A. Product Data: For each electrical identification product indicated.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

Piping & Equipment Identification

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR HVAC PIPING, DUCTWORK AND EQUIPMENT

SECTION ELECTRICAL IDENTIFICATION

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

SECTION IDENTIFICATION OF HVAC PIPING AND EQUIPMENT. A. Section includes nameplates, tags, stencils and pipe markers.

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

SECTION MECHANICAL IDENTIFICATION

1. ASME A Scheme for the Identification of Piping Systems.

SECTION IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT

SECTION IDENTIFICATION OF PLUMBING, PIPING AND EQUIPMENT. A. Section includes nameplates, tags, stencils and pipe markers.

SECTION MECHANICAL IDENTIFICATION

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017

B. Samples: For color, letter style, and graphic representation required for each identification material and device.

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SECTION IDENTIFICATION DEVICES

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR ELECTRONIC SAFETY AND SECURITY

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing).

SECTION COMMON WORK RESULTS FOR HVAC

Industrial Pipe Marking

Part VIII Electrical GENERAL REQUIREMENTS CHAPTER 33

SECTION WIRE AND CABLES. A. The CONTRACTOR shall provide wires and cable, complete and operable, in accordance with the Contract Documents.

SECTION PANELBOARDS

Michigan State University Construction Standards SWITCHBOARDS, PANELBOARDS, AND CONTROL CENTERS PAGE

Page PRODUCT DESCRIPTION

A. Deviation from this standard must be approved by the Project Architect.

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410

SECTION Display Case Door Series 1301-CM

The Saddle Rack. For Power And Communication Cables

SECTION SIGNAGE

SECTION IDENTIFYING DEVICES

TCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II

SECTION CABLE TRAYS

The School District of Palm Beach County Project Name SDPBC Project No. SECTION ( ) SIGNAGE PART 1 GENERAL 1.1 RELATED DOCUMENTS

Guide Specification Section Interior Suspended Sliding Glass Doors

SECTION COMMUNICATIONS COPPER BACKBONE CABLING

B. Manufacturers: Square-D, G.E. or Westinghosue.

SECTION INTERIOR SIGNAGE

SECTION MECHANICAL IDENTIFICATION

IDENTIFICATION DEPOT, INC. 206 East Second Street Washington, NC PHONE FAX

Electrical Identification

SECTION MEDIUM-VOLTAGE CABLES

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

SHEET METAL FLASHING AND TRIM Christ on the Mountain

CONTINUING EDUC ATION

SOLAR PV MICROINVERTER/ACM STANDARD PLAN - COMPREHENSIVE Microinverter and ACM Systems for One- and Two- Family Dwellings

SECTION CONCRETE REINFORCEMENT FOR STEAM UTILITY DISTRIBUTION

SECTION MECHANICAL IDENTIFICATION

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION MECHANICAL IDENTIFICATION. 1. Identification of mechanical products installed under Division 15.

Product Guide Specification

SECTION SHEET METAL FLASHING AND TRIM

COMMON WORK RESULTS FOR INTEGRATED AUTOMATION DESIGN AND CONSTRUCTION STANDARD

Fluid Sealing Association

Ash Brook Golf Course Scotch Plains, New Jersey

SECTION COMMUNICATIONS COPPER BACKBONE CABLING

SECTION FRAMELESS GLASS SLIDING BI-FOLD SHOWER DOOR HARDWARE

NEC 2014 Code Changes

Page PRODUCT DESCRIPTION

ROWAN COUNTY AIRPORT APRIL 2017 TERMINAL EXPANSION

Bol FEATURES: SPECIFICATIONS: 8' 24' Round Tapered and Straight Wood Poles STRUCTURA INC. FIXTURE TYPE: PROJECT NAME:

B. Division-16 Basic Materials and Methods section apply to work specified in this section.

Guide Specification Section Interior Aluminum Doors and Frames

B. Related Requirements: 1. Section "Interior Painting" for priming and backpriming of interior finish carpentry.

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.

Shrink temperature of 120 C. Rated for 600V, 90 C continuous use. T&B recommended up to 1kV. HS Series Specifications

SECTION INTERIOR FINISH CARPENTRY PART 1 - GENERAL 1.1 RELATED DOCUMENTS

SECTION CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY

Copyright 2017 AIA MasterSpec Premium 05/17 PRODUCT MASTERSPEC LICENSED BY ARCOM TO WEREVER PRODUCTS, INC.

FT DIX ELEMENTARY SCHOOL PHASE VII, CLASSROOM ADDITION PEMBERTON TOWNSHIP REGAN YOUNG ENGLAND BUTERA, PC PROJECT #5349A

A. Section includes surface preparation and the application of paint systems on exterior substrates.

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.

SECTION ARCHITECTURAL WOOD CASEWORK

SECTION FINISH HARDWARE

Wisconsin Contractors Institute Continuing Education

6o ft (18.3 m) Southwest Windpower, Inc West Route 66 Flagstaff, Arizona USA Phone: Fax:

Installation Instructions. Materials Needed. Parts Included. Tools You Will Need

American Electrical Institute

b. B aluminum and aluminum-alloy extruded bar, rod, wire, shape and tube

SECTION TRACER WIRE FOR NONMETALLIC PIPE

NOTICE OF RULE MAKING PROCEEDINGS AND PUBLIC HEARING

A. All trim that has been damages, broken, or missing shall be repaired or replaced with material of the same size, shape, and type.

SECTION BUILDING WIRE AND CABLE

SECTION COMMUNICATIONS COPPER OSP CABLING

PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES

Installation Instructions

SECTION DISTRIBUTION SWITCHBOARDS

SECTION EQUIPMENT WIRING

SECTION DISTRIBUTION SWITCHBOARDS

SECTION FINISH CARPENTRY PART 1 GENERAL. 1.1 SECTION INCLUDES A. Interior Finish Carpentry Work: 1. Refer to schedule at end of Section.

Heat-Shrinkable Tubing

Essex County College - West Essex Campus Addition And Renovations dlb # / SECTION EXPANSION FITTINGS AND LOOPS FOR HVAC PIPING

FLOOR ANCHOR SYSTEM APPLICATIONS L TRACK APPLICATIONS

Chevy Chase Club June 30, 2008 Bowie Gridley Architects

Heatex Identification System. The Heatex Product Programme Offers:

Transcription:

SECTION 16075 ELECTRICAL IDENTIFICATION PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.02 SUMMARY A. Section Includes: 1. Identification for raceways. 2. Identification of power cables. 3. Identification for conductors. 4. Underground-line warning tape. 5. Equipment identification labels. 6. Miscellaneous identification products. 1.03 ACTION SUBMITTALS A. Product Data: For each electrical identification product indicated. 1.04 QUALITY ASSURANCE A. Comply with ANSI A13.1 and IEEE C2. B. Comply with NFPA 70. C. Comply with 29 CFR 1910.144 and 29 CFR 1910.145. D. Comply with ANSI Z535.4 for safety signs and labels. E. Adhesive-attached labeling materials, including label stocks, laminating adhesives, and inks used by label printers, shall comply with UL 969. 1.05 COORDINATION A. Coordinate identification names, abbreviations, colors, and other features with requirements in other Sections requiring identification applications, Drawings, Shop Drawings, manufacturer's wiring diagrams, and the Operation and Maintenance Manual; and with those required by codes, standards, and 29 CFR 1910.145. Use consistent designations throughout Project. CONTRACT NO. 2773 16075-1 ELECTRICAL IDENTIFICATION

B. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be applied. C. Coordinate installation of identifying devices with location of access panels and doors. PART 2 - PRODUCTS 2.01 POWER RACEWAY IDENTIFICATION MATERIALS A. Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of color field for each raceway size. B. Metal Tags: Brass or aluminum, 2 by 2 by 0.05 inch (50 by 50 by 1.3 mm), with stamped legend, punched for use with self-locking cable tie fastener. 2.02 POWER CABLE IDENTIFICATION MATERIALS A. Comply with ANSI A13.1 for minimum size of letters for legend and for minimum length of color field for each cable size. B. Heat-Shrink Preprinted Tubes: Flame-retardant polyolefin tube with machine-printed identification label. Sized to suit diameter of and shrinks to fit firmly around cable it identifies. Full shrink recovery at a maximum of 200 deg F (93 deg C). Comply with UL 224. 1. Marker for Tags: Machine-printed, permanent, waterproof, black ink marker recommended by printer manufacturer. 2.03 CONDUCTOR IDENTIFICATION MATERIALS A. Color-Coding Conductor Tape: Colored, self-adhesive vinyl tape not less than 3 mils (0.08 mm) thick by 1 to 2 inches (25 to 50 mm) wide. B. Heat-Shrink Preprinted Tubes: Flame-retardant polyolefin tube with machine-printed identification label. Sized to suit diameter of and shrinks to fit firmly around conductor it identifies. Full shrink recovery at a maximum of 200 deg F (93 deg C). Comply with UL 224. 2.04 UNDERGROUND-LINE WARNING TAPE A. Tape: 1. Recommended by manufacturer for the method of installation and suitable to identify and locate underground electrical utility lines. 2. Printing on tape shall be permanent and shall not be damaged by burial operations. 3. Tape material and ink shall be chemically inert, and not subject to degrading when exposed to acids, alkalis, and other destructive substances commonly found in soils. B. Color and Printing: CONTRACT NO. 2773 16075-2 ELECTRICAL IDENTIFICATION

1. Comply with ANSI Z535.1 through ANSI Z535.5. 2. Inscriptions for Red-Colored Tapes: ELECTRIC LINE, HIGH VOLTAGE. C. Tag: Type ID: 1. Detectable three-layer laminate, consisting of a printed pigmented polyolefin film, a solid aluminum-foil core, and a clear protective film that allows inspection of the continuity of the conductive core, bright-colored, continuous-printed on one side with the inscription of the utility, compounded for direct-burial service. 2. Overall Thickness: 5 mils (0.125 mm). 3. Foil Core Thickness: 0.35 mil (0.00889 mm). 4. Weight: 28 lb/1000 sq. ft. (13.7 kg/100 sq. m). 5. 3-Inch (75-mm) Tensile According to ASTM D 882: 70 lbf (311.3 N), and 4600 psi (31.7 MPa). 2.05 EQUIPMENT IDENTIFICATION LABELS A. Self-Adhesive, Engraved, Laminated Acrylic or Melamine Label: Adhesive backed, with white letters on a dark-gray background. Minimum letter height shall be 3/8 inch (10 mm). B. Engraved, Laminated Acrylic or Melamine Label: Punched or drilled for screw mounting. White letters on a dark-gray background. Minimum letter height shall be 3/8 inch (10 mm). 2.06 MISCELLANEOUS IDENTIFICATION PRODUCTS A. Fasteners for Labels and Signs: Self-tapping, stainless-steel screws or stainless-steel machine screws with nuts and flat and lock washers. PART 3 - EXECUTION 3.01 INSTALLATION A. Verify identity of each item before installing identification products. B. Location: Install identification materials and devices at locations for most convenient viewing without interference with operation and maintenance of equipment. C. Apply identification devices to surfaces that require finish after completing finish work. D. Self-Adhesive Identification Products: Clean surfaces before application, using materials and methods recommended by manufacturer of identification device. Use where mechanical fasteners are not allowed or recommended by manufacture. E. Attach signs and plastic labels that are not self-adhesive type with mechanical fasteners appropriate to the location and substrate. F. Aluminum Wraparound Marker Labels and Metal Tags: Secure tight to surface of conductor or cable at a location with high visibility and accessibility. CONTRACT NO. 2773 16075-3 ELECTRICAL IDENTIFICATION

G. Underground-Line Warning Tape: During backfilling of trenches install continuous underground-line warning tape directly above line at 6 to 8 inches (150 to 200 mm) below finished grade. Use multiple tapes where width of multiple lines installed in a common trench exceeds 16 inches (400 mm) overall. H. Painted Identification: Comply with requirements in painting Sections for surface preparation and paint application. 3.02 IDENTIFICATION SCHEDULE A. Power-Circuit Conductor Identification, 600 V or Less: For conductors in vaults, pull and junction boxes, manholes, and handholes, use color-coding conductor tape to identify the phase. 1. Color-Coding for Phase Identification, 600 V or Less: Use colors listed below for ungrounded service, feeder and branch-circuit conductors. a. Color shall be factory applied[ or field applied for sizes larger than No. 8 AWG, if authorities having jurisdiction permit]. b. Colors for 240/120-V Circuits: 1) Line 1: Red. 2) Line 2: Black. 3) Neutral: White. c. Field-Applied, Color-Coding Conductor Tape: Apply in half-lapped turns for a minimum distance of 6 inches (150 mm) from terminal points and in boxes where splices or taps are made. Apply last two turns of tape with no tension to prevent possible unwinding. Locate bands to avoid obscuring factory cable markings. B. Control-Circuit Conductor Identification: For conductors and cables in pull and junction boxes, manholes, and handholes, use self-adhesive, self-laminating polyester labels with the conductor or cable designation, origin, and destination. C. Control-Circuit Conductor Termination Identification: For identification at terminations provide heat-shrink preprinted tubes with the conductor designation. D. Auxiliary Electrical Systems Conductor Identification: Identify field-installed alarm, control, and signal connections. 1. Identify conductors, cables, and terminals in enclosures and at junctions, terminals, and pull points. Identify by system and circuit designation. 2. Use system of marker tape designations that is uniform and consistent with system used by manufacturer for factory-installed connections. 3. Coordinate identification with Project Drawings, manufacturer's wiring diagrams, and the Operation and Maintenance Manual. E. Locations of Underground Lines: Identify with underground-line warning tape for power, lighting, communication, and control wiring and optical fiber cable. 1. Limit use of underground-line warning tape to direct-buried cables. CONTRACT NO. 2773 16075-4 ELECTRICAL IDENTIFICATION

2. Install underground-line warning tape for both direct-buried cables and cables in raceway. F. Equipment Identification Labels: On each unit of equipment, install unique designation label that is consistent with wiring diagrams, schedules, and the Operation and Maintenance Manual. Apply labels to central or master units of each system. Systems include power and lighting control systems unless equipment is provided with its own identification. 1. Equipment to Be Labeled: a. Panelboards: Typewritten directory of circuits in the location provided by panelboard manufacturer. Panelboard identification shall be engraved, laminated acrylic or melamine label. b. Enclosures and electrical cabinets. c. Enclosed controllers. d. Relays. END OF SECTION CONTRACT NO. 2773 16075-5 ELECTRICAL IDENTIFICATION