SIMATIC. ET 200S distributed I/O 2AI I 4WIRE HS analog electronic module (6ES7134-4GB62-0AB0) Preface. Properties 1. Parameters 2.

Similar documents
SIMATIC. ET 200S distributed I/O 2AI U HS analog electronic module (6ES7134-4FB52-0AB0) Preface. Properties 1. Parameters 2.

SIMATIC. ET 200S distributed I/O 2AI U HF analog electronic module (6ES7134-4LB02-0AB0) Preface. Properties 1. Parameters 2.

Analog electronic module SIMATIC. ET 200S distributed I/O Analog electronic module 2AI TC ST (6ES7134-4JB01-0AB0) Preface. Properties.

SIMATIC. ET 200S distributed I/O Analog electronic module 4AI TC ST (6ES7134-4JD00-0AB0) Preface. Properties 1. Parameters 2.

Digital electronic module 4DO DC24V/2A HF (6ES7132-4BD30-0AB0) SIMATIC

Analog input module AI 8xU BA (6ES7134-6FF00-0AA1) SIMATIC. ET 200SP Analog input module AI 8xU BA (6ES7134-6FF00-0AA1) Preface. Documentation guide 1

Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) SIMATIC. ET 200SP Analog input module AI 2xI 2/4-wire ST (6ES7134-6GB00-0BA1) Preface

Programming restrictions when operating SM 331; AI 8 x RTD with PROFIBUS masters which only support DPV0.

Analog input module. AI 2xU/I 2-/4-wire HF (6ES7134-6HB00-0CA1) SIMATIC. ET 200SP Analog input module AI 2xU/I 2-/4-wire HF (6ES7134-6HB00-0CA1)

SIMATIC ET 200SP. Digital input module DI 8xNAMUR (6ES7131-6TF00-0CA0) Manual. Answers for industry.

SIMATIC. ET 200SP Analog Input Module AI 4xU/I 2-wire ST (6ES7134-6HD01-0BA1) Preface. Documentation guide. Product overview.

Analog Input Module. AI 4xU/I/RTD/TC ST (6ES7531-7QD00-0AB0) SIMATIC. S7-1500/ET 200MP Analog Input Module AI 4xU/I/RTD/TC ST (6ES7531-7QD00-0AB0)

SIMATIC. ET 200SP Analog Input Module AI 4xI 2-/4-wire ST (6ES7134-6GD01-0BA1) Preface. Documentation guide. Product overview.

6.6 Analog input module SM 331; AI 8 x 13 Bit; (6ES7331-1KF02-0AB0)

SIMATIC Vision Sensor SIMATIC VS130-2 and VS 130-2vcr

General information. CiR - Configuration in RUN

SIMATIC. ET 200SP Analog input module AI 2xU/I 2-/4-wire HS (6ES7134-6HB00-0DA1) Preface. Documentation Guide. Product overview.

13 A. Temperature regulator FM SIMATIC. S7-300 Temperature regulator FM Preface. Product Overview

SIMATIC. S7-1500/ET 200MP Analog input module AI 8xU/I/RTD/TC ST (6ES7531-7KF00-0AB0) Preface. Documentation guide. Product overview.

Product type designation. General information. CiR - Configuration in RUN. Supply voltage. Input current

SIMATIC Ident RFID systems ANT 3 Compact Operating Instructions

Product type designation. General information. Supply voltage

SIMATIC. S7-1500/ET 200MP Analog Input/Output Module AI 4xU/I/RTD/TC/ AQ 2xU/I ST (6ES7534-7QE00-0AB0) Preface. Guide to documentation

SIMATIC. ET 200B Distributed I/O Station. Preface, Contents. System Overview. Technical Description. Mechanical and Electrical Installation

Product Information. Release 3 4 SIMATIC ET 200S. 4DI UC V High Feature Digital Electronic Module

SIMATIC. S7-1500/ET 200MP Analog input module AI 8xU/I/RTD/TC ST (6ES7531-7KF00-0AB0) Preface. Documentation guide. Product overview.

Positioning SIMATIC. ET 200S Positioning. Preface 1 1STEP 5V. 1PosUniversal. Operating Instructions 06/2010 A5E

General information. CiR - Configuration in RUN

SIMATIC. S7-1500/ET 200MP Analog Input Module AI 4xU/I/RTD/TC ST (6ES7531-7QD00-0AB0) Preface. Guide to documentation. Product overview.

Technology module TM Pulse 2x24V (6ES7138 6DB00 0BB1) SIMATIC ET 200SP (6ES7138 6DB00 0BB1) Preface. Documentation guide.

SIMATIC. ET 200SP HA Analog input module AI 16xTC/ 8xRTD 2-/3-/4-wire HA (6DL1134-6JH00-0PH1) Security information 1. Product overview 2.

SIMATIC Ident. RFID systems SIMATIC RF615A. Characteristics 1. Ordering data. Installing and mounting. Connecting the antenna 4

SINAMICS drives SINAMICS DCM. DC converters from 6 kw to 2500 kw for variable-speed direct-current drives

SINVERT. Technical requirements for medium-voltage transformers for use with SINVERT central inverters. Application manual 04/2012

General information. Supply voltage

6ES7314-6BH04-0AB0. STEP7 as of V5.5 + SP1 or STEP 7 V5.3 + SP2 or higher with HSP 204

Product type designation. General information. Hardware product version 01. Firmware version V2.6. Engineering with. update.

CPU 314C-2 PTP. Function

SIMATIC Ident. RFID systems SIMATIC RF200 IO-Link V1.1. Introduction 1. Description. System overview. Planning an RF200 IO-Link system 4

SIMATIC Ident RFID systems SIMATIC RF310R special version Scanmode Compact Operating Instructions

FM 355 CONTROLLER MODULE

SIMATIC. S7-1500/ET 200MP Technology Module TM PTO 4 (6ES7553-1AA00-0AB0) Preface. Documentation guide. Product overview.

General specifications and features

SINAMICS drives. SINAMICS DCM as a DC voltage source. Application. Answers for industry. Edition 01/2014

External brake resistor AX2090-BW5x

FM COUNTER MODULE

FM COUNTER MODULE

Manual. VIPA System 100V EM - Expansion modules 134-4Ex. Order No.: VIPA HB100E_EM Reference: RE_134-4Ex Rev. 08/23

2A (recommended) Power loss

SIMATIC RTLS. Localization systems SIMATIC RTLS PCB OEM AX (6GT2700-8DF00-0AX0) Device manual 10/2018 C79000-G8976-C518-01

FM HIGH-SPEED BOOLEAN PROCESSOR

6ES7214-1AG31-0XB0. General information Engineering with. Supply voltage 24 V DC Yes permissible range, upper limit (DC)

Original operating instructions Fail-safe inductive sensor GG507S / / 2013

Manual SIMATIC ET 200SP. Analog input module AI Energy Meter 400VAC ST (6ES7134-6PA01-0BD0) Edition. 10/2017 support.industry.siemens.

Data sheet VIPA CPU 314SC DPM (314-6CG23)

EP-5111, EP-5112, EP-5212, EP-5261, EP-5311, EP-5422, EP-5442

Data sheet CPU 313SC (313-5BF13)

Parallel. Parallel. data transmission. Technical Information TR - ECE - TI - GB /05/2016

Data sheet CPU 013C (013-CCF0R00)

SINAMICS DCM. DC converter Application - 12-pulse parallel connection with decoupled interphase transformer. Introduction 1

FM COUNTER MODULE

Original operating instructions Fail-safe inductive sensor GG507S

8V General information. 2 Order data 8V

MINI MCR-SL-UI-f(-SP)

SIMATIC S7-1200, CPU 1212C, COMPACT CPU, DC/DC/DC, ONBOARD I/O: 8 DI 24V DC; 6 DO 24 V DC; 2 AI 0-10V DC, POWER SUPPLY: DC

GE Fanuc IC695ALG312. Rx3i PacSystem

VIPA System SLIO. SM-AIO Manual. HB300 SM-AIO en Analog signal modules - SM 03x.

Original operating instructions Fail-safe inductive sensor GM504S / / 2010

SIPLUS SM 1234 ANALOG INPUT/OUTPUT MODULE

PU202 Level converter & encoder signal generator without potential separation

SINAMICS. OALINK Open Application Link. Communication between two Control Units via DRIVE-CLiQ. Function Manual. Answers for industry.

PACSystems* RX3i. Isolated RTD Input Module, 8 Channels, IC695ALG508-CA. Module Features. GFK-2501C November 2012

This data sheet is only valid in association with the IL SYS INST UM E user manual.

SIMATIC. EM 148-FC Frequency Converter A B. Preface, Contents. Product Overview. Wiring. Manual

Data sheet CPU 314ST/DPM (314-6CF02)

8V General information. 2 Order data 8V

1800 Series Attachable Loop-Powered Digital Indicators Operating Manual

SENTRON. Power Monitoring Device SENTRON PAC4200. Introduction 1. Safety instructions 2. Description 3. Operation planning 4.

SIMATIC S7-300 Function modules

The Allen-Bradley Servo Interface Module (Cat. No SF1) when used with the Micro Controller (Cat. No UC1) can control single axis

Original operating instructions Fail-safe inductive sensor GM705S

X20(c)AI General information. 2 Coated modules. 3 Order data. X20(c)AI4622

F2-04AD-1, F2-04AD-1L 4-Channel Analog Current Input

UniStream Uni-I/O Modules

3TK28 Safety Relays. General data. 7/70 Siemens LV

PULSE INPUT MODULE PI232/PI272 USER S MANUAL

F4-04DA-1 4-Channel Analog Current Output

Laser Measuring Device LE-200

SIMATIC ET 200SP. Motor Starter (3RK1308-0**00-0CP0) Manual. siemens.com. Edition 04/2016

MACX MCR-UI-UI-UP(-SP)(-NC)

SIMEAS-T. Operating Instructions Transducer without auxiliary power. 7KG6111 and 7KG6101. Operating Instructions

DUAL OUTPUT AC CURRENT/VOLTAGE TRANSDUCER

POINTAX 6000L2 Point Recorder

2CSG445013D0201 M2M PROFIBUS. Profibus DP interface user manual M2M ABB

C-Bus 8 Channel Low Voltage Relay

F4 08DA 2 8-Channel Analog Voltage Output

Strain Gauge Measuring Amplifier BA 662

This Datasheet is for the IC693ALG220. Analog Voltage Input - 4 Channel.

PACSystems* RX3i IC695MDL765

MRS ELECTRONIC DATASHEET CAN I/O AND PLC DESCRIPTION TECHNICAL DATA REGULATORY APPROVALS AND TESTING SOFTWARE/PROGRAMMING

Transcription:

SIMATIC ET 200S distributed I/O SIMATIC ET 200S distributed I/O 2AI I 4WIRE HS analog electronic module (6ES7134-4GB62-0AB0) Manual Preface Properties 1 Parameters 2 Diagnostics 3 Analog value representation 4 Connecting 5 01/2008 A5E01076124-02

Safety Guidelines Safety Guidelines This manual contains notices you have to observe in order to ensure your personal safety, as well as to prevent damage to property. The notices referring to your personal safety are highlighted in the manual by a safety alert symbol, notices referring only to property damage have no safety alert symbol. These notices shown below are graded according to the degree of danger. DANGER indicates that death or severe personal injury will result if proper precautions are not taken. WARNING indicates that death or severe personal injury may result if proper precautions are not taken. CAUTION with a safety alert symbol, indicates that minor personal injury can result if proper precautions are not taken. CAUTION without a safety alert symbol, indicates that property damage can result if proper precautions are not taken. NOTICE Qualified Personnel Prescribed Usage Trademarks indicates that an unintended result or situation can occur if the corresponding information is not taken into account. If more than one degree of danger is present, the warning notice representing the highest degree of danger will be used. A notice warning of injury to persons with a safety alert symbol may also include a warning relating to property damage. The device/system may only be set up and used in conjunction with this documentation. Commissioning and operation of a device/system may only be performed by qualified personnel. Within the context of the safety notes in this documentation qualified persons are defined as persons who are authorized to commission, ground and label devices, systems and circuits in accordance with established safety practices and standards. Note the following Disclaimer of Liability WARNING This device may only be used for the applications described in the catalog or the technical description and only in connection with devices or components from other manufacturers which have been approved or recommended by Siemens. Correct, reliable operation of the product requires proper transport, storage, positioning and assembly as well as careful operation and maintenance. All names identified by are registered trademarks of the Siemens AG. The remaining trademarks in this publication may be trademarks whose use by third parties for their own purposes could violate the rights of the owner. We have reviewed the contents of this publication to ensure consistency with the hardware and software described. Since variance cannot be precluded entirely, we cannot guarantee full consistency. However, the information in this publication is reviewed regularly and any necessary corrections are included in subsequent editions. 이기기는업무용 (A 급 ) 전자파적합기기로서판매자또는사용자는이점을주의하시기바라며가정외의지역에서사용하는것을목적으로합니다. Siemens AG Automation and Drives Postfach 48 48 90327 NÜRNBERG GERMANY A5E01076124-02 P 02/2008 Copyright Siemens AG 2008. Technical data subject to change

Preface Preface Purpose of the manual This manual supplements the ET 200S Distributed I/O System Operating Instructions. General functions for the ET 200S are described in the ET 200S Distributed I/O System Operating Instructions. The information in this document along with the operating instructions enables you to commission the ET 200S. Basic knowledge requirements To understand these operating instructions you should have general knowledge of automation engineering. Scope of the manual This manual applies to this ET 200S module. It describes the components that are valid at the time of publication. Recycling and disposal Thanks to the fact that it is low in contaminants, this ET 200S module is recyclable. For environmentally compliant recycling and disposal of your electronic waste, please contact a company certified for the disposal of electronic waste. Additional support If you have any questions relating to the products described in these operating instructions, and do not find the answers in this document, please contact your local Siemens representative. http//www.siemens.com/automation/partner The portal to our technical documentation for the various SIMATIC products and systems is available at http//www.siemens.com/automation/simatic/portal The online catalog and ordering system are available at http//www.siemens.com/automation/mall Manual, 01/2008, A5E01076124-02 3

Preface Training center We offer courses to help you get started with the ET 200S and the SIMATIC S7 automation system. Please contact your regional training center or the central training center in D -90327, Nuremberg, Germany. Phone +49 (911) 895-3200. http//www.siemens.com/sitrain Technical Support You can reach technical support for all A&D projects using the support request web form http//www.siemens.com/automation/support-request Phone + 49 180 5050 222 Fax + 49 180 5050 223 For more information about our technical support, refer to our Web site at http//www.siemens.de/automation/service Service & Support on the Internet In addition to our documentation services, you can also make use of our comprehensive online knowledge base on the Internet. http//www.siemens.com/automation/service&support There you will find Our Newsletter, which constantly provides you with the latest information about your products. The right documentation for you using our Service & Support search engine. The bulletin board, a worldwide knowledge exchange for users and experts. Your local contact for Automation & Drives in our contact database. Information about on-site services, repairs, spare parts. Lots more can be found on our "Services" pages. 4 Manual, 01/2008, A5E01076124-02

Table of contents Preface... 3 1 Properties... 7 1.1...7 1.2 Compatibility with the predecessor module...12 2 Parameters... 13 2.1 Parameters...13 2.2 Parameter description...14 3 Diagnostics... 15 3.1 Diagnostics using LED display...15 3.2 Error types...16 3.3 Interrupts...17 4 Analog value representation... 19 4.1 Introduction...19 4.2 Analog value representation for measuring range with SIMATIC S7...19 4.3 Measuring ranges...20 4.4 Effect on analog value representation...22 4.4.1 Effect of the supply voltage and the operating state on analog input values...22 4.4.2 Effect of the value range on the 2 AI I 4WIRE HS analog input...22 5 Connecting... 23 5.1 Connecting measuring sensors...23 5.2 Wiring unused channels of the analog input modules...26 5.3 Using the shield connection...26 Index... 27 Manual, 01/2008, A5E01076124-02 5

Table of contents 6 Manual, 01/2008, A5E01076124-02

Properties 1 1.1 Properties 2 inputs for current measurement per channel Current-limited sensor supply (90 ma) Input ranges 4 ma to 20 ma, resolution 15 bits 0 ma to 20 ma, resolution 15 bits ± 20 ma, resolution 15 bits + sign Supports isochronous operation Minimum time for the isochronous DP cycle (TDPmin) 250 µs Minimum conversion time of the input modules (TWE) 100 µs Firmware update of electronic module is possible. Note Inputs must not be connected in series for the current measurement. Manual, 01/2008, A5E01076124-02 7

Properties 1.1 General terminal assignment Note Terminals 4, 8, A4, A8, A3 and A7 are only available at specified terminal modules. Terminal assignment for 2AI I 4WIRE HS (6ES7134-4GB62-0AB0) Terminal Assignment Terminal Assignment Notes 1 M0+ 5 M1+ 2 M0-6 M1-3 L+ 7 L+ 4 Mana 8 Mana A4 AUX1 A8 AUX1 A3 AUX1 A7 AUX1 Mn+ Input signal "+", Channel n Mn- Input signal "-", Channel n L+ Power supply for four-wire measuring transducer Mana Ground (of power module) AUX1 Protective-conductor terminal or potential bus (freely usable up to 230 VAC) Usable terminal modules Usable terminal modules for 2AI I 4WIRE HS (6ES7134-4GB62-0AB0) TM-E15C26-A1 (6ES7193-4CA50-0AA0) TM-E15S26-A1 (6ES7193-4CA40-0AA0) TM-E15N26-A1 (6ES7193-4CA80-0AA0) TM-E15C24-01 (6ES7193-4CB30-0AA0) TM-E15S24-01 (6ES7193-4CB20-0AA0) TM-E15N24-01 (6ES7193-4CB70-0AA0) Spring terminal Screw-type terminal Fast Connect 8 Manual, 01/2008, A5E01076124-02

Properties 1.1 Block diagram µ Figure 1-1 Block diagram of the 2AI I 4WIRE HS Technical specifications for 2AI I 4WIRE HS (6ES7134-4GB62-0AB0) Dimensions and weight Width (mm) 15 Weight Approx. 40 g Module-specific data Supports isochronous operation Yes Supports I&M functions Yes Number of inputs 2 Cable length Shielded Max. 200 m Parameter length 12 bytes (4 bytes when used as 6ES7134 4FB60 0AB0) Address space 4 bytes Voltages, currents, potentials Rated load voltage L+ (from the power module) 24 VDC Reverse polarity protection Yes Galvanic isolation Between channels and backplane bus Yes Between channels and load voltage L+ Yes Between the channels No Permissible potential difference Between MANA and the backplane bus (UISO) 75 V DC, 60 V AC Insulation test voltage 500 VDC Current consumption Power supply and load voltage L+ (no load) Max. 130 ma 1 Power dissipation of the module Typically 2 W Status, interrupts, diagnostics Interrupts Hardware interrupt Can be assigned parameters 2 Diagnostics function Group error display Red "SF" LED Diagnostic information readable Possible 3 Manual, 01/2008, A5E01076124-02 9

Properties 1.1 Analog value generation Measuring principle SAR (Successive Approximation Register) Cycle time/resolution Conversion time in µs (per channel) 15 Cycle time in ms (per module) 0,25 Resolution (including overrange) 4 to 20 ma/15 bit 0 to 20 ma/15 bit ± 20 ma/15 bit + sign Suppression of interference, limits of error Crosstalk between the inputs < 50 db Operational limit ± 0,3 % (in the entire temperature range, with reference to the input range) Basic error limit (operational limit ± 0,2 % at 25 C with reference to input range) Temperature error (with reference to the input ±0.01 %/K range) Linearity error (with reference to the input range) ± 0,03 % Repeatability ± 0,1 % (in steady state at 25 C with reference to input range) Sensor power supply outputs Number of outputs 2 Output voltage With load L+ (-2.5 V) Output current Rated value Permitted range Short-circuit protection 80 ma (per channel) 0 ma to 80 ma Yes, electronic Data for selecting a sensor Input range (rated value)/input resistance Current 4 to 20 ma/106 Ω 0 to 20 ma/106 Ω ± 20 ma/106 Ω Connection of the sensors For current measurement as two-wire Supported transmitter Maximum input current for current input 30 ma (destruction limit) Smoothing of the measured values Yes, can be assigned parameters in 4 steps by means of digital filtering Step None Weak Medium Strong Time constant 1 x cycle time 4 x cycle time 16 x cycle time 32 x cycle time 1 Without encoder supply voltage 2 For interface modules with process interrupt capability only 3 Parameter assignment error/ violation of low limit/ violation of high limit/ open circuit (only with 4 to 20 ma)/ process interrupt lost 10 Manual, 01/2008, A5E01076124-02

Properties 1.1 Firmware update To add functions and for troubleshooting, it is possible to load firmware updates to the operating system memory of the electronic module using STEP 7 HW Config. Note When you launch the firmware update, the old firmware is deleted. If the firmware update is interrupted or canceled, the electronic module will no longer be capable of functioning. Restart the firmware update and wait until it has completed successfully. Note If the ET 200S is operated in conjunction with an S7-300 CPU with PROFIBUS DP interface or an ET 200S Interface Module IM151-3 PN HIGH SPEED, a station failure of the ET 200S can occur during the firmware update. I&M functions and firmware update The interface modules identified in the table below (as of order number) can be used to read and write I&M data from the module and for the firmware update. Interface module IM151-1 HIGH FEATURE IM151-3 PN IM151-3 PN HIGH FEATURE IM151-3 PN FO IM151-7 CPU as of order number 6ES7151-1BA02-0AB0 6ES7151-3AA22-0AB0 6ES7151-3BA22-0AB0 6ES7151-3BB22-0AB0 6ES7151-7AA20-0AB0 Manual, 01/2008, A5E01076124-02 11

Properties 1.2 Compatibility with the predecessor module 1.2 Compatibility with the predecessor module Compatible with 4AI 2WIRE HS analog electronic module (6ES7134-4GB61-0AB0 / 6ES7134-4GB60-0AB0) If you configure the 2AI 4WIRE HS (6ES7134-4GB62-0AB0) as the predecessor module (6ES7134-4GB61-0AB0/ 6ES7134-4GB60-0AB0), it behaves compatibly. The following technical specifications of the 2AI 4WIRE HS (6ES7134-4GB62-0AB0) are set according to the predecessor module (6ES7134-4GB61-0AB0/ 6ES7134-4GB60-0AB0) Technical specifications for 2AI 4WIRE HS 6ES7134-4GB62-0AB0 configured as 6ES7134-4GB61-0AB0/ 6ES7134-4GB60-0AB0 Analog value generation Cycle time in ms (per module) 0.25 ms 1 ms Resolution (including overrange) 4 to 20 ma/15 bits 4 to 20 ma/13 bits 0 to 20 ma/15 bits 0 to 20 ma/13 bits ± 20 ma/15 Bit ± 20 ma/13 Bit Sensor selection data Smoothing of the measured values Time constant 1 x cycle time 4 x cycle time 16 x cycle time 32 x cycle time Time constant 1 x cycle time 64 x cycle time 128 x cycle time 512 x cycle time Current consumption and power loss Note the change in the current consumption and power loss of the 2AI 4WIRE HS (6ES7134-4GB62-0AB0) compared to the predecessor module (6ES7134-4GB61-0AB0/ 6ES7132-4GB60-0AB0). 12 Manual, 01/2008, A5E01076124-02

Parameters 2 2.1 Parameters Table 2-1 Parameters for analog input module 2AI I 4WIRE HS Range of values Default setting Applicability Group diagnostics (parameter Disable assignment error, internal error) Enable Diagnostics Overflow/underflow Disable Enable Diagnostics Wire break* Disable Enable Smoothing None Weak Medium Strong Hardware interrupt enable Disable Enable Type/range of measurement Deactivated 4 to 20 ma 0 ma to 20 ma ± 20 ma High limit low to high limit of the overrange Low limit Low to high limit of the nominal range * in the measuring range 4 to 20 ma only Disable Disable Disable None Disable Module Module Channel Channel Module 4 to 20 ma Channel Depending on the measuring range Depending on the measuring range Channel Channel Note If you deactivate a channel of the electronic module, you do not gain any advantages in terms of speed due to the measuring procedure. Manual, 01/2008, A5E01076124-02 13

Parameters 2.2 Parameter description 2.2 Parameter description Smoothing The individual measured values are smoothed by digital filtering. The smoothing can be adjusted in four steps, in which the smoothing factor k multiplied by the cycle time of the electronic module equals the time constant of the smoothing filter. The higher the smoothing, the greater the time constant of the filter. The following diagrams show the step response with the various smoothing factors depending on the number of module cycles. Figure 2-1 Smoothing for 2AI I 4WIRE HS (as of 6ES7134-4GB62-0AB0) Figure 2-2 Smoothing for 2AI I 4WIRE HS (6ES7134-4GB61-0AB0/ 6ES7134-4GB60-0AB0) 14 Manual, 01/2008, A5E01076124-02

Diagnostics 3 3.1 Diagnostics using LED display LED display 1 1 Batch error (red) Status and error displays Event (LED) SF On Cause No configuration or incorrect module plugged in. No load voltage.present There is a diagnostic message. Remedy Check the parameter assignment. Check the load voltage. Evaluate the diagnostics. Manual, 01/2008, A5E01076124-02 15

Diagnostics 3.2 Error types 3.2 Error types Analog input module error types Table 3-1 Error types 31D 22D 16D Error type Meaning Remedy 11111 Channel The firmware is being updated. -- temporarily Channel 0 applies to the entire unavailable module. The module does not perform any measurements during this time. 10110 Hardware interrupt lost 10000 Parameter assignment error A hardware interrupt was not detected. Module cannot use the parameter for the channel Inserted module does not match the configuration. Faulty parameter assignment. 9D 01001 Errors Internal module error (diagnostics message at channel 0 applies to the entire module) 8D 01000 Lower value limit fallen below 7D 00111 Violation of higher limit 6D 00110 Open circuit Correction or coordination of the program, process, module Correct the configuration (align actual and set configuration). Correct the parameter assignment (diagnostics wire break only for the allowed measuring range parameterized). Replace the module. Value is below the underrange. Correct the module/actuator tuning. Value is above the overrange. Correct the module/actuator tuning. Line to the encoder Correct the process wiring. interrupted. 16 Manual, 01/2008, A5E01076124-02

Diagnostics 3.3 Interrupts 3.3 Interrupts Hardware interrupt of analog input modules Figure 3-1 Structure as of Byte x+4 and Byte x+5 for hardware interrupt (analog input) Manual, 01/2008, A5E01076124-02 17

Diagnostics 3.3 Interrupts 18 Manual, 01/2008, A5E01076124-02

Analog value representation 4 4.1 Introduction Electronic modules with analog outputs With the electronic module with analog inputs, continuously variable signals, such as those occurring in temperature measurement and resistance measurement, can be acquired, evaluated, and converted to digital values for further processing. 4.2 Analog value representation for measuring range with SIMATIC S7 Analog value representation With the same nominal range, the digitized analog value is the same for input and output values. Analog values are represented in two's complement. The following table shows the analog value representation for the analog electronic modules. Table 4-1 Analog value representation (SIMATIC S7 format) Resolution Analog value Bit number 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1 0 Significance of the bits S 2 14 2 13 2 12 2 11 2 10 2 9 2 8 2 7 2 6 2 5 2 4 2 3 2 2 2 1 2 0 Sign The sign (S) of the analog value is always in bit number 15 "0" + "1" Manual, 01/2008, A5E01076124-02 19

Analog value representation 4.3 Measuring ranges Analog values The following table shows the representation of the binary analog values and the corresponding decimal and hexadecimal representation of the units of the analog values. The table below shows the 11, 12, 13, 14, and 15 bit resolutions + sign. Each analog value is entered left aligned in the ACCU. The bits marked with "x" are set to "0". Table 4-2 Analog values (SIMATIC S7 format) Resolution in bits Units Analog value Decimal Hexadecimal High byte Low byte 11+S 16 10H S 0 0 0 0 0 0 0 0 0 0 1 x x x x 12+S 8 8H S 0 0 0 0 0 0 0 0 0 0 0 1 x x x 13+S 4 4H S 0 0 0 0 0 0 0 0 0 0 0 0 1 x x 14+S 2 4H S 0 0 0 0 0 0 0 0 0 0 0 0 0 1 x 15 + sign 1 1H S 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 4.3 Measuring ranges Introduction The following tables contain the digitized analog values for the measuring ranges of the analog input modules. Since the binary representation of the analog values is always the same, these tables only compare the measuring ranges with the units. Measuring ranges for current 0 to 20 ma, 4 to 20 ma Table 4-3 SIMATIC S7 format Measuring ranges 0 to 20 ma, 4 to 20 ma Measuring range Measuring range Units Range 0 to 20 ma 4 to 20 ma Decimal Hexadecimal > 23,5178 > 22,8142 32767 7FFFH Overflow 23,5178 22,8142 32511 7EFFH Overshoot range 20,0007 20,0005 27649 6C01H 20,0000 15,0000 20,0000 16,0000 27648 20736 6C00H 5100H Nominal range 0,0000 4,0000 0 0H Negative values are not supported 3,9995. -1 FFFFH Underrange 1,1852-4864 ED00H < 1,1852-32768 8000H Underflow 20 Manual, 01/2008, A5E01076124-02

Analog value representation 4.3 Measuring ranges Current measuring range ±20 ma Table 4-4 SIMATIC S7 format Measuring range ±20 ma Measuring range ±20 ma Units Range Decimal Hexadecimal > 23,5150 32767 7FFFH Overflow 23,5150 32511 7EFFH Overshoot range 20,0007 27649 6C01H 20,0000 14,9980 27648 20736 6C00H 5100H Nominal range -14,9980-20,0000-20736 -27648 AF00H 9400H -20,0007-27649 93FFH Underrange -23,5160-32512 8100H < -23,5160-32768 8000H Underflow Measured values in the event of a wire break in relation to enabled diagnostics The following additional information applies to the current measuring range 4 to 20 ma Table 4-5 Measured values in the event of a wire break in relation to enabled diagnostics Format Parameter assignment 1 Measured values Description Decimal Hexadecimal S7 "Wire break" diagnostics enabled 32767 7FFFH "Open circuit" diagnostic message "Wire break" diagnostics disabled -32767 8000H Measured value after leaving the underrange "Overflow/underflow" diagnostics enabled "Wire break" diagnostics disabled "Overflow/underflow" diagnostics disabled 1 Measuring range limits for wire break and underflow detection At 1.185 ma "Lower limit value undershot" diagnostic message -32767 8000H Measured value after leaving the underrange Manual, 01/2008, A5E01076124-02 21

Analog value representation 4.4 Effect on analog value representation 4.4 Effect on analog value representation 4.4.1 Effect of the supply voltage and the operating state on analog input values The input values of the analog modules are dependent on the supply voltage for electronics/encoders and on the operating state of the PLC (CPU of the DP master). This is illustrated by the table below. Table 4-6 Relationship between the analog input values for the operating state of the PLC (CPU of the master) and the supply voltage L+ Operating state of the PLC (CPU of the DP master) POWER ON RUN Supply voltage L+ on ET 200S (power module) L+ present Input value of the electronic module with analog inputs (evaluation possible on the CPU of the DP master) Process values 7FFFH until first conversion after startup, or after assignment of parameters for the module is completed. POWER ON STOP L+ missing 7FFFH L+ present Process value POWER OFF - L+ missing 7FFFH L+ present - L+ missing - 4.4.2 Effect of the value range on the 2 AI I 4WIRE HS analog input The way electronic modules respond to analog inputs depends on where the input values fall within the value range. This is illustrated by the table below. Table 4-7 Response of the analog modules, depending on where the analog input value falls within the range of values Measured value within... Input value in SIMATIC S7 format Input value in SIMATIC S5 format Nominal range Measured value Measured value Over-/underrange Measured value Measured value Overflow 7FFFH End of the overshoot range +1 plus overflow bit Underflow 8000H End of the underrange -1 plus overflow bit Before setting parameters or with faulty parameters 1 7FFFH 7FFFH 22 Manual, 01/2008, A5E01076124-02

Connecting 5 5.1 Connecting measuring sensors Introduction You can connect current transmitters to the 2AI 4WIRE HS analog input modules to act as Connecting 4-wire transducers. In this chapter you will find out how to connect the measuring encoders and what to watch out for when doing so. Cables for analog signals You should use shielded and twisted-pair cables for the analog signals. This reduces the effect of interference. You should ground the shield of the analog cables at both ends. If there are differences in potential between the cable ends, an equipotential bonding current that may interfere with the analog signals will flow across the shield. If this is the case, you should only ground the shield at one end of the cable. Analog input modules The analog input modules are galvanically isolated Between the logic and backplane bus No isolation Link between MANA and central grounding point Note Ensure that this difference in potential UISO does not exceed the permitted value. If there is a possibility of exceeding the permitted value, establish a connection between terminal MANA and the central grounding point. Connecting measuring encoders to analog inputs There can be only a limited potential difference UCM (common mode) between the measuring lines M- of the input channels and the reference point of the measuring circuit MANA. To ensure that the permitted value is not exceeded, you must take different steps depending on the whether the encoders are isolated or non-isolated. The steps you have to take are described in this chapter. Manual, 01/2008, A5E01076124-02 23

Connecting 5.1 Connecting measuring sensors Abbreviations used The meanings of the abbreviations in the figures below are as follows M + Measuring line (positive) M- Measuring line (negative) MANA M Analog measuring circuit reference potential Ground connection L+ Rated load voltage 24 V DC UCM UISO Potential difference between inputs Potential difference between M- and central grounding point Isolated measuring sensors The isolated measuring sensors are not connected to the local ground potential. These can be potential-free. Depending on local conditions or interference, potential differences UCM (static or dynamic) can occur between the measuring lines M- of the input channels and the reference point of the measuring circuit MANA. In environments with a high level of EMC interference, it is advisable to connect M- to MANA in order to prevent the permissible UCM value from being exceeded. The following schematic representation illustrates the connection of isolated measuring sensors to the analog input modules. 5 ma ma 1 2 3 4 1 2 3 4 5 Logic Backplane bus Ground bus Central grounding point Isolated measuring sensors 24 Manual, 01/2008, A5E01076124-02

Connecting 5.1 Connecting measuring sensors Non-isolated measuring sensors The non-isolated measuring sensors are connected to the local ground potential. You must connect MANA to the ground potential. Depending on local conditions or interference, potential differences UCM (static or dynamic) can occur between the locally distributed measuring points. If the permitted value for UCM is exceeded, there must be equipotential bonding conductors between the measuring points. The following schematic representation illustrates the connection of non-isolated measuring sensors to an optically isolated analog input module. Connection of non-isolated measuring sensors to an optically isolated analog input module 5 1 2 4 3 1 2 3 4 5 Logic Backplane bus Ground bus Equipotential bonding conductor Non-isolated measuring sensors Operating four-wire transducers on an external voltage supply If there is galvanic isolation between the output and the supply of the measuring transducer, you can connect it to the 2AI I 4WIRE without additional connections. If there is no galvanic isolation between the output and the transmitter supply, you can only connect the transmitter to the 2 AI I 4WIRE if the reference potential of the supply voltages (24 V DC) is the same. If there is an increase in interference radiation, a connection between M- and MANA on the terminal module of the 2 AI I 4WIRE is recommended. Manual, 01/2008, A5E01076124-02 25

Connecting 5.2 Wiring unused channels of the analog input modules Sensor selection Note the following factors when selecting the sensors Length, impedance, and capacitance of the cable Reaction speed of the utilized sensors 5.2 Wiring unused channels of the analog input modules Rules Pay attention to the following instructions when wiring unused channels "Deactivate" unused input channels when assigning parameters. A deactivated channel always returns the value 7FFFH. The cycle time remains unchanged at 250 µs. 5.3 Using the shield connection Rules To prevent interference we recommend the following for analog electronic modules Use shielded wires to the sensors and actuators. Lay out the wire shields on the shield connection. Connect the shield connection to the ground bus with low impedance. Note The permitted limit values can be exceeded (up to <10%) at the measuring inputs of the electronic module in the event of cable-related HF radiation up to 100 khz. This is made necessary by the specified measuring procedure. 26 Manual, 01/2008, A5E01076124-02

Index 2 2 AI I 4WIRE HS analog electronic module Block diagram, 9 2AI I 4WIRE HS analog electronic module Properties, 7 Terminal assignment, 8 4 4-wire transducer, 25, 26 A Analog input modules Error types, 16 Analog value processing, 23 B Basic knowledge requirements, 3 M Measured value resolution, 20 Measuring encoders, 23 Measuring ranges with SIMATIC S7, 19 N Non-isolated measuring sensors, 25 R Recycling, 3 S Scope Manual, 3 Service & Support, 4 Shield connection, 26 Smoothing, 14 C Cables for analog signals, 23 Connecting measuring encoders to analog inputs, 23 T Technical Support, 4 Training center, 4 D Disposal, 3 I Internet Service & Support, 4 Isolated measuring sensors, 24 L LED display, 15 Manual, 01/2008, A5E01076124-02 27

Index 28 Manual, 01/2008, A5E01076124-02