Ground fault supervision of 4 feeders with 7SJ82 or 7SJ85 with 4x I, 4x V

Similar documents
Acquisition of transformer tap positions via an analog measurement transformer

Breaker Pole Discrepancy Function

SIPROTEC 5 Application Note

Impedance protection on power transformer.

Line protection with transformer in the protection zone

SIPROTEC 5 Application Note

SIPROTEC 5 Application. SIP5-APN-025-en: 7UT8 Autotransformer bank with 2 sets of CT inside the delta connection of the compensation side

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Answers for energy

Fast fault location in medium-voltage cable and overhead line networks siemens.com/short-circuit-indicator

Application of Low-Impedance 7SS601 Busbar Differential Protection

SIPROTEC Protection Technology. The Basis for Highest Availability of Supply

ARC FLASH PPE GUIDELINES FOR INDUSTRIAL POWER SYSTEMS

7PG21 Solkor R/Rf Pilot Wire Current Differential Protection Energy Management

Repair & Retrofit new life for old transformers. Repair and retrofitting through TLM Transformer Lifecycle Management. Answers for energy.

Load Shedding (7RW80)

Overcurrent and Overload Protection of AC Machines and Power Transformers

SIPROTEC. Multi-Functional Generator Protection Relay 7UM61. Preface. Contents. Introduction 1. Functions 2. Mounting and Commissioning 3

SIPROTEC Feeder Automation Controller 7SC80

Reyrolle Protection Devices. 7PG21 Solkor R/Rf Pilot Wire Current Differential Protection. Answers for energy

Overcurrent Protection / 7SJ45

BUS2000 Busbar Differential Protection System

SIPROTEC. Power Supply Transfer Device 7VU68. Preface. Table of contents. Data of the PROFIBUS-DP messages 1. Standard mappings

EPSITRON Electronic Circuit Breakers Compact and Precise ECBs for DC Circuits

SIPROTEC. Multifunction protection with control 7SJ61 / 7SJ62 / 7SJ64. Preface. Table of Contents. Notes to SIPROTEC objects 1

SIPROTEC 5 V1.1 High-Voltage Bay Control Unit 6MD85/86. Technical Data. Extract from manual C53000-G5040-C015-1, chapter 11.

Relion 605 series Self-Powered Feeder Protection REJ603 Product Guide

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

889 Advanced Generator Protection Technical Note

3EK8 distribution class surge arresters. Catalogue HP-AR Version siemens.com/arresters

SIPROTEC Compact 7SJ80 V4.6 Overcurrent Time Protection

Reyrolle Protection Devices. 7PG18 - TR-A High speed tripping Relay. Energy Management.

Convincing technology creates compact performance

Extensive LV cable network. Figure 1: Simplified SLD of the transformer and associated LV network

Power System Protection Part VII Dr.Prof.Mohammed Tawfeeq Al-Zuhairi. Differential Protection (Unit protection)

Overview/Applications

SECTION SHORT CIRCUIT, COMPONENT PROTECTION, FLASH HAZARD AND SELECTIVE COORDINATION STUDY

Centralized busbar differential and breaker failure protection function

POWER SYSTEM ANALYSIS TADP 641 SETTING OF OVERCURRENT RELAYS

SIPROTEC 7SJ600 Numerical Overcurrent, Motor and Overload Protection Relay

Appendix S: PROTECTION ALTERNATIVES FOR VARIOUS GENERATOR CONFIGURATIONS

Application Guide High Impedance Differential Protection Using SIEMENS 7SJ602

E N G I N E E R I N G M A N U A L

ABB AG - EPDS. I S -limiter The worldʼs fastest limiting and switching device

Automatic reclosing function for high voltage networks

SIPROTEC easy 7SJ46 Numerical Overcurrent Protection Relay

Relay Coordination in the Protection of Radially- Connected Power System Network

SECTION OVERCURRENT PROTECTIVE DEVICE COORDINATION STUDY

Busbars and lines are important elements

Transformer protection IED RET 670

Excitation Systems RG3 - T4. Transistorized Excitation Systems for Synchronous Generators. Power Generation

This section applies to the requirements for the performance of power system studies by both the Design Engineer and the Contractor.

70 TH ANNUAL CONFERENCE FOR PROTECTIVE RELAY ENGINEERS TEXAS A&M UNIVERSITY COLLEGE STATION, TEXAS APRIL 3 APRIL 6, 2017

SIPROTEC 7SD60 Numerical Current Differential Protection Relay for Two Pilot-Wire Link

More flexibility for the manufacturing industry

SIPROTEC 7SS60 Centralized Numerical Busbar Protection

Electromechanical Power Products

Protecting Large Machines for Arcing Faults

SIEMENS SIPROTEC 7SS60 V3.1. Centralized Numerical Busbar Protection. www. ElectricalPartManuals. com E50417-G1176-C132-A2

SIPROTEC 5 V1.1 Distance Protection, Line Differential Protection and Breaker Management for 1-Pole and 3-Pole Tripping 7SA87, 7SD87, 7SL87, 7VK87

KENYA ELECTRICITY GENERATING COMPANY LTD

POWER SYSTEM ANALYSIS TADP 641 SETTING EXAMPLE FOR OVERCURRENT RELAYS

SIPROTEC 5 Generator Protection 7UM85. V7.50 and higher. Technichal Data. Extract from manual C53000-G5040-C027-3, chapter 11.

V7.50 and higher Low-Impedance Busbar Protection 7SS85

Babak Enayati National Grid Thursday, April 17

Company Replaces previous document Document ID Issue E.ON Elnät Sverige AB Ny engelsk utgåva D

SYNCHRONISING AND VOLTAGE SELECTION

MV ELECTRICAL TRANSMISSION DESIGN AND CONSTRUCTION STANDARD. PART 1: GENERAL 1.01 Transformer

AN4269. Diagnostic and protection features in extreme switch family. Document information


Overcurrent Protection 7SJ82/7SJ85. Technical Data. Extract from manual C53000-G5040-C017-6, chapter 11. Energy Automation

Embedded Generation Connection Application Form

Back to the Basics Event Analysis Using Symmetrical Components

Distance Relay Response to Transformer Energization: Problems and Solutions

NERC Protection Coordination Webinar Series June 9, Phil Tatro Jon Gardell

NEW DESIGN OF GROUND FAULT PROTECTION

MULTI FUNCTION OVER CURRENT AND EARTH FAULT RELAY[50/51X3,50/51N]

Reyrolle Protection Devices. 7SG14 Duobias M Transformer Protection. Answers for energy

Overcurrent Elements

ADDENDUM NO. 2 PROJECT: COURTLAND PUMP STATION CONTRACT: IFB NO COM.00030

Solutions to Common Distribution Protection Challenges

SIPROTEC 5 V7.50 and higher Overcurrent Protection 7SJ82/7SJ85 Technical Data Extract from manual C53000-G5040-C017-8, chapter 12 Energy Automation

Quick Reference Guide. DF5-... Frequency Inverters 02/02 AWB GB

Table of Contents. Introduction... 1

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

This document covers common questions concerning the design of an effectively grounded system.

Types CDG 11 and CDG 16 Inverse Time Overcurrent and Earth Fault Relay

U I. Time Overcurrent Relays. Basic equation. More or less approximates thermal fuse. » Allow coordination with fuses 9/24/2018 ECE525.

Electricity Fundamentals Training System

Setting Generic Distance Relay UTP-100#WPSC1. in the. Computer-Aided Protection Engineering System (CAPE)

Fuseless Capacitor Bank Protection

Predicting the Voltage Sag Performance of Electricity Distribution Networks

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

EE Lecture 14 Wed Feb 8, 2017

Relion 605 series. Self-Powered Feeder Protection REJ603 Application manual

DIGITAL UNDER-OVER VOLTAGE RELAY DMPVR SERIES

Embedded Generation Connection Application Form

Distributed busbar differential protection function and breaker failure protection

La protection sélective des réseaux électriques

REB500 TESTING PROCEDURES

SIPROTEC 7SD60 Numerical Pilot-Wire Current Differential Protection Relay

Transcription:

with 7SJ82 or 7SJ85 with 4x I, 4x V SIP5-APN-029, Edition 1 www.siemens.com/protection

SIPROTEC 5 Application Note with 7SJ82 or 7SJ85 with 4x I, 4x V SIP5-APN-029, Edition 1 Content 1 with 7SJ82 or 7SJ85 with 4x I, 4x V 3 1.1 Introduction 3 1.2 Device selection 3 1.3 DIGSI Settings 3 1.3.1 Measuring points MP 3 1.3.2 Function groups FG 4 1.3.3 Connection of the measuring points with the function groups 4 1.3.4 Functional overview in DIGSI 5 editor 6 1.3.5 Ground fault indication 6 1.4 Summary 7 SIP5-APN-029 2 Edition 1

1 with 7SJ82 or 7SJ85 with 4x I, 4x V 1.1 Introduction This application describes the ground fault supervision of four feeders realized with one SIPROTEC 7SJ82 or 7SJ85 with only four current and four voltage inputs. The ground fault supervision supposed to be the only function required in each of the feeders. 1.2 Device selection An overcurrent relay 7SJ82 or 7SJ85 with 4x I and 4x V and 120 function points (if only the ground fault supervision is required) is selected. The overview of the application with the connections of the device to the transformers and the functional structure of the device (measuring points, function groups and functions) is as follow: Fig.1: Overview of the device with function groups and measurement points. Hint: The realization with one 7SJ82 for this application depends on the required sensitivity of the ground current. If the secondary ground fault current to be measured should be smaller than 30mA, then a 7SJ85 with current transformer with sensitive inputs is required. The 7SJ82 does not offer this variant. 1.3 DIGSI Settings 1.3.1 Measuring points MP The measuring points displayed in fig. 1 must be configured in the device. The measuring points to be added in the measuring-point routing, the not used measuring points are deleted. The measuring points are routed to the transformer inputs, refer to fig. 2. Edition 1 3 SIP5-APN-029

Fig. 2: Routing of the measuring points in DIGSI 5 1.3.2 Function groups FG Following function groups are required: 4x FG V/I 1ph for the ground fault supervision of four feeders 1x FG V 3ph for the measuring of the phase-ground voltage for the correct determination of the network frequency. Circuit-breaker function groups will not be configured, because there are no 3-phase current measuring points present. No 3-phase current measurement is available in the feeders on the primary side. The cut out of the function group FG circuit-breaker has no impact of the application. 1.3.3 Connection of the measuring points with the function groups The measuring points must be connected to the different function groups afterwards, refer to the following figure. SIP5-APN-029

Fig. 3: Connection of the measuring points with the function groups in DIGSI 5 Edition 1 5 SIP5-APN-029

1.3.4 Functional overview in DIGSI 5 editor Fig. 4: Overview of the functions 1.3.5 Ground fault indication In most of the cases the ground fault should only be indicated. Indication Ground fault of each of the 4 protection functions will be used. In case that a trip should be initiated, it must be considered that there is no function group circuit breaker configured which usually issues the trip. Each of the protection function generate an own operate (trip) indication. The minimum operating time of the operate indication can be configured with the parameter shown in fig. 5. SIP5-APN-029

Fig 5: Setting for the duration of the indication The default value is 0 s, because it is usually not used. The settings need to be changed to a common value of e.g. 100ms. 1.4 Summary The expandability of function groups FG V/I 1ph as well as the flexible and an easy connection of the measurement points allow the ground fault supervision of 4 feeders with one SIPROTEC 7SJ8x with only 4 current and 4 voltage inputs. Edition 1 7 SIP5-APN-029

SIPROTEC 5 Application Error! Reference source not found. Published by and copyright 2015: Siemens AG Energy Management Products Humboldtstr. 59 90459 Nuremberg, Germany www.siemens.com/siprotec For more information, please contact your Siemens Partner or our Customer Support Center. Phone: +49 180 524 84 37 Fax: +49 180 524 24 71 (Charges depending on the provider) Email: support.energy@siemens.com Application Note: SIP5-APN-029, Edition 1 Printed on elementary chlorine-free bleached paper. All rights reserved. Trademarks mentioned in this document are the property of Siemens AG, its affiliates, or their respective owners. Subject to change without prior notice. The information in this document contains general descriptions of the technical options available, which may not apply in all cases. The required technical options should therefore be specified in the contract. SIP5-APN-029 For all products using security features of OpenSSL the following shall apply: This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit (www.openssl.org). This product includes cryptographic software written by Eric Young (eay@cryptsoft.com).