EE 340L Experiment 6: Synchronous Generator - Operation with the Grid

Similar documents
EE 340L Experiment 6: Synchronous Generator - Stand-Alone Operation

Generator Operation with Speed and Voltage Regulation

PMSM Control Using a Three-Phase, Six-Step 120 Modulation Inverter

LVSIM-EMS Help Table of Contents

Exercise 3. Doubly-Fed Induction Generators EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Doubly-fed induction generator operation

Exercise 7. The Buck/Boost Chopper EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. The Buck/Boost Chopper

Solving Simple AC Circuits Using Circuit Impedance Calculation

University of Saskatchewan Department of Electrical and Computer Engineering EE Power Electronics Lab Exercise 4

Voltage-Versus-Speed Characteristic of a Wind Turbine Generator

Four-Quadrant Dynamometer/Power Supply

Operation of a Three-Phase PWM Rectifier/Inverter

EE 340L EXPERIMENT # 3 SYNCHRONOUS GENERATORS

Exercise 2. The Buck Chopper EXERCISE OBJECTIVE DISCUSSION OUTLINE. The buck chopper DISCUSSION

Exercise 8. The Four-Quadrant Chopper EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. The Four-Quadrant Chopper

Exercise 6. The Boost Chopper EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. The boost chopper

Bidirectional PWM DC Motor Drive with Regenerative Braking

AC Power Transmission Training System

AC Power Transmission Training System

Courseware Sample F0

Exercise 4. Ripple in Choppers EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Ripple

Voltage Compensation of AC Transmission Lines Using a STATCOM

Introduction to High-Speed Power Switching

The Discussion of this exercise covers the following points: Phasor diagrams related to active and reactive power

Exercise 1. Basic PWM DC Motor Drive EXERCISE OBJECTIVE DISCUSSION OUTLINE. Block diagram of a basic PWM dc motor drive DISCUSSION

Harmonic Reduction using Thyristor 12-Pulse Converters

Grid-Tied Home Energy Production Using a Solar or Wind Power Inverter without DC-to-DC Converter

DISCUSSION OF FUNDAMENTALS

ECE 5671/6671 LAB 6. Wound-Field Synchronous Generators

Exercise 3. Phase Sequence EXERCISE OBJECTIVE DISCUSSION OUTLINE DISCUSSION. Phase sequence fundamentals

DC and AC Power Circuits Training System

Speed Feedback and Current Control in PWM DC Motor Drives

9063 Data Acquisition and Control Interface

Data Acquisition and Control Interface

Dynamic Power Factor Correction Using a STATCOM

9063-RC Data Acquisition and Control Interface

Renewable Energy. DC Power Electronics. Courseware Sample F0

Electric Power Systems 2: Generators, Three-phase Power, and Power Electronics

The Single-Phase PWM Inverter with Dual-Polarity DC Bus

MEHRAN UNIVERSITY OF ENGINEERING & TECHNOLOGY, JAMSHORO

A Super trainer with advanced hardware and software features only found in very expensive equipment.

8010-7A Home Energy Production Training System

Synchronous Generators II EE 340

Microprocessor Control Board Set Up Procedures (OR PLC)

SYNCHRONOUS MACHINES

DS1000E, DS1000D Series Digital Oscilloscope

impact VC-500LR Monolight INSTRUCTIONS

UNIT 9 DC Separately-Excited Generator

Electrical Machines (EE-343) For TE (ELECTRICAL)

EE 340L EXPERIMENT # 5.1 SYNCHRONOUS GENERATOR (STAND-ALONE OPERATION)

Exercise 3-3. Manual Reversing Starters EXERCISE OBJECTIVE DISCUSSION. Build manual reversing starters and understand how they work.

P. O. BOX 269 HIGHLAND, ILLINOIS, U.S.A PHONE FAX

Generator Advanced Concepts

EEL 3086 SWITCHGEAR AND PROTECTION EXPERIMENT 2 DIFFERENTIAL PROTECTION OF A THREE-PHASE TRANSFORMER

Frequency Agility and Barrage Noise Jamming

2.017 DESIGN OF ELECTROMECHANICAL ROBOTIC SYSTEMS Fall 2009 Lab 4: Motor Control. October 5, 2009 Dr. Harrison H. Chin

Exercise 4. Angle Tracking Techniques EXERCISE OBJECTIVE

Basic Measurement and M-G Set OBJECTIVE

Basic Measurement and M-G Set with the 208V L-L Motor

Design and Construction of Synchronizing Check Relay

The synchronous machine as a component in the electric power system

Single-Phase Power Transformers

Exercise 6. Range and Angle Tracking Performance (Radar-Dependent Errors) EXERCISE OBJECTIVE

PART 1 OWNER/APPLICANT INFORMATION

Exercise 3-3. Multiple-Source Jamming Techniques EXERCISE OBJECTIVE

SPECIFICATION, CONTROLS AND ACCESSORIES

The Discussion of this exercise covers the following points:

Single-Phase Grid-Tied Inverter (PWM Rectifier/Inverter)

Introduction to Basic Laboratory Instruments

Single-Phase AC Power Circuits

Experiment 3. Performance of an induction motor drive under V/f and rotor flux oriented controllers.

Laboratory Seven Stepper Motor and Feedback Control

CHAPTER 6 FABRICATION OF PROTOTYPE: PERFORMANCE RESULTS AND DISCUSSIONS

GENERATOR INTERCONNECTION APPLICATION Category 5 For All Projects with Aggregate Generator Output of More Than 2 MW

SOUTH CENTRAL INDIANA REMC Application for Operation of Member-Owned Small Power Generation Systems

TM1600. Circuit Breaker Analyzer System

Exercise 1-5. Antennas in EW: Sidelobe Jamming and Space Discrimination EXERCISE OBJECTIVE

The oscilloscope and RC filters

NTG MULTIFUNCTON GENERATOR PROTECTION RELAY. NTG-Slide

AC Power Transmission Training System Add- On to ( )

Power Line Series Compensation Demonstrator (EMS Version)

Top-Innovator EncoderAnalyzer. For testing encoders. Made in Germany Expect more. Winding testers

EASTERN ILLINI ELECTRIC COOPERATIVE Application for Operation of Member-Owned Generation

Conventional Paper-II-2013

EE 330/330L Energy Systems (Spring 2012) Laboratory 4 Synchronous Generator

Exercise 8. Troubleshooting a Radar Target Tracker EXERCISE OBJECTIVE

Name EET 1131 Lab #2 Oscilloscope and Multisim

EEE3410 Microcontroller Applications Department of Electrical Engineering Lecture 11 Motor Control

WRM-10 TM TRANSFORMER WINDING RESISTANCE METER

Owner/Customer Name: Mailing Address: City: County: State: Zip Code: Phone Number: Representative: Address: Fax Number:

Trouble Shooting MagnaPLUS / Mariner / Harsh Duty

GENERATOR INTERCONNECTION APPLICATION Category 3 For All Projects with Aggregate Generator Output of More Than 150 kw but Less Than or Equal to 550 kw

Introduction to basic laboratory instruments

DS1000B Series Digital Oscilloscope

crio Resolver Simulation crio RVDT Simulation Manual V3.0

Electricity and New Energy. DC Power Electronics. Courseware Sample F0

Programmable AC Power Source Model 9801

AMT-07. Amplifier for MID-IR PDs, with built-in cooler

Sampling and Reconstruction

UNIVERSITY OF CALIFORNIA, SANTA BARBARA Department of Electrical and Computer Engineering. ECE 2A & 2B Laboratory Equipment Information

PART 2 - ACTUATORS. 6.0 Stepper Motors. 6.1 Principle of Operation

Transcription:

EE 340L Experiment 6: Synchronous Generator - Operation with the Grid The synchronous machine (see Fig. 1) is mechanically coupled to the Four-Quadrant Dynamometer/Power Supply (see Fig. 2) using a timing belt. This second machine is used as a prime mover to provide mechanical power to the first electric generator. Figure 3 shows the synchronizing module that will assist with the synchronization process. 1. Stator winding terminals: 2. Thermistor Output. 3. Exciter input terminals: 4. Exciter switch. 5. Exciter knob: Fig. 1: Synchronous Machine

1. Power Input: 2. Main power switch: 3. Power Supply terminals 4. Operating Mode switch: 5. Function push-button: 6. Start/Stop push-button: 7. Command knob: 8. Liquid crystal display (LCD): 9. Command Input: 10. Shaft Encoder Outputs: 11. Analog Outputs 12. Thermistor Input: 13. USB port connector: Fig. 2: Four-Quadrant Dynamometer/Power Supply

Figure 3: Synchronizing Module. 1. Input Power Terminals (to energize coil of the 3-phase Contactor) 2. Syn. Switch (to energize or de-energize coil of contactor A) 3. Remote control (another alternative to energize or de-energize coil of contactor) 4. Contact terminals (of the two power sources to be synchronized) 5. Lamps switch (toggle switch must be set to I (on) for the indicator lamps to be operational). 6. Synchronizing lamps (indicate the relative level of the voltage across the three corresponding contact terminals. These are connected in parallel with the circuit breaker contacts). 1) Synchronizing the Generator with the Grid. Before synchronizing a three-phase synchronous generator to an ac power network, it is important to ensure that the following synchronization conditions are met: The phase sequence of the synchronous generator must be the same as that of the ac power network. The synchronous generator output frequency must be equal to the ac power network frequency. The synchronous generator voltage must be equal to the ac power network voltage The synchronous generator voltage must be in phase with the ac power network voltage. Connecting a synchronous generator to the ac power network when the above synchronization conditions are not met produces severe electrical and mechanical stress on the generator and can cause serious damage to it. Procedure: a) Connect the equipment as shown in Figure 4 below. This circuit represents a synchronous generator connected to an ac power network through a circuit breaker (three-phase contactor).

b) Make sure that the main power switch on the Four-Quadrant Dynamometer/ Power Supply is set to the O (off) position, then connect its Power Input to an ac power outlet. Connect the Power Input of the Data Acquisition and Control Interface to a 24 V ac power supply. Turn the 24 V ac power supply on. c) On the Synchronizing Module/Three-Phase Contactor, make sure that the Lamps switch is set to the (I) position. This ensures that the synchronizing lamps on the module are operational. Also make sure that the Sync. switch is set to the open (O) position. This ensures that the synchronous generator is not connected to the ac power network. d) Turn on the Four-Quadrant Dynamometer/Power Supply, select dynamometer operation, then under Function select CW rotation, start the prime mover, then increase the speed parameter of the prime mover until it reaches 1790 rpm. e) Turn On the 3-phase Power Supply slowly increase the DC voltage across the generator field winding until the phase voltage of the generator (E2) is nearly equal to that of the power supply (E1). f) On the Synchronizing Module/Three-Phase Contactor, observe the synchronizing lamps: If they are all flashing simultaneously in synchronism, then we have the correct phase sequence. If not, this indicates that two of the 3 phases are crossed. In this latter case, shut off the power supply, cross two of the phase of the power supply, and start over. g) In LVDAC-EMS, open the Oscilloscope, then make the appropriate settings in order to observe the waveforms of the ac power network voltage ( E1) and the synchronous generator voltage (E2). Select the ac power network voltage (input E1) as the trigger source of the Oscilloscope. Take a snapshot and describe briefly what you observed (home assignment). h) In the Four-Quadrant Dynamometer/Power Supply window, increase the Speed parameter of the prime mover slowly while watching the flashing rate of the lamps until the generator speed reaches 1800 rpm. Then adjust the generator field current until E1 E2. Make further necessary adjustments till the lamps become all dark. Observe the waveforms of these voltages on the Oscilloscope, and when these two voltages are equal in amplitude and in phase (that is when the lamps go 100% dark) take a snapshot, then it is time to set the Sync. switch on the Synchronizing Module/Three-Phase Contactor to the closed (I) position to synchronize the generator to the network. Then note the active and reactive power supplied by phase 1 of the generator. P1 =.. W Q1 =. VAR

Fig. 4: Generator-power system synchronization. 2) Generator operation after synchronization to the ac power network Once synchronized with the power network, the generator terminal voltage E2 is locked to the grid voltage E1. Hence, changing the field current won t affect the voltage, but instead, it affects the reactive power supplied by the generator. In addition, the generator frequency is locked to the grid frequency of 60 Hz. Hence, its rotor speed is locked to 1800 rpm, i.e., attempting to change the prime mover speed is not possible, instead, it affects the real power supplied by the generator. a) Real power control In the Four-Quadrant Dynamometer/Power Supply window, attempt to increase the Speed parameter of the prime mover slowly in small increments and note what happens to the generator real power, reactive power, and frequency. For each real power value below, record the frequency and reactive power. real power (W) 20 30 40 50 60 70 Reactive Power (VAR) Gen. frequency (Hz)

b) Reactive power control Adjust the Speed parameter of the prime mover backwards so that the generator active power is as close as possible to 0 W. Then on the Synchronous Motor/Generator, vary the setting of the Exciter knob in slow increments, and record the observed reactive power, real power, and voltage phase voltage E2. Fill in the table below. real power (W) Reactive Power (VAR) -30-20 -10 0 10 20 30 Phase voltage (V) Once finished, set the Sync. switch on the Synchronizing Module/Three-Phase Contactor to the open (0) position to disconnect the generator from the power network, stop the prime mover, then turn off the 3-phase power supply. Close the LVDAC-EMS. Disconnect all leads and return them to their storage location.