Regency ellavista 1XT-1 Gas Fireplace Specifications: Model 1XT-NG 1XT-LP Fuel Type Natural Gas Propane Gas Minimum Supply Pressure Manifold Pressure - High Manifold Pressure - Low 5 W.C. (1.5 kpa) 3.5 W.C. (.7 kpa) 1. W.C. (. kpa) 11 W.C. (.7 kpa) 1 W.C. (.9 kpa). W.C. (1. kpa) Orifi ce Size #3 DMS #9 DMS Minimum Input ltitude -5 ft. (-137m) Maximum Input ltitude -5 ft. (-137m) 3, TU/h (.79 kw),5 TU/h (1.5 kw) 9,5 TU/h (.5kW) 37,5 TU/h (1.99 kw) Vent Sizing 5 Inner / Outer 5 Inner / Outer pproved Venting Systems Flex Vent Systems: FPI strocap Flex Vent Rigid Pipe Vent Systems: Simpson Direct Vent Pro Selkirk Direct-Temp Metal-Fab Sure Seal ICC Excel Direct Framing Dimensions: Framing Description 1XT Dimensions M Framing Width 7-1/"(1mm) N Framing Height 9-1/" (157mm) O (Rear Vent) Framing Depth - Rear Vent 3-1/" (591mm) O (Top Vent) Framing Depth - Top Vent -5/" (575mm) P Corner Facing Wall Width -1/" (153mm) Q Corner Facing Wall Width 5-3/1" (13mm) R (Rear Vent) Framed Chase Ceiling - Rear 9-1/" (157mm) R (Top Vent) Framed Chase Ceiling - Top 5-1/" (13mm) S (Rear Vent) Vent Centerline Height - Rear -1/" (7mm) S (Top Vent) Vent Centerline Height - Top 7-1/" (17mm) Rigid / Flex T Gas Connection Height 1-1/" (3mm) U Gas Connection Inset 5" (17mm) V Gas Connection Width 3-1/" (mm) W Non-Combustible Top Height 13-1/" (33mm) ** Important: Framing height requires consideration of the hearth depth. Dimension N = N + the thickness of the installed hearth. R Unit Dimensions: -11/1 (11mm) Non-Combustible N Drywall, Wood (or other facing) W Non-Combustible Non-Combustible Facing 3-3/1 (97mm) M O 11" (79mm) dia. Hole through wall Vent. 19-7/1 (9mm) -5/1 (57mm) P Rear Vent S Top Vent S T 1 (5mm) 1-11/1 (159mm) (1mm) 35 (9mm) 3-11/1 (93mm) 9-3/1 (19mm) 3-1/ (591mm) 13-3/1 (335mm) -1/ (7mm) 3-3/ (9mm) 3-1/ (97mm) (17mm) 5-1/" Q -3/" (13mm) Material 1-3/" (1mm) 3-3/" (933mm) U V Opening for gas connection Non-Combustible Requirements: Min. 13-1/" (33mm) 7-1/" (1mm) Framing Min. 3-1/ (9mm) Min. 3-1/ (9mm)
Regency ellavista 1XT -1 Gas Fireplace Clearance Requirements: E D F C lcove F Minimum Vent Clearances to Combustibles Horizontal Top 3" (7mm) Horizontal Side " (51mm) Horizontal ottom " (51mm) Vertical Vent " (51mm) E Clearance: Dimension Measured From: : Mantel Height (min.) 15" (31mm) Top of Fireplace Opening : Sidewall 9" (9mm) Side of Fireplace Opening C: Ceiling 33-3/" (933mm) Top of Fireplace Opening D: Mantel Depth (max.) 1" (3mm) 3-1/" (19mm) from Top of Fireplace Opening E: lcove Width " (15mm) Wall to Wall (Minimum) F: lcove Depth 3" (9mm) Front to ack Wall (Maximum) Notes: " No Hearth Required NOTE: 1" deep non-combustible hearth pad is recommended for hardwood fl ooring and carpet. Combustible Mantels: Due to the extreme heat this fireplace emits, the mantel clearances are critical. Combustible mantel clearances from top of front facing are shown in the diagram on the right. Mantel Clearances 1XT From Top of Fireplace Opening C D 35-1/" (95mm) 3-1/" (591mm) 19-1/" (95mm) 15" (31mm) Note: Ensure the paint that is used on the mantel and the facing is heat resistant or the paint may discolour. 1 1 Mantel Leg Clearances: 1 7 Combustible Top View 1-1/ Side Wall (Measured from side of Fireplace Opening) Mantel leg 1-1/" Mantel leg 7 llowable mantel leg projection. 3" Inches C To Floor D Top of Fireplace Opening 1" 13-1/ Standoff Side View
Regency ellavista 1XT -1 Gas Fireplace Venting rrangements for Horizontal Terminations: The diagrams show all allowable combinations of vent runs with 5" x " venting using the Regency direct vent system or rigid vent system. vent guard should be used whenever the termination is lower than the specifi ed minimum or as per local codes. For horizontal terminations the Regency Direct Vent Flex System may be used for installations upto a maximum continuous vent length of 1ft (3.m). Note: Must use optional rigid pipe adaptor (Part # 77-99) when using Rigid Pipe vent systems. Maintain clearance to combustibles. Horizontal vent must be supported every 3 feet. Firestops are required at each floor level and whenever passing through a wall. 1 1 Max. 3 (.9m) Rigid or Flex 7-1/" (1.m) Max. 3"(.9m) - 1/"(.7m) Vent Restrictor - Set 1 Factory Setting - No Restrictor Required IMPORTNT Must use Rear Venting Deflector packaged with unit in rear vent horizontal termination applications. Horizontal Terminations - Rigid Pipe 5 x : Top Vent - No Vertical Rise When venting with a 9 elbow directly off the unit Flex vent or approved Rigid Vent System Max. 3 ft. horizontal run Rear Vent w/ Horizontal Termination Max. 3ft. horizontal run Horizontal Termination Cap Rigid Pipe daptor Horizontal Termination Cap o 9 Elbow Rigid Pipe daptor IMPORTNT Must use Rear Venting Deflector packaged with unit in rear vent horizontal termination applications.
Regency ellavista Horizontal Terminations: STROCP XL & RIGID RER VENT KIT FOR CORNER INSTLLTIONS Designed for a minimum vent confi guration when using a rear vent application with a horizontal termination in a corner installation. Kit# 9-1 Includes: 1 strocap XL 9-3/P 1 Rigid Pipe daptor 77-99 1 9-5 1 5DV-WT Placement of the Unit into the Corner ack Top Corner of Unit to Wall 3" Inside Corner out along the Wall -1/" cross the Face of the Unit, Wall to Wall 5-3/1" - Clearance to Outside Corner 13" - Clearance to Inside Corner 5-1/" 1 " Galvanized Rigid Pipe 5DV- 1-1/" Galvanized Pipe Extension 5DV- 1 5º Galvanized Elbow 5DV-E5 1 9ml MillPac 9-1 Standoff (Optional) 3-1/ strocap XL 5-3/1 5 elbow Rigid Pipe daptor IMPORTNT Must use Rear Venting Deflector packaged with unit in rear vent horizontal termination applications. asic Horizontal & Vertical Terminations: Rigid Pipe Vent Systems offer a complete line of component parts for installation of both horizontal and vertical installations. Many items are offered in decorative black, as well as galvanized fi nish. Vertical Terminal Storm Collar The minimum components required for a basic Horizontal Termination are: 1 strocap XL Termination Cap 1 9 o Elbow 1 Rigid Pipe daptor 1 1 Length of rigid pipe to suit wall thickness The minimum components required for a basic Vertical Termination are: 1 Vertical Termination Cap 1 Rigid Pipe daptor 1 Lengths of pipe to adequately penetrate roof 1 Ceiling Firestop 1 Flashing 1 Storm Collar Wall thickness is measured from the back standoffs to the inside mounting surface of termination cap. For siding other than vinyl, furring strips may be used, instead of a vinyl siding standoff, to create a level surface to mount the vent terminal. The Terminal must not be recessed into siding. Measure the wall thickness including furring strips. Flashing Ceiling Firestop Pipe Length o 9 Elbow Rigid Pipe daptor (77-99) strocap XL Termination Cap (Part #9-3/P) (Mandatory in all Horizontal Terminations) Vent Guard - if required* (Part #9-5/P) If a Standoff is required (it must be used with vinyl siding), measure to outside surface of wall without siding and add inches.
Regency ellavista VENTING RRNGEMENTS FOR HORIZONTL TERMINTIONS FOR VERTICL TERMINTIONS The diagram shows all allowable combinations of vertical runs with horizontal terminations, using one 9 o (two 5 o elbows equal one 9 o elbow). Maintain clearances to combustibles as listed in "Clearances" section Horizontal vent must be supported every 3 feet. Firestops are required at each floor level and whenever passing through a wall. wall thimble is mandatory for all horizontal terminations due to high temperatures. 1 1 1 1 The shaded area in the diagram shows all allowable combinations of straight vertical and offset to vertical terminations, using two 9 o elbows, with Rigid Pipe Venting Systems for Propane and Natural Gas. Two 5 o elbows equal to one 9 o elbow. Maximum of four 5 o elbows allowed. Vent must be supported at offsets. Firestops are required at each floor level and whenever passing through a wall. Maintain clearances to combustibles as listed in the "Clearances" section. Refer to the "Vent Restrictor Position" section for details on how to change the vent restrictor from the factory setting to 3-1/" opening, -1/"opening and to 1-1/" opening. 1 1 1 1 Restrictor 1-1/ Open Set 3 3 3 1 1 Restrictor -1/ Open Set Restrictor 3-1/ Open Set 1 3 3 3 Maximum: 35.5 ft. (1. m) Restrictor 1-1/ Open Set 3 7-1/" (17mm) Minimum Height Requirement 1 Restrictor -1/ Open Set 1 1 1 Restrictor 3-1/ Open Set 1 Maximum 1 Centerline to Centerline Min. 7-1/ (1.m) Minimum (.m) Maximum Centerline to Centerline