160 Individual Report Summary Power Frequency (x.1) Supply Voltage Variations (x.3.x) Rapid Voltage Changes (x.4.1) Flicker (x.4.2) Supply Voltage Dips (x.5) Short Interruption of Supply Voltage (x.6) Long Interruption of Supply Voltage (x.7) Temporary power frequency overvoltage (x.8) Supply Voltage Unbalance (x.10) Harmonic Voltage (x.11) Mains Signaling Voltage (x.13) Fail Fail Fail Meter Name Weekly report for 1/15

EN50160 (2007) Report Details Meter Type Nexus 1500 Meter Name Number Runtime Firmware 4.0000 Profile CRC 0xCE3F Profile Update Time 2014-08-08 20:12:48 Hookup Wye Supply Type Low Voltage Synchronous Connection No Nominal Voltage 230v Voltage Phase to Neutral Full Scale 230.000 Voltage Phase to Phase Full Scale 398.000 Mains Signaling Threshold 100.00 Phase AE Over-voltage Threshold 120.00 Phase BE Over-voltage Threshold 120.00 Phase CE Over-voltage Threshold 120.00 Allowed Long Interruptions in a Year 0 Rapid Voltage Change Source 10/12 cycles updated RMS Unbalance Upper Limit 2% Voltage A Dip Concern 10% Voltage B Dip Concern 10% Voltage C Dip Concern 10% Source Data Version 1 Report Type Weekly Report Date Range 2014-08-12 to 2014-08-17 Meter Name Weekly report for 2/15

Section x.1 Power Frequency (Not Synchronized) Under normal operating conditions for a non-synchronized system, the mean value of the fundamental frequency measured over 10 seconds shall be within ±2% of the nominal frequency for 95% of a week, and within ±15% for 100% of the year. This report gives the results over the course of the specified period. Zone Required Ac tual Result ±2% 95% 100.00% ed ±15% 100% 100.00% ed Meter Name Weekly report for 3/15

Section x.3.x Supply Voltage Variations Supply voltage shall vary no more than ±10% of Un for 95% of the week. The voltage must be within +10%/-15% of Un all of the time. Situations like those arising from faults or voltage interruptions, the circumstances of which are beyond the reasonable control of the parties, are excluded. Zone Required Volts A Volts B Volts C ±10% 95% 100.00% 100.00% 100.00% -15% to 10% 100.00% 100.00% 100.00% Meter Name Weekly report for 4/15

Section x.4.1 Rapid Voltage Changes A rapid voltage change of the supply voltage is mainly caused either by load changes in network users' installations, or by switching in the system. Under normal operating conditions, a rapid voltage change generally does not exceed ±5% Un, but a change of up to ±10% Un with a short duration might occur some times per day in some circumstances. Note: A negative voltage change resulting in a voltage less than 90% Un is considered a supply voltage dip. Note: The results displayed for ±10% Un are over the course of the week, and do not represent a single day. 7 ±10% changes are allowed in one week. Fail Zone Required Volts A Volts B Volts C ±5% 100,00% 100,00% 100,00% ±10% 7 2 1 5 > ±10% 0 0 1 6 Meter Name Weekly report for 5/15

Section x.4.2 Flicker Flicker is the impression of unsteadiness of visual sensation induced by a light stimulus whose luminance or spectral distribution fluctuates with time. Under normal operating conditions, during a period of one week, the long term flicker (PLT) severity caused by voltage fluctuations should be <= 1 for 95% of the time. Zone Required Volts A Volts B Volts C <= 1 95% 100,00% 98,48% 96,97% > 1 0,00% 1,52% 3,03% Meter Name Weekly report for 6/15

Section x.5 Supply Voltage Dips A Supply Voltage Dip is a sudden reduction of the supply voltage to a value between 90% and 1% of the declared voltage Uc, followed by a recovery after a short period of time. Fail Under normal operating conditions, the expected number of voltage dips in a year may be from a few tens up to one thousand. The majority of voltage dips have a duration less then 1s and a retained voltage greater then 10%. However, voltage dips with greater depth and duration can occur infrequently. Zone Volts A Volts B Volts C 1% to 10% 0 0 2 10% to 15% 0 0 1 15% to 20% 0 0 0 20% to 30% 0 0 0 30% to 40% 0 0 0 40% to 50% 0 0 0 50% to 60% 0 0 0 60% to 70% 0 0 0 70% to 85% 0 0 0 85% to 90% 0 1 2 Meter Name Weekly report for 7/15

Section x.6 Short Interruption of Supply Voltage An Interruption of Supply Voltage is a condition in which the voltage at the supply terminals is lower than 1% of the declared voltage Uc. A Short Interruption is defined as an event which lasts for less than 3 minutes. Under normal operating conditions, the annual occurence of short interruptions ranges from a few tens to several hundreds. The duration of approximately 70% of the Short Interruptions may be less than one second. Zone Required Volts A Volts B Volts C < 1sec 0 0 0 1sec to 3min 0 0 0 Meter Name Weekly report for 8/15

Section x.7 Long Interruption of Supply Voltage An Interruption of Supply Voltage is a condition in which the voltage at the supply terminals is lower than 1% of the declared voltage Uc. A Long Interruption is defined as an event which lasts for more than 3 minutes. Under normal operating conditions, the annual occurence of long interruptions ranges from 10 to 50, depending on the area. This location is allowed up to 0 long interruptions per year. Zone Required Volts A Volts B Volts C > 3min 0 0 0 0 Meter Name Weekly report for 9/15

Section x.8 Temporary Power Frequency Overvoltage A temporary power frequency overvoltage generally appears during a fault in the public distribution network, or in a network user's installation, and disappears when the fault is cleared. Under these conditions, the overvoltage may reach the value of the phase-to-phase voltage, due to a shift of the neutral point of the three-phase voltage system, the actual value depending upon the degree of load unbalance, and the remaining impedance between the faulty conductor and earth. Fail The duration of the event is limited by the time taken for protection to clear the fault, typically no more than 5 seconds. Zone Required Vne Vae Vbe Vc e < 1sec 0 0 0 0 1sec to 5sec 0 0 0 1 > 5sec 0% 1 0 1 3 Meter Name Weekly report for 10/15

Section x.10 Supply Voltage Unbalance Under normal operating conditions, during each period of one week, 95% of the 10 minute mean RMS values of the negative phase sequence component (fundamental) of the supply voltage shall be within the range of 0% to 2% of the positive phase sequence component (fundamental). Zone Required Ac tual Result 0% to 2% 95% 99,88% ed > 2% 0,13% ed Meter Name Weekly report for 11/15

Section x.11 Harmonic Voltage Under normal operating conditions, during each period of one week, 95% of the 10 min mean RMS values of each individual harmonic voltage shall be less than or equal to the limit value given in the results table. Additionally, the THD of the supply voltage (including all harmonics up to the 40th order) shall be less than or equal to 8%. Volts A Harmonic Summary Zone Required Limit % Out THD 0% 8% 0,00% 2nd <= 5% 2% 0,00% 3rd <= 5% 5% 0,00% 4th <= 5% 1% 0,00% 5th <= 5% 6% 0,00% 6th <= 5% 0.5% 0,00% 7th <= 5% 5% 0,00% 8th <= 5% 0.5% 0,00% 9th <= 5% 1.5% 0,00% 10th <= 5% 0.5% 0,00% 11th <= 5% 3.5% 0,00% 12th <= 5% 0.5% 0,00% 13th <= 5% 3% 0,00% 14th <= 5% 0.5% 0,00% 15th <= 5% 0.5% 0,00% 16th <= 5% 0.5% 0,00% 17th <= 5% 2% 0,00% 18th <= 5% 0.5% 0,00% 19th <= 5% 1.5% 0,00% 20th <= 5% 0.5% 0,00% 21st <= 5% 0.5% 0,00% 22nd <= 5% 0.5% 0,00% 23rd <= 5% 1.5% 0,00% 24th <= 5% 0.5% 0,00% 25th <= 5% 1.5% 0,00% Meter Name Weekly report for 12/15

- Volts B Harmonic Summary Zone Required Limit % Out THD 0% 8% 0,00% 2nd <= 5% 2% 0,00% 3rd <= 5% 5% 0,00% 4th <= 5% 1% 0,00% 5th <= 5% 6% 0,00% 6th <= 5% 0.5% 0,00% 7th <= 5% 5% 0,00% 8th <= 5% 0.5% 0,00% 9th <= 5% 1.5% 0,00% 10th <= 5% 0.5% 0,00% 11th <= 5% 3.5% 0,00% 12th <= 5% 0.5% 0,00% 13th <= 5% 3% 0,00% 14th <= 5% 0.5% 0,00% 15th <= 5% 0.5% 0,00% 16th <= 5% 0.5% 0,00% 17th <= 5% 2% 0,00% 18th <= 5% 0.5% 0,00% 19th <= 5% 1.5% 0,00% 20th <= 5% 0.5% 0,00% 21st <= 5% 0.5% 0,00% 22nd <= 5% 0.5% 0,00% 23rd <= 5% 1.5% 0,00% 24th <= 5% 0.5% 0,00% 25th <= 5% 1.5% 0,00% Meter Name Weekly report for 13/15

- Volts C Harmonic Summary Zone Required Limit % Out THD 0% 8% 0,00% 2nd <= 5% 2% 0,00% 3rd <= 5% 5% 0,00% 4th <= 5% 1% 0,00% 5th <= 5% 6% 0,00% 6th <= 5% 0.5% 0,00% 7th <= 5% 5% 0,00% 8th <= 5% 0.5% 0,00% 9th <= 5% 1.5% 0,00% 10th <= 5% 0.5% 0,00% 11th <= 5% 3.5% 0,00% 12th <= 5% 0.5% 0,00% 13th <= 5% 3% 0,00% 14th <= 5% 0.5% 0,00% 15th <= 5% 0.5% 0,00% 16th <= 5% 0.5% 0,00% 17th <= 5% 2% 0,00% 18th <= 5% 0.5% 0,00% 19th <= 5% 1.5% 0,00% 20th <= 5% 0.5% 0,00% 21st <= 5% 0.5% 0,00% 22nd <= 5% 0.5% 0,00% 23rd <= 5% 1.5% 0,00% 24th <= 5% 0.5% 0,00% 25th <= 5% 1.5% 0,00% Meter Name Weekly report for 14/15

Section x.13 Mains Signaling Voltage In some countries the public distribution networks may be used by the public supplier for the transmission of signals. Over 99% of a day, the 3 second mean of the signal voltage shall be less than or equal to the mains signaling threshold. The Mains Signaling Threshold is 100,00% of Un, or 230V. Zone Required Vae Vbe Vc e <= 100% Un 99% 100,00% 100,00% 100,00% > 100% Un <= 1% 0,00% 0,00% 0,00% Meter Name Weekly report for 15/15