EE 741. Primary & Secondary Distribution Systems

Similar documents
EE 340 Transmission Lines

EE 340 Transmission Lines. Spring 2012

EE 740 Transmission Lines

PRELIMINARIES. Generators and loads are connected together through transmission lines transporting electric power from one place to another.

Transmission Line Models Part 1

Fatima Michael college of Engineering and Technology

Transmission of Electrical Energy

III/IV B.Tech (Regular/Supplementary) DEGREE EXAMINATION

ELEC Transmission i and

ECE 422/522 Power System Operations & Planning/Power Systems Analysis II 5 - Reactive Power and Voltage Control

Roll No. :... Invigilator s Signature :.. CS/B.TECH(EE)/SEM-5/EE-502/ POWER SYSTEM-I. Time Allotted : 3 Hours Full Marks : 70

EL 403 MODEL TEST PAPER - 1 POWER SYSTEMS. Time: Three Hours Maximum Marks: 100

Determination of Optimal Account and Location of Series Compensation and SVS for an AC Transmission System

Generator Advanced Concepts

Busbars and lines are important elements

Case Study 1. Power System Planning and Design: Power Plant, Transmission Lines, and Substations

Electrical Power Systems

BE Semester- VI (Electrical Engineering) Question Bank (E 605 ELECTRICAL POWER SYSTEM - II) Y - Y transformer : 300 MVA, 33Y / 220Y kv, X = 15 %

Topic 6 Quiz, February 2017 Impedance and Fault Current Calculations For Radial Systems TLC ONLY!!!!! DUE DATE FOR TLC- February 14, 2017

EH2741 Communication and Control in Electric Power Systems Lecture 2

Exercises on overhead power lines (and underground cables)

3. What is hysteresis loss? Also mention a method to minimize the loss. (N-11, N-12)

Level 6 Graduate Diploma in Engineering Electrical Energy Systems

Placement Paper For Electrical

Aligarh College of Engineering & Technology (College Code: 109) Affiliated to UPTU, Approved by AICTE Electrical Engg.

EH27401 Communication and Control in Electric Power Systems Lecture 2. Lars Nordström

Single-turn and multi-turn coil domains in 3D COMSOL. All rights reserved.

Oscillators. An oscillator may be described as a source of alternating voltage. It is different than amplifier.

University of Jordan School of Engineering Electrical Engineering Department. EE 219 Electrical Circuits Lab

MAINS SIGNAL PROPAGATION THROUGH DISTRIBUTION SYSTEMS. J. Stones*, S. Perera*, V. Gosbell* and N. Browne**

Radio Frequency Electronics

CHAPTER 2. Basic Concepts, Three-Phase Review, and Per Unit

CONTENTS. 1. Introduction Generating Stations 9 40

G. KOEPPL Koeppl Power Experts Switzerland

Notes 1: Introduction to Distribution Systems

Transmission Lines Ac

Chapter 10: Compensation of Power Transmission Systems

University of Pennsylvania Department of Electrical and Systems Engineering ESE319

ENGINEERING ACADEMY X V

CHAPTER 3 COMBINED MULTIPULSE MULTILEVEL INVERTER BASED STATCOM

Ballast Resistance Measurement Theory and Practice

Cork Institute of Technology. Autumn 2008 Electrical Energy Systems (Time: 3 Hours)

ISSN: X Impact factor: (Volume 3, Issue 6) Available online at Modeling and Analysis of Transformer

SOFTWARE FOR CALCULATING ELECTRICAL POWER TRANSMISSION LINE PARAMETERS

UNIVERSITY OF TECHNOLOGY By: Fadhil A. Hasan ELECTRICAL MACHINES

What is Corona Effect in Power System and Why it Occurs?

RX Directional Antennas. Detuning of TX Antennas.

DHANALAKSHMI COLLEGE OF ENGINEERING, CHENNAI 301.

Alternating Current Page 1 30

Overview of Grounding for Industrial and Commercial Power Systems Presented By Robert Schuerger, P.E.

Inductors & Resonance

R10. III B.Tech. II Semester Supplementary Examinations, January POWER SYSTEM ANALYSIS (Electrical and Electronics Engineering) Time: 3 Hours

High Voltage Direct Current Transmission

Electronic Measurements & Instrumentation. 1. Draw the Maxwell s Bridge Circuit and derives the expression for the unknown element at balance?

Coil Products Beginnings 1960 State of the Art. Customer partnership around the globe. Continuous innovation since 1900

TRANSFORMER OPERATION

Chapter 12: Transmission Lines. EET-223: RF Communication Circuits Walter Lara

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

ABSTRACT 1 INTRODUCTION

Electronic Instrumentation

RESONANT TRANSFORMER

Fuel cell power system connection. Dynamics and Control of Distributed Power Systems. DC storage. DC/DC boost converter (1)

Introduce system protection relays like underfrequency relays, rate of change of frequency relays, reverse - power flow

SYNCHRONOUS MACHINES

HARMONICS CAUSES AND EFFECTS

Practical Transformer on Load

Volume I Issue VI 2012 September-2012 ISSN

Distribution Network Capacitor Resonance A Case Study

ELECTRICAL POWER ENGINEERING

Power System Analysis Prof. A. K. Sinha Department of Electrical Engineering Indian institute of Technology, Kharagpur

Chapter 2-1 Transformers

AC Power Instructor Notes

TUNED AMPLIFIERS 5.1 Introduction: Coil Losses:

SECTION 4 TRANSFORMERS. Yilu (Ellen) Liu. Associate Professor Electrical Engineering Department Virginia Tech University

VLSI is scaling faster than number of interface pins

Field Instrument Cable. Electrical Noise

Conventional Paper-II-2011 Part-1A

Downloaded from / 1

ECE 145A and 218A. Transmission-line properties, impedance-matching exercises

Calculation of Transients at Different Distances in a Single Phase 220KV Gas insulated Substation

Generation of Sub-nanosecond Pulses

148 Electric Machines

Power Quality. Case Study. Conrad Bottu Laborelec January 2008

The power transformer

EE273 Lecture 3 More about Wires Lossy Wires, Multi-Drop Buses, and Balanced Lines. Today s Assignment

Design and Simulation of Passive Filter


Distance Protection of Cross-Bonded Transmission Cable-Systems

Protection of Electrical Networks. Christophe Prévé

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

ELECTROMAGNETIC INDUCTION AND ALTERNATING CURRENT (Assignment)

SRI VIDYA COLLEGE OF ENGG AND TECH

TRANSFORMERS PART A. 2. What is the turns ratio and transformer ratio of transformer? Turns ratio = N2/ N1 Transformer = E2/E1 = I1/ I2 =K

In Class Examples (ICE)

THE COMPREHENSIVE APPROACH TO FACILITY POWER QUALITY

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

1 Introduction General Background The New Computer Environment Transmission System Developments Theoretical Models and Computer Programs

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

SIMULATION OF D-Q CONTROL SYSTEM FOR A UNIFIED POWER FLOW CONTROLLER

Transcription:

EE 741 Primary & Secondary Distribution Systems

Radial-Type Primary Feeder Most common, simplest and lowest cost

Example of Overhead Primary Feeder Layout

Example of Underground Primary Feeder Layout

Radial-Type Feeder with Tie and Sectionalizing Switches Higher service reliability Fast restoration of service by switching un-faulted sections of the feeder to adjacent primary feeders

Radial-Type Primary with Express Feeder

Radial-Type Phase Area Feeder

Loop Type Primary Feeder Loop tie disconnect switch normally open or normally closed

Primary Network Supplied by multiple substations Load supplied from multiple directions Highest reliability but more difficult to operate

Primary Voltage Levels: Factors Affecting Selection

Voltage Square Rule

Factor Affecting Conductor Size Selection

Tie Lines Provides emergency service from an adjacent feeder to customers thereby reducing outage time.

Voltage drop and Power Loss in Radial Feeder with Uniformly Distributed Load VD 1 zli 2 s P loss 1 3 rli 2 s

Derivation 2, 2 2 3 0, 0 2 2 3 1 ) 3 ( 2 1 ) 2 / (1 )] / (1 [ ) / (1 ) / (1 / / s l x LS s x LS x LS s l x s x x s x LS s x s x s rli P l x l x x ri dp P zli VD l x zx I dv VD rdx l x I rdx I dp dx l x z I zdx I dv l x I I l I c dx di

VD and Power Loss in Radial Feeder with Uniformly Increasing Load VD 2 zli 3 s P loss 8 15 rli 2 s

Radial Secondary Distribution System Common secondary main feeding a group of customers, In rural areas, a distribution transformer serves one customer.

Secondary Banking Secondary main served by multiple transformers (in parallel) that are fed from the same primary feeder. Improved voltage regulation and service reliability, reduced voltage dip

Secondary Network Meshed network that is powered by multiple feeders, trough network-type transformers Fault current limiters, network protectors (i.e., air circuit breakers) with back-up fuses are used for secondary network protection.

Economic Design of Secondary Circuits Total Annual Cost (TAC) = annual installed cost of transformer, secondary cable, pole and hardware + annual operating cost of transformer (excitation current, core and copper loss) and cable. TAC is a function of the transformer and cable sizes.

Physical Characteristics Overhead lines An overhead line usually consists of three conductors or bundles of conductors containing the three phases of the power system. In overhead lines, the bare conductors are suspended from a pole or a tower via insulators. The conductors are usually made of aluminum cable steel reinforced (ACSR).

Physical Characteristics underground cables Cable lines are designed to be placed underground or under water. The conductors are insulated from one another and surrounded by protective sheath. Cable lines are more expensive and harder to maintain. They also have capacitance problem not suitable for long distance.

Electrical Characteristics Transmission/distribution lines are characterized by a series resistance, inductance, and shunt capacitance per unit length. These values determine the power-carrying capacity of the line and the voltage drop across it at full load. The DC resistance of a conductor is expressed in terms of resistively, length and cross sectional area as follows:

Cable resistance The resistively increases linearly with temperature over normal range of temperatures. If the resistively at one temperature and material temperature constant are known, the resistively at another temperature can be found by

Cable Resistance AC resistance of a conductor is always higher than its DC resistance due to the skin effect forcing more current flow near the outer surface of the conductor. The higher the frequency of current, the more noticeable skin effect would be. Wire manufacturers usually supply tables of resistance per unit length at common frequencies (50 and 60 Hz). Therefore, the resistance can be determined from such tables.

Line inductance

Remarks on line inductance The greater the spacing between the phases of a transmission line, the greater the inductance of the line. Since the phases of a high-voltage overhead line must be spaced further apart to ensure proper insulation, a high-voltage line will have a higher inductance than a low-voltage line. Since the spacing between lines in buried cables is very small, series inductance of cables is much smaller than the inductance of overhead lines The greater the radius of the conductors, the lower the inductance of the line. In practical transmission lines, instead of using heavy and inflexible conductors of large radii, two and more conductors are bundled together to approximate a large diameter conductor, and reduce corona loss.

Per-Phase Inductance of 3-phase power line

Shunt capacitance Since a voltage V is applied to a pair of conductors separated by a dielectric (air), charges q of equal magnitude but opposite sign will accumulate on the conductors. Capacitance C between the two conductors is defined by q C V The capacitance of a single-phase transmission line is given by (see derivation in the book): (ε = 8.85 x 10-12 F/m)

Capacitance of 3-phase power line

Remarks on line capacitance 1. The greater the spacing between the phases of a line, the lower the capacitance of the line. Since the phases of a high-voltage overhead line must be spaced further apart to ensure proper insulation, a high-voltage line will have a lower capacitance than a low-voltage line. Since the spacing between lines in buried cables is very small, shunt capacitance of cables is much larger than the capacitance of overhead lines. 2. The greater the radius of the conductors, the higher the capacitance of the line. Therefore, bundling increases the capacitance.

Short line model Overhead lines shorter than 50 miles can be modeled as a series resistance and inductance, since the shunt capacitance can be neglected over short distances. The total series resistance and series reactance can be calculated as where r, x are resistance and reactance per unit length and d is the length of the transmission line.

Two-port network model: Short line model The equation is similar to that of a synchronous generator and transformer (w/o shunt impedance)

Short line Voltage Regulation: 1. If unity-pf (resistive) loads are added at the end of a line, the voltage at the end of the transmission line decreases slightly small positive VR. 2. If leading (capacitive) loads are added at the end of a line, the voltage at the end of the transmission line increases negative VR. 3. If lagging (inductive) loads are added at the end of a line, the voltage at the end of the transmission line decreases significantly large positive VR.

Short line simplified If the resistance of the line is ignored, then Therefore, for fixed voltages, the power flow through a transmission line depends on the angle between the input and output voltages. Maximum power flow occurs when δ = 90 o. Notes: The maximum power handling capability of a transmission line is a function of the square of its voltage. The maximum power handling capability of a transmission line is inversely proportional to its series reactance (some very long lines include series capacitors to reduce the total series reactance). The angle δ controls the power flow through the line. Hence, it is possible to control power flow by placing a phase-shifting transformer.

Example A line with reactance X and negligible resistance supplies a pure resistive load from a fixed source V S. Determine the maximum power transfer, and the load voltage V R at which this occurs. (Hint: recall the maximum power transfer theorem from your basic circuits course) Ans: P max 2 VS 2X, V R V S 2

Line Characteristics To prevents excessive voltage variations in a power system, the ratio of the magnitude of the receiving end voltage to the magnitude of the ending end voltage is generally within 0.95 V S /V R 1.05 The angle δ in a transmission line should typically be 30 o to ensure that the power flow in the transmission line is well below the static stability limit. Any of these limits can be more or less important in different circumstances. In short lines, where series reactance X is relatively small, the resistive heating usually limits the power that the line can supply. In longer lines operating at lagging power factors, the voltage drop across the line is usually the limiting factor. In longer lines operating at leading power factors, the maximum angle δ can be the limiting f actor.

Medium Line (50-150 mi) the shunt admittance must be included in calculations. However, the total admittance is usually modeled (π model) as two capacitors of equal values (each corresponding to a half of total admittance) placed at the sending and receiving ends. The total series resistance and series reactance are calculated as before. Similarly, the total shunt admittance is given by where y is the shunt admittance per unit length and d is the length of the transmission line.

Two-port network: Medium Line