Keywords: unbalanced voltage, unbalanced current, Load balancing transformer

Similar documents
INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Enhancement of Power Quality in Multi Feeders by using MC-DPFC

Power Quality enhancement of a distribution line with DSTATCOM

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Voltage and Current Waveforms Enhancement using Harmonic Filters

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

OPTIMAL DESIGN OF A SINGLE TUNED PASSIVE FILTER TO MITIGATE HARMONICS IN POWER FREQUENCY

CHAPTER 6 UNIT VECTOR GENERATION FOR DETECTING VOLTAGE ANGLE

Generation of Voltage Reference Signal in Closed-Loop Control of STATCOM

2020 P a g e. Figure.2: Line diagram of series active power filter.

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

An Introduction to the CSCT as a New Device to Compensate Reactive Power in Electrical Networks

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

Voltage-Current and Harmonic Characteristic Analysis of Different FC-TCR Based SVC

Power Quality Compensation by using UPFC

CHAPTER 5 DESIGN OF DSTATCOM CONTROLLER FOR COMPENSATING UNBALANCES

A Time Domain Reference-Algorithm for Shunt Active Power Filters

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

p. 1 p. 6 p. 22 p. 46 p. 58

Control Strategy for a cross phase connected and a conventional UPQC

ARE HARMONICS STILL A PROBLEM IN DATA CENTERS? by Mohammad Al Rawashdeh, Lead Consultant, Data Center Engineering Services

Improvement of Power Quality Using a Hybrid Interline UPQC

P.CHAITHANYAKUMAR, T.VARAPRASAD/

Development and Simulation of Dynamic Voltage Restorer for Voltage SAG Mitigation using Matrix Converter

SOURCES OF ERROR IN UNBALANCE MEASUREMENTS. V.J. Gosbell, H.M.S.C. Herath, B.S.P. Perera, D.A. Robinson

Behavior of Induction Motor at Voltage Unbalanced

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

Design of Unified Power Quality Conditioner (UPQC) Connected To Three Phase Four Wire System

Design and Simulation of Fuzzy Logic controller for DSTATCOM In Power System

Effects of Harmonic Distortion I

Bhavin Gondaliya 1st Head, Electrical Engineering Department Dr. Subhash Technical Campus, Junagadh, Gujarat (India)

Volume I Issue VI 2012 September-2012 ISSN

UNBALANCED CURRENT BASED TARRIF

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTION SYSTEM USING DIRECT POWER CONTROL METHOD

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

This is a refereed journal and all articles are professionally screened and reviewed. Electromechanical Active Filter as a Novel Custom Power device

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Improvement of Voltage Profile using D- STATCOM Simulation under sag and swell condition

Performance Of Distributed Power Flow Controller (DPFC) Under Fault Condition

Power Quality improvement of a three phase four wire system using UPQC

IJESR/Nov 2012/ Volume-2/Issue-11/Article No-21/ ISSN International Journal of Engineering & Science Research

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

APPLICATION OF INVERTER BASED SHUNT DEVICE FOR VOLTAGE SAG MITIGATION DUE TO STARTING OF AN INDUCTION MOTOR LOAD

Static Synchronous Compensator (STATCOM) for the improvement of the Electrical System performance with Non Linear load 1

Comparison and Detection of Abnormal Conditions in Induction Motors

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

A Voltage Controlled D-STATCOM for Power Quality Improvement with DVR

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Investigation of D-Statcom Operation in Electric Distribution System

Mitigation of voltage sag by using AC-AC PWM converter Shalini Bajpai Jabalpur Engineering College, M.P., India

Tripping of circuit breakers in PV installations due to zero sequence field impedance

Mitigation of Voltage Sag and Swell using D-STATCOM to improve Power Quality

Voltage Flicker Mitigation in Electric Arc Furnace using D-STATCOM

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Performance of DVR under various Fault conditions in Electrical Distribution System

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

Harmonic Distortion Evaluations

Effect of Harmonics on the Performance Characteristics of Three Phase Squirrel Cage Induction Motor

Compensation of Unbalanced Three Phase Currents in a Transmission line using Distributed Power Flow Controller

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

Modeling and Analysis of DPFC to Improve Power Quality

Neural Network Controlled Hybrid Active Power Filter with Distorted Mains for PMSM Drive

UNIFIED POWER QUALITY CONDITIONER IN DISTRIBUTION SYSTEM FOR ENHANCING POWER QUALITY

Power Quality Analysis in Power System with Non Linear Load

Performance Analysis of UPQC for Non-Linear Load by Using MATLAB

Journal of World s Electrical Engineering and Technology J. World. Elect. Eng. Tech. 3(1): 18-25, 2014

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Svpwm Technique to Eliminate Harmonics and Power Factor Improvement Using Hybrid Power Filter and By Using Dsp Tms 320lf2407

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Power Quality Improvement in Distribution System Using D-STATCOM

Power Quality Issues and Harmonics Reduction by Hybrid Filter

The Study of Magnetic Flux Shunts Effects on the Leakage Reactance of Transformers via FEM

Enhancement of Power Quality in Distribution System Using D-Statcom for Different Faults

We are IntechOpen, the world s leading publisher of Open Access books Built by scientists, for scientists. International authors and editors

Compensation of Distribution Feeder Loading With Power Factor Correction by Using D-STATCOM

Mitigation of Voltage Sag and Swell using Distribution Static Synchronous Compensator (DSTATCOM)

The Use of an Active Power Filter for Harmonic Elimination and Power Quality Improvement in a Nonlinear Loaded Electrical Installation

Enhancement of Power Quality using D-Statcom Fed Induction Motor Drive

Simulation and Comparison of DVR and DSTATCOM Used For Voltage Sag Mitigation at Distribution Side

Real and Reactive Power Control by using 48-pulse Series Connected Three-level NPC Converter for UPFC

ANALYSING THE EFFECT OF USSC CONNECTION TO DISTRIBUTION SYSTEM ON VOLTAGE FLICKER

Mitigation of Voltage Sag and Swell Using Dynamic Voltage Restorer

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

International Journal of Advance Engineering and Research Development

Harmonics Elimination Using Shunt Active Filter

A VOLTAGE SAG/SWELL ALONG WITH LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER of UPQC-S

Simulation of Five Phase Voltage Source Inverter with Different Excitation for Star Connected Load

Power Quality Improvement using Active shunt Power filter using PI Controller

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

Improve Power Factor and Reduce the Harmonics Distortion of the System

Comparison of Three leg and Four Leg VSC DSTATCOM for Power Quality Assessment

Stability Enhancement for Transmission Lines using Static Synchronous Series Compensator

Shunt Active Power Filter based on SRF theory and Hysteresis Band Current Controller under different Load conditions

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Multilevel Inverter Based Statcom For Power System Load Balancing System

SIMULATION OF DISTRIBUTED POWER FLOW CONTROLLER FACTS DEVICE IN VOLTAGE SAG AND SWELL MITIGATION

Performance of DVR & Distribution STATCOM in Power Systems

Transcription:

Effects of Distorted Source on Operating a Load-Balancing Transformer in a Distribution Network Danial Ahmadi Mohammad Tavakoli Bina Masoud Aliakbar Golkar Faculty of Electrical Engineering, K. N. Toosi University of Technology Tehran, Iran Tehran, Iran Tehran, Iran ahmadi.danial@gmail.com tavakoli@kntu.ac.ir magolkar@yahoo.com Abstract- A Load balancing transformer was suggested for improving the three-phase unbalanced currents in distribution networks. On the other hand, magnitude and phase unbalance commonly occur in power grid networks. This paper investigates the impacts of a distorted source on the operation of a Load-balancing transformer as well as the proposed Loadbalancing transformer in this paper. The proposed and original Load-balancing transformers are simulated with MATLAB and the effects of simultaneous unbalanced voltage and harmonics are analyzed under different circumstances and the results are discussed. Keywords: unbalanced voltage, unbalanced current, Load balancing transformer II. BACK GROUND OF LOAD BALANCING TRANSFORMERS In [1] a special transformer was suggested for improving the three-phase unbalanced currents, where each phase including one extra pair of coupling windings in addition to the primary and secondary windings of transformer. One coupling winding from each phase in series with one coupling winding from the second phase is reversely paralleled with the secondary winding of the third phase. Under unbalance condition, the unbalanced currents are distributed between the coupling and secondary windings that are supplied through different phases (shown in Fig 1). I. INTRODUCTION Unbalance load is a concern in distribution networks. It causes one phase of transformer to reach its rated value earlier, while there is unused capacity in the other phases. This is the reason for increase in manufacturing cost of transformer. Unbalancing in distribution networks also increases the losses in the conductors, brings in losses and produces voltage in the natural wire, and finally results in voltage drop in the network. However, some techniques have been previously proposed to reduce the unbalancing and its lateral effects. One of them is using of Loadbalancing transformer, on the other hand magnitude and phase commonly occur in power networks. The main causes of unbalance are single phase loads present in power systems, unbalanced impedances of transmission lines and transformers, and non-uniform compensation of threephases with capacitor banks. In additional the increased use of solid state converters produces harmonics in the supply current and voltage waveforms. Nonlinear loads, including adjustable speed drives, UPS, switch mode power converters, microprocessor controls, robotics, fax machines and laser printers create harmonics. These devices also tend to be the most sensitive to malfunction from harmonic distortion. The harmonic currents generated by these nonlinear loads do not only cause additional heating of power system components, but at the same time they flow through the system impedance and current harmonics create voltage drops at their respective harmonic frequencies distorting the voltage waveform. This paper compares the proposed and original Loadbalancing transformers which are supplied with unbalanced voltage. A proposed Load-balancing transformer can be simply obtained with a little change in the distribution transformer without any need additional instruments, while it is practical and inexpensive for being implemented in distribution systems. Fig 1.Original Load balancing transformer Fig 2.proposed Load balancing transformer The proposed Load-balancing transformer is a three-phase transformer which has an additional coupling winding in the secondary-side of each phase. The coupling winding from each phase is reversely seriesed with the secodary winding of the another phase. Under unbalanced condition, the unbalanced current flows through the coupling and secondary windings that each winding is fed from primary by using a separate phase. In this way, part of excess current Proceedings of ICEE 2010, May 11-13, 2010 978-1-4244-6760-0/10/$26.00 2010 IEEE

of one phase is transferred to the other phaes (shown in Fig 2). unbalanced factory higher than 1 %, the increase of the unbalanced current in the primary side is considerable. III. THE EFFESCTS OF UNBALANCED VOLTAGES ON THE LOAD BALANCING TRANSFORMER In many European countries, according to the European voltage characteristic standard EN 50160 [2], the permissible long-term voltage deviation is ±10%, and the ratio of the negative-sequence voltage component and the positive-sequence voltage component should not exceed 2%. The standard also says that in some power systems the ratio is up to about 3%. In this part the unbalance in the phase and the magnitude of the voltage has been considered. Fig 5. d,q,0 form of current in primery-side of Orginal Load balancing transformer (unbalance factor is 1%) In this part an unbalance of 10% is assumed for the phase of applied voltages of phase B and C. these voltages are supplied proposed Load-balancing transformer. It can be seen (Fig 3-5) a large amount of phase difference is produced by the Original design of the Load-balancing transformer. However, the proposed Load-balancing transformer which is supplied with unbalanced voltage is capable of moving towards balancing the unbalanced load both in magnitude and in phase (Shown in Fig 6). Fig 3.The current of primery-side of Original Load balancing transformer (unbalance factor is 1%) Fig 4.The current of primery-side of Original Load balancing transformer (unbalance factor is 2.5%) A. Unbalance in the Voltage Magnitude In this case the Load-balancing transformer is operating with an unbalance voltage at its terminals. So, the value of the voltages for phases A, B and C would be as follows: V AB =200, V BC =198, V CA =202, So the average is 200, and the maximum deviation from the average is 2, so the percent unbalance factor is 1 % (based on NEMA definition), unbalanced loads are connected to the secondary-side of original and proposed Load-balancing transformer. Now assume three phase voltages having of 205,195 and 200, the average is 200 and the maximum deviation from the average is 5, so the percent unbalance factor is 2.5 %. Figure 3 and 4 show an increase in the magnitude unbalance at the terminal of original one can increase unbalance current in the primary-side more than secondary-side. For an Fig 6. The current of primery-side of Proposed Load balancing transformer (unbalance factor is 10%) B. Unbalance in the Voltage Phase The impacts of unbalanced voltage on a Load-balancing transformer can be analyzed with symmetrical components, negative and positive sequence components. Their ratio, known as the Voltage Unbalance Factor (VUF) describes the voltage unbalance percentage (although other definitions of voltage unbalance percentage are commonly used): U VUF = 100% (1) U + Where U - is negative sequence voltage component and U + is positive sequence voltage component. In this part an unbalance of 1% is assumed for the phase of applied voltages, the applied three phase voltages are as follows: V A =200 0, V B =200 242, V C =200 122. It can be seen (Fig. 7) a large amount of phase difference is produced by

the Original design of the Load-balancing transformer in the primary side. introduced to the model. Moreover, a combination of these harmonics is considered as well. The Load-balancing transformer has been supplied with the rated voltage and the harmonics are injected in the voltage source. The applied voltage can be written as: V () t = V sin(2 ft) + V sin(2 kft + ) 1 π k π θk (2) k = 3,5,7 fundamental Harmonics Fig 7.the current of primery-side of Original Load balancing transformer (VUF=1%) Now in this part an unbalance of VUF=10% is assumed for the phase of applied voltages, these voltages are supplied proposed Load-balancing transformer. V A =200 0, V B =200 216, V C =200 132. According to Fig.8 a proposed Load-balancing transformer is capable of moving towards balancing the unbalanced load both in magnitude and in phase. If the supplied voltage unbalanced in phase and magnitude similarly through unsuccessful compensates generating a lot of amount of zero component current in the primary side of original one, so it is concerning power quality in public networks. However the proposed Load balancing transformer can compensate the unbalanced load successfully and the zero component of current at the primary-side is zero. Therefore use of the Original Loadbalancing transformer connected to an unbalanced voltage is not normally allowed. Fig 9.The current of primery-side of Original Load balancing transformer when 3 rd harmonic is injected Fig 10.The current of primery-side of Proposed Load balancing transformer when 3 rd harmonic is injected Fig 8. The current of primery-side of Proposed Load balancing transformer (VUF=10%) IV. HARMONIC ANALYSIS Harmonic distortion can be caused by both active and passive non-linear devices in a power system. The power transformer, for example, generates a magnetization current with third-order and higher odd harmonics. In the past, these passive devices were the primary source of harmonics. Today, most harmonic distortion is generated by input stage of (active) electronic power converters. In this part three major harmonics namely, 3 rd, 5 th, and 7 th harmonics are A. 3 rd Harmonic In this case the 3 rd harmonic is injected into the voltage 50Hz the harmonic frequency is 150Hz. According to the standards the magnitude of the harmonics should be less than 5% [22] of the main frequency magnitude. The magnitude of the main frequency voltage is 200 (V) so the magnitude of the voltage harmonic should be less than 10(v). Two cases are assumed here. In the first case the Original Load-balancing transformer but in the second case the proposed Load-balancing transformer. The voltages that are applied to the transformer three phases are as follows: VC = 200sin(2π50t + 120) + 5sin(3 V B = 200sin(2π50t + 240) + 5sin(3 (3) V A = 200sin( + 5sin(3 Figure 9 and 10 show the current of primary-side after compensation by Original and proposed design respectively. The proposed Load balancing transformer is capable of

balancing an unbalance load, but the original compensator is not. B. 5 th Harmonic In this case the 5th harmonic is injected into the voltage 50Hz the harmonic frequency is 250Hz. According to the standards the magnitude of the harmonics should be less than 5% of the main frequency magnitude. Fig. 11, 12 show the current primary-side after compensation by the Original and proposed design respectively. of amount of zero component current in distribution network and concerning power quality in public networks. Fig 13. The current of primery-side of Original Load balancing transformer when 7 th harmonic is injected Fig 11.The current of primery-side of Original Load balancing transformer when 5 th harmonic is injected Fig 14. The current of primery-side of Proposed Load balancing transformer when 7 th harmonic is injected Fig 12.The current in primery-side of Proposed Load balancing transformer when 5 th harmonic is injected C. 7 th Harmonic In this case the 7 th harmonic is injected into the voltage 50Hz the harmonic frequency is 350Hz. The magnitude of the main frequency voltage is 200(v) so the magnitude of the voltage harmonic is 5(v). Fig. 13 and 14 show the current of primary-side after compensation by the Original and proposed design respectively. The proposed Load balancing transformer has been simulated under unbalance load and compared with the original transformer. The performance of the both of them has been considered with several of harmonic voltage distortion. According to these figures (9-14) the current of primary-side of original load balancing transformer is more unbalanced than the current of secondary side (load). In additional through unsuccessful compensates generating lots V. CONCLUSION In this paper for balancing of the load in distribution network, a transformer has been proposed which can be simply provided with a little change in the ordinary distribution transformer without any need to the additional special instruments. Finally for improving the performance of this transformer which supplied with unbalanced voltage and harmonic voltage distortion in the Load-balancing, a method has been proposed and simulated using MATLAB and the results have been compared. With respect to low cost of implementation of the proposed idea, and the problems brought in the network by the unbalanced loads, it is recommended to use this transformer instead of the ordinary distribution transformer. REFERENCES [1] T. J. Reynal, "Load-balancing Transformer", U.S. Patent No. 5557249, September 1996. [2] P. Gnacinski; " Derating of an induction machine under voltage unbalance combined with over or undervoltages"; Energy Conversion and Management 50 (2009) 1101 1107 [3] L. Gyugyi, R. A. Otto and T. H. Putman, "Principles and Applications Of Static Thyristor-Controlled Shunt Compensators", IEEE Transactions on Power Apparatus and Systems, Vol. PAS-97, No. 5, pp. 1935-1945, Sept/Oct 1978. [4] V. B. Bhavaraju and Prasad N. Enjeti, "Analysis and Design of an Active Power Filter for Balancing Unbalanced Loads", IEEE

Transactions on Power Electronics. Vol. 8, No. 4, pp. 640-647, October 1993. [5] Z. Yongqiang and L. Wenhua, "Balancing Compensation of Unbalanced Load Based on Single Phase STATCOM", IPEMC Power Electronics and Motion Control Conference, Vol. 2, pp. 425-429, Aug 2004. [6] B. N. Singh, B. Singh, A. Chandra and K. Al-Haddad, "Digital Implementation of an Advanced Static Compensator for Voltage Profile Improvement, Power-Factor Correction and Balancing of Unbalanced Reactive Loads", Electric Power Systems Research 54 (2000) 101 111. [7] A. Sonnenmoser and P. W. Lehn, "Line Current Balancing with a Unified Power Flow Controller", IEEE Transactions on Power Delivery, Vol. 14, No. 3, pp. 1151-1157, July 1999. [8] J. H. Chen, W. J. Lee and M. S. Chen, "Using a Static Var Compensator to Balance a Distribution System", IEEE Transactions on Industry Applications, Vol. 35, No. 2, pp. 298 304, March/April 1999. [9] S. Y. Lee, C. J. Wu and W. N. Chang, "A Compact Control Algorithm for Reactive Power Compensation and Load-balancing with Static Var Compensator", Electric Power Systems Research 58 (2001) 63 70. [10] A. Chandra, B. Singh, B. N. Singh and K. Al-Haddad, "An Improved Control Algorithm of Shunt Active Filter for Voltage Regulation, Harmonic Elimination, Power-Factor Correction and Balancing of Nonlinear Loads", IEEE Transactions on Power Electronics, Vol. 15, No. 3, pp. 495-507, May 2000. [11] C. C. Chen and Y. Y. Hsu, "A Novel Approach to the Design of a Shunt Active Filter for an Unbalanced Three-Phase Four-Wire System under Nonsinusoidal Conditions", IEEE Transactions on Power Delivery, Vol. 15, No. 4, pp. 1258-1264, Octobe 2000. [12] S. Y. Lee and C. J. Wu, "Reactive Power Compensation and Loadbalancing for Unbalanced three-phase Four-Wire System by a Combined System of an SVC and a Series Active Filter", IEE Proceedings Electric Power Applications, Vol. 147, No. 6, pp. 563 578, Nov 2000. [13] T. J. E. Miller, "Reactive Power Control in Electric System", New York: Wiley, 1982. [14] J. D. Glover and M. Sarma, "Power System Analysis and Design", Second Edition, PWS Publishing Company, Boston, MA, 1994. [15] Yaw-Juen Wang and Ming-Jer Yang, "Probabilistic Modeling of Three-Phase Voltage Unbalance Caused by Load Fluctuations", IEEE Power Engineering Society Winter Meeting, Vol.4, pp. 2588 2593, 2000. [16] A. von Jouanne and B. B. Banerjee, "Assessment of voltage unbalance", IEEE Transactions On Power Delivery, Vol. 16, No. 4, pp. 782-790, October 2001. [17] Motors and Generators, NEMA Standards Publication No. MG 1-1993. [18] J. Wang, A. F. Witulski, J. L. Vollin, T.K. Phelps, G. I. Cardwell, "Derivation, Calculation and Measurement of Parameters for a Multi- Winding Transformer Electrical Model", APEC Applied Power Electronics Conference and Exposition, Vol. 1, pp. 220 226, March 1999. [19] C. L. Fortescue, "Method of Symmetrical Coordinates Applied to the Solution of Polyphase Networks", Transaction of ALEE, Vol. 37, pp. 1027-1140, 1918. [20] A.E. Emanuel et al., "Voltage Distortion in Distribution Feeders with Nonlinear Loads", IEEE Transactions on power Delivery, Vol. 9, No.1, January 1994. [21] Bachry, A.;Styczynski,Z.A; "An Analysis Of Distribution System Power Quality Problems Resulting From Load Unbalance And Harmonics", Transmission and Distribution Conference and Exposition, 2003 IEEE PES Volume 2, 7-12 sept. 2003 Pages: 763 766 Vol.2. [22] Amir Khoobroo; "Effects of System Harmonics and Unbalanced Voltages on Electromagnetic Performance of Induction Motors", IEEE 2008, pages:1173-1178 [23] P.Giridhar Kini; " A Novel Approach Toward Interpretation and Application of voltage Unbalance Factor"; IEEE transactions on industrial electronics, vol.54, No.4, August 2007. [24] P. Gnacinski; " Derating of an induction machine under voltage unbalance combined with over or undervoltages"; Energy Conversion and Management 50 (2009) 1101 1107