Progress Report on Failures of High Voltage Bushings with Draw Leads By Jim McBride and Larry Coffeen, JMX Services / NEETRAC 7/26/2010

Similar documents
Level 6 Graduate Diploma in Engineering Electrical Energy Systems

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

Tab 2 Voltage Stresses Switching Transients

Highgate Converter Overview. Prepared by Joshua Burroughs & Jeff Carrara IEEE PES

Advancements in online partial discharge monitoring and assessment of MV through EHV Substation assets

Switching Induced Transients:

Sources of transient electromagnetic disturbance in medium voltage switchgear

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Relay Protection of EHV Shunt Reactors Based on the Traveling Wave Principle

GIS Disconnector Switching Operation VFTO Study

Pinhook 500kV Transformer Neutral CT Saturation

Prepared By Pierre Archambault, PEng Power Survey International Inc Trans Canada Hwy. St-Laurent, QC H4S 1S4 CANADA

10. DISTURBANCE VOLTAGE WITHSTAND CAPABILITY

ETAP PowerStation. Electrical Transient Analyzer Program. ETAP PowerStation. Short Circuit Analysis. ANSI Standard 3-Phase Fault Currents

Calculation of Transient Overvoltages by using EMTP software in a 2-Phase 132KV GIS

Harmonics Issues that Limit Solar Photovoltaic Generation on Distribution Circuits

Solving Customer Power Quality Problems Due to Voltage Magnification

(participation = half letter grade, 5%)

700 Series AC Dielectric Test Sets

Modeling and Analysis of a 3-Phase 132kv Gas Insulated Substation

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Although shunt capacitors

Utility System Lightning Protection

DISTRIBUTION SYSTEM VOLTAGE SAGS: INTERACTION WITH MOTOR AND DRIVE LOADS

Jason Harchick, P.E. Sr. Manager, System Planning and Protection Ryan Young Manager, Substation Engineering

MEDIUM & HIGH VOLTAGE

VARIABLE FREQUENCY RESONANT TEST SYSTEM

Delayed Current Zero Crossing Phenomena During Switching of Shunt-Compensated Lines

New HVDC Interaction between AC networks and HVDC Shunt Reactors on Jeju Converter Stations

Equipment under Measurement: 6.6kV Alstom AIS Switchgear. Date of Measurement: 10 th August 2017

Surge Protection for Ladle Melt Furnaces

Transformer Factory Testing

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

ELECTRICAL POWER TRANSMISSION TRAINER

ATC s Mackinac Back to Back. Summary

Are snubbers required with Eaton s Cooper Power series liquid-filled hardened transformers?

Recent Improvements in K-Factor Models dl

Stor-Rotliden Transient analysis. 3/31/2017 Chalmers University of Technology, Tarik Abdulahovic

Notes 1: Introduction to Distribution Systems

700 Series AC Dielectric Test Sets

A Study on Ferroresonance Mitigation Techniques for Power Transformer

QUESTIONNAIRE for Wind Farm Power Stations only

Method for Static and Dynamic Resistance Measurements of HV Circuit Breaker

Resonances in Collection Grids of Offshore Wind Farms

VFTO STUDIES DUO TO THE SWITCHING OPERATION IN GIS 132KV SUBSTATION AND EFFECTIVE FACTORS IN REDUCING THESE OVER VOLTAGES

2. Current interruption transients

Joe Warner, Electric Power Industry Conference (EPIC), November 15, 2016 Advances in Grid Equipment Transmission Shunt Compensation

Mitigating Murphy s Law While Test. Frédéric Dollinger

Abstract. 1 Introduction

Session Four: Practical Insulation Co-ordination for Lightning Induced Overvoltages

A3-102 PCB ROGOWSKI COILS HIGH PRECISION LOW POWER SENSORS. Ljubomir A. Kojovic * Cooper Power Systems USA

Any wave shape can be reproduced by the sum of sine waves of the appropriate magnitude and frequency.

Power Factor & Harmonics

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Investigating Mechanical Integrity in Power Transformer Using Sweep Frequency Response Analysis (SFRA)

AC Dielectric Test Sets

This webinar brought to you by The Relion Product Family Next Generation Protection and Control IEDs from ABB

Substation Preventive Maintenance

SIMPLE SOLUTIONS FOR IMPROVING LIFE OF BREAKERS USED IN TRANSMISSION AND DISTRIBUTION SYSTEMS

MV network design & devices selection EXERCISE BOOK

MOBILE SUBSTATIONS 2015 MINNESOTA POWER SYSTEMS CONFERENCE

The University of New South Wales. School of Electrical Engineering and Telecommunications. High Voltage Systems ELEC9712. Appendix Partial Discharge

Impact Assessment Generator Form

3. COMBINED TRANSFORMERS Oil-paper insulation

Estimation of Re-striking Transient Overvoltages in a 3-Phase 132KV Gas insulated Substation

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

In power system, transients have bad impact on its

Estimation of Re-striking Transient Over voltages in a 132KV Gas insulated Substation

Reducing the magnetizing inrush current by means of controlled energization and de-energization of large power transformers

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser, OMICRON electronics Corp. USA

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 04, 2014 ISSN (online):

Delayed Current Zero Crossing Phenomena during Switching of Shunt-Compensated Lines

Grid Impact of Neutral Blocking for GIC Protection:

VOLTAGE OSCILLATION TRANSIENTS CAUSED BY CAPACITOR BANKING ENERGIZING FOR POWER FACTOR CORRECTION IN THE POWER SYSTEM

Single Line Diagram of Substations

Transformer differential protection

Practical Experience in On-Line Partial Discharge Measurements of MV Switchgear Systems

Application for A Sub-harmonic Protection Relay. ERLPhase Power Technologies

Chapter 7 Conclusion 7.1 General

Accurate Synchrophasor Estimation to Support the Islanding Maneuver of Active Distribution Networks

Visualization and Animation of Protective Relay Operation

Proceedings of the 5th WSEAS Int. Conf. on SIMULATION, MODELING AND OPTIMIZATION, Corfu, Greece, August 17-19, 2005 (pp )

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

OCCURRENCE OF DELAYED CURRENT ZERO CROSSING DUE TO LINE REACTIVE OVERCOMPENSATION LT CAMPINAS FERNAO DIAS 500 kv.

SAMPLE EXAM PROBLEM PROTECTION (6 OF 80 PROBLEMS)

Module 2 : Current and Voltage Transformers. Lecture 8 : Introduction to VT. Objectives. 8.1 Voltage Transformers 8.1.1Role of Tuning Reactor

Understanding the Value of Electrical Testing for Power Transformers. Charles Sweetser - OMICRON

Voltage Source Converter Modelling

Prediction of Transient Transfer Functions at Cable-Transformer Interfaces

Reference Sources. Prelab. Proakis chapter 7.4.1, equations to as attached

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Effect of High Frequency Cable Attenuation on Lightning-Induced Overvoltages at Transformers

Africa Utility Week Focus Day Substation Condition Monitoring Benefits of Ultrasound

Primary Metering. What is Primary Metering?

FRAX Series Sweep Frequency Response Analyzers

Connection Impact Assessment Application

General Technical Specifications of Frequency Converters for Tokyo-Chubu Interconnection Project

EH2741 Communication and Control in Electric Power Systems Lecture 2

Welcome. Power Survey International

Transcription:

The Team: Jim McBride: IEEE Member Larry Coffeen: IEEE Senior Member President, JMX Services, Inc. Senior Research Engineer, NEETRAC BS EE Georgia Tech BS EE Georgia Tech Testing, DAQ, and Measurement Substation Testing and Research 26 Years 43 Years 7/26/2010 IEEE PES July 26, 2010 1

Transients from 345/138 kv & 230/115 kv Substation Apparatus Recorded by NEETRAC/JMX On-line FRA Equipment Sensors located at H & X transformer bushing taps & across transformer neutral bushing Sensor Connection Neutral Bushing Sensor Bushing Tap 7/26/2010 IEEE PES July 26, 2010 2

OLFRA & OLRPF Cabinets 7/26/2010 IEEE PES July 26, 2010 3

OLRPF OLFRA 7/26/2010 IEEE PES July 26, 2010 4

OLFRA Cabinet 7/26/2010 IEEE PES July 26, 2010 5

Typical bushing tap + high pass filter + cabling frequency responses compared to laboratory reference divider (red trace in left column) 345kV System, Lapp POC, 2000A, Bottom Conn.,1999 yr 230kV System,Trench COTA 750,1400A,Draw Lead,1999yr 7/26/2010 IEEE PES July 26, 2010 6

Pre-strike of the 345 kv OCB contacts on energizing 345 kv transformer from high side The top trace is the magnitude vs. time overlay of the H1 bushing tap, the X1 bushing tap, & the Neutral bushing waveforms for the 345kV OCB prestrike transients on energizing the transformer. The waveforms are sampled at 12 bit, 20MHz w/ 64K records. The 60 Hz is filtered out to increase transient dynamic range of measurement. The bottom purple graph is the FFT of the H1 tap waveform that indicates frequency energy well into the MHz range. The FFT full scale is 5MHz. 7/26/2010 IEEE PES July 26, 2010 7

Zoom-in on highest burst from left upper waveform set. 2 usec. / big division. Blue = H1 bushing tap. (Bushing input max. approx. 10kV pk.) Red = X1 bushing tap. Green = Neutral bushing & represents pulse travel through H1 transformer winding / insulation combination from H1 to neutral. 7/26/2010 IEEE PES July 26, 2010 8

Picking Up Load with 138kV, SF6, Low Side Bank Breaker The top trace is the magnitude vs. time overlay of the H3 bushing tap, the X3 bushing tap, & the Neutral bushing waveforms for the transformer as the SF6 LS PCB picks up load (176 MW, 37MV, 740A on 138kV). The waveforms are sampled at 12 bit, 20MHz w/ 64K records. The 60 Hz is filtered out to increase transient dynamic range of measurement. The bottom purple graph is the FFT of the X3 tap waveform that indicates frequency energy well into the MHz range. The FFT full scale is 5MHz. 7/26/2010 IEEE PES July 26, 2010 9

Zoom-in on second burst from left upper waveform set. Blue = H3 bushing tap. Red = X3 bushing tap (bushing input max.approx. 5kV). Green = Neutral bushing & represents pulse travel through X3 transformer winding / insulation combination from X3 to neutral. 7/26/2010 IEEE PES July 26, 2010 10

Opening a 345 kv energized air disconnect switch to drop short bus & bushing capacitive load The top trace is the magnitude vs. time overlay of the H1 bushing tap, the X1 bushing tap, & the Neutral bushing waveforms for the transformer as a 345kV disconnect switch is opened to obtain a working clearance for 345kV line CCVTs. The waveforms are sampled at 12 bit, 20MHz w/ 64K records. The 60 Hz is filtered out to increase transient dynamic range of measurement. The bottom purple graph is the FFT of the H1 tap waveform that indicates frequency energy well into the MHz range. The FFT full scale is 5MHz. 7/26/2010 IEEE PES July 26, 2010 11

Zoom-in on first burst from left upper waveform set. Blue = H1 bushing tap (bushing max. input approx. 5kV). Red = X1 bushing tap. Green = Neutral bushing & represents pulse travel through H1 transformer winding / insulation combination from H1 to neutral. 7/26/2010 IEEE PES July 26, 2010 12

Pre-strike of the 230kV Air Disconnect Switch on Energizing 230kV Transformer from High Side The top trace is the magnitude vs. time overlay of the H1 bushing tap, the X1 bushing tap, & the Neutral bushing waveforms for the 230kV Air Disconnect Transients on energizing the transformer. The waveforms are sampled at 12 bit, 20MHz w/ 64K records. The 60 Hz is filtered out to increase transient dynamic range of measurement. The bottom purple graph is the FFT of the H1 tap waveform that indicates frequency energy well into the MHz range. The FFT full scale is 5MHz. 7/26/2010 IEEE PES July 26, 2010 13

Zoom-in on highest burst from left upper waveform set. 2 usec. / big division. Blue = H1 bushing tap. (Bushing input max. approx. 30kV pk.) Red = X1 bushing tap. Green = Neutral bushing & represents pulse travel through H1 transformer winding / insulation combination from H1 to neutral. 7/26/2010 IEEE PES July 26, 2010 14

230/115kV, 300MVA, Auto with 230kV High Side Air Disconnect Switch 230kV High Side Air Disconnect Switch OLFRA & OLRPF Equipment 7/26/2010 IEEE PES July 26, 2010 15

Fast transient currents entering top of bushing see an inductive draw lead in series with a large capacitance at winding to case with most all initial voltage drop across the bushing draw lead. 7/26/2010 IEEE PES July 26, 2010 16

Opening a 115kV, 58.5MVAR, Capacitor Bank OCB The top trace is the magnitude vs. time overlay of the H2 bushing tap, the X2 bushing tap, & the Neutral bushing waveforms for the transformer as a 115kV cap. bank OCB is opened. The waveforms are sampled at 12 bit, 20MHz w/ 64K records. The 60 Hz is filtered out to increase transient dynamic range of measurement. The bottom purple graph is the FFT of the X2 tap waveform that indicates frequency energy well into the MHz range. The FFT full scale is 5MHz. 7/26/2010 IEEE PES July 26, 2010 17

Zoom-in on first burst from left upper waveform set. Blue = H2 bushing tap Red = X2 bushing tap (bushing max. input approx. 6kV). Green = Neutral bushing & represents pulse travel through H2 transformer winding / insulation combination from H2 to neutral. 7/26/2010 IEEE PES July 26, 2010 18

115kV, 58.5MVAR, Capacitor Bank 7/26/2010 IEEE PES July 26, 2010 19

Pre-strike of 230kV SF6 PCB on Energizing 230kV, 180MVAR Capacitor Bank The top trace is the magnitude vs. time overlay of the H2 bushing tap, the X2 bushing tap, & the Neutral bushing waveforms for the 230kV SF6 PCB prestrike transients on energizing the cap bank. The waveforms are sampled at 12 bit, 20MHz w/ 64K records. The 60 Hz is filtered out to increase transient dynamic range of measurement. The bottom purple graph is the FFT of the H2 tap waveform that indicates frequency energy well into the MHz range. The FFT full scale is 5MHz. 7/26/2010 IEEE PES July 26, 2010 20

Zoom-in on highest burst from left upper waveform set. 2 usec. / big division. Blue = H2 bushing tap. (Bushing input max. approx. 7kV pk.) Red = X2 bushing tap. Green = Neutral bushing & represents pulse travel through H2 transformer winding / insulation combination from H2 to neutral. 7/26/2010 IEEE PES July 26, 2010 21

230kV, 180MVAR, Capacitor Bank 7/26/2010 IEEE PES July 26, 2010 22

Opening a 230kV Energized Air Disconnect Switch to Clear Up 230kV, 180MVAR Capacitor Bank for Maintenance The top trace is the magnitude vs. time overlay of the H3 bushing tap, the X3 bushing tap, & the Neutral bushing waveforms for the transformer as a 230kV disconnect switch is opened to obtain a working clearance for 230kV cap bank after the SF6 cap breaker is opened. The waveforms are sampled at 12 bit, 20MHz w/ 64K records. The 60 Hz is filtered out to increase transient dynamic range of measurement. The bottom purple graph is the FFT of the H3 tap waveform that indicates frequency energy well into the MHz range. The FFT full scale is 5MHz. 7/26/2010 IEEE PES July 26, 2010 23

Zoom-in on first burst from left upper waveform set. Blue = H3 bushing tap (bushing max. input approx. 2.5kV). Red = X3 bushing tap. Green = Neutral bushing & represents pulse travel through H3 transformer winding / insulation combination from H3 to neutral. 7/26/2010 IEEE PES July 26, 2010 24

Summary 1. Air disconnect switches and power circuit breakers are examples of devices that produce a significant number of medium voltage and/or current, fast transients as a result of normal switching operations. 2. These fast transients have rise times in the sub-microsecond range with frequencies well into the megahertz region. 3. The fast transients are characterized as they reach the high side, low side, and neutral bushings of the auto-transformer using the NEETRAC OLFRA equipment built by JMX Services, Inc. 7/26/2010 IEEE PES July 26, 2010 25