NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER

Similar documents
Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

ABSTRACT I. INTRODUCTION

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

Power Quality Improvement of Non-Linear Load by Using Instantaneous P-Q Theory

Power Quality improvement with Shunt Active Power filter using p-q control technique

Harmonics Reduction using 4-Leg Shunt Active Power Filters

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

Design of Shunt Active Filter to Improve Power Quality using Pq Theory

SCIENCE & TECHNOLOGY

Synchronous Reference Frame Theory For Nonlinear Loads using Mat-lab Simulink

5DESIGN PARAMETERS OF SHUNT ACTIVE FILTER FOR HARMONICS CURRENT MITIGATION

Active Harmonics Filtering of Distributed AC System

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Simulation Study of PWM Techniques for Voltage Source Converters

Power Quality Improvement using Shunt Passive Filter

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

Power Factor Improvement Using a Three Phase Shunt Active Power Filter

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

Power Control and Quality Management in DG Grid Interfaced Systems

Selective Harmonic Elimination Using Three Phase Shunt Active Power Filter

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

Fig. 1 Schematic Diagram Showing Connections to the Active Filter With Non-Linear Load

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

PI Controller Based Shunt Active Power Filter with Cascaded Multilevel Inverter

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

POWER QUALITY IMPROVEMENT USING SHUNT ACTIVE FILTER

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

ENHANCEMENT OF POWER QUALITY USING 9-LEVEL CASCADED H-BRIDGE BASED D-STATCOM WITH IRP THEORY SK. Meeravali* 1, Dr. K.

2020 P a g e. Figure.2: Line diagram of series active power filter.

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Review on Shunt Active Power Filter for Three Phase Four Wire System

Experimental Results of a Single-Phase Shunt Active Filter Prototype with Different Switching Techniques

Cascaded H-Bridge Five Level Inverter for Harmonics Mitigation and Reactive Power Control

SHUNT COMPENSATOR USED FOR POWER QUALITY IMPROVEMENT

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

PLL Synchronization with PID Controller Based Shunt Active Power Line Conditioners

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

Comparison of Shunt Active Power Filter Control Strategies for Harmonic Compensation in a Paper Industrial Factory

Hysteresis Controller and Delta Modulator- Two Viable Schemes for Current Controlled Voltage Source Inverter

Harmonics Reduction of 3 Phase Diode Bridge Rectifier by Implementing P-Q Theory with Active Filter

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

PERFORMANCE OF DISTRIBUTION STATIC COMPENSATOR IN LOW VOLTAGE DISTRIBUTION SYSTEM

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Comparison of Reference Current Extraction Methods for Shunt Active Power Filters

Comparison of Various Reference Current Generation Techniques for Performance Analysis of Shunt Active Power Filter using MATLAB Simulation

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

ICCCES Application of D-STATCOM for load compensation with non-stiff sources

Control of Shunt Active Power Filter for Improvement of Power Quality

Performance Improvement of Active Power Filter using a New Control Strategy under Unbalanced Grid Voltage

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Performance Analysis of Shunt Active Power Filter Base On Active Reactive Power Theory

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Design of Hybrid Active Filter for Power Quality Improvement of Electrical Distribution System Using Fuzzy Logic Controller

Hamdan bin Daniyal. University Malaysia Pahang Mohd Herwan Sulaiman

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 06, 2014 ISSN (online):

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

Application of Fuzzy Logic Controller in Shunt Active Power Filter

DESIGN AND DEVELOPMENT OF ACTIVE POWER FILTER FOR HARMONIC MINIMIZATION USING SYNCHRONOUS REFERENCE FRAME (SRF)

KKR &KSR institute of Technology and sciences,vinjanampadu(v),vatticherukuru(m) Guntur(D) , Andhra Pradesh,India. I.

CHAPTER 4 DESIGN OF DC LINK VOLTAGE CONTROLLER FOR SHUNT ACTIVE POWER FILTER

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Power Quality improvement of a three phase four wire system using UPQC

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Power Control Scheme of D-Statcom

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

DRIVE FRONT END HARMONIC COMPENSATOR BASED ON ACTIVE RECTIFIER WITH LCL FILTER

Multi Level Inverter Based Active Power Filter for Harmonic Reduction

Harmonic Reduction in Wind Energy Systems Using FLC and PI based Shunt Active Filter

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

Modeling of Shunt Active Filter Using P-Q Theory

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

Literature Review for Shunt Active Power Filters

International Journal of Advance Research in Engineering, Science & Technology

Comparative Analysis of Harmonics with and Without Shunt Active Power Filter

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Improvement of Power Quality Using a Hybrid Interline UPQC

POWER QUALITY IMPROVEMENT BY HARMONIC REDUCTION USING THREE PHASE SHUNT ACTIVE POWER FILTER WITH p-q & d-q CURRENT CONTROL STRATEGY

Improving the Power Quality by Four Leg VSI

TRANSFORMER LESS H6-BRIDGE CASCADED STATCOM WITH STAR CONFIGURATION FOR REAL AND REACTIVE POWER COMPENSATION

Application of Wavelet Transform for the Detection and Minimization of Harmonics using Shunt Active Filter

Modeling and Simulation of Matrix Converter Using Space Vector PWM Technique

Space Vector PWM Voltage Source Inverter Fed to Permanent Magnet Synchronous Motor

Compare Stability Management in Power System Using 48- Pulse Inverter, D-STATCOM and Space Vector Modulation Based STATCOM

Transcription:

NEUTRAL CURRENT COMPENSATION USING FOUR LEG SHUNT ACTIVE POWER FILTER Dr.V.Parimala 1, Dr.D.GaneshKumar 2 1 Asst.Prof (SG)-Dept of EEE, P.A College of Engineering and Technology. 2 Prof, Dept of ECE, P.A College of Engineering and Technology. Abstract This paper deals with improvement of power quality in three phase four wire system with neutral current compensation using four leg Shunt Active Power Filter (SAPF). The control of SAPF is based on reference current generation and current control methods. The generating reference current using instantaneous active and reactive power theory (p-q theory) and Modified d-q theory and to regulate the dc voltage using PI controller. The hysteresis controller is used to generate gate pluses and applied to four leg SAPF. The comparative study simulation of the work carried using MATLAB Simulink. Keywords: Hysteresis Controller, Modified d-q Theory, p-q Theory, PI Controller, SAPF 1. Introduction In the power system there is an increase in harmonic instability which caused by the power electronic equipment. The ac mains are connected with the nonlinear load so that harmonics is generated to affect power quality. The nonlinear loads are adjustable speed drives, static power supplies and uninterrupted power supplies (UPS) which causes harmonics instability [1]. The passive filter is simplest method to reduce harmonic distortion but it have some disadvantages are large size and increase resonance problem. The SAPF is compared to other technique has been better for solving the harmonic related issues and reduce the harmonics [6]. The three phase four wire system uses split capacitor and four leg shunt active filter for VSI topologies. The split capacitor use six IGBT for compensate three phase current and the neutral point is connected in the mid of DC link capacitor. The SAPF based split capacitor VSI topology has some drawback are two capacitor at voltage deviation problem and overheating of components. The four leg SAPF is commonly used, it has 8 IGBT, the three leg are connected to three phase current and fourth leg is connected to neutral point for compensating neutral current and DC link at capacitor. This work presents three phase four wire system with four leg shunt active filter in VSI topology, SAPF under instantaneous active and reactive power theory and instantaneous current component theory with PI controller for calculating reference current and the hysteresis current controller is used to generate gate pulses [4]. The work is organized as follows, chapter II described the proposed method, chapter III described the proposed control strategies in that a. instantaneous real and reactive power theory and b. instantaneous current component theory, chapter IV described the hysteresis controller and chapter V described the simulation result. 2. Proposed Method The three phase four wire system is connected to nonlinear load in that three phase and single phase uncontrolled rectifier is used. The filter design is based on the topology of four leg SAF. The PI controller is used to regulate the DC link voltage. The four leg shunt active filter at three leg compensate source current and fourth leg compensate neutral current or zero sequence current shown in Fig.1. 374

3.1 Instantaneous Real and Reactive Power Theory Fig.1 Four leg shunt active power filter with nonlinear 3. Proposed Control Strategies The p-q theory is based on set of instantaneous real and reactive power defined in time domain method. It is valid for both steady state and transient state [15]. This theory is efficient for designing shunt active filter. The three phase voltage and current (abc) are converted into αβ0 stationary reference frames. The Clarke and inverse Clarke transform of three phase voltage are given by, V0 Vα= V 1 0 Va Vb (1) Vc V V= V 1 0 Vα Vβ (2) Vᴑ Similarly three instantaneous line current ia,ib,ic can be converted into αβ0 coordinate, i0 iα= iβ 1 0 ia ib (3) ic i i= i 1 0 i0 iα (4) 0 iβ The three phase instantaneous real, reactive and zero sequence power calculated by, 375

p0 V0 0 0 i0 p= 0 Vα Vβ iα (5) q 0 Vβ Vα iβ The stationary reference frame used for calculating compensating reference current given by, = = ²² ²² (6) (7) The inverse clarke transform of three phase instantaneous compensated reference current given by, = ᴑ (8) = ᴑ (9) = ᴑ (10) The instantaneous real and reactive power theory having some drawbacks, they are unable to compensation of harmonics current under non sinusoidal voltage conditions [14]. The block diagram of reference current calculation, in that Clarke transform to calculate real, reactive and zero sequence power and stationary frame at compensated reference current generate by using PI controller shown in Fig.2. The SAPF at using DC link capacitor and DC link reference voltage and actual voltage compared to voltage to be regulated. Then inverse Clarke transform to calculate three phase compensated reference current [2]. The real and reactive power is calculated to pass low pass butterworth filter, in that cutoff frequency is 50Hz. The hysteresis current control is used to compare actual and reference current to trigger gate pulses and given to shunt active power filter. 3.2 Instantaneous Current Component Theory Fig.2 Block diagram of Reference Current Calculation Using p-q Theory The Modified d-q theory is based on set of rotating direct and quadrant power defined in time domain method. It is valid for both steady state and transient state. This theory is very efficient and flexible for designing shunt active filter 376

in non sinusoidal voltage condition. The three phase voltage and current (abc) are converted into dq0 synchronous rotating reference frames [12]. The park and inverse park transform of three phase current are given by, i0 iα= iβ = ˡ 1 0 ia ib (11) ic (12) sinɵ =cosɵ (13) sinɵ cosɵ The three phase compensated reference current calculated by inverse park transform is given by, =sin cos (14) =sin cos (15) =sin cos (16) = (17) The block diagram of shunt active power filter based Modified d-q theory shown in Fig.3. The three phase current is converted into rotating reference frame and passed to high pass filter (HPF), it attenuate higher order harmonics and through compute the compensated reference current using inverse Clarke transformation. 3.3 DC Link Voltage Regulator Fig.3 Block diagram of Reference Current Calculation using Modified d-q Theory The PI controller is generally used to regulate the DC Link voltage of shunt active power filter. The PI controller is used to compare actual dc link voltage and reference voltage in that error value is sampled. Its transfer function H(s) is represented as given by, = (18) Where Kp is proportional constant and Ki is integral constant. The Kp and Ki are used to determine dynamic response of dc link voltage control and settling time. The PI control is used to improve the loop gain and eliminate steady state 377

error values[16]. The PI controller is to compare actual and reference DC link voltage to be regulated shown in Fig.3. The rotating frame coordinates dq0 converted into three phase compensated reference current Ica, Icb, Icc. 3.4 Hysteresis Current Control The hysteresis current control is used to compare actual source current (ia,ib,ic) and compensated reference current (ica,icb,icc) to generate the triggering of gate pulses and applied to VSI based four leg shunt active power filter [7][17]. Fig.4 Hysteresis current control method The hysteresis control method involves selection of two levels of current; one slightly greater than the reference compensated current and other slightly lower the reference current shown in Fig.4. The actual current is taken by feedback signal. When the actual current is less than lower value, the IGBT are switched on, and when the current crosses the higher value, the IGBT are switched off [13]. As a result, the actual current remains within the upper and lower bands of the current reference. 4. Simulation Result and Discussion The Matlab/Simulink simulation tool was used to develop a three phase four wire system with 4leg SAPF model that allowed the simulation and testing of controllers. The open loop simulation of three phase four wire system is connected to nonlinear load in that three phase and single phase uncontrolled rectifier with RL load is used. The simulated output waveform for source voltage, source current, Load voltage, Load current and neutral current before filter circuit shown in Fig.5. Fig.5 Simulation Waveforms for before SAPF Filter 378

Fig.6 THD Value of source current before Filter Fig.7 THD Value of Neutral current before Filter The Fast Fourier transforms (FFT) analysis of open loop source current THD value is 34.90% shown in fig.6 and neutral current THD value is 56.40% shown in fig.7. The source current is sinusoidal by using four leg shunt active power filter. The closed loop system for three phase four wire system is connected to nonlinear load. The source current is controlled by using four leg shunt active power filter with instantaneous active and reactive power theory with PI controller. The four leg SAPF with dc link capacitor to compensate the current harmonics. In fig.8 the point of common coupling (PCC) at using four leg shunt active power filter with dc link capacitor. Fig.8 Simulation model of four leg SAPF with instantaneous active and reactive theory (p-q) 379

The three leg are compensating three phase current and fourth leg compensates neutral current in four leg SAPF method. The SAPF based reference current generated by using instantaneous active and reactive power theory with PI control. The PI control is comparing the actual and reference dc link voltage to eliminate error value and regulate of that voltage. Fig.9 Simulation Waveforms for p-q theory based on four leg SAPF Fig.10 FFT analysis of Source current in SAPF based p-q theory 380

Fig.11 FFT analysis of Neutral current in SAPF based p-q theory The simulated output waveform for p-q theory based four leg SAPF method shown in Fig.9. The Fast Fourier transforms (FFT) analysis of open loop source current THD value is 4.62% shown in Fig.10 and neutral current THD value is 5.32% shown in Fig.11. Fig.12 Simulation model of instantaneous current component theory (Modified d-q Theory) 381

Fig.13 Simulation Waveform for SAPF based instantaneous current component theory (Modified d-q theory) The closed loop simulation model of four leg SAPF with instantaneous current component theory (Modified d-q Theory) shown in Fig. 12. In that three phase four wire system and nonlinear load at four leg SAPF is connected in VSI. The SAPF at reference current calculated by using Modified d-q theory and dc link voltage is regulated using PI controller. The park transformation and inverse park transformation simulated in this diagram. Fig.14 FFT analysis of Source current in SAPF based instantaneous current component theory Fig.15 FFT analysis of Source current in SAPF based instantaneous current component theory The Simulation output waveform for SAPF based Modified d-q theory with PI controller shown in Fig.13. In that three phase Source Voltage and current, three phase load voltage and current, neutral voltage to be presented. The FFT of source current is 3.50% shown in fig.14 and neutral current should be 2.98% shown in Fig.15. The four leg SAPF based Modified d-q theory is compared to p-q theory harmonics to be less in source current and neutral current. The PI 382

controller is used to regulate the dc link voltage and improve the power factor. 4.1 Tables: Table 1: Comparison of THD Values THD Value Source current (Ampere) Neutral current (Ampere ) Before Filter SAPF based p-q theory SAPF based Modified d-q theory 34.90% 4.62% 3.51% 56.40% 5.32% 2.98 % Parameter Table 2: Parameter Values Value Supply Voltage Vs = 70.7 Source resistance Rs = 0.1Ώ Source inductance Ls = 0.5mH DC link capacitance Cdc = 3000µf DC link Voltage Vdc = 800 v PI Kp = 10 Ki = 0.4 Load resistance Load inductance 5. Conclusion Rl = 20Ώ Ll = 60mH In this paper four leg SAPF based two control strategies compared instantaneous real and reactive power theory and instantaneous current component theory (modified d-q theory), current control method at using hysteresis current controllers in three phase four wire system and their result are tabulated. In this method source current and neutral current harmonics has been compensated, THD value in IEEE 519 standard and reactive power to be compensated. References [1]. Parag Kanjiya, Vinod Khadkikar and Hatem H.Zeineldin, A Noniterative optimized algorithm for shunt active power filter under distorted and unbalanced supply voltages, IEEE trans. Industrial electronics, Vol.60, No.12, Dec 2013. [2]. M. Chakravarthy, P. M. Sarma and S. N. Saxena, Comparative Studies of Different Control Strategies for Shunt Active Filter, ARPN Journal of Engineering and Applied Sciences, Vol. 6, No. 11, pp.27-35, Nov 2011. [3]. Leszek S. Czarnecki, Instantaneous Reactive Power p-q Theory and Power Properties of Three-Phase Systems, IEEE Transactions on Power Delivery, Vol. 21, No.1, pp.362-367, Jan. 2006. [4]. Vikash Anand and Dr. S. K. Srivastava, Performance Investigation of Shunt Active Power Filter Using Hysteresis Current Control Method, IJERT, Vol.1, pp.1-8, June 2012. [5]. Kanchan Chaturvedi, Dr.Amita Mahor, Anurag Dhar Dwivedi, Active Power Filter Techniques for Harmonics Suppression in Non Linear Load, IJECT, Vol.1, pp.123-127, April 2012. [6]. H.Akagi, Modern active power filter and traditional passive filter, Bulletin of the technical science, Vol.54, No.3, pp.255-269, 2006. [7]. Y.Kusuma Latha, Ch.Saibabu, Y.P.Obulesh, Control strategy for three phase shunt active power with minimum current,measurement, IJECE, Vol.1, No.1, pp.31-42, Sep 2011. 383

[8]. Moleykutty George and Kartik Prasad Basu, Modeling and control of three phase shunt active power filter, American Journal of applied science, pp.1064-1070, 2008. [9]. Dr.R Prakask and Kiran R, Modelling and simulation of active shunt filter for compensation of system harmonics, IJEET, Vol.4, pp.172-179, June 2013. [10]. Marian P.Kazmierkowski and Luigi Malesani, Current control techniques for three phase voltage source PWM converter a survey, IEEE trans., Vol.45, No.5, Oct 1998. [11]. P Ramya and C N Arpitha, Reduction of THD in power system using generalized UPQC, IJEETC, Vol.2, No.4, Oct 2013. [12]. K.Sarasvathi and R.Rajalakshmi, Performance analysis of shunt active filter using different controllers, IJETT, Vol.4, pp.1815-1820, May 2013. [13]. Murat Kale and Engin Ozdemir, An adaptive hysteresis band current controller for shunt active power filter, ELSEVIER, pp.113-119, Sep 2004. [14]. Kiran Kumar Pinapatruni and Krishna Mohan L, DQ based control of DSTSTCOM for power quality improvement, VSRD-IJEECE, Vol.2, pp.207-227, 2012. [15]. Joao Afonso, Carlos Couto and Julio Martins, Active filter with control based on the p-q theory, IEEE trans., Vol.47, No.3, pp.5-10, Sep 2000. [16] Parimala, V, Chenthur Pandian, S and Ganeshkumar, D, An Efficient Particle Swarm Optimization Technique for 4-Leg Shunt Active Power Filter, International Journal of Circuits and Systems, Vol. 8, no. 7, pp. 1546-1559, June 2016. [17] Parimala, V, Chenthur Pandian, S and Ganeshkumar, D, Power Quality Improvement Using Four Leg Shunt Active Power Filter, International Journal of Applied Engineering Research, vol. 10, no.22, pp. 43207-43214, Dec 2015. 384