B. Samples: For color, letter style, and graphic representation required for each identification material and device.

Similar documents
SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 11/06/2017

UNIVERSITY SERVICES ANNEX James Madison University Harrisonburg, Virginia State Project Code: Architect s Project Number:

SECTION MECHANICAL IDENTIFICATION

SECTION IDENTIFICATION FOR FIRE SUPPRESSION PIPING AND EQUIPMENT

SECTION MECHANICAL IDENTIFICATION

PROJECT TITLE PROJECT NO: CONTRACT TITLE GRANT NO: UNIVERSITY OF CALIFORNIA, DAVIS CITY, CALIFORNIA

SECTION IDENTIFICATION FOR PLUMBING PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

CSP PSYCHIATRIC SERVICES UNIT SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

SECTION IDENTIFICATION FOR HVAC PIPING, DUCTWORK AND EQUIPMENT

Piping & Equipment Identification

Industrial Pipe Marking

SECTION IDENTIFICATION OF PLUMBING, PIPING AND EQUIPMENT. A. Section includes nameplates, tags, stencils and pipe markers.

SECTION MECHANICAL IDENTIFICATION

SECTION IDENTIFICATION OF HVAC PIPING AND EQUIPMENT. A. Section includes nameplates, tags, stencils and pipe markers.

A. Product Data: For each electrical identification product indicated.

1. ASME A Scheme for the Identification of Piping Systems.

SECTION IDENTIFICATION FOR HVAC PIPING AND EQUIPMENT

SECTION COMMON WORK RESULTS FOR HVAC

SECTION ELECTRICAL IDENTIFICATION

Excavating, Backfilling, and Compaction for Utilities Piping (Plumbing).

SECTION MECHANICAL IDENTIFICATION. 1. Identification of mechanical products installed under Division 15.

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY. Section ELECTRICAL IDENTIFICATION

SECTION MECHANICAL IDENTIFICATION

PART 0 DESIGN STANDARDS 0.01 GENERAL DESIGN GUIDELINES

SECTION SIGNAGE

SECTION IDENTIFICATION DEVICES

The School District of Palm Beach County Project Name SDPBC Project No. SECTION ( ) SIGNAGE PART 1 GENERAL 1.1 RELATED DOCUMENTS

UNIFIED FACILITIES GUIDE SPECIFICATIONS

PRESTON HEALTH SERVICES ARCHITECT S NO. 2700

University of Houston Master Construction Specifications Insert Project Name SECTION MECHANICAL SCOPE OF WORK PART 1 - GENERAL

SECTION IDENTIFYING DEVICES

A. Radius elbows with a construction radius of 1.5 the duct width are preferred to square elbows.

IDENTIFICATION DEPOT, INC. 206 East Second Street Washington, NC PHONE FAX

SECTION MECHANICAL IDENTIFICATION. 1. Identification of mechanical products installed under Division 15.

Union County Vocational - Technical Schools Scotch Plains, New Jersey

C. Samples for Initial Selection: Manufacturer's color charts showing the full range of colors available.

*********************************************************************************************************

Page PRODUCT DESCRIPTION

SECTION PANELBOARDS

Facility Services Subgroup Preface for Divisions 21` through 28

GRICE-TRIVERS JOINT VENTURE ARCHITECTS PAGE 1 PROJECT NO

SECTION ELECTRICAL IDENTIFICATION

A. Section includes surface preparation and the application of paint systems on exterior substrates.

Design and Construction Standards SECTION ATHLETIC LOCKERS

UNSIGNED HARDCOPY NOT CONTROLLED. Reference Designation Marking and Miscellaneous Coding

SECTION IDENTIFICATION FOR ELECTRONIC SAFETY AND SECURITY

1. State that all workmanship must conform to all pertinent laws, ordinances and regulations of all bodies having jurisdiction.

LOW PRESSURE STEEL DUCTWORK Mechanical Systems Insulation Outlets (HVAC) Testing and Balancing.

SECTION CABLE TRAYS

This specification describes the minimum requirements for piping systems for the following service:

SECTION PROJECT COORDINATION VIA BIM

A. Section includes surface preparation and the application of paint systems on the following exterior substrates: 1. Steel and iron.

SECTION SHEET METAL FLASHING AND TRIM

REVISION #1. Section. fire alarm B. C. the hot. intent of. required. manufacturer. materials. C. Warranty

Music Area Casework General 1.01 Summary Related Sections Definitions Qualifications and Quality Assurance

SECTION IDENTIFYING DEVICES

PRESTON HEALTH SERVICES ARCHITECT'S NO MITCHELL-HOLLINGSWORTH NURSING & REHAB

DOCUMENT ADDENDUM NO. 4. Issued to all Bidders: Date: October 14, Contract Name: Electrical Installation. Contract Number: C8410

PALM SQUARE SHOPPING CENTER TENANT SIGN CRITERIA

SECTION LOW PRESSURE DUCTWORK

A. Action Submittals: Written and graphic information that requires Architect's responsive action.

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

WESTERN UNDERGROUND COMMITTEE GUIDE 2.6 (2.6/00/0868)

SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL 1.1 RELATED DOCUMENTS

A. Submit properly identified manufacturer's literature before starting work.

SECTION INTERIOR SIGNAGE

FLUOROPOLYMER COATED DUCT FOR CAUSTIC ENVIRONMENTS

PLANNED SIGN PROGRAM CHECKLIST

SECTION BULLET- RESISTANT DOORS

EXTERIOR PAINTING

SECTION SHOP DRAWINGS, PRODUCT DATA, AND SAMPLES

SECTION SUBMITTAL PROCEDURES

Page PRODUCT DESCRIPTION

UNIVERSITY OF MISSOURI Liquid-Filled Utility Transformers 2016 Q1

UCCS University Hall Fire Sprinkler System Upgrade March 1, 2011 RTA SECTION SUBMITTAL PROCEDURES PART 1 - GENERAL

SECTION METAL FABRICATIONS

B. Samples: For each exposed product and for each color and texture specified.

1. This Section specifies the ethernet Category 5E data cabling system for buildings and structures.

Taylor County July 2011 SECTION SHOP DRAWINGS, WORKING DRAWINGS AND SAMPLES

A. Action Submittals: Written and graphic information that requires Engineer's responsive action.

NORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017

A. Section includes surface preparation and the application of paint systems on the following exterior substrates: 1. Steel.

SECTION CABLE TRAYS FOR ELECTRONIC SAFETY AND SECURITY

SECTION 025 INDUSTRIAL PAINTING

CONSULTANT PROCEDURES & DESIGN GUIDELINES Liquid-Filled Utility Transformers UNIVERSITY OF MISSOURI


1. Labels: Do not paint over UL, FMG, or other code-required labels or equipment name, identification, performance rating, or nomenclature plates.

SHEET METAL FLASHING AND TRIM Christ on the Mountain

Bol FEATURES: SPECIFICATIONS: 8' 24' Round Tapered and Straight Wood Poles STRUCTURA INC. FIXTURE TYPE: PROJECT NAME:

Page PRODUCT DESCRIPTION

Brown University Revised 2/1/2006 Facilities Design & Construction Requirements SECTION 16461C - DRY TYPE TRANSFORMERS

DIVISION 11 EQUIPMENT SECTION PHOTO DARKROOM FUME EXHAUST VENT-HOODS

SECTION CLOSEOUT SUBMITTALS SECTION CLOSEOUT SUBMITTALS

Health and Safety at Work (Hazardous Substances Markings for Pipework Connected to Above Ground Stationary Tanks) Safe Work Instrument 2017

.1 Comply with the General Conditions of the Contract, Supplementary General Conditions and the requirements of Division 1.

UNIFIED FACILITIES GUIDE SPECIFICATIONS

SECTION OPERATION AND MAINTENANCE DATA

SECTION CONCRETE REINFORCEMENT FOR STEAM UTILITY DISTRIBUTION

Transcription:

PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section. 1.02 SUMMARY A. Section Includes: 1. Equipment labels. 2. Warning signs and labels. 3. Pipe labels. 4. Duct labels. 5. Stencils. 6. Valve tags. 7. Warning tags. 1.03 ACTION SUBMITTALS A. Product Data: For each type of product indicated. B. Samples: For color, letter style, and graphic representation required for each identification material and device. C. Equipment Label Schedule: Include a listing of all equipment to be labeled with the proposed content for each label. D. Valve numbering scheme. E. Valve Schedules: For each piping system to include in maintenance manuals. 1.04 COORDINATION A. This section provides an outline of required labeling standards, coordinate with SCSU preferences and standards. B. Coordinate installation of identifying devices with completion of covering and painting of surfaces where devices are to be applied. C. Coordinate installation of identifying devices with locations of access panels and doors. 23 05 53 / 1 of 7

D. Install identifying devices before installing acoustical ceilings and similar concealment. PART 2 - PRODUCTS 2.01 EQUIPMENT LABELS A. Metal Labels for Equipment: 1. Material and Thickness: Brass, 0.032-inch minimum thickness, and having predrilled or stamped holes for attachment hardware. 2. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch. 3. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch for viewing distances up to 72 inches, and proportionately larger lettering for greater viewing distances. Include secondary lettering twothirds to three-fourths the size of principal lettering. 4. Fasteners: Stainless-steel rivets or self-tapping screws. B. Plastic Labels for Equipment: 1. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/8 inch thick, and having predrilled holes for attachment hardware. 2. Letter Color: White. 3. Background Color: Black. 4. Maximum Temperature: Able to withstand temperatures up to 160 deg F. 5. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch. 6. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch for viewing distances up to 72 inches, and proportionately larger lettering for greater viewing distances. Include secondary lettering twothirds to three-fourths the size of principal lettering. 7. Fasteners: Stainless-steel rivets or self-tapping screws. C. Label Content: Include equipment's Drawing designation or unique equipment number, Drawing numbers where equipment is indicated (plans, details, and schedules), plus the Specification Section number and title where equipment is specified. 23 05 53 / 2 of 7

D. Equipment Label Schedule: For each item of equipment to be labeled, on 8-1/2- by-11-inch bond paper. Tabulate equipment identification number and identify Drawing numbers where equipment is indicated (plans, details, and schedules), plus the Specification Section number and title where equipment is specified. Equipment schedule shall be included in operation and maintenance data. E. Plastic labels shall be plenum rated when located in plenums. 2.02 WARNING SIGNS AND LABELS A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/8 inch thick, and having predrilled holes for attachment hardware. B. Letter Color: White. C. Background Color: Red. D. Maximum Temperature: Able to withstand temperatures up to 160 deg F. E. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch. F. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch for viewing distances up to 72 inches, and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering. G. Fasteners: Stainless-steel rivets or self-tapping screws. H. Label Content: Include caution and warning information, plus emergency notification instructions. I. Plastic labels shall be plenum rated when located in plenums. 2.03 PIPE LABELS A. General Requirements for Manufactured Pipe Labels: Preprinted, color-coded, with lettering indicating service, and showing flow direction. B. Pretensioned Pipe Labels: Precoiled, semirigid plastic formed to cover full circumference of pipe and to attach to pipe without fasteners or adhesive. C. Pipe Label Contents: Include identification of piping service using same designations or abbreviations as used on Drawings, pipe size, and an arrow indicating flow direction. 1. Flow-Direction Arrows: Integral with piping system service lettering to accommodate both directions, or as separate unit on each pipe label to indicate flow direction. 23 05 53 / 3 of 7

2. Lettering Size: Conform to ASME/ANSI A13.1-2007. D. Plastic labels shall be plenum rated when located in plenums. 2.04 DUCT LABELS A. Material and Thickness: Multilayer, multicolor, plastic labels for mechanical engraving, 1/8 inch thick, and having predrilled holes for attachment hardware. B. Letter and Background Color: Refer to section 3.4. C. Maximum Temperature: Able to withstand temperatures up to 160 deg F. D. Minimum Label Size: Length and width vary for required label content, but not less than 2-1/2 by 3/4 inch. E. Minimum Letter Size: 1/4 inch for name of units if viewing distance is less than 24 inches, 1/2 inch for viewing distances up to 72 inches, and proportionately larger lettering for greater viewing distances. Include secondary lettering two-thirds to three-fourths the size of principal lettering. F. Fasteners: Stainless-steel rivets or self-tapping screws. G. Duct Label Contents: Include identification of duct service using same designations or abbreviations as used on Drawings, duct size, and an arrow indicating flow direction. 1. Flow-Direction Arrows: Integral with duct system service lettering to accommodate both directions, or as separate unit on each duct label to indicate flow direction. 2. Lettering Size: At least 1-1/2 inches high. H. Plastic labels shall be plenum rated when located in plenums. 2.05 STENCILS A. Stencils: Prepared with letter sizes according to ASME A13.1 for piping; minimum letter height of 1-1/4 inches for ducts; and minimum letter height of 3/4 inch for access panel and door labels, equipment labels, and similar operational instructions. 1. Stencil Material: Fiberboard or metal. 2. Paint: Exterior, acrylic enamel in colors according to ASME A13.1 unless otherwise indicated. 23 05 53 / 4 of 7

2.06 VALVE TAGS A. Valve Tags: Stamped or engraved with 1/4-inch letters for piping system abbreviation and 1/2-inch numbers. 1. Tag Material: Brass, 0.032-inch minimum thickness, and having predrilled or stamped holes for attachment hardware. 2. Fasteners: Brass beaded chain or S-hook. B. Valve Schedules: For each piping system, on 8-1/2-by-11-inch bond paper. Tabulate valve number, piping system, system abbreviation (as shown on valve tag), location of valve (room or space), normal-operating position (open, closed, or modulating), and variations for identification. Mark valves for emergency shutoff and similar special uses. 1. Valve-tag schedule shall be included in operation and maintenance data. 2.07 WARNING TAGS A. Warning Tags: Preprinted or partially preprinted, accident-prevention tags, of plasticized card stock with matte finish suitable for writing. 1. Size: Approximately 4 by 7 inches. 2. Fasteners: Brass grommet and wire. 3. Nomenclature: Large-size primary caption such as "DANGER," "CAUTION," or "DO NOT OPERATE." 4. Color: Red background with white lettering. B. Plastic labels shall be plenum rated when located in plenums. PART 3 - EXECUTION 3.01 PREPARATION A. Clean piping and equipment surfaces of substances that could impair bond of identification devices, including dirt, oil, grease, release agents, and incompatible primers, paints, and encapsulants. 3.02 EQUIPMENT LABEL INSTALLATION A. Install or permanently fasten labels on each major item of mechanical equipment. B. Locate equipment labels where accessible and visible. C. General: The Contractor shall make it possible for the personnel operating and maintaining the equipment and systems in this project to readily identify the various 23 05 53 / 5 of 7

pieces of equipment, valves, piping, etc., by marking them. All items of equipment such as fans, pumps, etc., shall be clearly marked using engraved nameplates as hereinafter specified. The item of equipment shall indicate the same number as shown on the Drawings. 3.03 PIPE LABEL INSTALLATION A. Locate pipe labels where piping is exposed or above accessible ceilings in finished spaces; machine rooms; accessible maintenance spaces such as shafts, tunnels, and plenums; and exterior exposed locations as follows: 1. Near each valve and control device. 2. Near each branch connection, excluding short takeoffs for fixtures and terminal units. Where flow pattern is not obvious, mark each pipe at branch. 3. Near penetrations through walls, floors, ceilings, and inaccessible enclosures. 4. At access doors, manholes, and similar access points that permit view of concealed piping. 5. Near major equipment items and other points of origination and termination. 6. Spaced at maximum intervals of 25 feet along each run. Reduce intervals to 10 feet in areas of congested piping and equipment. 7. On piping above removable acoustical ceilings. 8. And at all locations required to conform to ASME/ANSI A13.1-2007. B. Pipe Label Color Schedule: Conform to ASME/ANSI A13.1-2007. 3.04 DUCT LABEL INSTALLATION A. Install plastic-laminated duct labels with permanent adhesive on air ducts in the following color codes. All lettering shall be white, background colors shall be: 1. Blue: For cold-air supply ducts. 2. Yellow: For hot-air supply ducts. 3. Green: For exhaust-, outside-, relief-, return-, and mixed-air ducts. 4. ASME A13.1 Colors and Designs: For hazardous material exhaust. B. Stenciled Duct Label Option: Stenciled labels, showing service and flow direction, may be provided instead of plastic-laminated duct labels, at Owner's option, if lettering larger than 1 inch high is needed for proper identification because of distance from normal location of required identification. 23 05 53 / 6 of 7

C. Locate labels near points where ducts enter into concealed spaces and at maximum intervals of 50 feet in each space where ducts are exposed or concealed by removable ceiling system. D. Labeling/stenciling of all exposed ductwork shall be coordinated with the architect and engineer prior to the commencement. 3.05 VALVE-TAG INSTALLATION A. Install tags on valves and control devices in piping systems, except check valves; valves within factory-fabricated equipment units; shutoff valves; faucets; convenience and lawn-watering hose connections; and HVAC terminal devices and similar roughing-in connections of end-use fixtures and units. List tagged valves in a valve schedule. B. Valve-Tag Application Schedule: Tag valves according to size, shape, and color scheme and with captions similar to those indicated in the following subparagraphs: 1. Valve-Tag Size and Shape: a. All services: 1-1/2 inches, round. 2. Valve-Tag Color: a. All services: Natural. 3. Letter Color: a. All services: Black. 3.06 WARNING-TAG INSTALLATION A. Write required message on, and attach warning tags to, equipment and other items where required. END OF 23 05 53 / 7 of 7