Products for High Voltage Application. AT35, AT38, AT41 Indoor current transformer for oil-immersed power transformers

Similar documents
AT Current Instrument Transformer Instructions for installation, use and maintenance

MEDIUM VOLTAGE PRODUCT. TPE 6x.xx Indoor supporting current transformers

Medium Voltage Products. KECA 80 C85 Indoor current sensor

MEDIUM VOLTAGE PRODUCT. TJP 5.x Indoor voltage transformers

MEDIUM VOLTAGE PRODUCT. PARAMETERS GUIDE How to specify the indoor instrument transformers correctly

MEDIUM VOLTAGE PRODUCT. KOKM Cable current instrument transformers Instruction for Installation, use and maintenance

MEDIUM VOLTAGE PRODUCT. TJP 6.1, TJP 6.2 Indoor voltage transformers

PRODUCT FOR HIGH VOLTAGE APPLICATION. Current transformers for Gasinsulated. Instructions for installation, use and maintenance

MEDIUM VOLTAGE PRODUCTS. KEVA C Indoor voltage sensors for Cellpack separable connectors

KEVCY 24 RE1; KEVCY 24 RF1 Indoor combined sensor; Indoor voltage sensor

KEVA B Indoor voltage sensor

MEDIUM VOLTAGE PRODUCT. TJP 7.x Indoor voltage transformers

Instrument transformers for indoor applications. Product overview. Instrument transformers for indoor applications.

RING CORE CURRENT TRANSFORMERS FOR LOW VOLTAGE TYPE AOS USER MANUAL

SPECIFICATION FOR STEP UP TRANSFORMER 0.415/11Kv and (630KVA & 1000KVA)

ELECTRICAL NETWORKS SPECIFICATION TECHNICAL SPECIFICATION FOR A 230V/110V AND 400V/110V TRANSFORMER

MEDIUM VOLTAGE PRODUCTS. KEVA C Indoor voltage sensors

Capacitive voltage transformers

Current / residual current and voltage transformers. Current / residual current and voltage transformers

Current and Voltage (potential) Instrument transformers Instruction for installation, use and maintenance

1/23/2003. Sensor presentation

36kV VOLTAGE TRANSFORMERS (OUTDOOR TYPE)

Enhanced Quality with a Touch of Style

Capacitive voltage transformers

World-Class Accuracy & Measurement Range (40 Conventional Models)

Content. 1. Dimensiong of CT s. 2. Error definitions. 3. General design aspects. 4. Linear cores. Certified acc. to ISO 9001/14001, SN EN 45001

P2 H2 NAMEPLATE 6 HOLES M8-10 M SCREW S1 1S2 1S3 X1 X2 X3 PARALLEL HIGH RATIO

Arc Suppression Coils

Measuring current transformers of the W, W series

Combined Instrument Transformers. Types IVOKT and TMC

T-Line, current transformers

Powered by technology...driven by service CURRENT TRANSFORMERS. Multifunction Meters. Transducers & Isolators. Temperature Controllers

Inductive Voltage Transformers. Types VEOT and VEOS

3. COMBINED TRANSFORMERS Oil-paper insulation

Measuring current transformers of the W AB(P) series

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

Current Transformers. Type OSKF

Capacitive level meters CLM 40 INSTRUCTIONS MANUAL. průmyslová elektronika

Status Date Prepared Reviewed Endorsed Approved

OIL-IMMERSED ARC-SUPPRESSION COILS

CONTENTS Page 1 INTRODUCTION SUPPLEMENTARY INSTRUCTIONS TO BOOK 3 ELECTRICAL INSTALLATION Section Page 1 INTRODUCTION The cable supplied with your Mag

Ritz Instrument Transformers GmbH. Welcome

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

Smart Termination TECHNICAL SPECIFICATIONS CURRENT VOLTAGE INSTRUMENTRANSFORMER

Power Voltage Transformers for Air Insulated Substations. THE PROVEN POWER.

CABLE CURRENT TRANSFORMERS types: KOLMA, KOLA, KOKM, KORI, KOKU, KODI, KOLT. Catalogue

Summation current transformers, type KSU/SUSK

The Best Relaytion. Cradle Relay W Rev. B EC-JM ECOC: JM10 1. Aug. 04

MESP TECHNICAL SPECIFICATION FOR AN ESSENTIAL SERVICES SUPPLY STEP UP TRANSFORMER

Data Sheet. Summation Current Transformer. RISH SUMMATION CT : RISH XMER Sigma. RISH XMER Sigma. Page 1 of 5 00 / 1213

For the electronic measurement of current: DC, AC, pulsed..., with galvanic separation between the primary and the secondary circuit.

The Best Relaytion. Cradle Relay S Rev. B EC-JM ECOC: JM10 1. Aug. 04

Wind Direction Transmitter - compact - GMR, analogue output xxx xxx

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

Data Sheet. Summation Current Transformer OMEGA SUMMATION CT : SIGMA SERIES. Page 1 of 5 00 / 1213

COMBINED METERING TRANSFORMERS (OUT DOOR TYPE) FOR 11kV & 33kV SYSTEMS

Wind Transmitter - compact

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI

DATA SHEET FOR LIGHTING TRANSFORMER APPD. BY VDV PROJECT NO

Safety switches with slotted hole lever

Resistive capacitive voltage divider

Ohmic Voltage Sensor GSER 16

SPECIFICATION No SS-135/ kv METAL OXIDE SURGE ARRESTERS WITHOUT GAPS

Title: Southern States Type SLS Smart Sectionalizer Solid Dielectric Three Phase Sectionalizer. Product Specification Guide TABLE OF CONTENTS

NPS/002/016 Technical Specification for 33 kv Cable Joints and Terminations

50-SDMS-01 SPECIFICATIONS FOR

Data Sheet for Precision Potentiometer

TECHNICAL SPECIFICATION OF ELECTRICAL MATERIALS CT & PT GROUP C

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

INSTRUMENT TRANSFORMERS INSTRUMENT TRANSFORMERS OUTDOOR TYPES

User s Manual For CT Model IMB

Group F : Sl. No. - 1) 33/0.403 KV, 100 KVA Station Transformer GUARANTEED & OTHER TECHNICAL PARTICULARS. Table : A

Commissioning Manual Distribution Transformers - Three-phase Oil Filled

Wind Transmitter compact xx

Distribution transformers Part 2 Ground mounted transformers not closecoupled

COMPANY PROFILE... 1 QUALITY CERTIFICATES... 2 APPLICATIONS... 3

TRANSFORMER TECHNOLOGY GPT

The Best Relaytion. Cradle Relay N Rev. B EC-JM ECOC: JM10 1. Aug. 04

SPECIFICATION GUIDE. ABB Power Technology, S.A. Zaragoza, SPAIN. ABB Power Technologies Distribution Transformers

WDM-135A (2-wire type) WDM-136A (4-wire type) CONDUCTIVITY TRANSMITTER. Functions Features. Structure diagram. 10/ cm (note 3) 2-wire system

012: 2015 CEB SPECIFICATION GALVANIZED STEEL WIRE (EXCEPT SHIELDING WIRE FOR TOWER LINE APPLICATION)

5-step-switch for adjustment of sensitivity (switching threshold) LED (super-bright, yellow) for switching state indication.

Wiring ducts Easily allows for organization, pulling and separation of cables

Reactor and inductor are names used interchangeably for this circuit device.

Your safety first! This is the reason why our manual begins with the following guidelines:

Utility Systems Technologies, Inc. Sag Fighter. Deep Voltage Sag Protection:

DRIVIA cabinets LIMOGES Cedex France 1. DESCRIPTION, USE 3. DIMENSIONS 2. RANGE, CAT. NO. EQUIVALENCE TABLE

5-pole M12 connector. Connecting cable: cab-m12/5-g-2m. LED (red) for dirt accumulation indication

Cast resin transformers HARMONY TM

Onsite Mobile AC High Voltage Test System

Overtravel of 3.5 mm max. Power source DC D5C-1DS0 D5C-1DP0 D5C-1DA0 AC D5C-1AS0 D5C-1AP0 D5C-1AA0 Antenna only D5C-00S0 D5C-00P0 D5C-00A0

Advanced Test Equipment Rentals ATEC (2832) CP RC. Resonance circuit for GIS testing

CDV 22, 62. Voltage Controlled Overcurrent Relay GRID PROTECTION

Liquid-Filled Transformers

Measuring current transformer for universal measuring devices

Technical Specification For 33 KV, Single Phase, Dead Tank Type Out Door Current Transformer Of Different Ratio

Transformers, Power Supply Units and Socket Outlets

POTENTIAL TRANSFORMER

Type VDG 13 Undervoltage Relay

(

Transcription:

Products for High Voltage Application AT35, AT38, AT41 Indoor current transformer for oil-immersed power transformers

Technical parameters Value Highest voltage for equipment 1.2 kv Power frequency voltage, 1 min. 6 kv Rated primary current Up to 10 000 A (*) Rated short-time thermal current Up to 100 ka/1s Rated dynamic current Up to 120 ka Type Circle diameter of fixing holes [mm] AT41-650 619 AT41-750 720 AT41-870 837 AT41-970 940 AT41-1055 1 025 Fixing Max weight device [kg] M16 1 200 (*) Applicable for AT41 only. For AT35 and AT38 is rated primary current up to 5 000 A. Other parameters on request. Description AT transformers type have a frame construction and no primary winding. Under operating conditions, the bushing insulator, which is the main current transformer insulation, also serves as the primary winding. The secondary windings are evenly wound on the circumference of the toroidal core. AT35 and AT41 are a metal design with aluminum flanges and stainless steel fasteners and second one AT38 is an oil-absorbing design with laminated pressboard HDLC and composite fasteners. There are placed a secondary coils between flanges. The flanges and fasteners provide mechanical support. Operating temperature is up to 120 C. There are two subtypes and eleven different dimensions for metal design and eight different dimensions for oil-absorbing design. On both designs there is a major parameter outer diameter of flanges. Others as inner diameter and height are customized to depend on demand. The individual types of the oil-absorbing design transformer AT38: Type AT38-310 270 AT38-380 340 AT38-410 370 AT38-480 440 AT38-510 470 AT38-560 520 AT38-660 620 AT38-760 720 AT38-880 840 Circle diameter of fixing holes [mm] Fixing device M16 glass fiber stud Termination of the secondary winding Max weight [kg] 600 The secondary windings are designed for metering or protection purposes. Unused winding have to be earthed during the transformer operation (unused short-circuited also). Compliance with standards The transformers are designed and manufactured in conformity with the following standards: IEC 61869-1; 61869-2; IEC 60044-1; IEC 60044-6; ANSI/IEEE C57.13; GOST 7746-2001; Additional national standards and regulations on request. Fig. 1. The cables terminated by an end sleeve (cable section 6 mm 2 ) The transformer can be installed by authorized person only and needs to comply with instructions for installation, use and maintenance. Individual types The individual types of the metal design transformers AT35 and AT41: Type Circle diameter of fixing holes [mm] AT35-300 269 AT35-360 331 AT35-400 370 AT35-465 433 AT35-500 470 AT35-550 520 Fixing Max weight device [kg] M12 800 Fig. 2. The cables terminated by a cable lug (cable section 35 mm 2 ) The cable termination with an end sleeve (Fig. 1.) is standardly used for a secondary outlets, whereas a cable lug (Fig. 2.) is standardly used for testing primary or screening electrodes. Other options are available on request. 2 AT35, AT38, AT41 Indoor current transformer for oil-immersed power transformers

CT type AT35-xxx AT41-xxx AT38-xxx Outer diameter/ height [mm] Up to 550/500 Up to 1055/500 Up to 880/500 Insulation level kv 1.2/6/ - rated primary current [A] Up to 5 000 Up to 10 000 Up to 5 000 rated secondary current [A] 1 5 Number of secondary coils - 6 max. Accuracy class 0.2-0.2S-0.5-0.5S-1-3-5-5P-10P-TPY 0.3-0.6-1.2-Cxxx Rated ouput [VA] 200 Accuracy limit factor/ factor security - ALF 5-50/FS 5-10 Ith rated short-time current [ka/ 1s] Up to 100 Idyn dynamic withstand current [ka] Up to 120 Frequency [Hz] 50 or 60 Rated continous thermal current [%] Up to 200 Weight [kg] Up to 800 Up to 1 200 Up to 600 Operating temperature [ C] Up to 120 Installation (ambient conditions) - Fully immersed in transformer oil Number of output leads - 30 max. NOTE: All specified technical data noted according available market request. Marking of current transformer outlets Secondary outlets are marked with label and different color. What color and label is assigned to each wire you can see in table below. test wire (measure side) test wire (earth side) screen earth secondary wire xs1(x1, Y1, Z1, U1, V1, W1) secondary wire xs2(x2, Y2, Z2, U2, V2, W2) secondary wire xs3(x3, Y3, Z3, U3, V3, W3) secondary wire xs4(x4, Y4, Z4, U4, V4, W4) secondary wire xs5(x5, Y5, Z5, U5, V5, W5) secondary wire xs6(x6, Y6, Z6, U6, V6, W6) black or white marked with M black or white marked with Ground black or white marked with Ground black and marked with core/terminal no. red and marked with core/terminal no. yellow and marked with core/terminal no. blue and marked with core/terminal no. grey and marked with core/terminal no. brown and marked with core/terminal no. Fig. 3. An example of a secondary wire marking NOTE: The transformer in the picture (Fig. 3.) is equipped with a reactor. The possibility of applying the reactor is individual and can be placed in inside or outside diameter in case of use. Indoor current transformer for oil-immersed power transformers AT35, AT38, AT41 3

Dimensional Drawings AT35, AT38, AT41 AT35 and AT41 X H X Z A B C 1000 3000 ZNAK / HODNOTA / VALUE SIGN AT35 AT41 A [mm] 300-550 650-1055 B [mm] 269-520 619-1025 C [mm] ACC. REQUIREMENTS X [mm] 17 24 H [mm] ACC. REQUIREMENTS Z M12 M16 Testing primary Secondary outlets The Length of an outlets (testing primary, secondary outlets) is optional and depends on customer request. The fixing parts are a part of a delivery, mounting parts can be ordered separately as an attachment. 4 AT35, AT38, AT41 Indoor current transformer for oil-immersed power transformers

B AT38 A C A 1000 TESTING PRIMARY M16 22.5 H 22.5 500 3000 SIGN VALUE A [mm] 310-880 B [mm] ACC. REQUIREMENTS C [mm] 270-840 H [mm] ACC. REQUIREMENTS Testing primary Screening electrodes Secondary outlets The Length of an outlets (testing primary, secondary outlets) is optional and depends on customer request. The fixing parts are a part of a delivery, mounting parts can be ordered separately as an attachment. Indoor current transformer for oil-immersed power transformers AT35, AT38, AT41 5

Contact us ABB s.r.o. EPMV Brno Videnska 117, 619 00 Brno, Czech Republic Tel.: +420 547 152 021 +420 547 152 614 Fax: +420 547 152 626 E-mail: info.ejf@cz.abb.com 1VLC000752 rev. -, em 2016.04.19 www.abb.com The data and illustrations are not binding. We reserve the right to make changes without notice in the course of technical development of the product. Copyright 2016 ABB. All rights reserved.