Wireless Automated Transmission System For Guarding or Health Monitoring Of High Voltage Transformer

Similar documents
Implementation of Multiquadrant D.C. Drive Using Microcontroller

Keyword: - GSM kit, Transformer, sensors, rectifier, microcontroller, power supply, LCD.. Vol-3 Issue INTRODUCTION

Monitoring the Transformer Oil Temperature and Load Sharing Using Gsm

International Journal of Advance Engineering and Research Development

DISTRIBUTION TRANSFORMER MONITORING AND CONTROL SYSTEM FOR REMOTE ELECTRIC POWER GRIDS THROUGH GSM

Transformer Health Condition Monitoring Through GSM Technology

Design and Implementation of AT Mega 328 microcontroller based firing control for a tri-phase thyristor control rectifier

Automatic Gas Cooking Control System based on Microcontroller

Monitoring and Protection of Distribution Transformer Using GSM Module Jenifer A 1, Bharathi B R 2, Shanthi Mounika B 3

Development of Tsunami early warning embedded system with GSM alert

Prashant Sangulagi Assistant Professor, E&CE Dept. BKIT Bhalki, INDIA

International Journal of Advanced Research in Electrical, Electronics and Instrumentation Engineering. (An ISO 3297: 2007 Certified Organization)

Four Quadrant Speed Control of DC Motor with the Help of AT89S52 Microcontroller

International Journal of Advance Engineering and Research Development. Transformer Health Monitoring And Control Through Arduino

Wireless ID Verification and Updation Using RF-ID Tag in Vehicle

MONITORING OF DISTRIBUTION TRANSFORMER PARAMETERS USING PLC

GSM BASED AGRICULTURE MONITORING SYSTEM

Designing with STM32F3x

THE PERFORMANCE TEST OF THE AD CONVERTERS EMBEDDED ON SOME MICROCONTROLLERS

Automatic Load Sharing of Transformers using Microcontroller

I. INTRODUCTION II. LITERATURE REVIEW

REACTIVE POWER COMPENSATION IN DISTRIBUTION SYSTEM

The Development and Application of High Compression Ratio Methanol Engine ECU

Hello, and welcome to this presentation of the STM32 Digital Filter for Sigma-Delta modulators interface. The features of this interface, which

INTELLIGENCE HOME AUTOMATION SYSTEM USING LDR

Unit level 5 Credit value 15. Introduction. Learning Outcomes

DESIGN AND DEVELOPMENT OF A LOW-COST MICROCONTROLLER BASED SINGLE PHASE WATER-PUMP CONTROLLER

Autonomous Intelligent Robot for Emergency Services

CHAPTER 2 VSI FED INDUCTION MOTOR DRIVE

GSM BASED TRANSFORMER HEALTH MONITORING SYSTEM

Electric Bike BLDC Hub Motor Control Using the Z8FMC1600 MCU

IN ELECTRICAL ENGINEERING - I C M E T CRAIOVA

Hello, and welcome to this presentation of the STM32G0 digital-to-analog converter. This block is used to convert digital signals to analog voltages

Electrical Engineering Department Priyadarshani College of Engineering. Electrical Engineering Department Priyadarshani College of Engineering.

Monitoring and Controlling of Distribution Transformer Using GSM Module (AVR Microcontroller Based)

8-bit Microcontroller with 512/1024 Bytes In-System Programmable Flash. ATtiny4/5/9/10

DESIGN ANALYSIS AND REALIZATION OF MICROCONTROLLER BASED OVER CURRENT RELAY WITH IDMT CHARACTERISTICS: A PROTEUS SIMULATION

TMS320F241 DSP Boards for Power-electronics Applications

Multi Frequency RFID Read Writer System

Automatic Power Factor Correction by Using Synchronous Condenser with Continuous Monitoring.

Protecting power transformers from common adverse conditions

Imaging serial interface ROM

Power Line Communication Based Fault Monitoring And Control

Emergency Assisting Autonomous Robot Using GPS

8-bit Microcontroller with 2K Bytes In-System Programmable Flash. ATtiny20

Improve asset protection and utilization

Two hydrogen atoms meet. One says "I've lost my electron. The other says "Are you sure?" The first replies "Yes, I'm positive."

ADVANCED TRAFFIC CLEARANCE SYSTEM FOR AMBULANCE CLEARANCE USING RF-434 MODULE

3.3V regulator. JA H-bridge. Doc: page 1 of 7

Management of Home Appliances with Variation in Environment Aisha Jilani, Sahar Sultan, Intesar Ahmed and Sajjad Rabbani

Design of a Frequency Counter Based on Input Capture Function of a. Single Chip Computer. Wang Yanshuang; Liu Yuelong

32-bit ARM Cortex-M0, Cortex-M3 and Cortex-M4F microcontrollers

International Journal of Advance Engineering and Research Development PROTECTION OF TRANSFORMERS USING SENSORS

Design and Implementation of High Precision Automated Online Monitoring of Distribution Transformer (OMDT) Device

SIMULATION OF TRANSFORMER PROTECTION USING MICROCONTROLLER BASED RELAY & MONITORING USING GSM

Cortex-M3 based Prepaid System with Electricity Theft Control

Induction Motor Protection using Micro Controller

International Journal of Advance Engineering and Research Development AUTOMATIC METER READING FOR ELECTRIC BOARD USING RF (RADIO FREQUENCY)

Transformer Protection by Using Arduino with GSM Modem

Hardware Platforms and Sensors

8-bit Microcontroller with 4K Bytes In-System Programmable Flash and Boost Converter. ATtiny43U. Preliminary

Real Time Transformer Health Monitoring System using IOT

New Laboratory Stand and Teaching Program Transformer Monitoring System

Preliminary GHz Transceiver-µController-Module. Applications PRODUCT SPECIFICATION FEATURES MICROCONTROLLER MHz

High performance, low power AVR 8-bit microcontroller Advanced RISC architecture. Non-volatile program and data memories. Peripheral features

8-bit Microcontroller with 2/4/8K Bytes In-System Programmable Flash. ATtiny24/44/84. Preliminary

GSM BASED ENERGY THEFT MONITORING SYSTEM

Intelligent and passive RFID tag for Identification and Sensing

Smart Monitoring and Power Factor Correction of Distribution Transformer using IOT

Data Logger Subsystems Mark Buccini February 2012


CHAPTER 4 HARDWARE DEVELOPMENT OF STATCOM

8-bit Atmel tinyavr Microcontroller with 16K Bytes In-System Programmable Flash. ATtiny1634

HOME AUTOMATION WITH SPY ROBOT AND SECURITY SYSTEM

8-bit Microcontroller with 2/4/8K Bytes In-System Programmable Flash. Atmel ATtiny24/44/84. Automotive. Preliminary

DISTRIBUTION LINE FAULT DETECTION AND INTIMATION USING GSM

Simulation & Realization of Feeder Protection with Micro Controller

8-bit Microcontroller with 32K Bytes In-System Programmable Flash. ATmega32 ATmega32L

DSP BASED SYSTEM FOR SYNCHRONOUS GENERATOR EXCITATION CONTROLL

Embedded Robotics. Software Development & Education Center

8-bit Microcontroller with 16K Bytes In-System Programmable Flash. ATtiny1634

Programming and Interfacing

APPLICATION NOTE. AT11009: Migration from ATxmega64D3/128D3/192D3/256D3 Revision E to Revision I. Introduction. Features.

Index Terms IR communication; MSP430; TFDU4101; Pre setter

8-bit Microcontroller with 2/4/8K Bytes In-System Programmable Flash. ATtiny24/44/84. Preliminary

8-bit Microcontroller with 2/4/8K Bytes In-System Programmable Flash. ATtiny24/44/84. Preliminary

Ultra-Slim PLC (FP Sigma)

Power Factor Correction in Digital World. Abstract. 1 Introduction. 3 Advantages of Digital PFC over traditional Analog PFC.

International Journal Of Core Engineering & Management Volume-4, Issue-11, February-2018, ISSN No:

HIGH POWER TRANSMITTER MONITORING & CONTROL USING GSM

Draw the symbol and state the applications of : 1) Push button switch 2) 3) Solenoid valve 4) Limit switch ( 1m each) Ans: 1) Push Button

ATtiny25/45/85 Automotive

2.0 Discussion: 2.1 Approach:

AMBULANCE TRACKING AND ALTERNATE ROUTING

GDM1101: CMOS Single-Chip Bluetooth Integrated Radio/Baseband IC

- Continuous real-time measurement and PD trend analysis; not multiplexed data collection.

Design of a Microcontroller-Based Push-Pull Inverter with Automatic Voltage Regulator

Intelligent Traffic Light Controller

8-bit with 8K Bytes In-System Programmable Flash. ATmega8* ATmega8L*

SPECIFICATION, CONTROLS AND ACCESSORIES

Transcription:

Wireless Automated Transmission System For Guarding or Health Monitoring Of High Voltage Transformer Mr. V. B. Patil 1,Patil Pooja 2, Patil Dhanashree 3, More Tejaswini 4, Ghewari Vinayak 5, Patil Shailesh 6, Surve Amol 7 1,2,3,4,5,6,7 (Assistant Professor Department of EE, Vathar, Kolhapur.) ABSTRACT High voltage power transformer is extensively operated in the generation of electrical energy in either voltage stepping up or stepping down condition. The additional attachments namely breather, cooling fan, bushing, differential relay, Buchholz relay are synchronized with the transformer operation. It is essential to estimate the troubles occurring in it and to expound them as soon as desirable, so the high cost transformer does not get destructed and also helps in maximum use of it. Here it targets how to decrease and determine them in effective way. In this paper a tryout has been made of detailed use of system and wireless automated transmission system for guarding and ideal use of High voltage transformer. This project is about design and implementation of Arduino to monitor and record key parameters of a distribution transformer like currents, oil level and ambient temperature. The idea of monitoring system integrates a Global Service Mobile (GSM) Modem, with a standalone Arduino and different sensors. It is installed at the distribution transformer site and the above parameters are recorded using the analog to digital converter (ADC) of the embedded system. The obtained parameters are processed and recorded in the system memory. This mobile system will help the transformers to operate smoothly and identify problems before any catastrophic failure. Keywords-ARDUINO ATmega328, sensors. I.INTRODUCTION In power systems, distribution transformer is electrical equipment which distributes power to the low voltage users directly, and its operation condition is an important component of the entire distribution network operation. Operation of distribution transformer under rated condition guarantees their long life.however their life is significantly reduced if they are subjected to overloading, resulting in unexpected failures and loss of supply to a large number of customers thus effecting system reliability. Overloading and ineffective cooling of transformers are the major causes of failure in distribution transformers. The monitoring devices or systems which are presently used for monitoring distribution transformers have some problems and deficiencies. Few of them are mentioned below: 379 P a g e

1) Ordinary transformer measurement system generally detects a single transformer parameter, such as power, current, voltage. While some ways could detect multi- parameter, the time of acquisition and operation parameters is too long, and testing speed is not fast enough. 2) Detection system itself is not reliable. The main performance is the device itself instability, poor anti jamming capability, low measurement accuracy of the data, or even state monitoring system should is no effect. Many monitoring systems use power carrier communication to send data, but the power carrier communication has some disadvantages: serious frequency interference, with the increase in distance the signal attenuation serious, load changes brought about large electrical noise. So if use power carrier communication to send data, the real-time data transmission, reliability cannot be guaranteed. According to the above requirements, we need a distribution transformer real-time monitoring system to detect all operating parameters operation, and send to the monitoring centre in time. It leads to online monitoring of key operational parameters of distribution transformers which can provide useful information about the health of transformers which will help the utilities to optimally use their transformers and keep the asset in operation for a longer period. This will help to identify problems before any serious failure which leads to a significant cost savings and greater reliability. Widespread use of mobile networks and GSM devices such GSM modems and their decreasing costs have made them an attractive option not only for voice media but also for other wide area network application. II.SYSTEM LAYOUT The proposed block diagram has shown in fig 1 shows the entire system layout. The main transformer is the high voltage transformer that has to be protected. There are four parameters present i.e. voltage, current, gas & temperature for the monitoring purpose in the system. The CT (current transformer) is used to calibrate the current value coming from the supply and send it to the Arduino. The PT (potential transformer) is used to calibrate the voltage value coming from the supply and send to the Arduino. During fault condition in voltage and current the signal from the PLC is sent to the relay and the main transformer is disconnected. Gas sensor is provided to detect the gas produced in the main transformer. Generation of gas inside the transformer is a big issue which is developed due to atomization of oil, corona, overheating, arcing in the transformer, etc; all this transformation of instruction will be constantly monitored by the gas sensor and signal sent to the PLC and exhaust fan will be switched on. The part of the scheme complication clears away the heat in larger transformers. If under any prospects temperature increases above the particular level which consequently will alert the transformer performance. The temperature sensor gives the data to the Arduino and the suitable operation is carried out according to the requirement such as cooling fan 380 P a g e

Figure 1: Block Diagram A. Transformer Fault Analysis A power transformer consists of a set of windings around a magnetic core. The windings are insulated from each other and the core. Operational stresses can cause failure of the transformer winding, insulation, and core. The power transformer windings and magnetic core are subject to a number of different forces during operation: 1. Expansion and contraction caused by thermal cycling 2. Vibration caused by flux in the core changing direction 3. Localized heating caused by eddy currents in parts of the winding, induced by magnetic flux 4. Impact forces caused by fault currents. 5. Thermal heating caused by overloading. These operating limits only considered the thermal effects of transformer overload. Later, the capability limit was changed to include the mechanical effect of higher fault currents through the transformer. Power transformer faults produce physical forces that cause insulation wear. These effects are cumulative and should be considered over the life of the transformer. The following discussion highlights on different capability limits of transformer. B. Over Load:- Over Load Over current is the current flowing through the transformer resulting from faults on the power system. Fault currents that do not include ground are generally in excess of four times full-load current; fault currents that include ground can be below the full-load current depending on the system grounding method. Overload, by contrast, is current drawn by load, a load current in excess of the transformer nameplate rating. In summary, loading large power transformers beyond nameplate ratings can result in reduced dielectric integrity, 381 P a g e

thermal runaway condition (extreme case) of the contacts of the tap changer, and reduced mechanical strength in insulation of conductors and the transformer structure. C. Temperature:- Excessive load current alone may not result in damage to the transformer if the absolute temperature of the windings and transformer oil remains within specified limits. Transformer ratings are based on a 24-hour average ambient temperature of 30 C (86 F). Due to over voltage and over current, temperature of oil increases which causes failure of insulation of transformer winding. D. Over/Under Voltage:- The flux in the transformer core is directly proportional to the applied voltage and inversely proportional to the frequency. Over voltage can occur when the per-unit ratio of voltage to frequency (Volts/Hz) exceeds 1.05 p.u at full load and 1.10 p.u. at no load. An increase in transformer terminal voltage or a decrease in frequency will result in an increase in the flux. Over excitation results in excess flux, which causes transformer heating and increases exciting current, noise, and vibration. E. Oil Level Fault:- Oil mainly used in transformer for two purposes one is for cooling of transformer and another use is for insulation purpose. When temperature of transformer goes high, oil level in transformer tank decreases due to heating effect. For normal operation of transformer oil level should maintain at required level. If oil level decreases beyond required level, it affect cooling and insulation of the transformer. F. The ARDUINO ATmega328 The Atmel AVR core combines a rich instruction set with 32 general purpose working registers. All the 32 registers are directly connected to the Arithmetic Logic Unit (ALU), allowing two independent registers to be accessed in a single instruction executed in one clock cycle. The resulting architecture is more code efficient while achieving throughputs up to ten times faster than conventional CISC(Complex Instruction set computing) microcontrollers. The ATmega328/P provides the following features: 32Kbytes of In-System Programmable Flash with Read-While-Write capabilities, 1Kbytes EEPROM (Electrically erasable programmable read-only memory), 2Kbytes SRAM (Static Random Access Memory), 23 general purpose I/O lines, 32 general purpose working registers, Real Time Counter (RTC), three flexible Timer/Counters with compare modes and PWM, 1 serial programmable USARTs(Universal Synchronous and Asynchronous Receiver-Transmitter), 1 byteoriented 2-wire Serial Interface (I2C), a 6- channel 10-bit ADC (8 channels in TQFP and QFN/MLF packages), a programmable Watchdog Timer with internal Oscillator, an SPI (Serial Peripheral Interface) serial port, and six software selectable power saving modes. The Idle mode stops the CPU while allowing the SRAM (Static Random Access Memory), Timer/Counters, (Serial Peripheral Interface) SPI port, and interrupt system to continue functioning. The Power-down mode saves the register contents but freezes the Oscillator, disabling all other chip functions until the next interrupt or hardware reset. In Power-save mode, the asynchronous timer 382 P a g e

continues to run, allowing the user to maintain a timer base while the rest of the device is sleeping. The ADC Noise Reduction mode stops the CPU and all I/O modules except asynchronous timer and ADC to minimize switching noise during ADC conversions. In Standby mode, the crystal/resonator oscillator is running while the rest of the device is sleeping. This allows very fast start-up combined with low power consumption. In Extended Standby mode, both the main oscillator and the asynchronous timer continue to run. Atmel offers the Q Touch library for embedding capacitive touch buttons, sliders and wheels functionality into AVR microcontrollers. The patented charge-transfer signal acquisition offers robust sensing and includes fully denounced reporting of touch keys and includes Adjacent Key Suppression (AKS ) technology for unambiguous detection of key events. The easy-to-use Q Touch Suite tool chain allows you to explore, develop and debug your own touch applications. The device is manufactured using Atmel s high density non-volatile memory technology. The On-chip ISP (Image Signal Processor) Flash allows the program memory to be reprogrammed In-System through an SPI serial interface, by a conventional nonvolatile memory programmer, or by an On-chip Boot program running on the AVR core. The Boot program can use any interface to download the application program in the Application Flash memory. Software in the Boot Flash section will continue to run while the Application Flash section is updated, providing true Read-While-Write operation. By combining an 8-bit RISC (Reduced Instruction Set Computer) CPU with In-System Self-Programmable Flash on a monolithic chip, the Atmel ATmega328/P is a powerful microcontroller that provides a highly flexible and cost effective solution to many embedded control applications. The ATmega328/P is supported with a full suite of program and system development tools including: Compilers, Macro Assemblers, and Program Debugger/Simulators, In-Circuit Emulators, and Evaluation kits. Figure 2: Pin diagram 383 P a g e

a) Current and Voltage Transformer: Current Transformer or potential transformers are necessary for isolating the protection & control. The behavior of current and voltage transformer during and after the occurrence of fault is critical in electrical protection since error in signal b) Temperature Sensors LM35: LM35 can measure temperature more accurately than a using a thermistor. The sensor circuitry is impenetrable and not subject to rust, etc. The LM35 generates output voltage from transformer can cause mal operation of the relays. a) Gas Sensor Gas sensor is useful for gas leakage detection. It is suitable for detecting H 2, LPG, CH 4 CO, Smoke or Propane. Due to its high sensitivity and fast response time measurement can be taken as soon as possible. The sensitivity of the sensor can be adjusted by potentiometer. Figure 2: Gas Sensor I. SIMULATION Figure 5: Circuit diagram 384 P a g e

1. Voltage Output : Figure 6: Voltage Output In this parameter we set threshold value of voltage is 500V and we set difference between high voltage and low voltage is 40V. If fault occurs or any problem occurs then set value changed which is monitoring the ARDUINO and notification given to the operator who is connected to GSM modem. 2. Temperature Output : Figure 7: Temperature Output In this parameter we set threshold value of temperature is 100.If fault occurs or any problem occurs then set value changed which is monitor the ARDUINO and notification given to the operator who is connected to GSM modem. 3. Current Output : Figure 8: Current Output In this parameter we set threshold value of current is 10A.If fault occurs or any problem occurs then set value changed which is monitor the ARDUINO and notification given to the operator who is connected to GSM modem. 385 P a g e

III.CONCLUSION Transformers are among the most generic and expensive piece of equipment of the transmission and distribution system. Regular monitoring health condition of transformer not only is economical also adds to increased reliability. With the advancement of communication technology now it is possible to receive fault information of transformer through GSM technology. During abnormal conditions exceeding specified limits information is immediately communicated through GSM technology to the operator and also to concerned authority for possible remedial action also increases mean down time of transformer there by increased reliability and decreased cost of power system operations. REFERENCE [1] Mudhafar A. AI-Nema, Sinan M. Bashi, And Abdulhadi A. Ubaid," Microprocessor-Based Over current Relays", IEEE Transactions On Industrial Electronics, Vol. Ie-33, No. 1, February 1986 [2] S. Dharanya, M. Priyanka, R.Rubini and A.Umamakeswari "Real time Monitoring and Controlling of Transformers"Journal of Artificial Intelligence, ISSN 1994-5450,2012. [3] Yusuf Amrulloh, UdanthaAbeyratne, ChandimaEkanayake, "Gas and Optical Sensing Technology for the Field Assessment of Transformer Oil" International Journal of Emerging Electric Power Systems Volume II, Issue 4 2010 [4] D. L. Ayers, D. White, T. Wright" Development of a Low Noise FOA Transformer Cooler Part I: Fan and Heat Exchanger Design" R. C. Settembrini, Member, IEEE [5] Cao, J., S. Qian, H. Hu and S. Yang, 2008. Wireless monitoring and analyzing system of dissolved gases in the transformer oil. Proceedings of the 7th World Congress on Intelligent Control and Automation, June 25-27, 2008, China, pp: 5152-5157. [6] Girish R. Kamath" An Electrical Circuit based 3-D Steady State Thermal model of a Fan Cooled 60 Hz, 20 kw 3-Phase Plasma Cutting Power Supply Transformer" 01972618/07/$25.00 2007 IEEE 386 P a g e