MT372 Three-phase electronic meter with built-in modem or RS485 communication interface

Similar documents
ME162 Single-Phase Electronic Meter

ME371, MT371 Single- and Three-Phase Electronic Meters with Built-in DLC Communication Channel

ME371, MT371 Single- and Three-phase electronic meters with built-in DLC communication channel

MT174 Three-Phase Static Electricity Multi Tariff Meter with Maximum Demand Indicator and Load-profile

MT174 Three-Phase Static Electricity Multi Tariff Meter with Maximum Demand Indicator and Load-profile

MT173 Three-Phase Electronic Multi Tariff Meter with Maximum Demand Indicator

Energy Measurement and Management MT830/MT831. Three-phase electronic multi-function meter for industry. Technical Description. Version 1.

MD300 and MT300. Technical Description

E550 Series 2. Electricity Meters IEC/MID Industrial and Commercial ZMG310AR/CR. Technical Data

E550 Series 2. Electricity Meters IEC/MID Industrial and Commercial ZMG400AR/CR. Technical Data

Environmental Influences. Display. Inputs and Outputs. Electromagnetic Compatibility. Communication Interfaces. Insulation Strenght.

Introduction DIN rail mounted electricity meters

SULTANATE OF OMAN METERING AND DATA EXCHANGE CODE

INDUSTRIAL+COMMERCIAL ZMD310AT/CT TECHNICAL DATA. Measurement Accuracy. Measurement Behaviour. MID-specific data. Current (for Class B) General

INDUSTRIAL+COMMERCIAL ZMG400AR/CR, ZFG400AR/CR TECHNICAL DATA. IEC-specific data. Current. Measurement Accuracy. Measurement Behaviour.

INDUSTRIAL+COMMERCIAL ZMD400AR/CR, ZFD400AR/CR TECHNICAL DATA. Frequency. IEC-specific data. Current. Measurement Accuracy.

E650 Series 3. Electricity Meters IEC/MID Industrial and Commercial ZMD402AT/CT, ZFD402AT/CT. Technical Data

1 2 3 GridVis Pulse output 2 tariffs Modbus MID M-Bus

Energy Management Energy Meter Type EM110

PRELIMINARY DATA SHEET RI-D140. Three Phase Multifunction DIN Rail Energy Meter (MID Certified) MID

C series Product brief

MT830/MT831. Technical Description. Three-phase electronic multi-function meter for industry EAD Version 1.7,

High-set undervoltage stage with definitetime. or inverse definite minimum time (IDMT) characteristic. Low-set undervoltage stage with definitetime

RI-F200 Series. Single and Three Phase Multifunction Energy Meter. Telephone : +44 (0) Displayed Parameters

Energy Management Energy Meter Type EM111

Energy Management Energy Meter Type EM110

Energy Meters for DIN Rail Mounting Electric energy meter WS0101, WS0102,WS1102 WS0301, WS0302,WS1302

Energy Management Energy Meter Type EM112

DELTAplus. DIN Rail Mounted electricity meters. Technical Documentation

Energy Management Three-phase energy meter with output modules Type EM4-DIN

Energy Management Energy Meter Type EM340

Energy Management Energy Meter with plug-in Output Modules Type EM4-DIN

RI-D440. Three Phase easywire Multifunction DIN Rail Energy Meter. Telephone : +44 (0) Displayed Parameters

Energy Management Energy Meter GM3D

Energy Management Energy Meter Type EM21 72R Retro-Fit

MID. Energy Management Energy Meter Type EM33 DIN. Product Description. How to order EM33 DIN AV3 3 X XS PF. Type Selection EM33 DIN

Measuring centers MC7x0 series Multifunction Meter MC740

Multi-function (MI, ME, M2, M1) 2 NO (2 SPST-NO) 12 / / 400 3,000 1, / 0.3 / (5 / 5) AgNi

RISH PQM. Power Quality Monitor. Preliminary Datasheet subject to change without notice. Individual Harmonics measurement upto 56th Harmonics

ZMD405AT/CT, ZFD405AT/CT, ZMD410AT/CT, ZFD410AT/CT

RISH EM 3490 SS Kilowatt Hour Energy Meter With Rs485 RISH EM 3490 SS. Application : Product Features: Indication: Pulse Indication:

MID. Energy Management Energy Meter Type EM23 DIN. Product Description. Type Selection. How to order EM23 DIN AV9 3 X O1 PF A EM23 DIN

Technical Data Sheet. x1000. kwh R Y B

TECHNICAL DESCRIPTION THREE-PHASE SUBSTATION ELECTRONIC METERS

Energy Management Energy Analyzer Type EM210 MID

XUA1 AC Voltage and phase balance relay. (August 1996) Manual XUA1 (Revision New)

E35C. AD-FG/CG/GG Version 3.2. Technical Data. Communication Module Residential

Overcurrent Protection / 7SJ45

XUA1 - AC Voltage and phase balance relay

Flexible Counter Series in DIN size 24 x 48 mm

MID. Energy Management Energy Analyzer Type EM11 DIN. Product Description. How to order EM11 DIN AV8 1 X O1 PF. Type Selection EM11 DIN

Energy Management Energy Analyzer Type EM111

Protection components

SINGLE AND POLY-PHASE STATIC METERS

Energy Measurement and Management. ME381 and MT381 User manual

Energy Management Energy Meter GM3T E GM3T-RS485 E

ELECTRONIC SINGLE PHASE AND THREE PHASE L.V. METER SPECIFICATIONS

Supercal 531 Multi function Integrator that lives up to Your highest expectations

XU2-AC AC voltage relay. (Februar 1997) Manual XU2-AC (Revision New)

XP2-R Power and Reverse Power Relay

RISH EM 3490 DS Dual Source Energy Meter (With All Display Parameters) RISH EM 3490 DS. Application : Product Features:

DATASHEET - ETR4-70-A. Delivery program. Timing relay, 2W, 0.05s-100h, multi-function, VAC/DC, potentiometer connection

XF2 Frequency Relay. Manual XF2 (Revision A)

APL SEM 1P V2. Single phase Keypad Prepayment Energy Meter. Technical Manual

DATASHEET - ETR4-51-A. Delivery program. Technical data General. Timing relay, star-delta, 50 ms, 1W, 3-60s, VAC/DC

Multi-voltage Multi-function. Wiring diagram (without control signal)

SINGLE PHASE STS PREPAID METER

MT174 Three-phase Electricity Meter Technical Specification

AM 160 AM 360. The meter is MID certified as well as WELMEC 7.2 compliant and has been designed to serve billing purposes.

RS485 AMR Interface E350 User Manual

RE17RCMU off-delay timing relay - 1 s..100 h V AC - 1 OC

Centrale de mesure Power Meter PM500 Merlin Gerin

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

High precision measurement system for current and voltage IHC-A/B-RM01/03

PRELIMINARY DATA SHEET. RI-F400 Series. easywire Single and Three Phase Multifunction Energy Meter

RS Pro ENGLISH. Datasheet

User Manual Single Phase Electronic Meter For Active Energy HXE12R

ELECTRICAL NETWORK RECORDER - MC 750 ELECTRICAL NETWORK ANALYZER -MC 760 ENERGY METER - MC 720 POWER METER - MC 710 MULTIFUNCTION METER - MC 740

Energy Management Energy Analyzer Type EM210

RS Pro ENGLISH. Datasheet

FTU233. Ripple Control Receiver. Technical Data. Load Management Ripple Control

DRAFT TANZANIA STANDARD (Draft for comments only) Part 8: Electricity metering minimum accuracy and environmental requirements

UMG 103. UMG 103 Universal measurement device for DIN rails. GridVis Analysis software. Harmonics. Measurement accuracy 0.5.

RE17RAMU on-delay timing relay - 1 s..100 h V AC - 1 OC

HV / MV / LV electrical network quality analyzers Class A. Communication port: local, modem, integrated Ethernet, multi-point

3-phase energy meters with S0 pulse output

PRODUCT LEAFLET AUGIER-BOX. Remote Monitoring Unit for Street Lighting /07/2011

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Stabilized Differential Relay SPAD 346. Product Guide

Three phase CT Connection Smart Meter s Technical Specification

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Application Alpha 20 Measures important electrical parameters in 3 phase 4 Wire and 3 phase 3 Wire Network & replaces the multiple analog panel meters

ALPHA 20 MULTIFUNCTION METER (ALPHA SERIES)

83 Series - Modular timers 16 A. Features

XP2-R Power and reverse power relay. (January 2006) Manual XP2-R (Revision New)

XR1 Rotor Earth Fault Relay. (May 2007) Manual XR1 (Revision New)

AMIK 200 / 201 Technical Data Sheet

Electronic timer CT-MFS.21

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Transcription:

Energy Measurement and Management MT372 Three-phase electronic meter with built-in modem or RS485 communication interface Technical Description Version 1, 09.06. 2005 Content: MT372 Three-phase electronic meter... 3 1. Constituent parts... 4 2. Microcomputer... 4 2.1. Real time clock (RTC)... 4 2.2. LED... 4 2.3. Multi-tariff registration... 4 2.4. Power measurement... 4 2.5. Load profile... 4 3. Energy measurement and registration... 5 4. Display... 5 4.1. Data display on LCD... 5 4.2. Keys... 5 5. Communication interface... 5 5.1. IR communication interface... 5 5.2. RS485 communication interface - option... 6 5.3. Integrated GSM/GPRS communication interface with antenna - option... 6 5.4. Readout via built-in communication interfaces6 6. Input and outputs... 6 6.1. Inputs... 6 6.2. Outputs... 6 7. Circuit-breaker - option...7 8. Handling with the meter...7 9. Maintenance:...7 10. Lifetime:...7 11. Connection procedure...7 11.1. Connection procedure of GSM/GPRS communication interface...7 12. Casing...8 12.1. Dimensions...10 13. Terminal block...10 13.1.1. Terminal block...10 13.1.2. Current terminals...10 13.1.3. Auxiliary voltage terminals...10 13.1.4. Sliding voltage bridge...10 14. Connection...10 15. Technical data...11 16. Type designation...12

Energy Measurement and Management

MT372 Three-phase electronic meter Three-phase electronic meters are intended for measuring and registration of electric energy in three-phase four-wire network for direct connection. Measuring and technical characteristics of the meter comply with the IEC 62052-11 and IEC 62053-21 (IEC 61036) international standards for electronic active energy meters, class 1 or 2. The meters are designed and manufactured in compliance with the ISO 9001 standards as well as even more severe Iskraemeco internal standards. Meter characteristics Active energy meter accuracy class 1 or 2 Energy measuring and registration modes standard as an induction meter other options: bi-directional three-phase, two-phase, single-phase Connection to network: a three-phase meter can also function as a single-phase or a twophase meter. Additional functions: The forth measuring system, current measurement in neutral conductor. Neutral power-off detection, interruption of neutral conductor Detection of voltage unbalance Detection of phase unbalance Measurement of under- and over-voltages, and their recoding Generation of alarms and their transmission via communication interfaces One or multi tariff registration (1...4T): In compliance with real time clock LCD display: In compliance with VDEW requirements Display modes on LCD: automatic data circulation manual (trigerred with a key) Indications: LED: Imp / kwh LCD: Presence of phase voltages. L1,L2, L3 Phase currents direction Display of GSM/GPRS signal strength Auxiliary inputs/outputs: Output for load control with a relay Output for load control with Optomos relay Alarm input (low voltage) Up to two impulse inputs Communication interface: IR interface for local readout and meter programming Built-in GSM/GPRS modem with a bed for a SIM card Built-in RS485 communication interface Communication protocol: IR interface; IEC 62056 21, IEC 62056 46 GSM/GPRS modem; IEC 62056 46 Data organisation; IEC 62056 53 Identification system; IEC 62056 61 Detection of meter cover and terminal cover opening (option) Current terminals: a universal clamping terminal enables the same quality of the contact for all types and cross-sections of connection wires Voltage terminals: internal and external connection a sliding bridge (for simple separation of a voltage part from a current part) Quality: high accuracy as well as time stability of measurement high reliability of operation High immunity to EMC disturbances Simple and fast assembly A compact plastic casing, made of highquality self-extinguishable materials, and resistant to water and dust (IP54). 3

1. Constituent parts 1. A measuring chip (R phase) 2. A measuring chip (S phase) 3. A measuring chip (T phase) 4. A meter power supply unit 5. A microprocessor 6. LCD 7. An impulse diode 8. A»Call«and»Set«keys 9. IR optical interface 10. GSM/GPRS with a bed for a SIM card or RS485 communication interface 11. Inputs; impulse, alarm 12. Outputs; relay, circuit breaker switch off 13. Impulse inputs supply unit 14. Tariff inputs 15. Control circuits 16. Real time clock 17. FRAM memory 2.2. LED The meter is provided with a LED on the front plate. It is intended for checking the meter accuracy. Impulse constant depends on the meter version. 2.3. Multi-tariff registration The meter enables registration of energy and power. Max. four tariffs for power and energy can be registered. Tariff changeover is defined with hour and minute. Minimal resolution between changeovers is one minute. Different combinations of the tariff program are avaliable: Up to 4 seasons Up to 8 daily definitions of the changeover program Up to 8 individual changeovers inside individual daily program Up to 32 holidays Support to lunar holidays in compliance with the Gregorian calendar. 2.4. Power measurement Power is measured inside a measuring period. The measuring period is a meter parameter and can be set. Values that can be set are 15, 30 and 60 minutes. After termination of the measuring period, the measured meter value is transferred from current measuring period registers to registers for previous measuring period that can be later used for the formation of billing values. 2. Microcomputer Fig.1 Meter block diagram A microcomputer collects impulses from measuring circuits, processes them at their inputs, forms values for measured energy, and saves results in energy registers depending on the tariff program or state at tariff inputs. The microcomputer task is formation of an output impulse for a calibration LED. 2.1. Real time clock (RTC) A real time clock involves an internal calendar that assures information on year, month, day, day in a week, hour, minute, second and leap year. The clock accuracy should comply with the IEC 62052-21 standard for time switches. 2.5. Load profile Load profile recorder can be provided up to two channels. In each channel up to four objects can be stored of which two are reserved for time and status. The remaining two objects are used for saving energy by tariffs. Values of energy registers by tariffs depending on the set saving period Meter status. Record in a profile is equipped with a time flag and with the meter status in the last saving period and a check sum. The time flag indicates the end of a recording period. The saving period (a recording period) can be set. Possible values are 15, 30 and 60 minutes or a daily value. A super capacitor is used as an auxiliary power supply for surmounting longer power failures (up to 10 days). For a complete charging of the super capacitor the meter should be connected to network voltage for at least 35 minutes. The clock is driven by a crystal with 32.768 khz frequency. 4

3. Energy measurement and registration The meter measures or registers electric energy: In a three-phase three-wire, Single-phase two-wire, Three-phase four-wire network: by individual phases L1, L2, L3 (R, S, T) or total ( Li) only positive active energy positive and negative active energy (A+, A-) separately absolute active energy A Measurement can be performed in max. four different tariffs. 4. Display Fig.2 LCD An LCD is a 7-segment display and complies with the VDEW requirements. Used OBIS identification codes of displayed data (IEC 62056 61) are 5- digit type with 6 mm high characters. Data are 8- digit with 8 mm character size. Additional designations indicate: energy flow direction, a physical unit of a momentary displayed data and failure of L1, L2 and L3 phase voltages. Eleven flags on the display bottom show the state of a valid tariff and data on the meter operation. CODE DESCRIPTION 2.8.2 Negative active energy in second tariff (T2) 2.8.3 Negative active energy in third tariff (T3) 2.8.4 Negative active energy in forth tariff (T4) 1.6.1 A+ max. billing demand in first tariff (T1) 1.6.2 A+ max. billing demand in second tariff (T2) 1.6.3 A+ max. billing demand in third tariff (T3) 1.6.4 A+ max. billing demand in forth tariff (T4) 2.6.1 A- max. billing demand in first tariff (T1) 2.6.2 A- max. billing demand in second tariff (T2) 2.6.3 A- max. billing demand in third tariff (T3) 2.6.4 A- max. billing demand in forth tariff (T4) F.F Fatal error 4.2. Keys Table 1 - Display of register codes Two keys are built on the cover: RESET: orange with possible sealing CALL: blue. The keys enable: Changeover between meter operation modes, Listing of measuring results and settings, Billing generation, Alarms reset 5. Communication interface 5.1. IR communication interface A built-in optical interface is intended for setting meter parameters and a local readout of measuring results. The protocol for transmitting data via an optical communication interface is IEC62056-46 (DLMS-HDLC). 4.1. Data display on LCD Data that are defined in auto scroll and manual scroll sequences are displayed. Data are reviewed with a key or they are cyclically displayed. Actual display can differ from a display of registers in a table and depends on actual meter configuration. Maximal set of registers that are available for a display is shown in a table. CODE DESCRIPTION 0.0.0 Device number C.1.0 Device factory number 0.9.1 Time 0.9.2 Date 1.2.1.8.0 Register state of the first impulse input 1.3.1.8.0 Register state of the second impulse input 1.8.0 Total positive active energy (A+) 1.8.1 Positive active energy in first tariff (T1) 1.8.2 Positive active energy in second tariff (T2) 1.8.3 Positive active energy in third tariff (T3) 1.8.4 Positive active energy in forth tariff (T4) 2.8.0 Total negative active energy (A-) 2.8.1 Negative active energy in first tariff (T1) Fig. 3 Meter readout via an optical interface A physical level of the interface complies with the IEC62056-21 standard. Communication mode is serial asynchronous. Available settings of data transfer rate are 300, 600, 1200, 2400, 4800, 9600, 19200 bit/s 5

5.2. RS485 communication interface - option A built-in communication interface enables setting of meter parameters and a local readout of measuring results. The protocol for data transfer is IEC 62056 46. 5.3. Integrated GSM/GPRS communication interface with antenna - option It enables data transmission via a communication interface towards the centre for management and billing or a data concentrator. Data transmission rate via network is 9600 baud/s, while actual data transmission rate depends on momentary conditions in network. A GSM antenna is built in the meter. It enables operation in three frequency ranges 900 MHz 915 MHz 1800 MHz If a built-in antenna does not meet the needs of covering the signal, an external antenna can be mounted. Coupling circuit is placed on the meter cover and enables a simple mounting of a coupling module. network, and the flag above the DRO mark indicates that communication is going on. Fig. 5 Display legend 6. Input and outputs Input-output connection terminals are placed on the right side of the meter terminal block as well as on the upper additional plate. Eleven auxiliary connection terminals are used for Output for load control performed by a relay Output for load control performed by a optomos Output for circuit breaker control. On request outputs can be used as pulse outputs Up to two impulse inputs Input for an alarm (low voltage) A bed for a SIM card Fig. 5Input / output terminals Fig. 4 Coupling circuit 5.4. Readout via built-in communication interfaces Built-in communication interfaces enable: Reading of registers Reading of load profile Reading of meter parameters Changing of meter parameters Communication state is shown on a display, i.e. RS485 and IR interface: during communication, a flag above a DRO mark is blinking GSM/GPRS interface: at successful communication, several flags are displayed. The flag above the SQ mark indicates signal strength, the flag above the REG mark if present - indicates that the meter is ready for telecommunication 6.1. Inputs The meter is equipped with three inputs that occupy five connection terminals. Impulse inputs are active SO inputs that are supplied from the meter. Input for the alarm is a passive type and is controlled with voltage on terminals. Control voltage is from 3 V to 240 V AC/DC, and 230 V control voltage is available on request. 6.2. Outputs The meter is equipped with three outputs occupying six connection terminals. There are two outputs for load control. One with a relay that is capable of switching 250 V, 6 A, and another one that is performed with an Optomos element and is capable of switching 250 V, 100 ma. It is possible to control each control output separately, depending on the written tariff program or on received command. 6

Three connection terminals are intended for breaking module control. The central terminal is common, the left one is used for breaking module switch-on, and the right one for switch-off. On request outputs can be used as SO pulse outputs. 7. Circuit-breaker - option On request, the meters can be equipped with an external plug-in unit a circuit breaker. The circuit breaker is equipped with a terminal cover, and can be sealed. Assembly is simple since one part is inserted into the meter terminal block, and another part is extension of the terminal block. The meter with the circuit-breaker as a whole complies with the DIN 43857 standard or the stated fixing dimensions. 10. Lifetime: The meter is designed for an 18-year lifetime at normal operating conditions. 11. Connection procedure 1. Place the meter to a connection place. 2. Connect the meter to network; conductors fixing torque is 2.5 Nm. 3. Check connection indication: LED is lit (load current is less than inverse current) LED is blinking (proportional to load current strength) 4. Check connection see LCD indications: Presence of all three phases - L1 L2 L3 all symbols displayed, Phase failure a symbol for a failed phase is not lit Wrong phase sequence - L1 L2 L3 symbols of wrongly connected phases are blinking Fig. 6 A circuit-breaker 8. Handling with the meter Two sets of tools are available: For service programming and readout: MeterView (Iskraemeco software) An optical probe PC: a desk-top, a laptop The tool is intended for the operators who service or re-programme the meters in the laboratory or in a field. For billing readout: The SEP2W program package with Collect, Data Base and Report modules. A central station a server with a corresponding software and hardware For billing readout and programming: MeterRead (Iskraemeco software) for all types of Palm-top PCs operating in the WinCE environment An optical probe The tool is intended for readers in the field. 9. Maintenance: The meter is designed and manufactured in such a way that it does not need any maintenance interventions in the entire lifetime. Measuring stability assures that no recalibration is required. 11.1. Connection procedure of GSM/GPRS communication interface Checking of the presence of a SIM card 1. Remove a terminal block cover. 2. Check if a SIM card is inserted as shown on a figure below 3. If a SIM card is not inserted, insert it into the shown place Fig. 8 SIM card bed Check the GSM/GPRS signal strength on LCD: a. The flag is permanently lit; good covering with a GSM/GPRS signal. b. The flag is blinking; bad covering with the GSM/GPRS signal. It is recommended to find a better location for meter installation. c. The flag is not lit; it is recommended to find a better location for installation. If the flag is not lit even on a new place, an external antenna is required. Note, limits are adjustable 7

12. Casing The meter casing is made of self-extinguishable polycarbonate that can be recycled. 1. LCD 2. Technical data 3. Coupling circuit 4. A legend of registers display on LCD 5. A meter cover sealing screw 6. A meter serial number 7. A terminal cover sealing screw 8. A terminal cover 9. Project number 10. A meter BAR code 11. Impulse LED 12. Meter technical data 13. CALL and RESET keys 14. IR optical interface Fig. 9 Meter constituent parts 1. Coupling circuit 2. SIM card bed 3. Current terminals 4. A sliding voltage bridge 5. A switch for detection of terminal cover opening 6. Additional voltage terminals 7. Outputs for load control 8. Impulse inputs 9. Output for circuit breaker control 10. Alarm input (low voltage) Fig. 10 Details of a terminal block for GSM/GPRS meter version 1. RS485 communication interface 2. Current terminal 3. Sliding voltage bridge 4. Switch for selection of terminal cover opening 5. Additional voltage terminals 6. Outputs for load control 7. Impulse inputs 8. Output for circuit breaker control 9. Alarm input (low voltage) Fig. 11 Details of a terminal block for RS485 meter version 8

Terminal cover sealing screw Position 0 Position 1 Sliding voltage bridge Auxiliary terminals Terminal cover sealing screw Fig. 12 Terminal block constituent parts 9

12.1. Dimensions Fig. 13 Meter fixing dimensions. 13.3. Auxiliary voltage terminals The meter can be equipped with max. four auxiliary voltage terminals 2 (L1), 5 (L2), 8 (L3), 11 (N). They enable simple connection of additional external devices. 13.4. Sliding voltage bridge A sliding voltage bridge is intended for fast and simple separation of meter current and voltage circuit used for calibration or accuracy testing. A special slider is built in each phase of the connection terminal. It can be shifted up and down with a screwdriver. When a voltage bridge is in»0«position, it means that the voltage part is separated from the current part, while in position»1«it is closed. Mounting and fixing meter dimensions comply with the DIN 43857 standard. 14. Connection The meter can be connected to network as a singlephase, two-phase or three-phase meter. Fig. 14 Fixing dimensions of meters with a mounted breaking module 13. Terminal block 13.1. Terminal block A terminal block complies with the DIN 43857 standard. It is made of high quality polycarbonate assuring resistance to high temperatures, voltagebreakdown and mechanical strength. 13.2. Current terminals Current terminals are made of zinc-plated iron and have only one screw. A universal clamping terminal assures the same quality of the contact irrespective of the shape of the connection conductor (a compact wire, a stranded wire, greater or smaller crosssections). It also assures faster meter assembly. Available current terminals are: Current terminal according DIN standard for currents up to 85A with hole diameter is 8.5 mm, Current terminal for currents up to 120A with hole diameter is 9.5 mm, Current terminal for current up to 6A with hole diameter is 5.5 mm, CLAMP MAX MAX VOLTAGE CURRENT DIAMETER 71 27 V 27 ma 2,5 mm 70 Common clamp 2,5 mm 72 27 V 27 ma 2,5 mm 15 Common clamp 2,5 mm 20 27 V 24 ma 2,5 mm 33 250 V 100 ma 2,5 mm 35 Common clamp 2,5 mm 34 250 V 6 A 2,5 mm 73 27 V 20 ma 2,5 mm 75 Common clamp 2,5 mm 74 27 V 20 ma 2,5 mm 28,29,27,29,27 Communication interface 2,5 mm Fig. 15 Connection diagrams 10

15. Technical data GENERAL METER MEASURING CHARACTERISTICS Accuracy class 2 or 1 ( IEC 1036 ) Nominal current 5 A Max. current 85 A direct connected meter Max. current 120 A direct connected meter Max. current 6 A transformer connected meter Thermal current 1.2 I max direct connection Starting current <0.005 I b at cos ϕ = 1, for class 2 <0.004 I b at cos ϕ = 1, for class 1 Short-circuit 30 I max current Nominal voltage 3x230/400 V, 3x400 V other voltages on request Voltage range 0.8 U n... 1.15 U n Nominal frequency 50 Hz or 60 Hz Meter constant 1000 imp/kwh at Imax = 85 A (impulse LED) 500 imp/kwh at Imax = 120 A 10000 imp/kwh at Imax = 6 A Temperature -25 C... +60 C range of operation Extended -40 C... +70 C temperature range Storing -40 C... +80 C temperature Voltage circuit < 2W / 10VA self-consumption Current circuit selfconsumption < 0.16 VA irrespective of nominal current I n INTERNAL CLOCK Accuracy (at 6 ppm or ±3 min / year 25 C) Reserve power > 150 hours, supercapacitor supply Clock signal Quartz crystal 32 khz Optical communication interface Interface IEC62056-21 (IEC61107) Mode E, Protocol IEC62056-46, Registers marking in compliance with OBIS (IEC62056-61) Transmission rate 19200 bit/sec RS485 communication interface Protocol IEC62056-46, Marking of registers in compliance with OBIS (IEC62056-61) Data transmission 19200 bit/sec rate GSM/GPRS communication interface Protocol Data transmission rate IEC62056-46, GSM: 9600 bit/sec GPRS: 28000 bit/sec LOAD PROFILE Number of channels OUTPUTS High voltage output High voltage output Low voltage output INPUTS Low voltage input Low voltage input 1 or 2 Hardware type; bistable relay Output type; Load control Switching voltage: 250 V Switching current: 6 A Hardware type; Optomoss Output type; Servis control Switching voltage: 250 V Switching current: 100mA Hardware type; transistor Output type; circuit breaker control or pulse output Switching voltage: 27 V Switching current: 27 ma Hardware type: Active transistor input Inputs type; SO impulse inputs Switching voltage: 27 V Switching current: 27 ma Hardware type: Passive transistor input Inputs type; Alarm input Switching voltage: 3 24 V AC/DC CIRCUIT BREAKER Circuit breaker Input type:; 3 x bistable relay Switching voltage: 3 x 44 0V Switching current: 3 x 100 A METER RESISTANCE TO ELECTROMAGNETIC DISTURBANCES Insulation strength 4 kv, 50 Hz, 1 min Electrostatic 15 kv ( IEC 1000-4 - 2 ) discharges Electroma- 10 V/m ( IEC 1000-4 - 3 ) gnetic field Burst test highfrequency disturbances 4 kv ( IEC 1000-4 - 4 ) Shock voltage 12 kv, 1,2/50 µs ( IEC 61036 ) to meter main circuit DIMENSIONS W xh xl Mass W xh xl Mass Breaking module Meter with terminal cover and breaking module 86 x 250 x 178 1300 g Meter with terminal cover and breaking module 86 x 250 x 178 1300 g 650 g Table 2 Technical data Actual rate depends on network configuration! 11

16. Type designation M Electronic meter T Three-phase three-system meter 372 With built-in communication module - D1 Terminal block up to 85 A (DIN standard) D2 Terminal block up to 120 A T1 Terminal block up to 6 A A4 Active energy measurement, accuracy class 1 A5 Active energy measurement, accuracy class 2 1 Energy measurement in one direction 2 Energy measurement in two directions - V Low voltage passive transistor input 1 No. of inputs 2 Control voltage is phase voltage W Low voltage active transistor input n Number of inputs (n = 1, 2) 2 Resistive impulse input B High voltage output relay type 1 One relay contact 1 Make contact G Low voltage output N Number of outputs (n=1, 2) 2 Transistor output L High voltage output Optomoss type 1 One control output 1 Make contact - M Internal clock 2 Back-up power supply super capacitor K Communication interface 0 Optical interface in compliance with IEC 62056-21 3 RS485 communication interface (on request) 8 GSM modem (on request) a GPRS modem (on request) Z Load profile (option) Table 3 Type designation Owing to periodically improvements of our products the supplied products can differ in some details from data stated in this technical description. Iskraemeco d.d., Energy Measurement and Management 4000 Kranj, Savska loka 4, Slovenia Telephone (+386 4) 206 40 00, Fax: (+386 4) 206 43 76 http://www.iskraemeco.si, E-mail: info@iskraemeco.si Published: Iskraemeco, Marketing, Data subjected to alteration without notice. MT372_Technical_Description.doc 12