Data Sheet Head mounted Temperature Transmitter TF0/TF0-Ex FOUNDATION Fieldbus H, Pt 00 (RTD), thermocouples, or independent channels Input Resistance thermometer (-, -, -wire circuit) Thermocouples Resistance remote signalling unit (0...500 Ω, 0...000 Ω) Voltages, mv calibrator (-0...+00 mv) Input functionality or channels Electrcal isolation (I/O) between input and output Digital, long-term solid processing of measuring values Customer-specific linearization Continuous sensor and self-monitoring EMC acc. to EN 66 and NAMUR recommendation NE Parameterization via DD and CFF file Output FOUNDATION Fieldbus H acc. to specification. Certified with Interoperbility Test Kit. IT Campaign Number: IT 05000 Bus design acc. to IEC 658-,.5 kbit/s Backup LAS function Reserve voltage protection and solid bus current limitation Approvals for explosion protection intrinsically safe ATEX Suitable for connecting to systems according to: Entity model FISCO model
Technical data Device type Link Master Device Link Active Scheduler (LAS) capability implemented Power supply (at transmitter terminals) Supply voltage U s = 9... V DC for explosion protection application dependent on the Ex supply unit Supply voltage, poling protected Current consumption Operating (quiescent): 0.5 ma Fault current limiting: 5 ma Output Interface/Protocol FOUNDATION Fieldbus H IEC 658- / FF-HVersion..5 kbit/s FF Registration: IT05000 Interoperbility Test Kit. Function blocks tested function blocks x AI (s) operating time: 5 ms other function blocks x RB (s) x TB (c) Input Resistance ) IEC 75 a = 0.0085; JIS a = 0.0096; SAMA a = 0.0090 Max. line resistance (R W ) per core -, -, -wire 5 Ω, 0 Ω, 50 Ω Measuring current 00 µa Sensor short-circuit < 5 Ω Sensor break (temperature/resistance measurement, -, -, -wire) Measuring range 0... 500 Ω > 50 Ω Measuring range 0...000 Ω > 00 Ω Sensor wire break monitoring in accordance with NAMUR Sensor wire break detection -wire resistance measurement > 5 Ω -wire resistance measurement >.7 kω Input filter 50/60 Hz Thermocouples/Voltages Types B, C, D, E, J, K, L, N, R, S, T, U Voltages Range Accuracy -0 mv...+00 mv 0 µv - 75 mv...+ 75 mv µv Sensor monitoring current µa between the measuring cycles Sensor wire break monitoring in accordance with NAMUR Thermocouple measurement > 5 kω Voltage measurement > 5 kω Input filter 50/60 Hz Internal reference junction Pt00, via software switchable (no jumper necessary) Resistance thermometer n Pt00 up to Pt000 (IEC 75: n = 0.; 0.5; ; ; 5; 0) (JIS 60: n = 0.; 0.5; ; ; 0) (SAMA: n = 0.; 0.5; ) Ni50, Ni00, Ni0, Ni000, Cu0, Cu00 Resistance Range Accuracy 0...500 Ω mω 0...000 Ω 0 mω Input element Standard Sensor IEC 58- Thermocouple type B Thermocouple type E Thermocouple type J Thermocouple type K Thermocouple type R Thermocouple type S Thermocouple type T Thermocouple type N W, Thermocouple type C ASTME 998 Thermocouple type D DIN 70 Thermocouple type L Thermocouple type U IEC 75; JIS; SAMA ) Resistance thermometer Pt00 -, - and -wire Resistance thermometer Pt000 DIN 760 Resistance thermometer Ni00 -, - and -wire (a = 0.0068) Resistance thermometer Ni000 Resistance, -, - and -wire Ω 0...500 Ω / 0...000 Ω Voltage mv -0 mv...+00 mv - 75 mv...+ 75 mv Measuring range 0...+80 C (+...+08 F) -70...+000 C (-5...+8 F) -0...+00 C (-6...+9 F) -70...+7 C (-5...+50 F) - 50...+768 C (- 58...+5 F) - 50...+768 C (- 58...+5 F) -70...+ 00 C (-5...+ 75 F) -70...+00 C (-5...+7 F) 0...+5 C (+...+00 F) 0...+5 C (+...+00 F) -00...+ 900 C (-8...+65 F) -00...+ 600 C (-8...+ F) -00...+ 850 C (-8...+56 F) -00...+ 850 C (-8...+56 F) - 60...+ 50 C (- 76...+ 8 F) - 60...+ 50 C (- 76...+ 8 F)
General characteristics Response time < 0.5 s Vibration resistance Vibration in operation Resistance to shock Electrical isolation (I/O).5 kv AC Long-term stability 0. % p. a. or 0. K p. a. Environment conditions g acc. to DIN IEC 68T.-6 g acc. to DIN IEC 68T.-7 Ambient temperature range -0...+85 C Transport and storage temperature -0...+00 C Relative humidity < 00 % (00 % humidity with isolated terminals only) Condensation permitted Mechanical construction Dimensions cf. dimensional drawing Weight 6 g Housing material Polycarbonat Color (Epoxy) black (Non-Ex type), blue (Ex-type) Terminals, pluggable.5 mm, screw terminals (stainless steel screws) Influences Influence of ambient temperature acc. to IEC 68-- Pt 00 ± 0.05 K/0 K resistance measurement 0...500 W ± 0 mω/0 K 0...000 Ω ± 00 mω/0 K Thermocouple e. g. type K ± 0.05 K/0 K voltage measurement -0 mv...+00 mv ± 50 µv/0 K - 75 mv...+ 75 mv ± 0 µv/0 K Characteristics at rated conditions acc. to IEC 770 (related to 5 C) Measuring error incl. characteristic deviation Pt 00 ± 0. K resistance measurement 0...500 Ω ± 0 mω 0...000 Ω ± 0 mω Thermocouple e. g. type K ± 0.5 K voltage measurement -0 mv...+00 mv ± 50 µv - 75 mv...+ 75 mv ± 0 µv Additional influence of the internal ref. junction Pt00 DIN IEC 75 Cl. B Parameterization / structure Type of input ( independent channels), measuring range, input filter, damping, alarm function, limit values, safing all data proof against mains failure Standard parameter (factory settings) Channel Pt00, -wire circuit, 0 +00 C damping 0 s, unit C Channel disabled Electromagnetic compatibility (EMC) According to NAMUR NE recommendation With Pt00 sensor and thermocouple Type of test Degree Standard Burst to signal/ data lines kv EN 6000-- EN 66 Static disgarge EN 6000-- contact discharge to: contact plate terminals 8 kv 6 kv radiated field EN 6000-- 80 MHz... GHz 0 V/m coupling 50 khz - 80 MHz 0 V EN 6000--6
Explosion protection Intrinsically safe EC Certificate DMT 0 ATEX E 068 X (Intrinsically safe Zone 0/ and Mine) Zone 0/ II G EEx ia IIC T6 Zone 0 T T5 Ambient temperature: -0 +60 C T6 Ambient temperature: -0 +50 C Zone T T Ambient temperature: -0 +85 C T5 Ambient temperature: -0 +65 C T6 Ambient temperature: -0 +50 C Mine Supply circuit Supply and communication circuit ia/ib IIC I M EEx ia I Ambient temperature: -0 +60 C Supply and communication circuit ia/ib IIB Measuring circuit ia/ib Max. voltage U i V U i V U o = 5.5 V Short-circuit current I i = 60 ma I i = 80 ma I o < 5 ma Max. power P i =.5 W P i = 5. W P o < 5 mw Internal inductance L i 0 µh L i 0 µh neglectable Internal capacitance C i = 5 nf C i = 5 nf C i = 60 nf Non sparking na ATEX EC Certificate BVS 0 E 7 X Zone (TF0-Ex N) II G EEx na [nl] IIC T6 T T Ambient temperature: -0 +85 C T...T5 Ambient temperature: -0 +65 C T...T6 Ambient temperature: -0 +50 C Canadian Standards Association and Factory Mutual Intrinsically Safe FM Class I Div. /Div., Groups A, B, C, D T6 Class I Zone 0, AEx ia or Zone 0, AEx ib IIC CSA Class I Div. /Div., Groups A, B, C, D T6 Nonincendive FM Class I Div., Groups A, B, C, D T6 CSA Class I Div., Groups A, B, C, D T6 Suitable for connceting to systems according to Entity model and FISCO model Block diagram Sensor ; (T) Value_ (T) AI Block AI out value sensor + Status Transducer Block TB Value_ (T) AI Block AI out value sensor + Status Sensor ; (T) Resource Block Reference junction Pt00 by request only read by request read/write
Connection diagram + - Output Foundation Fieldbus (H) Microprocessor Reference junction Pt 00 Input ϑ ϑ ϑ Resistance sensors/potentiometer ϑ Ch ϑ Ch Ch Ch Thermocouples/Voltages Ch Ch Ch Ch Combination Resistance sensor/ Thermocouple Ch Ch ϑ a) b) c) d) e) f) g) h) i) j) k) l) m) a) Resistance thermometer, -wire circuit b) Resistance thermometer, -wire circuit c) Resistance thermometer, -wire circuit d) Double resistance thermometer, -wire circuit Potentiometer: 0...500 Ω or 0...000 Ω e) Potentiometer, -wire circuit f) Potentiometer, -wire circuit g) Potentiometer, -wire circuit h) Potentiometer, -wire circuit i) Thermocouple j) Double thermocouple Voltages: -75 mv...+75 mv or -0 mv...+00 mv k) Voltage measurement i) -fold voltage measurement m) Combination thermocouple and resistance thermometer Dimensional drawing (dimensions in mm), Automation - Products TF0 Messumformer/Transmitter/Transducteur,8 Snap-on fixing for DIN rail mounting(5mm) (optionally) 5,5 5
Ordering information Catalog No. EUR Deliv. time TF0/TF0-Ex V57- - wks. Bus system FOUNDATION Fieldbus (H) acc. to Fieldbus standard IEC-658-;.5 kbit/s LAS functionality standard FR - Explosion protection TF0 (without explosion protection) 7,00 * Type of protection: Non Sparking "na" ATEX TF0-Ex N DMT/ATEX Zone : II G EEx na [nl] IIC T6 N 69,00 * Type of protection: intrinsically safe ATEX TF0-Ex DMT/ATEX Zone 0: II G EEx ia IIC T6 (+ Mine: I M EEx ia I) 5 69,00 * Type of protection: intrinsically safe FM and CSA TF0-Ex FM IS Class I, Div. /Div., Groups A, B, C, D T6 7 69,00 * IS Class I, Zone 0, AEx ia oder AEx ib IIC (Class II Groups E,F, G; Class III if built in BUZH head or AGLH head) nonincendive, Class I, Div., Groups A, B, C, D T6 (Class II Groups F, G; Class III if built in BUZH head or AGLH head) TF0-Ex CSA IS Class I, Div. and Div., Groups A, B, C, D T6 9 69,00 * (Class II Groups E, F, G; Class III if built in BUZH head or AGLH head) nonincendive, Class I, Div., Groups A,B,C,D T6 (Class II Groups F, G; Class III if built in BUZH head or AGLH head) Construction Module - Module with sensor connecting line 7,85 * Module with snap-on fixing 0,0 * Module built into connection head with sensor connecting line BUZH head R,50 * BUSH head P,0 * BUKH-Ex head N,60 * AUZH head V 56,90 * AUSH head U 58,0 * AGLH-head without display ) X 65,50 * Attention: The sensor connecting lines correspond to the order for the type of sensor or its type of circuitry Connections no head selected 0 - with cable screw connections M0 x,5 cable screw connection ) M 0,00 * Programming Factory standard parameter Pt 00, -wire circuit, channel, 0 00 C, Damping off 0 - Customer-specified parameter definition (all parameter without user curve) 7,00 * Accessories Catalog No. EUR Deliv. time Simulation plug for TF0/TF0 with bus system FOUNDATION Fieldbus 795785,60 * ) protective pipe connection M x.5 (optional M0 x.5; /" NPT; /" NPT) ) Standard: Aluminum, metal-cable-screw-connection M0 x.5 EEx e (cable diameter.5 8.7 mm); (do not use for EEx d applications, see data sheet 0/0-.8 EN for EEx d details) 6
The Industrial IT wordmark is a registered or pending trademark of ABB. ABB has Sales & Customer Support expertise in over 00 countries worldwide. www.abb.com/instrumentation The Company s policy is one of continuous product improvement and the right is reserved to modify the information contained herein without notice. Printed in the Fed. Rep. of Germany (0.05) ABB 005 Rev. B ABB Ltd. Salterbeck Trading Estate Workington, Cumbria, CA 5DS UK Tel: +(0)96-80-6 Fax: +(0)96-8-66 ABB Inc. 5 E. County Line Road Warminster, PA 897 USA Tel: + 5-67-6000 Fax: + 5-67-78 ABB Automation Products GmbH Borsigstr. 6755 Alzenau Germany Tel: +9 55 905-5 Fax: +9 55 905-555 CCC-support.deapr@de.abb.com