Original instructions. SIRe Advanced. Modbus communication ... 2

Similar documents
Modbus communication module for TCX2: AEX-MOD

DPX³ 250 Electronic 4P - ModbusTable LGR EN v1.01.xls

GUIDE SPECIFICATIONS CONTROLS SPECIFICATIONS AND CONTROL POINT DATA MAP GENERAL DESCRIPTION

REH FC-BMS3 Modbus Manual

Device connection and commissioning can only be carried out by qualified professionals. Always make the connections while the power is switched off.

Installation and User Guide

VT8600 Series User Interface Guide Rooftop Unit, Heatpump and Indoor Air Quality Controller

SRC-110 Series Zone Controllers with Modbus RTU

SE8600 Series User Interface Guide Rooftop Unit, Heat Pump and Indoor Air Quality Controller

InsuLogix T MODBUS Protocol Manual

Fan Coil Actuator FCA 2

CONTENTS Project name WMHpc Revision 1.3

Communicative heating controller

theben Fan Coil Actuator FCA 1 Fan Coil Actuator FCA 1 FCA Version: Jan-08 (Subject to change) Page 1 of 77

AQUAVAR CPC. Modbus Communications (Software Version 204 and later)* INSTRUCTION MANUAL ADAQCPC R1

Data Acquisition Modules/ Distributed IO Modules

NetBiter I/O Extender 4RO 6RTD 8DIO - DAIO User Manual Revision 1.00

PRODUCT CATALOGUE TEMPERATURE CONTROL Grässlin products for individual control of temperature

FCU-503 FAN COIL CONTROLLER WITH RDU-TOUCH INTERFACE

About AB Industrietechnik

User Instructions For TopTronic RS-10

745 Transformer Protection System Communications Guide

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

WIRELESS MODBUS GATEWAY WGW410

MODBUS RTU (RS485) Installation or Upgrading Platinum Control to MODBUS. Installation and Operation Manual. RS485 socket connect to MODBUS

Know your energy. Modbus Register Map EB etactica Power Bar

CoolEx User Manual 2008 XDIMAX LTD. Revision 1.0

Home Automation, Inc. Omnistat2. RC-1000 and RC-2000 Communicating Thermostat. Serial Protocol Description

CooLink Programmers Reference Manual (PRM)

Know your energy. Modbus Register Map EM etactica Power Meter

Industrial Modbus I/O Modules

BACnet- MS/TP COMMUNICATION V

Option H2, Modbus communication Automatic Gen-set Controller H SW version 2.33.X

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Use of the application program. Contents. 1. Functional description General. GAMMA instabus Application program description.

Application Programs Descriptions

Modbus Integration Integration for Modbus Functionality for VT8300 Series

10 Error Code List. Motion Control SW. NTI AG / LinMot User Manual Motion Control SW/ Page 87/94

MV110-8AS. Analog input module 8 channel. User guide

GB QUICK GUIDE FOR THE CONFIGURATION OF VARIABLE SPEED DRIVES

HARDWARE GUIDE. Digital Sensor - T1100 Series. Specifications and Operational Guide

OPTIVENT ULTRA VAV damper CONTROL UNIT FOR MODBUS 227VMZ-MB

ADAM-4022T Serial Base Dual Loops PID Controller User s Manual

LVCSi Continuous Vertical Level Sensor with Integrated Display

INSTRUCTION MANUAL Redox sensor M 1322 C

Universal Controller

micro Technical Manual

CHAPTER AC DRIVE PARAMETERS. In This Chapter...

FCU-501 FAN COIL CONTROLLER WITH RDU-4 INTERFACE

RAM 712 KNX room thermostat for surface-mounted and flush-mounted installation

GS1 Parameter Summary Detailed Parameter Listings...4 9

MODBUS RS485 SERIAL PROTOCOL

Series F4P Communications Guide

BusWorks 900EN Series Modbus TCP/IP 10/100M Industrial Ethernet I/O Modules

vacon 100 flow ac drives application manual

InfraStruXure Manager v4.x Addendum: Building Management System Integration

TAC5 Regulation + SAT KNX Module

Modbus Communications System for Micrologic A, P, and H Trip Units Class 0613

Channels that are not occupied by temperature sensors, can take over alternative functions:

Relay Driver Overview and Applications

CONTROL MANUAL. Dry-Pic 09PE - 09VE

Ocean Controls KT-5221 Modbus IO Module

MU110-16R(K) Digital output module 16 channel. User guide

R7426A. MicroniK 200 TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

CT435. PC Board Mount Temperature Controller

HHC Hand-Held Communicator. User s Guide

815LT Submersible Smart Level Transmitter

DTAP. universal programmable controller. Универсален програмируем контролер

Intelligent Installation Systems. ABB i-bus KNX Room Thermostat Fan Coil with Display 6138/11-xx-500 Product Manual

Addendum SmartPAC Third Party Communications Firmware

Single Phase Power Meter,with external CT

Specification GRUNER YSP 227C

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

PL420 PROGRAMMABLE LOGIC CONTROLLER

Modbus VAV Controller Configuration Properties

User manual CLIMATIC 60

2F. No.25, Industry E. 9 th Rd., Science-Based Industrial Park, Hsinchu, Taiwan Application Note of OGM220, AN001 V1.8

TAS APFC Controller / Load Managers with MOD-BUS Interface

maxon document number:

ELECTRICAL VARIABLE ANALYZER RELAY EVAR

Installation Guide. ECL Comfort 310, application A Table of Contents

Integrations GW Programming manual

DEIF A/S. Description of options. Option H3 Serial communication Profibus DP Multi-line 2 version 2. Description of option. Functional description

Signal Isolators & Conditioners

VAV-Compact. Contents. Modbus General Notes 2 Modbus Register Overview 3 Modbus Register Description 4

BATCHMATE 1500 Batch Control Computer Technical Bulletin

SilverMax Datasheet. QuickSilver Controls, Inc. NEMA 23 Servomotors.

Use of the application program. Contents. instabus EIB Application program description. September S2 Room temperature controller

Control equipment. Regula 1.4. lindab we simplify construction

Instruction Manual D

AEROCONNECT 1B NA C Control manual

BAS Integration Manual

PROCESS & TEMPERATURE CONTROLLERS

Temperature Controller model MFC-301/T-Dry. Version for Dry Transformers and Motors. Technical Manual. Licht

G3P-R232. User Manual. Release. 2.06

Room thermostat solo, FM Type: 6124-xx

NO WARRANTIES OF ANY KIND ARE IMPLIED ON THE INFORMATION CONTAINED IN THIS DOCUMENT.

User Manual. KNX MultiLight Dali. Article number: function Technology AS. Picture: KNX MultiLight products

High Performance Process & Temperature Controllers

MultiController E Regulate 24V og 230V

Transcription:

Original instructions SIRe Advanced Modbus communication GB... 2

SIRe Modbus This manual describes how to connect SIRe Advanced with Modbus/RTU via RS485, the technical specification of the protocol in SIRe, the parameters and their use. For more information about other functions in SIRe, please see the main manual. For more information about Modbus please contact your BMS supplier or www.modbus.org Connection Modbus/RTU via RS485, connects on a 3 pole contact on terminal [BUS] on the SI- ReA1N. What information is presented Please see list of parameters. What information is not presented Information regarding run times for each individual unit is stored on the B1-pcb and can only be viewed locally. Modbus Information Supported functions Function codes 01, 02, 03, 04, 05, 06, 08, 15, and 16 are supported. Diagnostics (08) supports sub-codes 0, 2, 10, 11, 12, 13, and 14. Start and stop bits One start bit, one stop bit. Parity Current software uses only 'None' parity mode. Broadcast Broadcast not supported because A1 fails to not to respond broadcast. Setting values outside valid range If written values are outside their allowed range, they will be set to the nearest value which is in the range. Bus termination Bus is not terminated but it has 4.7 kohm pull-up and pull-down resistors. Registers used Coils, discrete inputs, and input registers are supported, but there are no registers. So the responce is always "Illegal data address". Holding register 16 bit integer register R/W PDU length Maximum PDU length is 256 bytes. Supported network topology General 2-wire topology described in Modbus specifications is supported. Multiple slaves are supported. Software supports only RTU mode; ASCII mode serial transmission is not supported. Ground level Internal and external bus shares the same common ground, the RS-485 signals are not isolated.

Terminal Modbus/RTU RS-485 Function (EIA/TIA-485) 23 D0 A/A Non-inverting Pull-down [-] 24 D1 B/B Inverting Pull-up [+] 25 Com C/C Signal ground SIReUA1 Menu structure - Gateway functions > Installer menu Mixing cabinet External control General settings control 0-10V fan control 0-10V heat control Gateway functions System on/off enable Room temp. enable Outdoor temp. enable =4x00051 Fan speed enable Heating step enable Door position enable =4x00049 Baud rate and Modbus ID is set locally, using the control panel, SIReUA1, see menu structure. Explanation: AC FH All Ambient Electrically heated Water heated Air Curtains Fan Heaters All type System on/off enable Room temp. enable Outdoor temp. enable =4x00046 Room temp. enable Outdoor temp. enable Water temp. enable =4x00047 Outdoor temp. enable Water temp. enable Fan speed enable =4x00086 Water temp. enable Fan speed enable Heating step enable =4x00048 Heating step enable Door position enable Week program enable =4x00050 Door position enable Week program enable Modbus ID =4x00052 Week program enable Modbus ID Baud rate Set using UA1 Week program enable Modbus ID Baud rate Set using UA1

Modbus Register Min Max Unit Type Notes 4x00001 Room temperature -1500 1500 0.1 C All Read or write room temperature. To write: set parameter 4x00046=1 4x00002 Outdoor temperature -1500 1500 0.1 C All Read or write outdoor temperature. To write: set parameter 4x00047=1 4x00003 Fan speed 0 100 % All Read or write fan speed. To write: set parameter 4x00048=1 4x00004 Heating step 0 100 % All Read or write heat step. To write: set parameter 4x00049=1 4x00005 Door position 0 1 AC 0 = Closed door, 1 = Open door. To write: set parameter 4x00050=1 4x00006 System on/off 0 1 All 0 = Off, 1 = On. To write: set parameter 4x00051=1 4x00007 Week program 0 2 All 0 = Off, 1 = Day, 2 = Night. To write: set parameter 4x00052=1 4x00008 Room temp. day SET 5 35 C All Temperature setpoint during Day time (deafault value) 4x00009 Room temp. night SBT 5 35 C All Temperature setpoint when Night is active 4x00010 High speed limit 0 100 % All Limits the fans maximum speed (For AC, at open door) 4x00011 Speed closed door Low 0 100 % AC Speed limit at closed door 4x00012 Summer/Winter Season 0 1 All 0 = Summer (no heat), 1 = Winter (Heat available) Parameter not active in Advanced. 4x00013 Door mode 0 2 AC 0 = Auto, 1 = Fix Open/Close, 2 = Fix open Set depending on use of door (Always open, open/closed or a mix.) 4x00014 Fan mode FanMode 0 3 FH 0 = Auto, 1 = Thermostat, Manual fan, 2 = Thermostat, Auto fan, 3 = Manual 4x00015 Stepless fan control 0 1 All 0 = Off, 1 = On Used for controlling a unit with frequency inverter, EC-motors or other 0-10VDC controlled fan. 4x00016 T max speed winter TmaxH -30 30 C AC At what outside temperature the AC should run at high speed during winter conditions 4x00017 T min speed winter TminH -30 30 C AC At what outside temperature the AC should run at low speed during winter conditions 4x00018 T min speed summer TminC -30 30 C AC At what outside temperature the AC should run at low speed during summer conditions 4x00019 T max speed summer TmaxC -30 30 C AC At what outside temperature the AC should run at high speed during summer conditions 4x00020 Over run mode Auto/fix 0 1 AC 0 = Auto, 1 = User See main manual for function description. 4x00021 High speed over run Hdelay 0 180 s AC Reads currently used overrun time when 4x00020=0 and not the manually set value. Rounds to nearest multiple of 10. Manually set overruntime for High speed when parameter 4x00020=1 4x00022 Low speed over run Ldelay 0 500 s AC Set overruntime for low speed when parameter 4x00020=1 4x00023 Outdoor temp. limit TLIMH 5 35 C All Blocks the heat when value on outdoorsensor is above set value. 4x00024 Eco / Comfort TcomfortMode 0 1 All 0 = Eco, 1 = Comfort. See main manual for function description. 4x00025 Open door setp. diff. DiffS 0 10,0 0,1 C AC Increase of temperature set value when the door opens. 4x00026 Heating step diff. DiffH 0 10,0 0,1 C All The temperature difference between activation of electrical heating steps or increase of fan speed for water heated FH. 4x00027 Room temp. sensor Calib -10,0 10,0 K All Offset of the room temperature value 4x00028 Outdoor temp. sensor Calib -10,0 10,0 K All Offset of the outdoor temperature value 4x00029 Return temp. sensor 0 1 0 = Room, 1 = Return water. If WTA is used, set 4x00029=1 4x00030 Return temp. limit 0 90 C Maximum temperature of return water when WTA is used (temp. > [set value] reduces the waterflow) 4x00031 Heating step limit 0 3 Step All Limit the heat, when using stepless heat, 0-100%

Modbus Register Min Max Unit Type Notes 4x00032 Stepless heat control 0 1 All 0 = Off, 1 = On. For water heated units 4x00032=1. For electrical units additional external components must be used for stepless heat. 4x00033 Control range limit 5 35 C All Limits a Users maximum set value 4x00034 Filter timer on/off 0 1 All 0 = Off, 1 = On. Activates the filter timer 4x00035 Filter timer setting 0 9950 h All Set countdown time for the filter alarm. Rounds to nearest multiple of 50. 4x00036 External filter guard 0 1 All 0 = Off, 1 = On. Activate if external filter guard is connected to terminals 9 and 10. 4x00037 Last filter change HCFL h All Time since last filter change. Read only 4x00038 Mixing cabinet ctrl ON/OFF 0 1 FH 0 = Off, 1 = On. Activate when fan heater is used together with mixing cabinet. 4x00039 Min outlet temp. 5 35 C FH Set minimum air outlet temperature. 4x00040 Day damper pos. DPD 0 100 % FH sets damper position during day time or if no week program is used 4x00041 Night damper pos. DPN 0 100 % FH sets damper position during night time 4x00042 External on/off ON/OFF 0 1 All 0 = Off, 1 = On (ExternalOnOffEnable) A1X T15-16 Activate if external On/Off signal is connected to terminals 15 and 16 4x00043 0-10V fan control ON/OFF 0 1 All 0 = Off, 1 = On (ExternalFanControlEnable) A1X T11-12 Activate if external fan rpm signal is connected to terminals 11 and 12 4x00044 0-10V heat control ON/OFF 0 1 All 0 = Off, 1 = On (ExternalHeatControlEnable) A1X T13-14 Activate if external heat signal is connected to terminals 13 and 14 4x00045 Set point correction -10 10 C All If central sensor is used and offset is required 4x00046 Enable ext. room temp. 0 1 All 0 = Off, 1 = On Set =1 if BMS should write value to SIRe 4x00047 Enable ext. outd. temp. 0 1 All 0 = Off, 1 = On Set =1 if BMS should write value to SIRe 4x00048 Enable ext. fan speed 0 1 All 0 = Off, 1 = On Set =1 if BMS should write value to SIRe 4x00049 Enable ext. heating step 0 1 All 0 = Off, 1 = On Set =1 if BMS should write value to SIRe 4x00050 Enable ext. door contact 0 1 AC 0 = Off, 1 = On Set =1 if BMS should write value to SIRe 4x00051 Enable ext. on/off 0 1 All 0 = Off, 1 = On Set =1 if BMS should write value to SIRe 4x00052 Enable ext. week prgm. 0 1 All 0 = Off, 1 = On Set =1 if BMS should write value to SIRe 4x00053 Clock, year 2010 2099 All Reading year copies system clock to internal buffer. All reads and writes are from/to internal buffer. Writing seconds copies time from internal buffer to system clock. 4x00054 Clock, month 1 12 All 4x00055 Clock, day of month 1 31 All 4x00056 Clock, hours 0 23 h All 4x00057 Clock, minutes 0 59 m All 4x00058 Clock, seconds 0 59 s All 4x00059 Max over run time Delay/ DelayF 10 300 s All Fan overrun countdown after heat has been on. Rounds to nearest multiple of 10. 4x00060 It over run stop T 10 40 C All If internal temp. Drops below set value during overrun countdown, the fan stops. 4x00061 Time interval stages ET 1 10 min AC During the function Stages (see main manual) the roomtemp is measured every [set value] minute

Modbus Register Min Max Unit Type Notes 4x00062 Functionality mode Comp/Adv 0 1 All 0 = Advanced, 1 = Competent. Set functionlevel. If competent is set, the system ignore outdoor sensor value or errors 4x00063 Min. water flow 0-3 V, 0,1V step 0 30 0,1V Set minimum waterflow when valve is closed. 0,1V=1% 4x00064 Door contact func. NC/NO 0 1 AC 0 = NC, 1 = NO. (Only physical contact). Invert door contact function 4x00065 It_react 5 15 C Frost protection: Internal temp sensor Set value opens valve 4x00066 It_alarm 5 15 C Frost protection: Internal temp sensor Set value opens valve, stops fan and closes damper 4x00067 RTG_react 5 20 C Frost protection: Return water sensor (WTA) Set value opens valve 4x00068 RTG_alarm 5 20 C Frost protection: Return water sensor (WTA) Set value opens valve, stops fan and closes damper 4x00069 Min. return temp. 5 30 C Frost protection: At stationary fan, [Set value] is the minimum return water temperature. 4x00070 Device ID Read only: All 1=AC1, 2=AC2, 129=FH1, 130=FH2 254/255=Unknown or error. Unit program, Reads from B1. Depends on unit. Should not be changed. 4x00071 Motor alarm TK 0 1 All 0 = Normal, 1 = Disabled. Activate/Deactivate motorprotection alarm 4x00072 Over heating alarm ON/OFF 0 1 All 0 = Normal, 1 = Disabled. Activate/Deactivate internal over heat alarm 4x00073 Outlet temp. Limit 20 100 C All [Set value] limits the air outlet temperature in Comfort mode, overides set 4x00074 Outlet temp. limit Eco 20 100 C All [Set value] limits the air outlet temperature in Eco mode (32 C) Heat decreases 4x00075 Outlet temp. limit Diff 0 100 0,1 C All [Set value] above outlet temp. Limit, Heat=0 4x00076 Outlet temp. limit Alarm 30 100 C All [Set value] = overheat alarm 4x00077 Installation year All Read only. For information only. 4x00078 Installation month All Read only. For information only. 4x00079 Installation day All Read only. For information only. 4x00080 Reserved for future use, no access. 4x00081 Return water temperature. (WTA) SIRe to receive water temp. from BMS. Write/Read to/from BMS. To write: set parameter 4x00086=1 4x00082 Mixing Cab. Outdoor temp. limit -50 50 FH 4x00083 Reserved for future use, no access. 4x00084 Modbus ID All Read only. 4x00085 Baud rate All 0 = 2400, 1 = 4800, 2 = 9600, 3 = 19200, 4 = 38400, 5 = 57600 4x00086 Enable ext. return water temp. 0 1 1 = Off, 1 = On. Set =1 if BMS should write value to SIRe 4x00087 Reserved for future use, no access. 4x00088 Reserved for future use, no access. 4x00089 Reserved for future use, no access. 4x00090 Reserved for future use, no access. 4x00100 Reset alarm 0 1 All Reads 1 if at least one alarm is active. Write 1 to reset all alarms. 4x00101 E1 Communication error 0 1 All Communication error may sometimes not be presented via Modbus. 4x00102 E2 two or more B1 have same ID 0 1 All Please see QG/main manual for information regarding alarm and errors.

Modbus Register Min Max Unit Type Notes 4x00103 E3 B1 without program 0 1 Please see QG/main manual for information regarding alarm and errors. 4x00104 E4 Missing/faulty RTX sensor on B1 0 1 Please see QG/main manual for information regarding alarm and errors. 4x00105 Always zero, writes ignored 4x00106 E6 Faulty RTG sensor on B1 0 1 Please see QG/main manual for information regarding alarm and errors. 4x00107 E7 Missing RTG (when mandatory) 0 1 Please see QG/main manual for information regarding alarm and errors. 4x00108 E8 It sensor error 0 1 Please see QG/main manual for information regarding alarm and errors. 4x00109 Always zero, writes ignored 4x00110 E10 two B1 with different program 0 1 Please see QG/main manual for information regarding alarm and errors. 4x00111 Always zero, writes ignored 4x00112 E12 Missing/faulty RTX on A1X 0 1 Please see QG/main manual for information regarding alarm and errors. 4x00113 Always zero, writes ignored 4x00114 E14 Outdoor sensor error 0 1 Please see QG/main manual for information regarding alarm and errors. 4x00115 Always zero, writes ignored 4x00116 Always zero, writes ignored 4x00117 Always zero, writes ignored 4x00118 Always zero, writes ignored 4x00119 Always zero, writes ignored 4x00120 Always zero, writes ignored E20 not available through Modbus. Please see QG/main manual for more information. 4x00121 E21 Sensor error in UA1 0 1 4x00122 Always zero, writes ignored E22 not available through Modbus. Please see QG/main manual for more information. 4x00123 E23 Incompatible B1 Units with software from different generations. Require excahange of components, contact Frico 4x00124 Always zero, writes ignored 4x00125 Always zero, writes ignored 4x00126 Always zero, writes ignored 4x00127 Always zero, writes ignored 4x00128 Always zero, writes ignored 4x00129 A1 Motor alarm 4x00130 A2 Overheat alarm 0 1 Please see QG/main manual for information regarding alarm and errors. 4x00131 A3 Freeze alarm 0 1 Please see QG/main manual for information regarding alarm and errors. 4x00132 A4 Filter alarm 4x00133 A5 External alarm 4x00134 Reserved for future use, no access. 4x00135 Reserved for future use, no access. Empty Empty Empty

Notes