VFSC9 ELECTRONIC SPEED CONTROLLER. Mounting and operating instructions

Similar documents
ERV-M ELECTRONIC FAN SPEED CONTROLLER. Mounting and operating instructions

RSMFX-2R MULTIFUNCTIONAL

MTV-1-CP 230 VAC POTENTIOMETER WITH MIN & MAX SETTINGS, DRY CONTACT. Mounting and operating instructions

Measuring Transducer MT4xx series Programmable AC Current Transducer MT418

S11 Adjustable Speed Drive Engineering Specification

VF-nC1 Adjustable Speed Drive Engineering Specification

Programmable AC Current Transducer MT418

E3 Adjustable Speed Drive Engineering Specification

SRC-110 Series Zone Controllers with Modbus RTU

AxCent Servo Drive A50A100

AxCent Servo Drive A25A100

Z-10-D-IN. RS485 Modbus Module 10 Digital Inputs

CONTENTS XV300K GB r doc XV300K 2/13

Programmable AC Voltage Transducer MT416

Analog Servo Drive. Peak Current 16 A (11.3 A RMS )

Ambient Conditions Storage Conditions Installation Minimum Clearances and Air Flow...2 3

Electrical data Nominal voltage AC 230 V Nominal voltage frequency

Analog Servo Drive 25A20DD

Ocean Controls KT-5221 Modbus IO Module

METERSUK. SmartLink D Y N A M i T E. EM415 MOD Series. User Manual KEY FEATURES INDEX 3. TECHNICAL DESCRIPTION. Single Phase Metering

Analog Servo Drive 20A20

DTAP. universal programmable controller. Универсален програмируем контролер

MU110-8R(K) Digital output module 8 channel. User guide

B850 Boiler House Energy Monitor

BU: EPBP GPG: DIN Rail Products Devices for the permanent control of insulation on supply lines for medical locations ISOLTESTER-DIG-RZ/RS/PLUS

MU110-16R(K) Digital output module 16 channel. User guide

Data Acquisition Modules/ Distributed IO Modules

Energy Management Energy Meter Type EM340

Peak Current. Continuous Current. See Part Numbering Information on last page of datasheet for additional ordering options.

B850 Boiler House Energy Monitor

Switched mode power supply for DIN rail mounting type SMP21 DC24V/10A

EY-EM 527: Remote I/O module, ecolink527

Energy Management Energy Analyzer Type EM112

HD 48V01T... HD 4977T...

Analog Servo Drive 30A20AC

Modbus communication module for TCX2: AEX-MOD

External RF Driver. Electrical Driver for AOTF-crystal. Instruction Manual

sw rev. 55B DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS

MV110-8AS. Analog input module 8 channel. User guide

ATV12HU22M2. Main. Range of product Altivar 12. Component name Quantity per set Set of 1. Built-in fan. Motor power hp Communication port protocol

Analog Servo Drive. Continuous Current. Features

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

INSTRUCTIONS MANUAL DEVICE FOR THE PERMANENT CONTROL OF INSULATION ON THE SUPPLY LINES IN MEDICAL PRACTICE PLACES INSTALLATIONS HRI-R40W

Energy Management Energy Analyzer Type EM111

Analog Servo Drive 100A40

SX (400 V) System configuration

isma-b-w0202 Modbus User Manual GC5 Sp. z o.o. Poland, Warsaw

SilverMax Datasheet. QuickSilver Controls, Inc. NEMA 23 Servomotors.

PRetrans Table of contents

System configuration. Ratings 400 V Class three-phase 90 to 800 kw 690 V Class three-phase 90 to 1000 kw SX-D. Frequency inverters.

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

A6500-UM Universal Measurement Card

ELECTRONIC FAN SPEED CONTROL

Electronic AC Load ZSAC Series. 400 W up to 21,000 W 260 V up to 440 V 3 A up to 100 A. Rev. 3.03

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Operation Manual. SWF Series Switch Mode Power Supply. SANKEN ELECTRIC CO., LTD No.PAN E-01.

Integrated servo motor

Analog Servo Drive 30A8

SER8300 Series Terminal Equipment Controller with Optional PIR sensor Installation Guide

Orbital GFI Inverter Series

Precipitation Monitor ,

Energy Management Energy Meter Type EM111

Energy Management Energy Meter Type EM112

ADC5000 SERIES. AC/DC Switch Mode Power Supplies and Rectifiers for Industrial and Telecom Applications. 60W, 125W and 250 W

Contents. Instruction Leaflet IL E Effective March HMi VU Series Instruction Leaflet. Description... Page. Preface...

ATV12H018F1 variable speed drive ATV kW hp V - 1ph

SX (690 V) System configuration

ATV12H037F1 variable speed drive ATV kW hp V - 1ph - with heat sink

Electrical data Nominal voltage AC/DC 24 V Nominal voltage frequency

Digital flow transmitter for continuous flow measurement

STR-LCF. Security Advice Caution. Notes on Disposal. Electronic Fan Coil Thermostat (Flush mounting) Datasheet. Application

ATV12HU40M3 variable speed drive ATV12-4kW - 5hp V - 3ph - with heat sink

SX (400V) System configuration

DPAfour125, DPAfour250 AMPLIFIERS. Operating Manual

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Smart Power Relay E I...

Z170REG. Universal converter module with galvanic insulation between 2 analog outputs

SECTION 16483D ADJUSTABLE FREQUENCY DRIVE - MICRODRIVE (MVX <10-HP)

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Analog Servo Drive 30A8

CDG. Carbon Dioxide - User Manual Gas Detector. 1 Intended Use. 2 Functional Description. 3 Installation. 4 Electrical Connection.

EY-EM 522, 523: Remote I/O module, ecolink522, 523

IP1 Datasheet PWM OUTPUT WITH SINGLE CHANNEL ADC MODULE FEATURES DESCRIPTION CONNECTOR DETAILS

Roline L1 Series. Humidity - Temperature Transmitters INSTRUCTION MANUAL

Table of Contents. HWIO-Gateway User Manual

D.C. BRUSHLESS MOTORS DRIVE. BLD07-IT Service Manual

Energy Management Energy Meter with plug-in Output Modules Type EM4-DIN

JBUS/MODBUS communication card

INSTALLATION MANUAL. SENECA s.r.l. Via Germania, Z.I. CAMIN PADOVA ITALY Tel Fax

maxon document number:

Model FLSC-C3-XX. DC Powered Microprocessor Controlled Transmitter

This section is specifically about safety matters

NX Series Inverters. HVAC Pocket Programming Guide

PROMUX Distributed MODBUS I/O Modules Catalog and Design Guide

Introduction. Specifications LF620,LF622. Field Intelligent Device Series Electromagnetic Flowmeter Converter

Programmable transmitter of temperature, relative humidity and other derived humidity values with 4-20 ma outputs Instruction Manual

Multifunction Digital

PowerPlex Compact Module PP-C-COM24

SUPPLY NETWORK ANALYZER CVM-96 SERIES

D SERIES EM16 IP 20 / NEMA 1 & IP 66 / NEMA 4X COMPACT VECTOR CONTROL DRIVE EM 16 COMPACT VECTOR CONTROL DRIVE

Transcription:

ELECTRONIC SPEED CONTROLLER Mounting and operating instructions

Table of contents SAFETY AND PRECAUTIONS 3 PRODUCT DESCRIPTION 4 ARTICLE CODES 4 INTENDED AREA OF USE 4 TECHNICAL DATA 4 STANDARDS 5 WIRING AND CONNECTIONS 5 OPERATIONAL DIAGRAMS 6 MOUNTING INSTRUCTIONS IN STEPS 7 3SMODBUS COMMUNICATION SETUP 8 SENSISTANT COMMUNICATION SETUP 9 VERIFICATION OF INSTALLATION 10 MODBUS REGISTER MAPS 11 TRANSPORT AND STOCK KEEPING INFORMATION 12 WARRANTY INFORMATION AND RESTRICTIONS 12 MAINTENANCE 12 MIW--25-EN-000-03 / 01 / 2017 www.sentera.eu 2-12

SAFETY AND PRECAUTIONS Read all information, the datasheet, mounting instructions and wiring scheme before working with the product. For personal and equipment safety, and for optimum product performance, make sure you entirely understand the contents before installing, using, or maintaining this product. For safety and licensing (CE) reasons, unauthorised conversion and / or modifications to the product are not permitted. The product must not be exposed to abnormal conditions, such as: extreme temperatures, direct sunlight or vibrations. Chemical vapours with high concentration in combination with long exposure times can affect the product performance. Make sure the work environment is as dry as possible; check for condensation spots. All installations shall comply with the local health and safety regulations and local electrical codes. This product can only be installed by an engineer or a technician who has an expert knowledge of the product and safety precautions. Avoid contacts with energised electrical parts; always treat the product as if it is life. Always disconnect the power source before connecting the power cables, servicing or repairing the product. Always verify that you apply appropriate power supply to the product and use wires with appropriate size and characteristics. Make sure that all the screws and nuts are well tightened and fuses (if any) are fitted well. Recycling of equipment and packaging should be taken into consideration and disposed in accordance with local and national legislation / regulations. In case there are any questions that are not answered, please contact your technical support or consult a professional. MIW--25-EN-000-03 / 01 / 2017 www.sentera.eu 3-12

PRODUCT DESCRIPTION are electronic fan speed controllers for single phase induction motors (110 240 VAC / 50 60 Hz). They have a selectable analogue input (0 10 VDC / 0 20 ma / PWM) and Modbus RTU communication. Compared to phase angle control (Triac fan speed controllers), the series generates an output signal with almost perfect sinusoidal shape, while the EMC pollution remains limited, the power factor exceeds 95 %. ARTICLE CODES Code Max. output current, Imax Max. load Potentiometer -25-FP yes 2,5 A 600 W -25-FC no INTENDED AREA OF USE Fan speed control in ventilation systems For indoor use only TECHNICAL DATA Selectable analogue input 0 10 VDC / 0 20 ma / PWM Modbus RTU (RS485) communication Software configurable network bus terminator (NBT) Stand-by power consumption: < 1 W Two LED indications Potentiometer knob* Adjustable minimum and maximum speed Selectable input control: Modbus, Analogue Input / Potentiometer* Adjustable OFF level: 1 4 VDC / 2 8 ma / 10 40 % PWM Passive heatsink Adjustable acceleration / deceleration rate Digital input for run / stop command Reinforced enclosure ABS UL94-V0 (IP, grey (RAL 7035) Supply voltage: 110 240 VAC / 50 60 Hz (single phase) Power factor: > 95 % Maximum output current (Imax): 2,5 A Maximum load: 600 W Adjustable settings via Modbus registers: Minimum speed: 20 65 % Maximum speed: 70 90 % Input control: Modbus, Analogue Input / Potentiometer* OFF level: 1 4 VDC / 2 8 ma / 10 40 % PWM Acceleration / deceleration: 1 10 %/s Protections: fuse, thermal contact (TK) input Protection standard: IP54 (according to EN 60529) Operating ambient conditions: temperature: -10 40 C rel. humidity: 5 85 % rh (non-condensing) Storage temperature: -20 50 C *Potentiometer knob is available only in the FP version MIW--25-EN-000-03 / 01 / 2017 www.sentera.eu 4-12

STANDARDS Low Voltage Directive 2014/35/EU EMC Directive 2014/30/EU: EN 61000-6-2: 2005 / AC: 2005; EN 61000-6-3: 2007 / A1: 2011 / AC: 2012; EN 61000-6-3: 2014 WIRING AND CONNECTIONS L N PE Supply voltage 110 240 VAC / 50 60 Hz Neutral Earth terminal U1, U2 Regulated output to the motor TK, GND Di, GND Ai, GND A Thermal contact input Digital input Analogue input Modbus RTU (RS485), signal A /B Modbus RTU (RS485), signal /B +V Supply output 15 VDC for external potentiometer 10 kω RJ45 connector on PCB Modbus RTU (RS485) connection L, N, PE 0,75 1,5 mm 2, 3-wire insulated U1, U2 TK, GND 0,75 1,5 mm 2, 2-wire, screened and insulated Connections Di, GND 0,5 1,25 mm 2 Ai, GND 0,5 1,25 mm 2, screened / shielded + V A, /B, GND Cat 5 network cable, screened, foil-shielded, twisted pair (S/FTP) MIW--25-EN-000-03 / 01 / 2017 www.sentera.eu 5-12

OPERATIONAL DIAGRAMS Input / Output Startup diagram Requested fan speed Ui [PWM duty cycle] [VAC] Max 0 ωt Regulated (Ai / Pot / Modbus) Uo [VAC] Start Value 0 Io [VAC] ωt 0 t t[s] If min. > 45 %, Start value = min. If min. < 45 %, Start value = 45 % ( Regulated StartValue) If Regulated > Start Value, t = acceleration ( Regulated StartValue) If Regulated < Start Value, t = deceleration 0 When the motor starts, it runs at proportional step (acceleration / deceleration) from the start value to the regulated value. The start value can be equal to 45 % of PWM duty cycle or equal to the minimum value of PWM duty cycle, depending on the minimum value of PWM duty cycle. Analogue input (Ai) with OFF level Requested fan speed [PWM duty cycle] 90 Max range Max 70 65 Min range 20 Min 0 1 VDC Min 4 VDC range 2 ma 8 ma 10% PWM 40% PWM Off level range ωt Ai - OFF Level PWM duty cycle = Min + (Max - Min) A - OFF Level imax 10 VDC Ai 20 ma [VDC / ma / %] 100% PWM OFF level OFF level value of analogue input (VDC / ma / %) OFF level range (1 4 VDC / 2 8 ma / 10 40 % PWM) Analogue input (Ai) - output related to acceleration / deceleration Ai [VDC / ma / %] 100 PWM duty cycle [%] Max Max Maximum value of PWM duty cycle (%) Min Minimum value of PWM duty cycle (%) Regulated Regulated value of PWM duty cycle (%) Start Value The value of PWM duty cycle to start the motor (%) t Analogue input (Ai) Requested fan speed [PWM duty cycle] 90 Max range Max 70 65 Min range Min 20 Time duration to reach the regulated value according to proportional step (acceleration / deceleration) 0 Ai PWM duty cycle = Min + ( Max - Min) A Max Maximum value of PWM duty cycle (%) Min Minimum value of PWM duty cycle (%) Max. range Min. range Ai Ai max imax 10 VDC Ai 20 ma [VDC / ma / %] 100% PWM Range of maximum value of PWM duty cycle (70 90 %) Range of minimum value of PWM duty cycle (20 65 %) Analogue input (settable) Maximum value of analogue input (10 VDC / 20 ma / 100 % PWM) Acceleration Deceleration 0 Input (Ai / Pot) Output (PWM) t[s] Min MIW--25-EN-000-03 / 01 / 2017 www.sentera.eu 6-12

MOUNTING INSTRUCTIONS IN STEPS Before you start mounting the -25 controller, read carefully Safety and Precautions. Choose a smooth surface for an installation location (a wall, panel, etc.) Follow these steps: ATTENTION Before mounting the controller, switch OFF the mains supply! 1. Unscrew the 4 screws on the front cover and open the enclosure. Mind the wires that connect the potentiometer with the printed circuit board. 2. Loosen the cable glands. 3. Insert the cables through the cable glands and connect adhering to the information from the Wiring and connections section, Fig. 1 Wiring diagram and the following instructions: 3.1 Connect the motor / fan. 3.2 Connect the thermal cut-off contact cables, if any, or use a bridge on TK input. Do not leave it open! 3.3 Connect the power supply cables. 3.4 Connect the digital input (remote) cables, if any, or use a bridge on Di input. Fig. 1 Wiring diagram RJ45 connection A /B GND CNVT-USB-RS485 Supply voltage Single phase AC motor Run / Stop 0 10 VDC / 0 20 ma / PWM / Potentiometer 10 kω Legend L, N Supply voltage: 110 240 VAC / 50 60 Hz (single phase) PE Power earth U1, U2 Regulated output, Imax = 2,5 A (single phase) TK, GND Thermal contact input Di, GND Digital input Ai, GND Analogue input +V Supply voltage 15 VDC for external potentiometer 10 kω A, /B Modbus RTU (RS485) communication 4. Tighten the cable glands. MIW--25-EN-000-03 / 01 / 2017 www.sentera.eu 7-12

1 2 3 4 5 6 7 8 5. Fix the unit to the wall or panel using the provided screws and dowels. Mind the correct mounting position and unit mounting dimensions. (See Fig. 2 Mounting dimensions and Fig. 3 Mounting position above). Put back the front cover and fix it. Fig. 2 Mounting dimensions 115 4x 4,60 102 Fig. 3 Mounting position Acceptable Not acceptable 100 210 140 6. Switch on the power supply. 7. Set the Modbus registers, if necessary (refer to the Modbus registers settings below). NOTE The controller has 4 cable glands: an M16, an M20, and two M12 (metric size). Make sure you use appropriate cable sizes, so that they can fit into the provided cable glands. 3SMODBUS COMMUNICATION SETUP -25 is ready to use. If required, the advanced settings can be changed from a PC via Modbus communication using the 3SModbus software. IMPORTANT The device ID for calling -25 is 1 (default). The -25 has baud rate 19200, Even parity (default). To connect the -25 to the 3SModbus software on the PC, follow these steps: 1. Setup the Modbus (RS485) cable*. You needs a 3-wire cable to connect the converter to the -25: a wire for A signal, a wire for /B signal, and a wire for ground. 2. Turn OFF the -25 and connect the Modbus wires to the -25. There are two options for connecting the wires to -25: 2.1 Connect directly to the Terminal Block slot A, /B (see Fig. 4); 2.2 Plug an RJ45 connector into the socket (see Fig. 5). * The Modbus (RS485) cables to connect the -25 to the PC are not included in the set. It is highly recommended that you use shielded twisted-pair cable (S/FTP) for this connection. Fig. 4 3SModbus terminal block connection Fig. 5 3SModbus RJ45 connection RJ45 GND /B A NC CNVT-USB-RS485 CNVT-USB-RS485 MIW--25-EN-000-03 / 01 / 2017 www.sentera.eu 8-12

Connections Pins 1 & 2 Pins 3 & 4 Pins 5 & 6 Pins 7 & 8 Not connected (NC) A signal /B signal Ground (GND) NOTE Make sure the Modbus cables fit into the cable glands. If the cables have an RJ45 connector, it is recommended that you plug the RJ45 connector into the RJ45 socket first and then insert the wires through the cable gland before connecting to the Modbus (RS485) converter. 3. Insert a Modbus (RS485) converter (CNVT-USB-RS485) into the PC USB port. SENSISTANT COMMUNICATION SETUP -25 is ready to use. If required, the advanced settings can be changed from a SENSISTANT configurator. The information below illustrates the way to connect the -25 to a SENSISTANT. IMPORTANT via PDM (see Fig. 9 Connecting to SENSISTANT). The device ID for calling -25 is 1 (default). The -25 has baud rate 19200, Even parity (default). To connect the -25 to the SENSISTANT Modbus configurator, follow these steps 1. Remove the power supply from the -25 and the PDM unit. Connect the -25 to the PDM unit using a standard network cable with an RJ45 connector at both ends. 2. Connect the SENSISTANT to the PDM using a standard network cable with an RJ45 connector at both ends. Network bus terminator The network bus termination resistor (NBT) should be connected only in case the unit is first or last on the line of device (See Fig. 6 NBT example). The NBT is connected via holding register 40020. Fig. 6 NBT Example Master NBT RX ТX NBT Slave 1 Slave 2 Slave n LED indications 1. When the green LED on the enclosure cover (see Fig. 7 Operating LED indications) indicates the that the power is on and the modes, depending on if the light signal is blinking or permanent: 1.1 Blinking green: Power ON, stand-by mode; 1.2 Permanent green : Power ON, run mode (the motor runs). 2. The red LED on the enclosure cover indicates that there is thermal contact alarm. MIW--25-EN-000-03 / 01 / 2017 www.sentera.eu 9-12

3. Th e green LED on the main board and the controller board indicate that a 3,3 VDC supply voltage. 4. Blinking green LEDs on the RS485V board indicate that the controller transmits (Tx) and receives (Rx) packages via Modbus (Fig. 8 Communication LED indication). Fig. 7 Operating LED indications Fig. 8 Communication LED indication VERIFICATION OF INSTALLATION Switch OFF the remote control input (Di) and switch ON the power supply. The green LED must blink, the red LED must be off, and the motor must not run. If the red LED is ON, the power supply should be restarted. Check the motor for a thermal problem or a thermal contact (TK) problem before restarting the power supply. For FC version 1. pply a 10 VDC control signal to the analogue input. Switch ON the remote A control input (Di). The green LED must be on and the motor must start running at maximum speed. 2. A pply a 0 VDC control signal to the analogue input. The green LED must be on and the motor must start running at minimum speed. 3. Switch off the remote control input (Di). The motor must stop. For FP version 1. urn the potentiometer at the front of the enclosure to MAX position. Switch T ON the remote control input (Di). The green LED must be on and the motor must start running at maximum speed. 2. Turn the potentiometer at the front of the enclosure to MIN position: 3. The GREEN LED should light and the motor running to minimum speed. 4. Switch OFF the remote control input (Di). The motor must stop. NO T E ATTENTION MIW--25-EN-000-03 / 01 / 2017 If the controller does not operate according to the instructions, the wiring connections and settings need to be checked. Hot surface! The surface of the unit may become hot and cause burns if touched. Avoid contact with the unit when in operation! www.sentera.eu 10-12

MODBUS REGISTER MAPS INPUT REGISTERS Data type Description Data Values 30001 Output value unsigned int. Output value (PWM duty cycle) in % 0 90 8 80% 30002 30003 Minimum value of PWM duty cycle Maximum value of PWM duty cycle unsigned int. Minimum value of PWM duty cycle in % 20 65 145 = 45 % unsigned int. Maximum value of PWM duty cycle in % 70 90 8 80%h 30004 Input mode unsigned int. Active input 1 2 30005 Work mode unsigned int. Current work mode 0 2 2 = 2 = Analogue input External potentiometer input STOP RUN ALARM / TK HOLDING REGISTERS Data type Description Data Default Values 40001 Device slave address unsigned int. Modbus device address 1 247 1 40002 Modbus baud rate unsigned int. Modbus communication baud rate 0 5 2 40003 Modbus parity mode unsigned int. Parity check mode 8N1 8E1 2 = 8O1 1 2 = 3 = 4 = 5 = 2 = 4.800 bps 9.600 bps 19.200 bps 38.400 bps 57.600 bps 115.200 bps None Even Odd 40004 Device type unsigned int. Device type (Read only) 3012 3012 = -XX 40005 HW version unsigned int. Hardware version of the device (Read only) XXXX 0 x 010 HW version 1.00 40006 FW version unsigned int. Firmware version of the device (Read only) XXXX 0 x 020 FW version 2.00 40007 unsigned int. Reserved, returns 0 40008 Overwrite mode unsigned int. Overwrite mode selection 0 1 0 40009 Reserved, returns 0 40010 Modbus registers reset unsigned int. Resets all Modbus registers to default values (except registers 1 3) 40011 40012 Minimum value of PWM duty cycle Maximum value of PWM duty cycle unsigned int. unsigned int. Sets minimum PWM duty cycle value in percentage Sets maximum PWM duty cycle value in percentage 0 1 0 40013 Input mode unsigned int. Selects active input 0 2 0 40014 Analogue input mode unsigned int. Selects analogue input mode 0 2 0 40015 Off level unsigned int. Sets OFF level value 0; 10 40 0 40016 Acceleration unsigned int. Sets acceleration speed 0 10 5 40017 Deceleration unsigned int. Sets deceleration speed 1 10 5 40018-40019 40020 Network bus terminator (NBT) unsigned int. Reserved, return 0 Sets unit as first or last unit on the line by connecting the NBT resistor Inactive Active Idle Reset 20 65 40 45 = 45% PWM 70 90 90 8 80% PWM 1 1 0 2 = 2 = 1 1 1 Auto Analogue input External potentiometer input Voltage mode (0 10 VDC) Current mode (0 20 ma) PWM mode (100%) Without Off level 10 % of input ON minimum acceleration maximum acceleration minimum deceleration maximum deceleration Disconnected (NBT open) Connected (NBT connected) PWM duty cycle value (Overwrite 40021 Overwrite value unsigned int. 0; 20 90 60 5 50 % PWM mode) in percentage For more information about Modbus over serial line, please visit: http://www.modbus.org/docs/modbus_over_serial_line_v1_02.pdf MIW--25-EN-000-03 / 01 / 2017 www.sentera.eu 11-12

TRANSPORT AND STOCK KEEPING INFORMATION Avoid shocks and extreme conditions. Stock in original packing at temperatures -20 50 C. WARRANTY INFORMATION AND RESTRICTIONS Two years from the delivery date against defects in manufacturing. Any modifications or alterations to the product after the date of publication relieve the manufacturer of any responsibilities. The manufacturer bears no responsibility for any misprints or mistakes in this data. The warranty will be void in the event of damage caused by failure to observe the safety instructions! We do not assume liability for any resulting damage. MAINTENANCE In normal conditions these controllers are maintenance-free. If soiled, clean with a dry or dampish cloth. In case of heavy pollution, clean with a non-aggressive product. In these circumstances, the unit should be disconnected from the main supply. Pay attention that no fluids enter the unit. Only reconnect the controller to the main supply when it is completely dry. MIW--25-EN-000-03 / 01 / 2017 www.sentera.eu 12-12