Insulation monitoring relays CM-IWN.4/5/6 For unearthed AC, DC and mixed AC/DC systems up to U n = 400 V AC and 600 V DC

Similar documents
Insulation monitoring relay CM-IWN.5 For unearthed AC, DC and mixed AC/DC systems up to U n = 400 V AC and 600 V DC

Three-phase monitoring relay CM-PFS

Insulation monitoring relay CM-IWS.1 For unearthed AC, DC and mixed AC/DC systems up to U n = 250 V AC and 300 V DC

Insulation monitoring relay CM-IWN.1 For unearthed AC, DC and mixed AC/DC systems up to U n = 400 V AC and 600 V DC

Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Three-phase monitoring relays CM-PVS CM-PVS.31, CM-PVS.41 and CM-PVS.81

Voltage monitoring relay CM-EFS.2 For single-phase AC/DC voltages

Current monitoring relays CM-SRS.2 For single-phase AC/DC currents

Current monitoring relays CM-SRS.1 For single-phase AC/DC currents

Insulation monitoring relay CM-IWS.2 For unearthed AC systems up to U n = 400 V AC

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

Three-phase monitoring relays CM-PSS CM-PSS.31 and CM-PSS.41

Three-phase monitoring relays CM-PVS.81

Liquid level monitoring relay CM-ENS.2x

Electronic timer CT-AHS.22 OFF-delayed with 2 c/o (SPDT) contacts

Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages

Current monitoring relays CM-SRS.M1 For single-phase AC/DC currents

Electronic timer CT-WBS.22 Impulse generating and flashing with 2 c/o (SPDT) contacts

Coupling unit CM-IVN For expansion of the insulation monitoring relay CM-IWN.x measuring range up to U n = 690 V AC and 1000 V DC

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23 and CM-MPS.43

Voltage monitoring relays CM-ESS.1 for single-phase AC/DC voltages

Current monitoring relays CM-SRS.2 for single-phase AC/DC currents

Multifunctional three-phase monitoring relays CM-MPS CM-MPS.23

ABB 1. Multifunctional three-phase monitoring relays. CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. Features. Approvals. Marks.

Electronic timer CT-MXS.22 Multifunctional with 2 c/o (SPDT) contacts

Current monitoring relays CM-SRS.1 for single-phase AC/DC currents

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Three-phase monitoring relays CM-PFE and CM-PFE.2

Electronic timer CT-MVS.12 Multifunctional with 1 c/o (SPDT) contact

ABB 1. Multifunctional three-phase monitoring relays. CM-MPN.52, CM-MPN.62 and CM-MPN.72 Data sheet. Features. Approvals. Marks.

Electronic timer CT-SDS.22

Multifunctional three-phase monitoring relays CM-MPN CM-MPN.52, CM-MPN.62 and CM-MPN.72

Electronic timer CT-TGD.12 Pulse generator with 1 c/o (SPDT) contact

Three-phase monitoring relay

Electronic timer CT-MFS.21 Multifunctional with 2 c/o (SPDT) contacts

Three-phase monitoring relay CM-PVE

Electronic timer CT-MBS.22 Multifunctional with 2 c/o (SPDT) contacts

ABB NEW. Three-phase monitoring relays. CM-PVS.31 and CM-PVS.41 Data sheet. Features J. Approvals. Marks. Order data. Order data - Accessories

Three-phase monitoring relays

Electronic timer CT-EBE Flasher starting with OFF, 1 c/o (SPDT) contact

CM-MPS.11, CM-MPS-21, CM-MPS.31 and CM-MPS.41 Data sheet. UL 508, CAN/CSA C22.2 No.14 GL GOST CB scheme CCC

Three-phase monitoring relay CM-PBE

Electronic timer CT-MVS.23 Multifunctional with 2 c/o (SPDT) contacts

Electronic timer CT-YDE Star-delta change-over with 1 c/o (SPDT) contact

ABB NEW. Multifunctional three-phase monitoring relays. CM-MPS.23 and CM-MPS.43 Data sheet. Features J. Approvals. Marks.

Electronic timer CT-MFS.21 Multifunctional with 2 c/o (SPDT) contacts

Electronic timer CT-SDE Star-delta change-over with 1 n/c + 1 n/o contact

Electronic timer CT-SDS.22 Star-delta change-over with 2 n/o contacts Data sheet

Electronic timer CT-MFS.21

Measuring and monitoring relays CM-SRS.1 Current monitoring relays, single-phase AC/DC

Electronic timer CT-TGD.22

Electronic timer CT-SDD.22

Electronic timer CT-AHE OFF-delayed with 1 c/o (SPDT) contact

Electronic timer CT-AWE Impulse-OFF with auxiliary voltage, 1 c/o (SPDT) contact

Power supply CP-T 48/5.0 Primary switch mode power supply

Power supply CP-T 24/40.0 Primary switch mode power supply

Power supply CP-T 24/10.0 Primary switch mode power supply

Power supply CP-T 48/20.0 Primary switch mode power supply

Power supply CP-D 12/2.1

Power supply CP-T 24/20.0 Primary switch mode power supply

Type CP-S, CP-C & CP-A Switch mode

Power supply CP-E 24/2.5

Three-phase monitoring relay

Power supply CP-E 24/20.0

Power supply CP-E 24/0.75

Control module CP-A CM

Primary switch mode power supplies Product group picture

Three-phase monitoring relays Product group picture

CP-E range Benefits and advantages

Power supply CP-E 48/5.0 Primary switch mode power supply Data sheet

Power supply CP-E 12/10.0 Primary switch mode power supply Data sheet

Power supply CP-E 24/2.5

CP-T range Product group picture

Three-phase monitoring relays Table of contents

Three-phase monitoring relays Product group picture

Power supply CP-D 24/1.3

CP-T range Benefits and advantages

Power supply CP-D 24/4.2 Primary switch mode power supply

Insulation Monitoring Relays CM range

ABB ABB 59 2CDC110004C0205. Measuring and monitoring relays. CM and C5xx range. Content

Electronic timer CT-AWS Impulse-OFF with 1 c/o contact Data sheet

Thermistor motor protection relays

CM-IWM.11 Insulation monitoring relay

Electronic timer CT-ERS ON-delayed with 2 c/o contacts Data sheet

Control module CP-A CM

Analog signal converters CC range

Grid feeding monitoring relay acc. VDE AR-N 4105 CM-UFD.M21

Thermistor motor protection relays

Pluggable interface relays CR-U Universal relays

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

Switching power supplies CP range, Linear power supplies CP-L range. Content

isolr275 / AGH-LR Digital Ground Fault Monitor / Ground Detector For Low-Resistance Ungrounded (Floating) AC/DC Systems

Subject to changes 11/2003 Page 1/7

s s s 3-60 s min min 3-60 min h h 3-60 h V AC, 50/60 Hz

Electronic timer CT-SDE

Type: EASY719 AC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 115/230 V AC. Description

Analog signal converters CC-E I/I

Type: EASY719 DA RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 12 V DC. Description

Transcription:

Data sheet Insulation monitoring relays CM-IWN.4/5/6 For unearthed AC, DC and mixed AC/DC systems up to U n = 400 V AC and 600 V DC The CM-IWN serves to monitor insulation resistance in accordance with IEC 61557-8 in unearthed IT AC systems, IT AC systems with galvanically connected DC circuits, or unearthed IT DC systems with a voltage up to 400 V AC and 600 V DC. The measuring range can be extended up to 690 V AC and 1000 V DC by using the coupling unit CM-IVN. It can be configured to the requirements of the applications and therefore used multi-functional. All devices are available with two different terminal versions. You can choose between the proven screw connection technology (double-chamber cage connection terminals) and the completely tool-free Easy Connect Technology (push-in terminals). 2CDC 251 021 V0012 Characteristics For monitoring the insulation resistance of unearthed IT systems up to U n = 400 V AC and 600 V DC According to IEC/EN 61557-8 Electrical safety in low voltage distribution systems up to 1000 V a.c. and 1500 V d.c. Equipment for testing, measuring or monitoring of protective measures Part 8: Insulation monitoring devices for IT systems" 1) Specifically for applications with high system leakage capacitances, for example in photovoltaic environments Rated control supply voltage 24-240 V AC/DC Prognostic measuring principle with superimposed square wave signal Two measuring ranges 1-100 kω and 2-200 kω One (1 x 2 c/o) or two (2 x 1 c/o) threshold values R an 1/R1 1) (final switch-off) and R an 2/R2 2) (prewarning) configurable 3) Precise adjustment of the threshold values in 1 kω steps (R1) and 2 kω steps (R2) Interrupted wire detection configurable Non-volatile fault storage configurable Open- or closed-circuit principle configurable Precise adjustment by front-face operating controls Screw connection technology or Easy Connect Technology available Housing material for highest fire protection classification UL 94 V-0 Tool-free mounting on DIN rail as well as demounting 45 mm (1,77 in) width 3 LEDs for the indication of operational states 1) CM-IWN.6 does not meet the requirements of IEC/EN 61557-8 regarding the response time t an. 2) term acc. to IEC/EN 61557-8 3) R2 only active with 2 x 1 c/o configuration Approvals A UL 508, CAN/CSA C22.2 No.14 K IEC/EN 60947-5-1, CB scheme pending E D L Marks a b GB14048.5-2001, CCC GOST RMRS CE C-Tick

Order data Insulation monitoring relay Type Nominal voltage U n of the distribution system to be monitored Rated control supply voltage System leakage capacitance, max. Connection technology Order code CM-IWN.4P 0-400 V AC / 0-600 V DC 24-240 V AC/DC 500 µf Push-in terminals 1SVR 760 660 R0300 CM-IWN.4S Screw type terminals 1SVR 750 660 R0300 CM-IWN.5P 0-400 V AC / 0-600 V DC 24-240 V AC/DC 1000 µf Push-in terminals 1SVR 760 660 R0400 CM-IWN.5S Screw type terminals 1SVR 750 660 R0400 CM-IWN.6P 0-400 V AC / 0-600 V DC 24-240 V AC/DC 2000 µf Push-in terminals 1SVR 760 660 R0500 CM-IWN.6S Screw type terminals 1SVR 750 660 R0500 Accessories Type Description Order code CM-IVN.P CM-IVN.S Coupling unit for connection of the CM-IWN to systems with voltages U n up to 690 V AC and 1000 V DC with Push-in terminals Coupling unit for connection of the CM-IWN to systems with voltages U n up to 690 V AC and 1000 V DC with Screw type terminals 1SVR 760 669 R9400 1SVR 750 669 R9400 ADP.02 Adapter for screw mounting 1SVR 440 029 R0100 MAR.12 Marker label for devices with DIP switches 1SVR 730 006 R0000 COV.12 Sealable transparent cover 1SVR 750 005 R0100 2 - Insulation monitoring relays CM-IWN.4/5/6 Data sheet

Connection technology Maintenance free Easy Connect Technology with push-in terminals Type designation CM-xxN.yyP Approved screw connection technology with double-chamber cage connection terminals Type designation CM-xxN.yyS 2CDC 253 026 F0011 2CDC 253 025 F0011 Push-in terminals Tool-free connection of rigid and flexible wires with wire end ferrule according to DIN 46228-1-A, DIN 46228-4-E Wire size: 2 x 0.5-1.5 mm², (2 x 20-16 AWG) Easy connection of flexible wires without wire end ferrule by opening the terminals No retightening necessary One operation lever for opening both connection terminals For triggering the lever and disconnecting of wires you can use the same tool (Screwdriver according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in)) Constant spring force on terminal point independent of the applied wire type, wire size or ambient conditions (e. g. vibrations or temperature changes) Opening for testing the electrical contacting Gas-tight Double-chamber cage connection terminals Terminal spaces for different wire sizes: fine strand with/without wire end ferrule: 1 x 0.5-2.5 mm² (2 x 20-14 AWG), 2 x 0.5-1.5 mm² (2 x 20-16 AWG) rigid: 1 x 0.5-4 mm² (1 x 20-12 AWG), 2 x 0.5-2.5 mm² (2 x 20-14 AWG) One screw for opening and closing of both cages Pozidrive screws for pan- or crosshead screwdrivers according to DIN ISO 2380-1 Form A 0.8 x 4 mm (0.0315 x 0.157 in), DIN ISO 8764-1 PZ1 ø 4.5 mm (0.177 in) Both the Easy Connect Technology with push-in terminals and screw connection technology with double-chamber cage connection terminals have the same connection geometry as well as terminal position. Data sheet Insulation monitoring relays CM-IWN.4/5/6-3

Functions Operating controls 1 1 Front-face rotary switches to adjust the threshold value: R1.1 for R1 tens figure: 0, 10, 20, 30, 40, 50, 60, 70, 80, 90 kω in ten kω steps R1.2 for R1 units figure: 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 kω in one kω steps 2CDC 251 021 V0012 2 3 4 R2.1 for R2 tens figure: 0, 20, 40, 60, 80, 100, 120, 140, 160, 180 kω in twenty kω steps R2.2 for R2 units figure: 2, 4, 6, 8, 10, 12, 14, 16, 18, 20 kω in two kω steps 2 Test and reset button 3 Indication of operational states U: green LED control supply voltage F1: red LED fault message F2: yellow LED relay status 4 DIP switches (see DIP switch functions) Application / monitoring function The CM-IWN serves to monitor insulation resistance in accordance with IEC 61557-8 in unearthed IT AC systems, IT AC systems with galvanically connected DC circuits, or unearthed IT DC systems. The insulation resistance between system lines and system earth is measured. If this falls below the adjustable threshold values, the output relays switch into the fault state. The device can monitor control circuits (single-phase) and main circuits (3-phase). Supply systems with voltages U n = 0-400 V AC (15-400 Hz) or 0-600 V DC can be directly connected to the measuring inputs and their insulation resistance being monitored. For systems with voltages above 400 V AC and 600 V DC the coupling unit CM-IVN can be used for the expansion of the CM-IWN voltage range. Measuring principle A pulsating measuring signal is fed into the system to be monitored and the insulation resistance calculated. This pulsating measuring signal alters its form depending on the insulation resistance and system leakage capacitance. From this altered form the change in the insulation resistance is forecast. When the forecast insulation resistance corresponds to the insulation resistance calculated in the next measurement cycle and is smaller than the set threshold value, the output relays are activated or deactivated, depending on the device configuration. This measuring principle is also suitable for the detection of symmetrical insulation faults. Additional monitoring functions When interrupted wire detection u is activated, the CM-IWN automatically controls the system/measuring circuit connections L+ and L- when the system starts up. This can be repeated at any time by activating the test function. The CM-IWN cyclically monitors the measuring circuit connections w and KE for wire interruption. In case of a wire interruption in one of the connections, the output relays switch to the fault state. In addition, the unearthed AC-, DC- or AC/DC system is monitored for inadmissible system leakage capacitance. If the system leakage capacitance is too high, the output relays switch to the fault state. Also incorrect settings that could cause a faulty function of the device are monitored. When the device detects such an incorrect setting, the output relays switch to the fault state. 4 - Insulation monitoring relays CM-IWN.4/5/6 Data sheet

Operating mode The system to be monitored is connected to terminals L+ and L-. The earth potential is connected to terminals w and KE. Depending on the setting, the device operates according to the open-circuit principle h (fault state: relay energized) or closed-circuit principle g (fault state: relay de-energized). Once the control supply voltage has been applied the insulation monitoring relay runs through a system test routine. The system is diagnosed and the settings are tested. If no internal or external faults are found after this test routine is completed, the output relays switch into the operational state. All operating states are signalled by the front-face LEDs. See table "LEDs, status information and fault messages" on page 10. Configuration 1 x 2 c/o contacts j (final switch-off) With this configuration the settings for the threshold value for prewarning (R2) have no influence on the operating function. If the measured value drops below the set threshold value, the output relays switch into the fault state. If the measured value exceeds the threshold value plus hysteresis, the output relays switch back into their original state. Configuration 2 x 1 c/o contact i (prewarning and final switch-off) If the measured value drops below the set threshold value for prewarning the second output relay 21-22/24 switches. If the measured value drops below the threshold value for final switch-off, the first output relay 11-12/14 switches. If the measured value exceeds the threshold value for final switch-off plus hysteresis, the first output relay 11-12/14 switches back into its original state. If the measured value exceeds the threshold value for prewarning plus hysteresis, also the second output relay 21-22/24 switches back to its original state. Test function The test function is only possible when there is no fault. By pressing the front-face combined test/reset button a system test routine is executed. The output relays switch to the fault state as long as the test/reset button is pressed, the control contact S1-S3 is closed or the test functions are processed. The test function can be activated either with the front-face combined test/reset button or with a remote test button connected as shown in the picture. S1 S2 S3 2CDC 252 109 F0009 Fault storage, reset function and remote reset When fault storage f is active, the output relays remain in the fault state and only switch back to their original state after the combined test/reset button is pressed or after the remote reset (terminals S2-S3) is activated, and when the insulation resistance is higher than the set threshold value(s) plus hysteresis. The fault storage is designed non-volatile (remanent). This means that after switch-off and return of the control supply voltage the device returns to the state it was prior to the switch-off until a reset is executed. Depending on the configuration of DIP switch 2, there are several possibilities of resetting the device, as shown in the picture. DIP switch 2 e f S1 S2 S3 1.) Front 2.) Remote 3.) A1-A2 1.) Front 2.) Remote S1 S2 S3 S1 S2 S3 1.) Front 2.) A1-A2 1.) Auto- Reset 1.) Front 2CDC 252 110 F0009 Data sheet Insulation monitoring relays CM-IWN.4/5/6-5

Measuring range expansion by using the coupling unit CM-IVN The coupling unit CM-IVN serves to connect the CM-IWN to systems up to 690 V AC and 1000 V DC. Terminals VS, V1+, V1- are connections for the coupling unit. Function descriptions/diagrams G Control supply voltage not applied / Output contact open / LED OFF B Control supply voltage applied / Output contact closed / LED ON A1-A2 S1-S3 S2-S3 Measured value Hysteresis Threshold value Open-circuit principle h 11-14 11-12 21-22 U: green LED F: red LED R: yellow LED t s 2CDC 252 027 F0211 Closed-circuit principle g 11-14 11-12 U: green LED F: red LED R: yellow LED t s = Start-up time, see table Typical start-up times 2CDC 252 027 F0211 Insulation resistance monitoring w/o fault storage e, auto reset, 1 x 2 c/o j A1-A2 S1-S3 S2-S3 Measured value Hysteresis Threshold value Open-circuit principle h 11-14 11-12 21-22 U: green LED F: red LED R: yellow LED t s t s 2CDC 252 028 F0211 Closed-circuit principle g 11-14 11-12 U: green LED F: red LED R: yellow LED t s = Start-up time, see table Typical start-up times 2CDC 252 028 F0211 Insulation resistance monitoring with fault storage f, manual reset, 1 x 2 c/o j 6 - Insulation monitoring relays CM-IWN.4/5/6 Data sheet

A1-A2 S1-S3 S2-S3 Measured value Hysteresis Prewarning Hysteresis Final switch-off Open-circuit principle h 11-14 11-12 21-22 U: green LED F: red LED R: yellow LED t s 2CDC 252 029 F0211 Closed-circuit principle g 11-14 11-12 U: green LED F: red LED R: yellow LED t s = Start-up time, see table Typical start-up times 2CDC 252 029 F021 Insulation resistance monitoring w/o fault storage e, auto reset, 2 x 1 c/o i A1-A2 S1-S3 S2-S3 Measured value Hysteresis Prewarning Hysteresis Final switch-off Open-circuit principle h 11-14 11-12 21-22 U: green LED F: red LED R: yellow LED t s t s 2CDC 252 030 F0211 Closed-circuit principle g 11-14 11-12 U: green LED F: red LED R: yellow LED t s = Start-up time, see table Typical start-up times 2CDC 252 030 F0211 Insulation resistance monitoring with fault storage f, manual reset, 2 x 1 c/o i Data sheet Insulation monitoring relays CM-IWN.4/5/6-7

Connection and wiring Connection diagram A1 11 21 S1 S2 S3 A1-A2 S1-S3 Control supply voltage Remote test L+ L- KE w 11 21 S2-S3 Remote reset R < w A1 A2 12 14 L+ VS 22 24 L- KE 12 14 22 24 V1+ V1- A2 w 2CDC 252 104 F0009 L+, L w, KE VS, V1+, V1-11-12/14 21-22/24 Measuring circuit/input, system connection Measuring circuit/input, earth connections Connections for the coupling unit (if used) Output relay 1, open- or closed-circuit principle Output relay 2, open- or closed-circuit principle Wiring diagrams Always connect L+ and L- to different conductors. L+ and L- can be connected to any of the conductors. U n 400 V AC; 600 V DC (For monitoring of systems with higher voltages, use coupling unit CM-IVN.) A1 11 21 S1 S2 S3 A1 11 21 S1 S2 S3 12 14 L+ VS V1+ V1-22 24 L- KE A2 w 12 14 L+ VS V1+ V1-22 24 L- KE A2 w 2CDC 252 082 F0009 L N PE 2CDC 252 086 F0009 2CDC 252 088 F0009 PWM DC L+ L- PE 2CDC 252 086 F0009 2-wire AC system 2-wire DC system A1 11 21 S1 S2 S3 A1 11 21 S1 S2 S3 12 14 L+ VS V1+ V1-22 24 L- KE A2 w PWM DC L+ L- 12 14 L+ VS V1+ V1-22 24 L- KE A2 w 2CDC 252 089 F0009 L1 L2 L3 PE 2CDC 252 093 F0009 2CDC 252 095 F0009 PWM DC L+ L- L+ M L- PE 2CDC 252 093 F0009 3-wire AC system 3-wire DC system A1 11 21 S1 S2 S3 12 14 L+ VS V1+ V1-22 24 L- KE A2 w 2CDC 252 096 F0009 L1 L2 L3 N PE 2CDC 252 100 F0009 4-wire AC system 8 - Insulation monitoring relays CM-IWN.4/5/6 Data sheet

Configuration and settings Rotary switches R1.1, R1.2, R2.1 and R2.2 (treshold values) By means of four separate 10 position rotary switches with direct reading scales, the threshold values for the insulation resistance R F of the systems to be monitored can be adjusted. With the Rx.1 rotary switch the tens figure is set and with the Rx.2 rotary switch the units figure is set. The set threshold value is then the addition of the two values. For example, R1.1 set to 70 and R1.2 set to 8 leads to a threshold value for R1 of 78 kω. DIP switches Position 4 3 2 1 ON OFF i ufg j v e h 2CDC 252 050 F0b09 DIP switch 1 Operating principle of the output relays DIP switch 2 Non-volatile fault storage DIP switch 3 Interrupted wire detection DIP switch 4 2 x 1 c/o, 1 x 2 c/o ON Closed-circuit principle g If closed-circuit principle is selected, the output relays are energized. They de-energize if a fault is occuring. Fault storage activated (latching) f If the fault storage function is activated, the output relays remain in tripped position until a reset is done either by the front-face button or by the remote reset connection S2-S3. This function is non-volatile. Interrupted wire detection activated u With this configuration, the CM-IWN monitors the wires connected to L+ and L- for interruptions. 2 x 1 c/o (SPDT) contact i If operating principle 2 x 1 c/o contact is selected, the output relay R1 (11-12/14) reacts to threshold value R1 (final switch-off) and the output relay R2 (21-22/24) reacts to threshold value R2 (prewarning) OFF (default) Open-circuit principle h If open-circuit principle is selected, the output relays are de-energized. The energize if a fault is occuring. Fault storage de-activated (non latching) e If the fault storage function is de-activated, the output relays switch back to their original position as soon as the insulation fault no longer exists. Interrupted wire detection de-activated v With this configuration the interrupted wire detection is de-activated. 1 x 2 c/o (SPDT) contacts j If operating principle 1 x 2 c/o contacts is selected, both output relays R1 (11-12/14) and R2 (21-22/24) react synchronously to threshold value R1 (final switch-off). Settings of the threshold value R2 have no effect on the operation. Data sheet Insulation monitoring relays CM-IWN.4/5/6-9

Indication of operational states LEDs, status information and fault messages Operational state LED U (green) LED F (red) LED R (yellow) Start-up No fault Prewarning Insulation fault (below threshold value) OFF OFF W OFF 1) V V W W 1) V V KE/w wire interruption V U L+/L- wire interruption during W / X S system start-up / test function System leakage capacitance too high / invalid measurement result V T Internal system fault 1) X Setting fault 2) W W W 1) 1) 1) 1) Test function No fault after fault storage 3) X V OFF 1) 4) X 1) Depending on the configuration (see "Function descriptions/diagrams" on page 6. 2) Possible faulty setting: The threshold value for final switch-off is set at a higher value than the threshold value for prewarning. 3) The device has triggered after an insulation fault. The fault has been stored and the insulation resistance has returned to a higher value than the threshold value plus hysteresis. 4) Depending on the fault Application example CM-IWN.5 PV-module Converter control system 1 1 1 1 1 1000 V DC 2 2 2 2 2 DC AC Medium voltage grid monitored circuits VL+ A1 11 21 S1 S2 S3 C e 1000 μf L+ L- KE w 11 21 R < w L+ VL- V1+ L- V1- VS VE Vw A1 A2 12 14 22 24 12 14 L+ VS V1+ V1-22 24 L- KE w A2 20 20 20 20 20 PE Insulation monitoring system CM-IWN.5 with coupling unit CM-IVN String 1... String n 2CDC 252 031 F0211 10 - Insulation monitoring relays CM-IWN.4/5/6 Data sheet

Technical data Data at T a = 25 C and rated values, unless otherwise indicated Input circuits Input circuit - Supply circuit A1 - A2 Rated control supply voltage U s 24-240 V AC/DC Rated control supply voltage tolerance -15...+10 % Typical current / power consumption 24 V DC 55 ma / 1.3 VA 115 V AC 20 ma / 2.3 VA 230 V AC 15 ma / 3.5 VA Rated frequency f s DC or 15-400 Hz Frequency range AC 13.5-440 Hz Power failure buffering time min. 20 ms Start-up time t s See Typical start-up times on page 15. Input circuit - Measuring circuit Monitoring function Measuring principle Nominal voltage U n of the distribution system to be monitored L+, L-, w, KE insulation resistance monitoring of IT systems (IEC/EN 61557-8) prognostic measuring principle with superimposed square wave signal 0-400 V AC / 0-600 V DC Voltage range of the distribution system to be monitored 0-460 V AC / 0-690 V DC (tolerance +15 %) Rated frequency f N of the distribution system to be monitored DC or 15-400 Hz Tolerance of the rated frequency f N 13.5-440 Hz System leakage capacitance C e CM-IWN.4 max. 500 µf CM-IWN.5 max. 1000 µf CM-IWN.6 max. 2000 µf Extraneous DC voltage U fg (when connected to an AC system) max. 460 V DC Voltage range expansion of the measuring input with coupling unit CM-IVN Number of possible response / threshold values 2 Adjustment range of the specified response value R an (threshold) min.-max. R1 min.-max. R2 Adjustment resolution R1 1 kω Tolerance of the adjusted threshold value / Relative percentage uncertainty A at -5...+45 C, U n = 0-115 %, U s = 85-110 %, f N, f s, C e = 1µF Hysteresis related to the threshold value R2 use connection terminals V1+, V1-, VS max. length of connection cable 40 cm 1-100 kω 2-200 kω (activated/de-activated by DIP switch) 2 kω Internal impedance Z i at 50 Hz 155 kω Internal DC resistance R i 185 kω Measuring voltage U m 24 V Tolerance of measuring voltage U m +10 % Measuring current I m at 1-15 kω R F ±1 kω / in combination with CM-IVN ±1.5 kω at 15-200 kω R F ±8 % 25 %; min. 2 kω 0.15 ma Response time t an pure AC system 0.5 x R an and C e = 1 µf max. 10 s (except CM-IWN.6: max. 60 s) DC system or AC system with connected rectifiers max. 15 s (except CM-IWN.6: max. 90 s) Repeat accuracy (constant parameters) Accuracy of R a (measured value) within the rated control supply voltage tolerance Accuracy of R a (measured value) within the operation temperature range Transient overvoltage protection (w - terminal) at 1-10 kω R F at 10-200 kω R F < 0.1 % of full scale < 0.05 % of full scale 5 Ω / K 0.05 % / K avalanche diode Data sheet Insulation monitoring relays CM-IWN.4/5/6-11

Input circuit - Control circuits S1 - S2 - S3 Control inputs - volt free S1-S3 remote test S2-S3 remote reset Maximum switching current in the control circuit 1 ma Maximum cable length to the control inputs 50 m - 100 pf/m (164 ft - 30.5 pf/ft) Minimum control pulse length 150 ms No-load voltage at the control input 24 V DC User interface Indication of operational states Control supply voltage U green LED Fault message F red LED Relay status R yellow LED Details see table "LEDs, status information and fault messages" on page 10 and "Function descriptions/diagrams" on page 6. Operating elements and controls Adjustment of threshold value R1 R1.1 rotary switch, 10 kω steps for the tens figure R1.2 rotary switch, 1 kω steps for the units figure Adjustment of threshold value R2 R2.1 rotary switch, 20 kω steps for the tens figure R2.2 rotary switch, 2 kω steps for the units figure Configuration of DIP switch 1 operating principle of the output relays DIP switch 2 non volatile fault storage DIP switch 3 interrupted wire detection DIP switch 4 2 x 1 c/o, 1 x 2 c/o Output circuits Kind of output 11-12/14 21-22/24 relay, 1st c/o (SPDT) contact relay, 2nd c/o (SPDT) contact 2 x 1 or 1 x 2 c/o (SPDT) contacts configurable Operating principle open- or closed-circuit principle 1) configurable Contact material AgNi alloy, Cd free Rated operational voltage (IEC/EN 60947-1) 250 V AC / 300 V DC Minimum switching voltage / Minimum switching current 24 V / 10 ma Maximum switching voltage / Maximum switching current see "Load limits curves" on page 19 Rated operational current I e AC12 (resistive) at 230 V 4 A (IEC/EN 60947 5 1) AC15 (inductive) at 230 V 3 A DC12 (resistive) at 24 V 4 A DC13 (inductive) at 24 V 2 A AC rating (UL 508) Utilization category B 300, pilot duty general purpose (250 V, 4 A, cos φ 0.75) (Control Circuit Rating Code) max. rated operational voltage 250 V AC max. continuous thermal current at B 300 4 A max. making/breaking apparent 3600/360 VA power at B 300 Mechanical lifetime 30 x 10 6 switching cycles Electrical lifetime AC12, 230 V, 4 A 0.1 x 10 6 switching cycles Max. fuse rating to achieve short-circuit protection n/c contact 6 A fast-acting n/o contact 10 A fast-acting Conventional thermal current I th (IEC/EN 60947-1) 4 A 1) Closed-circuit principle: Output relay(s) de-energize(s) if measured value falls below the adjusted threshold value R an Open-circuit principle: Output relay(s) energize(s) if measured value falls below the adjusted threshold value R an 12 - Insulation monitoring relays CM-IWN.4/5/6 Data sheet

General data MTBF on request Duty time 100 % Dimensions (W x H x D) 45 x 78 x 100 mm (1.78 x 3.07 x 3.94 in) Screw connection technology Easy Connect Technology (push-in) Weight net weight CM-IWN.4 0.241 kg (0.531 lb) 0.217 kg (0.478 lb) Mounting Mounting position CM-IWN.5 0.241 kg (0.531 lb) 0.217 kg (0.478 lb) CM-IWN.6 0.241 kg (0.531 lb) 0.217 kg (0.478 lb) gross weight CM-IWN.4 0.270 kg (0.595 lb) 0.246 kg (0.542 lb) Minimum distance to other units vertical not necessary CM-IWN.5 0.270 kg (0.595 lb) 0.246 kg (0.542 lb) CM-IWN.6 0.270 kg (0.595 lb) 0.246 kg (0.542 lb) horizontal Degree of protection housing / terminal IP50 / IP20 DIN rail (IEC/EN 60715), snap-on mounting without any tool any 10 mm (0.39 in) at U n > 400 V Electrical connection Wire size Stripping length fine strand with(out) wire end ferrule rigid Screw connection technology 1 x 0.5-2.5 mm² (1 x 20-14 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) 1 x 0.5-4 mm² (1 x 20-12 AWG) 2 x 0.5-2.5 mm² (2 x 20-14 AWG) 8 mm (0.32 in) Tightening torque 0.6-0.8 Nm (5.31-7.08 lb.in) - Easy Connect Technology (push-in) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) 2 x 0.5-1.5 mm² (2 x 20-16 AWG) Environmental data Ambient temperature ranges operation -25...+60 C storage -40...+85 C transport -40...+85 C Climatic category IEC/EN 60721-3-3 3K5 (no condensation, no ice formation) Damp heat, cyclic IEC/EN 60068 2 30 6 x 24 h cycle, 55 C, 95 % RH Vibration, sinusoidal IEC/EN 60255-21-1 Class 2 Shock, half-sine IEC/EN 60255-21-2 Class 2 Data sheet Insulation monitoring relays CM-IWN.4/5/6-13

Isolation data Rated impulse withstand voltage U imp supply circuit / measuring circuit 6 kv (IEC/EN 60947-1, IEC/EN 60664-1) supply circuit / output circuits 6 kv measuring circuit / output circuits 6 kv output circuit 1 / output circuit 2 4 kv Pollution degree (IEC/EN 60664-1) 3 Overvoltage category (IEC/EN 60664-1) III Rated insulation voltage U i supply circuit / measuring circuit 600 V (IEC/EN 60947-1, IEC/EN 60664-1) supply circuit / output circuits 300 V measuring circuit / output circuits 600 V output circuit 1 / output circuit 2 300 V Basic insulation for rated control supply supply circuit / measuring circuit 400 V AC / 600 V DC voltage (IEC/EN 60664-1) supply circuit / output circuits 250 V AC / 300 V DC measuring circuit / output circuits 400 V AC / 600 V DC output circuit 1 / output circuit 2 250 V AC / 300 V DC Protective separation supply circuit / output circuits 250 V AC / 250 V DC (IEC/EN 61140, EN 50178) supply circuit / measuring circuit 250 V AC / 250 V DC measuring circuit / output circuits 250 V AC / 250 V DC Test voltage supply circuit / output circuits 2.32 kv, 50 Hz, 2 s (IEC/EN 60255-5, IEC/EN 61010-1) supply circuit / measuring circuit 2.32 kv, 50 Hz, 2 s measuring circuit / output circuits 2.53 kv, 50 Hz, 1 s Standards Product standard IEC/EN 61557-8, IEC/EN 60255-6 Other standards EN 50178 Low Voltage Directive EMC Directive RoHS Directive 2006/95/EC 2004/108/EC 2002/95/EC Electromagnetic compatibility Interference immunity to IEC/EN 61000-6-1, IEC/EN 61000-6-2, IEC/EN 61326-2-4 electrostatic discharge IEC/EN 61000-4-2 Level 3, 6 kv / 8 kv radiated, radio-frequency, electromagnetic field IEC/EN 61000-4-3 Level 3, 10 V/m (1 GHz) / 3 V/m (2 GHz) / 1 V/m (2.7 GHz) electrical fast transient/burst IEC/EN 61000-4-4 Level 3, 2 kv / 5 khz surge IEC/EN 61000-4-5 Level 3, installation class 3, supply circuit and measuring circuit 1 kv L-L, 2 kv L-earth conducted disturbances, induced by radiofrequency IEC/EN 61000-4-6 Level 3, 10 V fields voltage dips, short interruptions and voltage IEC/EN 61000-4-11 Class 3 variations harmonics and interharmonics IEC/EN 61000-4-13 Class 3 Interference emission IEC/EN 61000-6-3, IEC/EN 61000-6-4 high-frequency radiated IEC/CISPR 22, Class B EN 55022 high-frequency conducted IEC/CISPR 22, Class B EN 55022 14 - Insulation monitoring relays CM-IWN.4/5/6 Data sheet

Technical diagrams Typical start-up times R F overall [kohm] 1 µf 20 µf 250 µf 500 µf Start-up time [s] * ) 1 45 45 45 45 10 45 45 80 80 20 45 45 111 240 24 45 45 240 240 28 45 45 240 240 33 45 45 240 240 50 45 45 240 525 66 45 45 270 810 100 45 45 270 810 200 45 45 810 870 * ) incl. first measuring cycle Start-up times CM-IWN.4 R F overall [kohm] 1 µf 20 µf 250 µf 500 µf 750 µf 1000 µf Start-up time [s] * ) 1 47 47 47 47 47 47 10 47 47 80 80 205 205 20 47 47 80 205 205 265 24 47 47 205 205 205 745 28 47 47 205 205 745 745 33 47 47 205 205 745 745 50 47 47 205 745 745 745 66 47 47 205 745 745 745 100 47 47 265 745 745 745 200 47 47 745 745 745 2785 * ) incl. first measuring cycle Start-up times CM-IWN.5 R F overall [kohm] 1 µf 20 µf 250 µf 500 µf 750 µf 1000 µf 1500 µf 2000 µf Start-up time [s] * ) 1 70 70 70 70 70 70 70 70 10 70 70 70 70 230 230 230 230 20 70 70 120 230 230 230 770 770 24 70 70 230 230 230 740 770 770 28 70 70 230 230 230 770 770 770 33 70 70 230 230 770 770 770 800 50 70 70 230 260 770 770 800 830 66 70 70 230 770 770 830 830 2910 100 70 70 260 800 830 830 2910 2910 200 70 70 800 860 890 2910 3010 3040 * ) incl. first measuring cycle Start-up times CM-IWN.6 Certain parameters, such as voltage variations and frequency fluctuation etc., may have an impact on these start-up times. The initialization of the CM-IWN with default values can result in a start-up time (incl. first measuring cycle) that is shorter than the later maximum duration of a measuring cycle. Data sheet Insulation monitoring relays CM-IWN.4/5/6-15

Typical measuring times The indicated time values are the pure measuring times in a stable system, not considering the start-up times. Certain parameters, such as voltage variations and frequency fluctuation etc., may have an impact on these measuring times. When an insulation fault occurs, the maximum reaction time until the output relays switch is 2 times the typical measuring time, provided that no other parameters in the system change. Measuring times of CM-IWN.4 R F overall 1 µf 20 µf 250 µf 500 µf [kohm] Measuring time [s] 1 6 6 6 6 10 6 6 35 65 20 6 6 65 128 24 6 6 65 254 28 6 6 128 254 33 6 6 128 254 50 6 10 128 254 66 6 10 254 508 100 6 18 254 508 120 6 18 254 508 140 6 18 254 1010 160 6 18 508 1010 180 6 18 508 1010 200 6 18 508 1010 Measuring time [s] 1000 800 600 400 200 0 0 20 500 μf 250 μf 20 μf 1 μf 40 60 80 100 120 140 160 180 200 Overall insulation resistance R F [kω] 2CDC 252 021 F0212 Measuring time [s] 10000 1000 500 400 300 200 100 R F = 160 kω 180 kω 200 kω R F = 140 kω R F = 100/120 kω R F = 66 kω R F = 50 kω R F = 28/33 kω R F = 24 kω R F = 20 kω R F = 10 kω 10 R F = 1 kω 1 1 20 250 500 2CDC 252 020 F0212 System leakage capacitance, max. C e 16 - Insulation monitoring relays CM-IWN.4/5/6 Data sheet

Measuring times of CM-IWN.5 R F overall 1 µf 20 µf 250 µf 500 µf 750 µf 1000 µf [kohm] Measuring time [s] 1 4 4 6 10 18 18 10 4 6 65 130 254 254 20 4 10 65 254 254 505 24 4 10 130 254 254 505 28 4 10 130 254 505 505 33 4 10 130 254 505 505 50 4 18 254 505 1010 1010 66 4 18 254 505 1010 1010 100 4 34 254 505 1010 1010 120 4 34 505 1010 1010 1010 140 4 34 505 1010 1010 2016 160 4 34 505 1010 1010 2016 180 4 34 505 1010 1010 2016 200 4 34 505 1010 1010 2016 Measuring time [s] 2500 2000 1500 1000 500 0 0 20 1000 μf 750 μf 500 μf 250 μf 20 μf 1 μf 40 60 80 100 120 140 160 180 200 Overall insulation resistance R F [kω] 2CDC 252 026 F0211 Measuring time [s] 10000 1000 500 400 300 200 100 R F = 140 kω 160 kω 180 kω 200 kω R F = 120 kω R F = 100 kω R F = 50/66 kω R F = 28/33 kω R F = 24 kω R F = 20 kω R F = 10 kω R F = 1 kω 10 1 20 250 500 750 1000 2CDC 252 002 F0212 System leakage capacitance, max. C e Data sheet Insulation monitoring relays CM-IWN.4/5/6-17

Measuring times of CM-IWN.6 R F overall [kohm] 1 µf 20 µf 250 µf 500 µf 750 µf 1000 µf 1500 µf 2000 µf Measuring time [s] 1 33 33 33 33 33 33 33 33 10 33 33 33 66 128 128 254 254 20 33 33 66 128 254 254 506 506 24 33 33 66 254 254 254 506 1010 28 33 33 128 254 254 506 506 1010 33 33 33 128 254 506 506 1010 1010 50 33 33 128 254 506 506 1010 1010 66 33 33 254 506 506 1010 1010 2020 100 33 33 254 506 1010 1010 2020 2020 120 33 33 254 506 1010 1010 2020 2020 140 33 33 254 506 1010 1010 2020 2020 160 33 33 506 1010 1010 2020 2020 4027 180 33 33 506 1010 1010 2020 2020 4027 200 33 33 506 1010 1010 2020 2020 4027 Measuring time [s] 4000 3500 2000 µf 3000 2500 2000 1000 μf 1500 µf 1500 1000 500 0 0 20 500 μf 750 μf 250 μf 20 μf 1 μf 40 60 80 100 120 140 160 180 200 Overall insulation resistance R F [kω] 2CDC 252 022 F0212 Measuring time [s] 10000 1000 500 400 300 200 100 R F = 160/180/200 kω R F = 100/120/140kΩ R F = 66 kω R F = 33/50kΩ R F = 28kΩ R F = 24 kω R F = 20 kω R F = 10 kω R F = 1 kω 10 1 20 250 500 750 1000 1500 2000 2CDC 252 023 F0212 System leakage capacitance, max. C e 18 - Insulation monitoring relays CM-IWN.4/5/6 Data sheet

Load limits curves AC voltage [V] 400 300 200 100 80 60 50 40 30 20 10 0.1 0.2 0.5 resistive load 1 2 4 6 10 AC current [A] 2CDC 252 157 F0206 AC voltage [V] 400 300 200 100 80 60 50 40 30 20 10 0.1 0.2 0.5 resistive load 1 2 4 6 10 AC current [A] 2CDC 252 158 F0206 AC load (resistive) DC load (resistive) 1.0 0.9 0.8 F 0.7 0.6 0.5 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0 cos ϕ Derating factor F at inductive AC load 2CDC 252 192 F0205 Switching cycles 10 6 10 5 10 4 1 2 3 4 250 V AC resistive load 5 6 7 8 Switching current [A] 2CDC 252 156 F0206 Contact lifetime Data sheet Insulation monitoring relays CM-IWN.4/5/6-19

Dimensions in mm and inches 114.5 4.51 107.0 4.21 45.0 1.77 85.6 3.37 104.8 4.13 2CDC 252 022 F0011 Accessories in mm and inches 11.5 0.453 45.0 0.89 9.3 0.37 5.75 0.23 45 1.772 35 1.378 6.5 0.256 60 2.362 62.5 2.461 70 2.756 10 0.394 20 0.787 2CDC 252 009 F0010 22.2 0.874 4T22 19.9 0.783 7.85 0.309 2CDC 252 020 F0011 68 2.68 front to back 111.8 4.40 2CDC 252 023 F0011 ADP.02 Adapter for screw mounting MAR.12 Marker label for devices with DIP switches COV.12 Sealable transparent cover Further documentation Document title Document type Document number Electronic products and relays Catalog 2CDC 110 004 C02xx CM-IWN.1, CM-IWN.4, CM-IWN.5, CM-IWN.6 Instruction sheet 1SVC 750 020 M0000 You can find the documentation on the internet at www.abb.com/lowvoltage -> Control Products -> Electronic Relays and Controls -> Insulation Monitors. 20 - Insulation monitoring relays CM-IWN.4/5/6 Data sheet

Contact us ABB STOTZ-KONTAKT GmbH P. O. Box 10 16 80 69006 Heidelberg, Germany Phone: +49 (0) 6221 7 01-0 Fax: +49 (0) 6221 7 01-13 25 E-mail: info.desto@de.abb.com You can find the address of your local sales organisation on the ABB home page http://www.abb.com/contacts -> Low Voltage Products and Systems Document number 2CDC 112 197 D0201 (11.2012) Note: We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB AG does not accept any responsibility whatsoever for potential errors or possible lack of information in this document. We reserve all rights in this document and in the subject matter and illustrations contained therein. Any reproduction, disclosure to third parties or utilization of its contents in whole or in parts is forbidden without prior written consent of ABB AG. Copyright 2012 ABB All rights reserved