Module Title: Electrical Installation II Laboratory Sheet:

Similar documents
2394 EXAM PAPER. 1. State THREE circumstances that would require a periodic inspection and test to be carried out on an installation

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations. Earth Fault Loop Impedance Tests

NOTE: This paper relates to a closed book exam & therefore candidates should attempt this exam paper with no study-notes or text books.

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

C&G Level 3 Award in the Periodic Inspection, Testing and Certification of Electrical Installations

7 o/c4 - To meet the requirements of BS 7671, all fault current protective devices without back-up protection on the supply side must be capable of:

Licensed Electricians Practical Assessment (LEP)

returned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit.

Licensed Electricians Practical Assessment (LEP)

ET 61 - Electrician Theory Examination Marking Schedule

ET 40 - Electrician Theory Examination Marking Schedule

ET 51 - Electrician Theory Examination Marking Schedule

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Les Hampson Cert Ed FSCTE, Chairman CAI Technical Committee

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET

Instruction Manual for Digital Grounding Resistance Meter

Circuits and Circuit Elements

EAS Electrical Appliance Serviceperson Answer Schedule

Instruction Manual for Digital Grounding Resistance Meter. Table of Contents

FINAL - ER 70 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes

power Knowledge The Hager Guide to current thinking on the regulations, protection and control of Klik lighting circuits.

EASQ ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) MARKING SCHEDULE. SECTION 1 Marks Reference Marking notes Qu 1 A 10 MΩ (2 marks)

Portable Appliance Testers. OmegaPAT MI 2140 BetaPAT MI 2141 User Manual Ver Code No

CURRENT FUTURE REGULATIONS PROPOSALS

INSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET

Residual Current Operated Circuit-Breakers (RCCBs)

Section 3. Test Procedures

17TH EDITION BS TH EDITION BS7671 HOW THIS AFFECTS YOU. A BITESIZE LOOK at RCDs and parts of the 18th edition DPC. wylexreasons.co.

EurotestCOMBO MI 3125 / MI 3125E Short instructions Version 2.2, Code no

TN, TT & IT Earthing Arrangements

Preface...x Chapter 1 Electrical Fundamentals

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Installation Tester BENNING IT 115. Operating Manual

Intermediate Physics PHYS102

Chapter F Protection against electric shocks

Multi-Function Installation Tester MEGGER CM500. User Guide MEGGER

MEGGER CM300 MK II, CM400 MK II & CM500

G SAFETY WARNINGS. LT300 High current loop tester. User guide

1. general. 1.1 electric shock. 1.2 direct and indirect contact. electric shock. indirect contact. direct contact

E X A M I N A T I O N S C O U N C I L SECONDARY EDUCATION CERTIFICATE EXAMINATION ELECTRICAL AND ELECTRONIC TECHNOLOGY TECHNICAL PROFICIENCY

G.F.C.I. by Sam Goldwasser -- exerpts from: Sci.Electronics.Repair FAQ:

1. General Instructions 2 2. Safety 2 3. Lamp Starting Test Instrument LSTI 5 3

FINAL - EST Electrical Service Technician Answer Schedule

Installation Tester BENNING IT 130. Operating Manual

, Power Industries and Communications Industry Training Board

INSTRUCTION MANUAL MULTI-FUNCTION TESTER KEW 6016

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

νµθωερτψυιοπασδφγηϕκλζξχϖβνµθωερτ ψυιοπασδφγηϕκλζξχϖβνµθωερτψυιοπα σδφγηϕκλζξχϖβνµθωερτψυιοπασδφγηϕκ χϖβνµθωερτψυιοπασδφγηϕκλζξχϖβνµθ

ECP GROUND-MOUNTED SWITCHGEAR WITH PROTECTION RELAYS COMMISSIONING PROCEDURE

2/15/2015. Current will always try to return to its source. In order for there to be current, there must be a complete circuit

Syllabus OP49 Test electrical conduction in a variety of materials, and classify each material as a conductor or insulator

Chapter F Protection against electric shocks

ER 87 Electrician Regulations Answer Schedule. Question 1 Marks Reference Marking notes. (1 mark) ESR 27(2) (2 marks) ESR 74A(1AA)

ECP GROUND-MOUNTED SWITCHGEAR COMMISSIONING PROCEDURE

2 Grounding of power supply system neutral

EI HIGH VOLTAGE INSULATION TESTING POLICY

FAQ ON EARTHING STANDARDS 16/08/2018

Grounding Recommendations for On Site Power Systems

Busbars and lines are important elements

SERVICING & METERING SERVICING AND METERING SECTION 5 SEC5:

ECE 528 Understanding Power Quality

Item ref: UK MTM01 DIGITAL MULTITESTER. User Manual

Company Directive STANDARD TECHNIQUE: SD5R/2. Earth Fault Loop Impedances and Phase to Neutral Loop Impedances at LV Installations

PEN TYPE DIGITAL MULTIMETER OPERATION MANUAL T8211D

NOTE: Fully read and understand this manual before using this Digital Multimeter.

FINAL - ET 60 - Electrician Theory Examination Marking Schedule

NATIONAL CERTIFICATE (VOCATIONAL) ELECTRICAL WORKMANSHIP NQF LEVEL 3 NOVEMBER 2009

The future of installation testing is here. The Fluke 1650 Series Multifunction Testers

Thank you again for choosing AstroAI, if you have any questions or concerns regarding your product, please contact us at

EPG. by Chris C. Kleronomos

Residual Current Operated Circuit-Breakers (RCCBs)


lama M:ZSO 2SA 30oM 11ov m

VCE VET Integrated Technologies

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Item ref: UK MTTR01 TRUE RMS DIGITAL MULTITESTER WITH USB INTERFACE. User Manual

Automatic disconnection of lighting circuits from dimming equipment

3B SCIENTIFIC PHYSICS

User's Guide. AC Circuit Load Tester. Model CT70

DVM645BI BENCH MULTIMETER TAFELMULTIMETER MULTIMETRE DE TABLE BANCO MULTÍMETRO TISCHMULTIMETER. User Manual. Gebruikershandleiding

Tech Talk (12) Down to Earth: A Discussion of the General Requirements for the Earthing of Control and Instrumentation Systems

FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2

COOPERATIVE PATENT CLASSIFICATION

M.I. Cable High Resistance Fault Locator

DIGITAL MULTIMETER CONTENTS DIGITAL MULTIMETER CONTENTS

Chapter 12 Electric Circuits

Electronic Circuit Breaker with reset input ESS20-1..

Substation Preventive Maintenance

INSTITUTE OF TESTING AND CERTIFICATION (INDIA) PVT. LTD.

OPERATOR S INSTRUCTION MANUAL

ECP COMPACT AND MICRO SUBSTATION COMMISSIONING PROCEDURE

TT W Wireless receiver Inline Switch

3B SCIENTIFIC PHYSICS

Unit 15: Electrical Circuits and their Applications

Chapter 1. Applied Grounding and Bonding. Applied Grounding and Bonding 9/18/2011. Introduction. Introduction. Paul Dobrowsky Member NEC Panel 5

QUICK SETUP GUIDE SECULIFE IP

CHAPTER 15 GROUNDING REQUIREMENTS FOR ELECTRICAL EQUIPMENT

Transcription:

Vocational Training Council Hong Kong Institute of Vocational Education Department of Engineering Module Title: Electrical Installation II Laboratory Sheet: Student name: Course / Year: Subject: Date: Inspection & Earth Loop Impedance Test for Electrical Installation Objectives: To understand the principles and to have hands-on experience on:- Insulation Tests using a 500V Meggar Tester, Earth Loop Impedance measurement with a Phase-Earth Loop Impedance Tester, Apparatus: 500V Meggar (AVO model BM201) (x1) Phase-Earth Loop Impedance Test (Kyoritsu model 4141) (x1) 13A socket outlets (4 nos.) of correct & incorrect polarities (1 set) Components: a short run of cable with good insulation (x1) a short run of cable with defective insulation (x1) Ver Author(s) Date Remark 1.0 hcho 5-03 For Elect. Installation II Page 1 of 10

Part A: Background 1. Introduction Electrical installations may be categorised as being portable or fixed. Fixed electrical installation may be defined as being a low or high voltage electrical installation that is fixed to premises but does not include any electrical equipment that is supplied with electricity after passing through a socket of the installation at which the supply can be disconnected without the use of a tool. Otherwise, the electrical installation may be classified as portable. To ensure safety, all fixed electrical installation, no matter new or alteration, shall satisfy the inspection and testing procedures as set down by the Code of Practice for the Electricity (Wiring) Regulations. In particular, the testing procedures for Low Voltage (<1000 V) electrical installations are particular relevant to general fixed electrical installations. Examples of low voltage fixed electrical installations include distribution boards, lighting installations, socket outlet installations, etc. It is a statutory requirement that all fixed electrical installations, >200A industrial and >100A domestic, are to be tested regularly. Precautionary measures should be taken during testing and the method of tests should be such that no danger to persons or property can occur even if the circuit being tested is defective. The following tests, where relevant, are to be tested preferably in the sequence indicated below:- (i) continuity of ring final circuit conductors, (ii) continuity of protective conductors, including main and supplementary equipotential bonding, (iii) earth electrode resistance, (iv) insulation resistance, (v) polarity, (vi) earth fault loop impedance, (vii) functions of all protective devices, (viii) functions of all items of equipment. In the event of any test indicating failure to comply, that test and those preceding, the results of which may have been influenced by the fault indicated, should be repeated after the fault has been rectified. Among these tests, items (iv) and (vi) are studied in this experiment to highlight the key principles of the inspection and testing of electrical installations. Page 2 of 10

2. Insulation resistance The object of the test is to verify that the quality of the insulation is satisfactory and has not deteriorated or short circuited. There are two tests under this heading:- (i) (ii) insulation resistance (IR) between conductors and IR between conductors and earth. Before these tests are carried out, it is essential to disconnect any neons and capacitors from the circuit because they will upset the readings obtained. In addition, any control devices which contain semiconductor components must also be disconnected as they can be damaged by the test. IR between conductors For this test, all lamps have to be removed and all switches closed. The test instrument is then connected between phase and neutral (if the supply is single-phase) and the test voltage applied. The minimum acceptable value of IR is 0.5 MΩ for low voltage installations. In new and otherwise electrically healthy circuits, the reading will be higher than this value. If a zero reading is obtained, this indicates a shortcircuit. If a significant resistance reading is obtained, this might indicate, say, a lamp is left in the circuit (e.g. the filament resistance of a 100W lamp would be in the region of 600Ω). IR between conductors and earth For this test all fuses (or MCBs) should be in place, all switches closed (including the main switch if practicable) together. Again the minimum acceptable value is 1 MΩ. Figure A.1 Test for insulation-resistance to earth Page 3 of 10

Figure A.2 Test for insulation-resistance between conductors Table A.1 Minimum values of insulation resistance 3. Earth-fault loop impedance Earth fault loop impedance is the impedance of the earth fault-current loop starting and ending at the point of earth fault (Figure A.3). It comprises the following starting at the point of fault: (i) (ii) (iii) (iv) (v) the circuit protective conductor; the consumer s earthing terminal and earthing conductor; the earth return path (for TT system); the path through the earthed neutral point of the transformer and the transformer winding; the phase conductor from the transformer to the point of fault. Page 4 of 10

Figure A.3 Path for earth fault current showing the complete earth fault loop impedance The significance of earth fault loop impedance is that a fast disconnection time of the protective device means that a high fault current is required to blow the fuse or to trip the circuit breaker. In order to allow sufficient fault current to flow in order to trip the protective device, the earth fault loop impedance must have a low value. The instrument commonly used is a phase-earth loop tester which has two indicating lamps, both of which must be ON before a test is carried out. One lamp indicates that the polarity of the circuit is correct, P-N, and the other ensures that a proven earth connection is available, P-E. There is usually a recommendation that there should be at least a 20-second interval between tests. This is to allow any heat generated in the current limiting resistor to dissipate. The instrument passes a current of around 20A into the earth loop path. The reading obtained must be compared with the maximum Z s values given in the table in the COP (Table A.2). These values vary according to the type of overcurrent protective device and its current rating and whether the circuit feeds socket-outlets or fixed equipment. If it exceeds the recommended figure, the circuit must be investigated to find out the underlying reason. The reading obtained should also be compared with the reading of the previous test (if this information is available) to see whether the Z s value is on the increase, which might indicate a potential dangerous condition appearing in the circuit. For example, if the maximum Z s was 2 Ω and the test reading was 1.2 Ω on a previous test but is now 1.8 Ω, this indicates that the next would produce an unacceptable reading with the possibility that an earth fault occurring in the circuit would not produce enough fault current to operate the overcurrent protective device in either 0.4 second and 5 seconds, thus increasing the risk of electric shock to persons using the installation. Page 5 of 10

Tables A.2 Maximum Earth Fault Loop Impedance Page 6 of 10

Tables A.2 (Cont d) Maximum Earth Fault Loop Impedance Page 7 of 10

Part B: Procedures 1. Insulation Test Figure B.1 Connection diagram for insulation test of a cable (i) (ii) (iii) (iv) Test the operation of the 500V meggar by shorting the two terminals. Use the meggar to test the cable with the undamaged insulation and take the reading directly in ohms. Replace the cable with defective insulation and take the reading of the meggar. Repeat the insulation resistance tests with the 30A TPN switch in the laboratory. Take the reading of R-E, R-Y, Y-B, B-R and RYB-N in turns and record all results in Table B.1. No Test Items Meggar Reading (Ω) 1 Cable with perfect insulation 2 Cable with defective insulation 3 30A TPN Switch (i) R-E (ii) Y-E (iii) B-E (iv) R-N (v) Y-N (vi) B-N (vii) R-Y (viii) Y-B (ix) B-R (x) RYB-N (xi) RYB-E Table B.1 Insulation test Remarks Page 8 of 10

2. Earth Loop Impedance Test Four socket outlets are provided. Only one of the four is correctly wired. Figure B.2 Connection diagram for earth loop impedance test (i) (ii) The 'Phase-Earth Loop Impedance' Tester is plugged into the 13A socket outlet at the bench. Press the button. The pointer will move the give a reading directly in ohms. This is the phase-earth loop impedance. Repeat procedure (i) for the 4 nos. 13A socket outlets. If the pointer moves to give a reading, record the results. If the pointer does not move or move to give an excessive reading, also note down the observations. Justify the results recorded in Table B.2. 1st 13A S/O 2nd 13A S/O 3rd 13A S/O 4th 13A S/O P-N LED (ON/OFF) Response of the Impedance Tester P-E LED (ON/OFF) Movement of Pointer Table B.2 Earth fault loop impedance Reading (Ω) By measurement, the earth fault loop resistance = Ω Page 9 of 10

Part C: Discussions 1. Comment on the results recorded in Table B.1. Suggest the minimum values of the test results to be acceptable. 2. What is the potential problem if the equipment/cable fails the insulation test? 3. Does all the earth fault loop impedance measured for the functional socket outlets in Part B.2 comply with the requirement as laid down in table A.2? - End - Page 10 of 10