Wireless Temp/Setpoint & Override Room Transmitter

Similar documents
Wireless Room Temperature and Humidity Transmitter (Units without Temperature Setpoint or Override) Installation and Operating Instructions

Wireless Analog Output Modules

Wireless 900 MHz Receiver

Wireless HVAC Sensors

BAPI-Stat 4 X-Combo, Room %RH and Temp. Sensor BA/BS4XC Installation & Operating Instructions

IMPORTANT: READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

IMPORTANT: THIS DEVICE MUST BE PROFESSIONALLY INSTALLED. READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION.

IMPORTANT: THIS DEVICE MUST BE PROFESSIONALLY INSTALLED READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE BEGINNING INSTALLATION

TOP VIEW. 6.75" (171.5mm) Network ID Selector. Input Voltage Selection Jumper 7.285" (185mm) Battery Positive Terminal SIDE VIEW. 6.12" (155.

instruction manual for Open LRS New Generation

HLC-1000 High-limit Humidity Control

Operating Instructions

E-BUS Digital Room Sensor Technical Guide

200 RTH OFF ON IN OUT ALARM RESET

DDC Series Dial Digital Controller INSTALLATION AND OPERATING INSTRUCTIONS

Digital Room Sensor Technical Guide

Delta Style Room Humidity Units

Blue Point Engineering Inc.

ELECTRONIC THERMOSTAT: T920

RF3405E. Installation Instructions Wireless (RF) Inertia Transmitter

Lifetime Power Energy Harvesting Development Kit for Wireless Sensors User s Manual - featuring PIC MCU with extreme Low Power (XLP) Technology

WPR400 Wireless Portable Reader

DR-TRC105-EV Evaluation Kit. User s Guide

Table of Contents. Wall Mount Installation Page 2 Double Mount Installation Page 3. Wiring Information... Page 4. Operational Instructions Pages 5-8

LAZERPOINT RF WIRELESS DOOR ACTIVATION SYSTEM

Home Automation, Inc. Model 12A00. Wireless Receiver. Installation Manual

LAZERPOINT RF WIRELESS DOOR ACTIVATION SYSTEM

BeeLine TX User s Guide V1.1c 4/25/2005

BRB900 GPS Telemetry System August 2013 Version 0.06

Wireless Copilot. Safe2Fly - Height Only Version. Page NanoQuip Ltd

Lazerpoint TM RF RX-91 Basic Receiver Installation Instructions

TRC EV DR TRC EV DR TRC EV

Wireless Room Thermostat Installation and Operation Y6630D1007

SmartZone-2 & SmartZone-4

Radio Link Starter Kit

Astra-R Kit Wireless Alarm System Operation Manual

Activity 3: Wireless Communication Student Handout. Parts Descriptions. Wireless Communications: Wireless Burglar Alarm

Allure ECW-Sensor Series

OPERATING INSTRUCTIONS ARE ON PAGE 5. SECTION 2 Technical Data Transmitter Unit. RVHT 2 MULTI-FIT Programmable R/F Thermostat-Pair SECTION 1

SE3401. Installation Instructions Wireless (RF) Point Tracking Transmitter

Installation Notes. SCR Single Channel

CD-Pxx-00-0 Series Duct Mount CO 2 Transmitter

WEL-200 O P E R A T I N G I N S T R U C T I O N S W I R E L E S S E D G E L I N K

STI REPEATER HOW THE PRODUCT WORKS BEFORE YOU START. Installation and Operation Manual. Model: STI-34109

AIRCRAFTSCALES.COM WIRELESS WEIGHING INSTRUCTIONS.

Micro-Trak All-In-One APRS Transmitter

Point Six Wireless Unique, High Value Wireless Solutions. 418 MHz Transmitter

Wireless Rain and Wireless Rain/Freeze Sensor

Wireless sensor system

WVP. Wireless Valve Programmer. Programmer for use with WVC Multi-Station Battery Powered Irrigation Controllers

STI REPEATER. BEFORE YOU START Refer to this drawing to become familiar with all the parts. Installation and Operation Manual.

IRRIGATION 810-3R RECEIVER GUIDE

P700WLS IoProx Receiver

DESCRIPTION DIMENSIONS HOW TO ORDER

Radio Link Starter Kit

Wireless Pressure Station with Backlight

9RCT4334 Four Button. 2 3/4 X 1 3/8 X 9/16 (70mm x 35mm x 14mm) 2 3/4 x 2 1/8 x 1 (70mm x 55mm x 25mm)

OVEN INDUSTRIES, INC. Model 5C7-362

SER8300 Series Terminal Equipment Controller with Optional PIR sensor Installation Guide

H LONTalk Integration Node For Use With H704 and H663 Branch Current Monitors (BCM) H NOTICE DANGER INSTALLATION GUIDE DIMENSIONS

TE-7700 Series Radio Frequency (RF) Wireless Room Temperature Sensing System

Zlinx Wireless I/O. Peer-to-Peer and Modbus I/O PRODUCT INFORMATION B&B ELECTRONICS

VIPER Remote Control Systems

2025 RTH 2025 P 2025 OFF ON IN OUT ALARM RESET

WIRELESS 868 MHz TEMPERATURE STATION Instruction Manual

AKR-1. Digital Keyless Entry System With Built-in Wireless Receiver. Installation and Programming Instructions

+GF+ SIGNET Temperature Transmitter Instructions

The RSW11 replaces the original RadioSwitch, Model RSW1.

Installation & Operation Manual SAGA1-K Series Industrial Radio Remote Control

Proximity Probe Checker PC-100

THE PROBE, 5 METER, 2WIRE, LOOP POWERED SINGLE POINT LEVEL MEASUREMENT SYSTEM (ULTRASONIC)

TRACEABLE RADIO-SIGNAL REMOTE THERMOMETER INSTRUCTIONS

TABLE OF CONTENT A. Installation and Mounting Installation 3 2. Mounting Receiver Addressing... 5 B. Key Interface. 7 C.

HDC Controller. Operating Manual. Rain Pro. Intelligent Irrigation Solutions. 4 or 6 Station

Wireless Occupancy Sensor User Guide

CONTENTS OF THE BOX. *PIR sensor only **Dual Technology and PIR sensors only. Description PIR Ultrasonic Dual Technology

Viconics VT76x7 Series Rooftop Unit Controllers Engineering Guide Specification

Table 1. Placing the Sensor in the Sensor Cradle. Step Instruction Illustration

MFJ-219/219N 440 MHz UHF SWR Analyzer TABLE OF CONTENTS

Hub and Cluster. ogramming Manual. Pro MAN3090

Jaguar Motor Controller (Stellaris Brushed DC Motor Control Module with CAN)

WS-7220U-IT 915 MHz Wireless Weather Station. Instruction Manual

CX105 Conductivity/Resistivity Transmitter

Wireless Pressure Station

April 1994 UCM-420A. Setpoint Controller. Operating and Installation Instructions

FC Series Signal Conditioners

Microprocessor Control Board Set Up Procedures (OR PLC)

CD42-STS Operating Manual Diver/ROV Pipeline Pig Location & Tracking System

VZ-WFF. (Wireless Follow Focus) Instruction Manual

KOBOLD EchoKing NEO-5003 Series Ultrasonic Level Transmitter User Instructions KOB

Table of Contents. Introduction...3 Specifications...6 Installation Instructions...6

S ENSORLINK INSTALLATION MANUAL

BFS / BFSM SERIES Installation & Maintenance Manual

in Control When It Counts LED Indicators Mounting Bracket Meter Seal Mounting Brackets ½ seal tight or ¾ NPT

User Manual. ProRF Encoder Transmitter & Receiver

Wireless Essential Weather Station

MESA-HPX. Assembly and Installation Manual. w/appendix A for Prodelin Antenna. 901-Manual-MESA-HPX

Brushed DC Motor Control. Module with CAN (MDL-BDC24)

Preliminary. 4-Channel RTD/4-20 ma Wireless Sensor Node SN24R420-4

Wireless Ceiling Motion Sensor for Occupancy / Vacancy Detection with integrated diagnostic tools INSTALLATION GUIDE

Transcription:

Overview The BAPI Wireless Combination Transmitter measures the room temperature and relative humidity and transmits the data at 418MHz or 433MHz RF to a receiver. Temperature setpoint and override button status is also transmitted. The transmitter is mounted in a BAPI-Stat 2 style enclosure and has an open-air range of 100 feet. The transmit rate is approximately once every 10 seconds with an estimated battery life of 5 to 8 years using two highcapacity 3.6V lithium batteries. Each transmitter has a unique address with built in error detection. Each variable sent by the transmitter is picked up by the receiver and converted by a separate BAPI Analog Output Module to a voltage, current or resistance signal which is sent to the controller. Note: The installation process requires that each transmitter and its associated output module or modules be trained in a binding process. This teaches each output module to receive communications from the correct transmitter. The binding process is easiest to do on a test bench so that the transmitter and receiver/output module are within arm s reach of each other. Pushing buttons in a defined sequence on the transmitter and associated output module will bind the two units together in non-volatile memory. Binding the units together is easiest when the units are within arm s reach of each other but can be done in the field. Field binding will require two people and a set of walkie talkies or cell phones. (See output module training later in this document for details) Be sure to place a unique identification mark on the transmitter and associated output modules after they have been trained so that they can be matched together at the job site. If more than one variable is transmitted, each variable requires a separate output module. Perform the training sequence for each output module. Any transmitted variable can be trained to more than one output module. There are two sections that describe how to train the override function; 1. Override in parallel with setpoint or in parallel with space temperature; 2. Override as a separate output. Please remember that the override is trained by pressing the override button, not the transmitter training button Fig. 1: Wireless System Diagrams Product Identification Battery polarity important or damage to the unit may occur Transmitter Training Button Override Button Setpoint Transmit LED Fig. 2 Wireless Temperature, Humidity, Setpoint & Override Room Transmitter 1

Mounting (a) The wireless installation process is most effectively accomplished by training the room transmitters first with the output modules before they are mounted in their final location. After each module is trained, the batteries can be removed for mounting. The training is permanently retained by the modules in non-volatile memory. Note: The transmitter should have been trained to the output module at this point of the installation. Provided Drywall Anchors Provided #6 x 1" Screws 3.25" (80mm) Fig. 3: Drywall Mounting Drywall Mounting 1. Place the base plate against the wall where you want to mount the sensor. Typically 5 feet above the floor. 2. Using a pencil, mark out the two mounting holes. 3. Drill two 3/16" (4.7 mm) holes in the center of each marked mounting hole. Insert a drywall anchor into each hole. 4. Secure the base to the drywall anchors using the #6 x 1 inch mounting screws provided. 5. Install provided batteries and follow polarity as shown above in figure 2 or damage may occur. The unit will work on just one battery however the battery life will be cut in half. 6. Attach cover by latching it to the top of the base, rotating the cover down and snapping it into place. 7. Secure the cover by backing out the lock-down screws using a 1/16" Allen wrench until they are flush with the bottom of the cover. Output Module Training Temperature - Analog Output Module Training Output Module Service Button Fig. 4: Output Module 1. To bind an output module to a Temperature variable, select an output module, BA/(VOM, ROM,COM), calibrated to the temperature range you need and connect it to the receiver. 2. Apply power to the receiver and output modules. The power LED on the Receiver should light and remain lit. Reminder: Loop power must be connected and turned on for current output modules, BA/COM., 4. Press and hold down the Service Button on the output module (Figure 4). hen, press and release the training button (Figure 2) on the transmitter. When the output module has received a valid data packet from the transmitter the output module s red LED will light and remain lit as long as you hold down the output module s service button. Release the service button on the output module and the output module s LED will go out. During normal operation the output module s LED will flash indicating data 5. Mount the transmitter at the desired location. See Mounting above. Continued on next page 2

Output Module Training Continued Humidity - Analog Output Module Training To bind an output module to a Humidity variable, select an output module, BA/(VOM, COM)-M calibrated to the humidity range you need and connect it to the receiver. 1. Apply power to the receiver and output modules. The power LED on the Receiver should light and remain lit. Reminder: Loop power must be connected and turned on for current output modules, BA/COM. 2. Remove the cover of the transmitter and install the batteries, observe polarity or 3. Press and hold down the Service Button on the output module (Figure 4). Then, press and release the training button (Figure 2) on the transmitter. When the output module has received a valid data packet from the transmitter the output module s red LED will light and remain lit as long as you hold down the output module s service button. Release the service button on the output module and the output module s LED will go out. During normal operation the output module s LED will flash indicating data 4. Mount the transmitter at the desired location. See Mounting above. 5. Replace the transmitter's cover and back out the security screws. Setpoint - Analog Output Module Training 1. To bind an output module to a Setpoint variable, select an output module, BA/SOM, calibrated to the setpoint range you need and connect it to the receiver. 2. Apply power to the receiver and output modules. The power LED on the Receiver should light and remain lit. Reminder: Loop power must be connected and turned on for current output modules BA/SOM-16. 4. Press and hold down the Service Button on the output module (Figure 4). Then, press and release the OVERRIDE button (Figure 2) on the transmitter. (NOTE: If unit was not ordered with an override button, the button is inside the case). When the output module has received a valid data packet from the transmitter, the output module s red LED will light and remain lit as long as you hold down the output module s service button. Release the service button on the output module and the output module s LED will go out. During normal operation the output module s LED will flash indicating data 5. Mount the transmitter at the desired location. See Mounting above. Continued on next page 3

Output Module Training Continued Override in Parallel with Setpoint or Temperature Analog Output Module Override Training Squeeze Figure 5: Remove Cover Service Button Squeeze J4 Figure 6: Service Button & Jumper Positions 1. An Override variable can only be bound in parallel with a previously trained Setpoint or Temperature output module. Train the Setpoint or Temperature output module as described above. Remove the Output Module s cover by squeezing the top and bottom of the cover as shown in Figure 5. Apply power to the receiver and output modules BA/(VOM,ROM,COM). Note: Loop power must be connected and turned on for current output modules, BA/COM. 2. The power LED on the Receiver should light and remain lit. 4. Place the previously trained Temperature or Setpoint output module s jumper J4 in the Override Training Position. (See Figures 6 and 7) Press and hold down the Service Button on the output module (Figure 4). Then, press and release the OVERRIDE button (Figure 2) on the transmitter. When the output module has received a valid data packet from the transmitter, the output module s red LED will light and remain lit as long as you hold down the output module s service button. Release the service button on the output module and the output module s LED will go out. During normal operation the output module s LED will flash indicating data reception approximately once every 10 to 20 seconds in time with the transmitter trained to it. The output module is now receiving data from the transmitter. Remove the jumper on J4 and store it on the right Storage Position Pin. (Figure 7) Replace the Output Module s cover. 5. If you wish to un-attach the override function on an output module you re-teach the output module to the first variable, Temperature or Setpoint. This erases the override function on the output module. 6. Mount the transmitter at the desired location. See Mounting above. Fig. 7: J4 Jumper Positions J4 Training Position Override as Separate Output Relay Output Module Override Training 1. To bind an output module to an Override variable, connect a BA/RYOM output module the receiver. 2. Apply power to the receiver and output modules. The power LED on the Receiver should light and remain lit. 4. Press and hold down the Service Button on the output module (Figure 4). Then, press and release the OVERRIDE button (Figure 2) on the transmitter. When the output module has received a valid data packet from the transmitter, the output module s red LED will light and remain lit as long as you hold down the output module s service button. Release the service button on the output module and the output module s LED will go out. During normal operation the output module s LED will flash indicating data 5. Mount the transmitter at the desired location. See Mounting above. J4 Storage Position 4

Table 1 Under Cover J4 Position to Train Output Modules Room Transmitter Output Module J4 Position Output Module Field Transmitter Variable Training J4, ON or OFF, (Fig. 6 & 7) Training Button Training Button Room Temperature OFF (standard VOM,COM,Rom Modules Service Button + SW 1 Training Button Room Humidity ON (standard for all -M or -N modules) Service Button + SW1 Training Button Setpoint Temperature OFF (standard for SOM analog modules) Service Button + SW2 Override Button Override Button ON (standard for RYOM, DO modules) Service Button + SW2 Override Button Output Module Analog Output Module J4 Position Analog Output Module Field Transmitter Override Training J4, ON, (Fig. 6 & 7) Training Button Training Button Override Training** ON* (Change as needed, see above) Service Button + SW2 Override Button * After override training, put J4 back to the OFF position on standard analog output modules VOM, COM, ROM, & SOM types. Leave J4 in the ON position for -M or -N analog output modules (RH%) and on RYOM digital output (DO) modules. **Note:Standard variable signal training must be completed first before override training is attempted. If the standard signal is re-taught to the same output module again, the training is erased. Operation Sequence The variable outputs are trained to the output modules as selected and represent the measured signal value (Temp, RH, & Setpoint) from the transmitter. After override training, the output modules selected receive the override button operation wirelessly and change its measured signal output to a low signal value (see specs) for 5 seconds then resumes back to the measured signal value. Operating Notes 1. If you need to bind any temperature, humidity, setpoint or override value from a single transmitter to more than one controller, you may train multiple output modules to that value. 2. If an output module does not receive data from its assigned transmitter for 15 minutes the red LED on the output module will blink rapidly. The module output signals will react as follows; Voltage output modules calibrated for temperature will set their output to zero volts. Current output modules calibrated for temperature will set their outputs to 4 milli-amps Resistance output modules calibrated for temperature will set their outputs to their highest resistance, lowest temperature, values. Voltage output modules calibrated for humidity will set their outputs to the maximum of 5 VDC or 10 VDC. Current output modules calibrated for humidity will set their outputs to the maximum of 20 milli-amps. Setpoint output modules will hold their last values indefinitely. Relay output modules will go to their normal output, open or closed depending on module selected. When transmitted data is restored the output modules will revert to normal operation in 30 seconds or less. 3. Output modules are trained to a transmitter simulator during BAPI s final test. When you receive them they will not be trained to any of the transmitters in your shipment. Do not be alarmed if the output module s LED blinks rapidly upon power up or shortly thereafter, just train the output module to a transmitter and all will be OK. 4. The BA/RCV receivers and BA/xOM output modules are inter-connected and require module power along the power bus on the two bottom terminals. The bus can be powered from either the receiver end (left side) or the last output module (right side). Be sure you have enough DC current or AC VA for all the devices on the bus. 5. The BA/COM-a or BA/SOM-16 (Current Analog Output Module) signal is LOOP POWERED and must be externally powered (9-36 VDC) so that the BAS input receives the analog current signal. Other Analog Output Modules source the analog output from the power bus. 6. The printed lines on the BA/RCV receivers represent the power buss flow and are just there for appearance. They do not represent an electrical wire connection. Always be sure to follow the polarity (+ or -) listed on each module to maintain communication and power buss integrity. 5

Diagnostics Temperature or Humidity is reading its low limit or not reading at all. - Check wire from output modules to controller for proper connections and polarities. - Check to see if the controller's software is configured properly. - Check transmitter to see if its LED flashes about every 10 seconds. If not replace the batteries. - Check power to the receiver and output module. - Check output modules LED, if it is blinking fast Check the associated transmitter and receiver for proper operation Retrain the output module If there are repeaters in the data stream, check for proper operation - Move the transmitter next to the receiver (~ one meter away) Temperature or Humidity reading is coming out the wrong output module - Retrain the modules. Temperature or Humidity is reading incorrectly - Check wire from output modules to controller for proper connections and polarities. - Check to see if the controller's software is configured properly. - Check to see if the correct output module is connected to the correct controller. Specifications Supply Power: Two AA 3.6V Lithium batteries, 2.25 AH 5 to 8 year battery life at 10 second transmit rate Potential Inputs: Temperature - Thermistor Relative Humidity Capacitive Setpoint Potentiometer Override SPST switch Accuracy: ±0.54 F (±0.3 C) / ±2% RH Transmitted Range: -40 to 185 F (-40 to 85 C ) 0-100% RH Output Module override value for 5 seconds: BA/VOM 0v BA/COM 4 ma BA/SOM 0v or 4mA (Module Dependent) BA/ROM Less than 100Ω BA/RYOM Energized Antenna: Built inside the enclosure Environmental Operation Range: Temp: 32 to 140 F (0 to 60 C) Humidity: 5% to 95% RH non-condensing Material: ABS Plastic Material Rating: UL94 V-0 Radio Frequency: 418 MHz North America 433 MHz International Transmitter Interval: ~10 seconds FCC Approval: FCC ID# T4F061213RSO (418MHz only) 6