IJRREST INTERNATIONAL JOURNAL OF RESEARCH REVIEW IN ENGINEERING SCIENCE & TECHNOLOGY (ISSN ) VOLUME-4, ISSUE-3, November 2015

Similar documents
Investigation of D-Statcom Operation in Electric Distribution System

Power Quality enhancement of a distribution line with DSTATCOM

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

A Power Control Scheme for UPQC for Power Quality Improvement

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

INTERLINE UNIFIED POWER QUALITY CONDITIONER: DESIGN AND SIMULATION

Performance of DVR under various Fault conditions in Electrical Distribution System

Reduction of Voltage Imbalance in a Two Feeder Distribution System Using Iupqc

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter

Reduction of Power Quality Issues in Micro-Grid Using Fuzzy Logic Based DVR

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Design of Dynamic Voltage Restorer for three phase network as steady state device in the Distribution System

Mitigating Voltage Sag Using Dynamic Voltage Restorer

Design and Simulation of Dynamic Voltage Restorer (DVR) Using Sinusoidal Pulse Width Modulation (SPWM)

Design and Simulation of DVR Used For Voltage Sag Mitigation at Distribution Side

IMPROVEMENT OF POWER QUALITY USING CUSTOM POWER DEVICES

OVERVIEW OF SVC AND STATCOM FOR INSTANTANEOUS POWER CONTROL AND POWER FACTOR IMPROVEMENT

ISSN Vol.07,Issue.21, December-2015, Pages:

Power Quality Improvement using Hysteresis Voltage Control of DVR

Performance of DVR & Distribution STATCOM in Power Systems

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

Power Quality Improvement by DVR

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

IMPROVEMENT OF VOLTAGE SAG MITIGATION USING DYNAMIC VOLTAGE RESTORER (DVR)

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

FUZZY CONTROLLED DSTATCOM FOR HARMONIC COMPENSATION

p. 1 p. 6 p. 22 p. 46 p. 58

2020 P a g e. Figure.2: Line diagram of series active power filter.

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

Power Quality Improvement By Using DSTATCOM Controller

Protection from Voltage Sags and Swells by Using FACTS Controller

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

Downloaded from

Simulation and Implementation of DVR for Voltage Sag Compensation

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Simulation of Dynamic Voltage Restorer Using Matlab to Enhance Power Quality in Distribution System

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

PUBLICATIONS OF PROBLEMS & APPLICATION IN ENGINEERING RESEARCH - PAPER CSEA2012 ISSN: ; e-issn:

ANFIS based 48-Pulse STATCOM Controller for Enhancement of Power System Stability

Compensation of Different Types of Voltage Sags in Low Voltage Distribution System Using Dynamic Voltage Restorer

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

Voltage Sags in Distribution Systems with Induction Motor Loads Fed by Power Converters and Voltage Mitigation using DVR and D-STATCOM

Power Quality and the Need for Compensation

Power Quality Improvement using Active shunt Power filter using PI Controller

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

FUZZY LOGIC CONTROL BASED DYNAMIC VOLTAGE RESTORER FOR POWER QUALITY IMPROVEMENT IN DISTRIBUTION SYSTEM

Design Strategy for Optimum Rating Selection of Interline D-STATCOM

SIMULATION OF D-STATCOM IN POWER SYSTEM

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

Voltage Sag and Swell Identification Using FFT Analysis and Mitigation with DVR

Unit.2-Voltage Sag. D.Maharajan Ph.D Assistant Professor Department of Electrical and Electronics Engg., SRM University, Chennai-203

Voltage Sag Mitigation of DVR using Matlab Simulation

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Power-Quality Improvement with a Voltage-Controlled DSTATCOM

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

Mitigation of voltage disturbances (Sag/Swell) utilizing dynamic voltage restorer (DVR)

Enhancement of Power Quality Using Advanced Series Active Power Filters

Interline Power Quality Conditioner for Power Quality Improvement

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Performance of Indirectly Controlled STATCOM with IEEE 30-bus System

A DYNAMIC VOLTAGE RESTORER (DVR) BASED MITIGATION SCHEME FOR VOLTAGE SAG AND SWELL

II. RESEARCH METHODOLOGY

SIMULATION OF D-STATCOM AND DVR IN POWER SYSTEMS

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

HARMONIC COMPENSATION USING FUZZY CONTROLLED DSTATCOM

Enhancement of Voltage Stability & reactive Power Control of Distribution System Using Facts Devices

Real and Reactive Power Control by using 48-pulse Series Connected Three-level NPC Converter for UPFC

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Voltage Improvement Using SHUNT FACTs Devices: STATCOM

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

ENHANCEMENT OF POWER QUALITY BY INJECTING SERIES VOLTAGE USING DVR

CHAPTER 4 PV-UPQC BASED HARMONICS REDUCTION IN POWER DISTRIBUTION SYSTEMS

Improvement of Power Quality Using a Hybrid Interline UPQC

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

Design of Interline Dynamic Voltage Restorer for Voltage Sag Compensation

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer

Application of Dynamic Voltage Restorer for Voltage Balancing with ASD Load Using DQO Transformation

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

MITIGATION OF VOLTAGE SAG AND SWELL FOR POWER QUALITY IMPROVEMENT USING DISTRIBUTED POWER FLOW CONTROLLER

A Modified Control Method For A Dual Unified Power Quality Conditioner

Performance Analysis of UPQC for Non-Linear Load by Using MATLAB

Mitigation of Faults in the Distribution System by Distributed Static Compensator (DSTATCOM)

Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM)

Voltage Quality Enhancement in an Isolated Power System through Series Compensator

Mitigation of Flicker Sources & Power Quality Improvement by Using Cascaded Multi-Level Converter Based DSTATCOM

Design and Control of Interline Unified Power Quality Conditioner for Power Quality Disturbances

Cascaded Two Level Electrical Converter-Based Multilevel STATCOM for High Power Utilization

A CONTROL TECHNIQUE FOR INSTANT MITIGATION OF VOLTAGE SAG/SWELL BY DYNAMIC VOLTAGE RESTORER

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

Voltage Sag Mitigation Using Distribution Static Compensator System

B.Tech Academic Projects EEE (Simulation)

Dynamic Modeling and Simulation of Unified Power Quality Conditioner

COMPARITIVE STUDY ON VOLTAGE SAG COMPENSATION UTILIZING PWM SWITCHED AUTOTRANSFORMER BY HVC

Transcription:

PERFORMANCE ANALYSIS OF FACTS (D-STATCOM AND DVR) DEVICES Manoj Garg 1 & Rajeev Kumar 2 1 Research Scholar, GIMT, Kurukshetra, Haryana, India 2 Assistant Professor, GIMT, Kurukshetra, Haryana, India Abstract The Power Quality Analysis aspires to bring out electricity consumers for improved power quality with application of power electronics. The research work involves in-depth analysis of the interaction among loads, power networks and various power quality improvement devices. It ultimately leads to better design of mitigation devices like Dynamic Voltage Restorer (DVR), Distribution Static Synchronous Compensator (DSTATCO M) and Unified Power Quality Conditioner (UPQC) to alleviate various power quality related problems. The main objective of this research work is to develop a model of DVR and DSTATCO M for enhancement of power quality. DVR and DSTATCO M are among the custom power devices that are used as an effective solution for the protection of sensitive loads against voltage disturbances in power distribution system. The efficiency of the FACTS devices depends on the performance of the control technique, which involved in switching the inverters. A comparative analysis of PI controlled DVR and DSTATCO M has been carried out for better power system stability enhancement. The validity of the proposed method and achievement of the desired compensation are confirmed by the results of the simulation in Matlab/ Simulink. 1. INTRO DUCTIO N Power quality is a word that means different things to different inhabitants. Institute of Electrical and Electronic Engineers (IEEE) Standard IEEE1100 defines power quality as, The conception of powering and grounding sensitive electronic equipment in a manner suitable for the equipment. As suitable as this description might seem, the drawback of power quality to sensitive electronic equipment might be subject to deviation. Electrical equipment susceptible to power quality or more appropriately to need of power quality would fall within an apparently boundless domain. All electrical devices are prone to failure or breakdown when exposed to one or more power quality problems. The electrical device might be an electric motor, a transformer, a generator, a computer, a printer, communication equipment or a home appliance. All of these devices and others react undesirably to power quality issues, depending on the severity of problems. However, nearly everybody accepts that it is a very important aspect of power systems and electric machinery with direct impacts on efficiency, security and reliability. Various sources use the term power quality with different meaning. It is used synonymously with supply reliability, service quality, voltage quality, current quality, quality of supply and quality of consumption. Nonlinear loads generate harmonic currents that can promulgate to other locations in the power system and ultimately return back to the source. Therefore, harmonic current promulgation produces harmonic voltages throughout the power systems. Many mitigation techniques have been suggested and employed to maintain the harmonic voltages and currents within proposed levels. 1. Design of High power quality equipment, 2. Cancellation of Harmonics, 3. Dedicated line or transformer, 4. Capacitor banks optimal placement and sizing, 5. Derating of power system devices and 6. Harmonic filters (passive, active and hybrid) and custom power devices such as active power line conditioner (APLC), DVR, DSTATCOM and Unified Power Quality Conditioners. The phenomenon of power quality through application of power electronics is studied in the research work. The aim of the control scheme is to develop Simulink model of DVR and DSATCOM maintain constant voltage magnitude at the point where a sensitive load is connected, under system disturbances. The wide range of power quality disturbances covers sudden, short duration variations, e.g. impulsive and oscillatory transients, voltage sags, short interruptions, as well as steady state deviations, such as harmonics mitigation by using DVR. This research work, specifically examine the use of a power electronic shunt compensator named as DSTATCOM to correct the current drawn from a utility to closely approximate balanced sinusoidal waveforms, without adversely affecting the voltage at the point of common coupling. Thus, adjustment of the feedback gains makes it possible to reduce voltage fluctuation in transient states, when the active filter has the function of combined harmonic damping and voltage regulation. By using UPQC the control scheme of a shunt active power filter must calculate the current reference waveform for each phase of the inverter, maintain the dc voltage constant and generate the inverter gating signals. To correct for the effects of supply voltage distortion, the series compensator is required to inject appropriate harmonic voltages. A novel strategy for the improvement of power quality based on custom power devices the analysis of the results obtained from various techniques, ijrrest.org 5 P a g e

like PI Controller and Fuzzy Logic Controller are presented. The main objectives of the research work are to develop model for DVR for the enhancement of power quality in electrical power networks. The objective which has been laid down for this work is the development of DVR and DSTATCOM model simulation model and their performance analysis through simulation. Research has been carried out to achieve the above mentioned objectives. The effectiveness of the DSTATCOM and DVR in solving the power quality problems has been proved through simulations, model development and analysis. Custom power devices transient performance observed. Control techniques developed to overcome the problems related to DC Link voltage deviations. produces fewer harmonic than a single bridge, resulting in smaller filters and improved dynamic response. In this case, the inverter modulation frequency is 28*60=1.68 khz so that the first harmonics will be around 3.36 khz. LC damped filters connected at the inverter output. Resistances connected in series with capacitors provide a quality factor of 40 at 60 Hz. a 10000-microfarad capacitor acting as a DC voltage source for the inverter a voltage regulator that controls voltage at bus B3 a PWM pulse generator using a modulation frequency of 1.68 khz Anti-aliasing filters used for voltage and current acquisition. 2. D-STATCO M MO DEL DESCRIPTIO N A Distribution Static Synchronous Compensator (D- STATCOM) is used to regulate voltage on a 25-kV distribution network. Two feeders (21 km and 2 km) transmit power to loads connected at buses B2 and B3. A shunt capacitor is used for power factor correction at bus B2. The 600-V load connected to bus B3 through a 25kV/600V transformer represents a plant absorbing continuously changing currents, similar to an arc furnace, thus producing voltage flicker. The variable load current magnitude is modulated at a frequency of 5 Hz so that its apparent power varies approximately between 1 MVA and 5.2 MVA, while keeping a 0.9 lagging power factor. This load variation will allow you to observe the ability of the D-STATCOM to mitigate voltage flicker. The D-STATCOM regulates bus B3 voltage by absorbing or generating reactive power. This reactive power transfer is done through the leakage reactance of the coupling transformer by generating a secondary voltage in phase with the primary voltage (network side). This voltage is provided by a voltage-sourced PWM inverter. When the secondary voltage is lower than the bus voltage, the D- STATCOM acts like an inductance absorbing reactive power. When the secondary voltage is higher than the bus voltage, the D-STATCOM acts like a capacitor generating reactive power. The D-STATCOM consists of the following components: a 25kV/1.25kV coupling transformer which ensures coupling between the PWM inverter and the network. The D-STATCOM controller consists of several functional blocks: a Phase Locked Loop (PLL). The PLL is synchronized to the fundamental of the transformer primary voltages. two measurement systems. Vmeas and Imeas blocks compute the d-axis and q-axis components of the voltages and currents by executing an abc-dq transformation in the synchronous reference determined by sin(wt) and cos(wt) provided by the PLL. an inner current regulation loop. This loop consists of two proportional-integral (PI) controllers that control the d-axis and q-axis currents. The controllers outputs are the Vd and Vq voltages that the PWM inverter has to generate. The Vd and Vq voltages are converted into phase voltages Va, Vb, Vc which are used to synthesize the PWM voltages. The Iq reference comes from the outer voltage regulation loop (in automatic mode) or from a reference imposed by Qref (in manual mode). The Id reference comes from the DC-link voltage regulator. an outer voltage regulation loop. In automatic mode (regulated voltage), a PI controller maintains the primary voltage equal to the reference value defined in the control system dialog box. a DC voltage controller which keeps the DC link voltage constant to its nominal value (Vdc=2.4 kv). The electrical circuit is discretized using a sample time Ts=5 microseconds. The controller uses a larger sample time (32*Ts= 160 microseconds). a voltage-sourced PWM inverter consisting of two IGBT bridges. This twin inverter configuration, ijrrest.org 6 P a g e

Fig. 1 Simulation & Model of DSTATCOM 2.1 D-STATCOM DYNAMIC RESPONSE During this test, the variable load will be kept constant and you will observe the dynamic response of a D-STATCOM to step changes in source voltage. Check that the modulation of the Variable Load is not in service (Modulation Timing [Ton Toff]= [0.15 1]*100 > Simulation Stop time). The Programmable Voltage Source block is used to modulate the internal voltage of the 25-kV equivalent. The voltage is first programmed at 1.077 pu in order to keep the D-STATCOM initially floating (B3 voltage=1 pu and reference voltage Vref=1 pu). Three steps are programmed at 0.2 s, 0.3 s, and 0.4 s to successively increase the source voltage by 6%, decrease it by 6% and bring it back to its initial value (1.077 pu). Note that when the D-STATCOM changes from inductive to capacitive operation, the modulation index of the PWM inverter is increased from 0.56 to 0.9 (trace 4 of Scope2) which corresponds to a proportional increase in inverter voltage. Reversing of reactive power is very fast, about one cycle, as observed on D-STATCOM current (magenta signal on trace 1 of Scope1). Start the simulation. Observe on Scope1 the phase A voltage and current waveforms of the D-STATCOM as well as controller signals on Scope2. After a transient lasting approximately 0.15 sec., the steady state is reached. Initially, the source voltage is such that the D-STATCOM is inactive. It does not absorb nor provide reactive power to the network. At t = 0.2 s, the source voltage is increased by 6%. The D-STATCOM compensates for this voltage increase by absorbing reactive power from the network (Q=+2.7 Mvar on trace 2 of Scope2). At t = 0.3 s, the source voltage is decreased by 6% from the value corresponding to Q = 0. The D-STATCOM must generate reactive power to maintain a 1 pu voltage (Q changes from +2.7 MVAR to - 2.8 MVAR). Fig. 2 DSTATCOM in dynamic mode (Scope 1), ijrrest.org 7 P a g e

2.2 MITIGATION OF VOLTAGE FLICKER During this test, voltage of the Programmable Voltage Source will be kept constant and you will enable modulation of the Variable Load so that you can observe how the D-STATCOM can mitigate voltage flicker. In the Programmable Voltage Source block menu, change the "Time Variation of" parameter to "None". In the Variable Load block menu, set the Modulation Timing parameter to [Ton Toff]= [0.15 1] (remove the 100 multiplication factor). Finally, in the D-STATCOM Controller, change the "Mode of operation" parameter to "Q regulation" and make sure that the reactive power reference value Qref (2nd line of parameters) is set to zero. In this mode, the D- STATCOM is floating and performs no voltage correction. Run the simulation and observe on Scope3 variations of P and Q at bus B3 (1st trace) as well as voltages at buses B1 and B3 (trace 2). Without D-STATCOM, B3 voltage varies between 0.96 pu and 1.04 pu (+/- 4% variation). Now, in the D-STATCOM Controller, change the "Mode of operation" parameter back to "Voltage regulation" and restart simulation. Observe on Scope 3 that voltage fluctuation at bus B3 is now reduced to +/- 0.7 %. Fig. 3 controller of DSTATCOM in dynamic mode (Scope 2) The D-STATCOM compensates voltage by injecting a reactive current modulated at 5 Hz (trace 3 of Scope3) and varying between 0.6 pu capacitive when voltage is low and 0.6 pu inductive when voltage is high. Fig. 4 Bus data of bus 1 & Bus 3 in dynamic mode (Scope 3) Fig. 5 DSTATCOM in Mitigation of voltage flickering mode (Scope 1), ijrrest.org 8 P a g e

active power transfer capability. This active power is transferred via the dc link, and is supplied either by a diode bridge connected to the ac network, a shunt connected PWM converter or by an energy storage device. It works as a harmonic isolator to prevent the harmonics in the source voltage reaching the load in addition to balancing the voltages and providing voltage regulation. Fig. 8 Dynamic Voltage Restorer Fig. 6 Controller of DSTATCOM in Mitigation of voltage flickering mode (Scope 2) The Three-Phase Source block implements a balanced three-phase voltage source with an internal R-L impedance. The three voltage sources are connected in Y with a neutral connection that can be internally grounded or made accessible. You can specify the source internal resistance and inductance either directly by entering R and L values or indirectly by specifying the source inductive short-circuit level and X/R ratio The three-phase inductive short-circuit power, in volts-amperes (VA), at specified base voltage, used to compute the internal inductance L. This parameter is available only if Specify impedance using short-circuit level is selected. The internal inductance L (in H) is computed from the inductive threephase short-circuits power Psc (in VA), base voltage Vbase (in Vrms phase-to-phase), and source frequency f (in Hz) as follows: The Three-Phase Fault block uses three Breaker blocks that can be individually switched on and off to program phase-to-phase faults, phase-to-ground faults, or a combination of phase-to-phase and ground faults. Fig. 7 Bus Data of bus 1 & bus 3 in Mitigation of voltage flickering mode (Scope 3) 3. DYNAMIC VO LTAGE RESTO RER (DVR) DVR injects a voltage component in series with the supply voltage as shown in figure-4.21, thus compensating voltage sags and swells on the load side. Control response is on the order of 3msec, ensuring a secure voltage supply under transient network conditions. Voltage injection of arbitrary phase with respect to the load current implies Fig. 9 Three-Phase Fault with breakers The ground resistance Rg is automatically set to 106 ohms when the ground fault option is not programmed. For example, to program a fault between the phases A and B you need to select the Phase A Fault and Phase B Fault block parameters only. To program a fault between the phase A and the ground, you need to select the Phase A, ijrrest.org 9 P a g e

Fault and Ground Fault parameters and specify a small value for the ground resistance. If the Three-Phase Fault block is set in external control mode, a control input appears in the block icon. The control signal connected to the fourth input must be either 0 or 1, 0 to open the breakers, 1 to close them. If the Three-Phase Fault block is set in internal control mode, the switching times and status are specified in the dialog box of the block. Series Rp-Cp snubber circuits are included in the model. They can be optionally connected to the fault breakers. If the Three- Phase Fault block is in series with an inductive circuit, an open circuit or a current source, you must use the snubbers. In the proposed simulink model DVR has been modeled using IGBT based voltage converter. The effectiveness of DVR has been checked by introducing a three phase fault at 0.4 sec. the output waveform is compared in two condition, with and without using DVR. The PI-controlled DVR has proven its effectiveness as analysed from the output waveforms. Fig. 10 DVR model simulated with PI controller 4. CO NCLUSION AND FUTURE SCO PE The conclusions drawn from the different aspects of the study in this research work are summarized in this chapter. The scope for further study in this area is also dwelt upon at the end. Fig. 11 output waveform on occurring fault at 0.4seconds of waveform on occurring fault Fig. 12 Expended view of waveform on occurring fault using PI controller After analyzing output waveforms on occurring fault at 0.4seconds we can conclude that using DVR we can maintain power quality using different control strategies. Nonlinear loads produce harmonic currents that can propagate to other locations in the power system and eventually return back to the source. Therefore, harmonic current propagation produces harmonic voltages throughout the power systems. Mitigation techniques have been proposed and implemented to maintain the harmonic voltages and currents within recommended levels are harmonic filters passive, active and hybrid) and custom power devices DSATATCOM and DVR. The different sources and occurrences of voltage Sags, swells and interruptions have been presented. DSTATCOM and DVR with PI Controller has been designed to mitigate the effects of the power quality problems during different faults like three phase fault, single line to ground fault and double line fault. The performance analysis with two different control techniques gives equally effective results. Any one of the proposed control technique will be equally effective in the successful, ijrrest.org 10 P a g e

operation of DVR. The investigation of results performance has been successfully demonstrated in MATLAB/Simulink. The study made in the research work mainly concentrates on the power quality improvement through DSTATCOM and DVR (Custom power Device) with optimized technique PI controller for the distribution power system. Furthermore one can evaluate some more analysis can be done for the custom power devices for the improvement of power quality in different angles like advanced PWM methodologies like sinusoidal, hysteresis (bang bang) and space vector (symmetrical or asymmetrical) implementations with programmable digital signal processors for the optimum control of the filtering devices through various advanced Artificial Intelligent Techniques like expert systems, Natural language processing, neuro fuzzy, genetic algorithms, or swarm intelligence. Controllers like multilevel inverters or matrix converters selection for the custom power devices to improve power quality based on the problem. From the various problems, selection of suitability of the equipment among the available devices with optimized cost for the total process and minimum time. REFERENCES [1] Fang Zheng Peng and Jih-Sheng Lai, Generalized Instantaneous Reactive Power Theory for Three-phase Power Systems, IEEE Transactions on instrumentation and measurement, vol. 45, no. 1, february 1996. [2] B.H. Li, S.S. C hoi and D.M.Vilathgamuwa Design considerations on the line-side filter used in the dynamic voltage restorer IEE Proc.-Gmer. Trunsm.Distrib., Vol. 148, No. 1. January 2001. [3] B.H. Li, S.S. Choi and D.M. Vilathgamuwa, Transformerless dynamic voltage restorer, IEE Proc,-Gener. Trunsm.Dktrib., Vol. 149, No. 3, May 2002. [4] Arindam Ghosh and Gerard Ledwich Compensation of Distribution System Voltage Using DVR IEEE Transactions on power delivery, vol. 17, no. 4, october 2002. [5] Chris Fitzer, Atputharajah Arulampalam, Mike Barnes and Rainer Zurowski, Mitigation of Saturation in Dynamic Voltage Restorer Connection Transformers,IEEE Transactions on power electronics, vol. 17, no. 6, november 2002. [6] Changjiang Zhan, Atputharajah Arulampalam and Nicholas Jenkins, Four-Wire Dynamic Voltage Restorer Based on a Three-Dimensional Voltage Space Vector PWM Algorithm, IEEE Transactions on power electronics, vol. 18, no. 4, july 2003. [7] Chi-Jen Huang, Shyh-Jier Huang and Fu-Sheng Pai Design of Dynamic Voltage Restorer With Disturbance-Filtering Enhancement IEEE Transactions on power electronics, vol. 18, no. 5, september 2003. [8] C.-J. Zhan, X.G. Wu, S. Kromlidis, V.K. Ramachandara murthy, M. Barnes, N. Jenkins and A.J. Ruddell Two electrical models of the lead-acid battery used in a dynamic voltage restorer, IEE proc, Gener-Transm-Distrib, vol.150, No.2, March 2003. [9] Francisco Jurado, Neural Network Control for Dynamic Voltage Restorer, IEEE Transactions on industrial electronics, vol. 51, no. 3, june 2004. [10] EngKian Kenneth Sng, S. S. Choi and D. Mahinda Vilathgamuwa, Analysis of Series Compensation and DC-Link Voltage Controls of a Transformer-less Self-Charging Dynamic Voltage Restorer IEEE Transactions on power delivery, vol. 19, no. 3, july 2004. [11] Sang-Joon Lee ; Sch. of Electr. Eng. & Comput. Sci., Seoul Nat. Univ., South Korea ; Hyosung Kim ; Seung-Ki Sul; A novel control method for the compensation voltages in dynamic voltage restorers; Applied Power Electronics Conference and Exposition, 2004. APEC '04. Nineteenth Annual IEEE (Volume:1 ); 2004 [12] Chris Fitzer, Mike Barnes and Peter Green, Voltage Sag Detection Technique for a Dynamic Voltage Restorer, IEEE Transactions on industry applications, vol. 40, no. 1, january/february 2004. [13] Changjiang Zhan, Vigna Kumaran Ramachandaramurthy, Atputharajah Arulampalam, Chris Fitzer, Stylianos Kromlidis, Mike Barnes and Nicholas Jenkins, Dynamic Voltage Restorer Based on Voltage-Space-Vector PWM Control IEEE [14] Arindam Ghosh and Avinash Joshi, The Concept and Operating Principles of a Mini Custom Power Park, IEEE Transactions on power delivery, vol. 19, no. 4, october 2004. [15] Arindam Ghosh,Amit Kumar Jindal and Avinash Joshi Design of a Capacitor-Supported Dynamic Voltage Restorer (DVR) for Unbalanced and Distorted Loads IEEE Transactions on power delivery, vol. 19, no. 1, january 2004 [16] Fernandes, D.A. ; Dept. of Electr. Eng., Fed. Univ. of Campina Grande ; Naidu, S.R. ; Costa, F.F.; A Differentiation Matrix for Simulating the Steady-state Response of Power Converters; Power Electronics Specialists Conference, 2005. PESC '05. IEEE 36th; 16-16 June 2005 [17] Yun Wei Li ; Sch. of Electr. & Electron. Eng., Nanyang Technol. Univ., Singapore ; Vilathgamuwa, D.M. ; Poh Chiang Loh; A grid-interfacing power quality compensator for threephase three-wire microgrid applications; Power Electronics, IEEE Transactions on (Volume:21, Issue: 4 ); july 2006 [18] Bingsen Wang, GiriVenkataramanan and Mahesh Illindala, Operation and Control of a Dynamic Voltage Restorer Using Transformer Coupled H-Bridge Converters, IEEE Transactions on power electronics, vol. 21, no. 4, july 2006. [19] Amruta N. Jog, Narayan G. Apte, An Adaptive Hysteresis Band Current Controlled Shunt Active Power Filter, 2007 IEEE. [20] Yun Wei Li ; Nanyang Technol. Univ., Singapore ; Vilathgamuwa, D.M. ; Poh Chiang Loh ; Blaabjerg, F.; A Dual-Functional Medium Voltage Level DVR to Limit Downstream Fault Currents; Power Electronics, IEEE Transactions on (Volume:22, Issue: 4 ); July 2007 [21] Li, G.J. ; Tsinghua Univ., Beijing ; Zhang, X.P. ; Choi, S.S. ; Lie, T.T. ; Control strategy for dynamic voltage restorers to achieve minimum power injection without introducing sudden phase shift; Generation, Transmission & Distribution, IET (Volume:1, Issue: 5 ); September 2007 [22] Marei, M.I. ; Ain Shams Univ., Cairo ; El-Saadany, E.F. ; Salama, M.M.A.; A New Approach to Control DVR Based on Symmetrical Components Estimation; Power Delivery, IEEE Transactions on (Volume:22, Issue: 4 ); Oct. 2007, ijrrest.org 11 P a g e