Operator Manual. Transmitters Series KAT-... Analog transmitters in 2-wire technique

Similar documents
Operator Manual. Transmitter Model RT - R and RT - RH. Programmable transmitter in 2 wire - technique

TF 02 / TF 02-Ex. Head mounted temperature transmitters, FOUNDATION Fieldbus (H1), Pt 100 (RTD), thermocouples, 1 or 2 independent channels

Head mounted Temperature Transmitter TF02/TF02-Ex

TR 104, TR 104-Ex Rail mounted Temperature Transmitters

FieldIT Temperature Transmitter, rail mounted TH102/TH102-Ex

Temperature Input Module for Zone 1 Series 9482/32

SEM210 SERIES. Programmable In-head Universal Temperature Transmitter INDEX SECTION CONTENTS PAGE NO.

Rail mounted Temperature Transmitter TH102/TH102-Ex

OPTITEMP TT 10 C/R Technical Datasheet

Inductive sensor slot-type SI2-K08-AP7

MODEL: B3HU. Space-saving Two-wire Signal Conditioners B3-UNIT

Digital temperature transmitter for resistance sensors Model T15.H, head mounting version Model T15.R, rail mounting version

Operating Instructions

R88000 T (including ATEX)

Temperature transmitter itemp PCP DIN rail TMT 121

Digital temperature transmitter Model T15.H, head mounting version Model T15.R, rail mounting version

Indicomp 2, Indicomp 2-Ex. Indicator and alarm signalling unit 10/ EN

3 Ex i Isolators. Temperature Transmitter with Output 0/ ma, without Limit Value Contact (Field Circuit Ex i) Type 9182/.0-5.

SINEAX V 624 Programmable Temperature Transmitter for RTD and TC inputs

3 Ex i Isolators. Temperature Transmitter without Output 0/ ma, with Limit Value Contact (Field Circuit Ex i) Type 9182/.

Assembly. Front view. Parametrization interface. Power Bus

Temperature head transmitter itemp PCP TMT 181

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

Isolators A3/1.

Intrinsically Safe Compact Controller CTR 210i. Intrinsically Safe Bargraph Indicator. BGI 210i

SINEAX TI 807 Passive DC signal isolator. SINEAX TI 807 Passive DC signal isolator

SINEAX TI 807 Passive DC signal isolator

Isolators A3/1. Vibration Transducer Supply Unit Series

Contents. TS 11, TS 11-Ex. Intelligent transmitter for temperature sensor head mounting

09746E00. ATEX / IECEx NEC 505 NEC 506 NEC 500 Class I Class I Class II Class III Zone Zone Division Ex i

Temperature Transmitters TMT 136, TMT 137

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

Universal Intelligent 2-wire DIN Rail Transmitters

Temperature head transmitter itemp TC TMT 188

2 Safety Barriers. Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Contrans T TEU 471, TEU 471-Ex. Intelligent four-wire temperature transmitters EN

itemp HART DIN rail TMT112

Isolating Repeater Input Series 9163

Digital Temperature Transmitters Model T12.10, Universally Programmable, Head Mounting Model T12.30, Universally Programmable, Rail Mounting

Temperature Measurement

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160

Temperature transmitter itemp RTD DIN rail TMT 127

Isolators A3/1.

Isolators A3/1. Temperature Transmitter Field Circuit Non-Ex i Series

JUMO dtrans T02 Programmable 4-wire Transmitter (Smart Transmitter)

PRetrans Table of contents

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

Operating Instructions

Process Protection Acoustic sensors for pump monitoring

Intrinsically safe pressure transmitter MBS 4201, MBS 4251, MBS 4701 and MBS 4751

KFS. Flap-type flow meter. Design and range of application

MCR-VAC-UI-0-DC. Voltage transducer for AC voltages. INTERFACE Data sheet _en_02. 1 Description

Plug-in module SIRAX V 606, 1 or 2 channels Programmable Temp. Transmitter for RTD and TC inputs

Analog Input Module HART Ex i / I.S. Inputs, Channels Type 9461/

Temperature Measurement Transmitters for mounting in sensor head

SINEAX B 811 Power Pack with additional Functions

Power supply. Calibration. Surface finishing. Seal. Process connection

STT 3000 Series STT170 SMART TEMPERATURE TRANSMITTER Models STT171, STT173, STT17H, STT17F, STT17C

Miniature resistance thermometer Explosion-protected version Model TR34, thread-mounted

SALES SERVICE +358 (0)

MODEL: B6U-B B6-UNIT. [2] LCD DISPLAY 0: Without 1: With

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series 9160 Rev. F

Pressure transmitters MBS 4201, MBS 4251, MBS 4701 and MBS 4751

Digital Input Output Module for Zone 2 Series 9470/33

MACX MCR-EX-T-UI-UP. Extract from the online catalog. Order No.:

MCR-T-UI(/NC) MCR-T-UI-E(/NC)

Universal Intelligent 2-wire In-head Transmitters

JUMO dtrans T01 HART / T01T HART / T01 Junior / T01 Ex / T01 HART Ex Programmable 2-wire transmitter

MACX MCR-UI-UI-UP(-SP)(-NC)

Transmitter for temperature and direct current variables in four-wire circuit. Contrans T TEU 315, TEU 315-Ex, TEU 325, TEU 325-Ex 11-3.

SITRANS T measuring instruments for temperature

Analog Universal Module HART for Zone 2 Series 9468/33

Design and applications

English. Operating manual. Temperature measuring transducer MU125. Save for later reference. Company / brands of GHM

MINI MCR-SL-UI-f(-SP)

Temperature Measurement

Two-channel safety barriers Series 9002

... for hydraulic and general applications in hazardous areas

Digital Input Module NAMUR Ex i / I.S. Inputs, 16 Channels for Zone 1 / Div. 1 Series 9470/22

Isolators A3/1. Transmitter Supply Unit Field Circuit Ex i Series

2002 IS Catalog. Page

OPTITEMP TT 20 Technical Datasheet

itemp PA TMT184 Technical information

MCR-FL-TS-LP-I-EX SIL IEC Programmable Intrinsically Safe Loop-Powered Temperature Measuring Transducer With HART Protocol

Analogue Temperature Transmitter Model T24.10, PC configurable, Head Mounting

MINI-PS AC/2X15DC/1

PROGRAMMABLE FIELD TEMPERATURE TRANSMITTER

MINI-PS AC/24DC/1.3

0 2 1 â Ó. itemp HART TMT182. Technical Information

0 2 1 â Ó. itemp HART TMT182. Technical Information

Binary Output Series 9175

Operating Manual * * Differential pressure transmitter. Table of Contents. 1 Safety guidelines. 1.1 General Information

TxBlock-USB Transmitter

Temperature Transmitter itemp RTD DIN rail TMT 127

RAD-IN/OUT-8D. Digital extension modules for the bidirectional wireless system. INTERFACE Data sheet _en_05. 1 Description

Universal Intelligent 2-wire DIN Rail Transmitters

FieldIT Temperature Transmitter, head mounted TH02/TH02-Ex

Two-channel safety barriers Series 9002

Single-Channel Safety Barriers with Electronic Current Limitation Series 9004

Two-Wire Programmable Transmitter for:

Transcription:

Operator Manual Transmitters Series KAT-... Analog transmitters in 2-wire technique

Important Safety Notes! In the case of non-observance of the installation and safety notes or improper use of the transmitter heavy or fatal injuries may occur. In the case of wrong assembly, faulty programming or inadequate voltage supply the output signal of the transmitter may be out of order, i.e. the current sensor condition is no longer given at the output. For a safe operation of the series KAT- transmitters proper packing, appropriate storage, professional installation, operation and maintenance are of the essence. Only professionally trained and qualified personnel should carry out installation, operation and maintenance. Special attention must be paid to the contents of this operator manual; the pertinent safety regulations for the installation and operation of electrical equipment, as well as the rules and regulations on explosion protection; the regulations, standards and rules mentioned in this operator manual apply in Germany. When operating the transmitters in other countries the pertinent national rules and regulations are to be observed. The transmitter has left the factory in impeccable condition. The mentioned safety notes must be strictly observed in order to assure the further operational safety of the unit. The operator has to make sure that all equipment connected to the transmitter meet the applicable regulations mentioned in the accident prevention regulation VBG 4. Please contact Rössel Messtechnik GmbH if you require further information regarding this operator manual. 2

Summary The transmitter converts the signal from a thermocouple, resistance thermometer or potentiometer into a standard signal of 4 20 ma. The non-linear characteristic line of the temperature sensor is given, depending on programming, to the output current tension-linear (KAT-T) resp. temperature-linear (KAT-W) or resistance-linear (KAT-P). Installation and Operation Scope of Supply 1 pc. transmitter KAT-W.. / KAT-T.. / KAT-P.. with operator manual Accessories Assembly legs : to fasten the transmitters on a standard 35 mm rail Identification Plate Lettering Type : KAT-W.. for resistance thermometer input KAT-T.. for thermocouple input KAT-P for potentiometer input Input : sensor type Range : measuring range for sensor No. Ex : serial manufacturing number : Explosion proof design to CENELEC standards Observe operator manual! Assembly Installation position : any Attention: When installing the transmitter KAT-... in Ex-type, the rules and regulations on electrical equipment in explosion-hazard areas, the regulations on the erection of electrical equipment in explosion-hazard areas, and the conformity certificate must be observed. Fig. 1: Mounting of KAT-W in connection head (Example: form BKD-SPH) 3

Connection Diagram Fig. 2: Terminal assignments Terminals for sensors 1. 2. 3. 4. power supply Us 5. 1 2 3 1 2 3 1 2 3 1 2 3 + - ϑ ϑ - + 1. KAT-W : resistance thermometer or resistance measurement in 3-wire technique 2. KAT-W : resistance thermometer or resistance measurement in 2-wire technique 3. KAT-T : thermocouple 4. KAT-P : potentiometer input only in 2-wire technique 5. power supply / output signal Operation Attention The unit must never be opened, as in that case proper functioning can no longer be guaranteed. Secure separation of contact-endangered electric circuits is only guaranteed if the connected equipment meets the requirements of norm VDE 0106 T.101 (basic requirements for secure separation). For spurious rejection and safety it is necessary to lay the supply cable separate from the contact-endangered electric circuits. Should this not be possible an additional insulation must be made. If grounding of intrinsically safe circuits to balance potential is needed from a measuring-technical point of view, it must be done at one point only. If an instrument with a certified intrinsically safe electrical circuit is connected to a KAT- transmitter, the intrinsic safety of the interconnection has to be documented according to VDE 0165/2.91. The maximum values shown in the conformity certificate must be observed! 4

Installation: 1. Open the cover or connection head. 2. Connect sensor and power supply. 3. Close cover or connection head. 4. Switch-on power supply. 5. Check functioning of transmitter. Load:measuring,instruments, recorder,... Power supply unit - + * Sensor input Sensor or simulator Important Note The minimum supply voltage at the terminals of the transmitter (see data sheet) must be ensured at all times. For load calculation always take into consideration the highest power consumption (see data sheet). Maintenance Attention! If any work has been carried out on an explosion-protected instrument by non-trained persons and by persons not authorized by the manufacturer, these instruments must be examined by an expert prior to renewed operation. This is not necessary if the work has been carried out by personel authorized by the manufacturer. Before operating the instrument safety measures regarding explosion protection must be carried out on the instruments and must be strictly adhered to! It must be assumed that hazard-free operation is no longer possible - if the transmitter shows visible damages; - if the transmitter does not work; - after longer storage under unfavourable conditions; - after tough conditions during transport. In these case the instrument is no longer safe to operate. It must immediately be taken out of service and be marked accordingly. The defective instrument should be sealed to avoid inadvertent use. 5

Technical Data KAT-W... Resistance thermometers KAT-P.. Potentiometer resistance 6 KAT-T.. Thermocouples Sensor input 2- or 3-wire technique 2-wire technique Cool joint compensation Internally : automatic Reference temperature 0 C ± 0.5 K Cool joint ± 0.2 K / 10 K temperature drift Measuring range 18.5 Ω (-200 C) 0 Ω -15 mv lower limit Measuring range 391 Ω (850 C) 50 kω 75 mv upper limit Minimum range 20 K 10 Ω 2 mv Sensors Pt100 Potentiometer, resistor DIN IEC standardized characteristic lines: type K, J, N, T, E, R, S,B DIN 43710: type L ASTM: W, W3, W5 Measuring deviation incl. linearity error 0.2 % of range; min. 0.1 Ω 0.2 % of range; min. 10 µv Measuring current 1 ma depending on measuring range < 125 na Sensor failsafe 23 ma (2-3, open) wire failsafe (1-2, open) 3 ma --- Short circuit at 3 ma Sensor ambient (2-3) temperature. Output current constant, dependent on measuring range Output current 4 20 ma, upscale characteristic temperature-linear resistance-linear voltage-linear Current limit Permitted load Influence of temperature drift on lower range limit Influence of temperature drift on measuring range Linearity error Calibration error Long term drift 40mA during operation Us 12 V la max = max.. permi RB = la max Us = supply voltage < 0.15 % / 10 K of range 1 < 0.1 C / 10 K < 0.15 % / 10 K of range 1 < 0.2 Ω / 10 K ssible ouput current < 0.2 % / 10 K of range 1 < 30 µv / 10 K < 0.15 % / 10 K of range < 0.2 % / 10 K of range 0.1 % of range 0.1 % of range 0.15 % of range Supply voltage 2 12.0 36.0 VDC ; 12.0 28.0 VDC for Ex 2 Influence on the <0.005 % / V of range output signal 1) The higher value applies 2) Observe conformity certificate for Ex-type

Electro-Magnetic Compatibility of Series KAT test sequence Applicability Influence* Standard Burst on power 1 kv < 1 % EN61000-4-4 supply, signal and data conductor Emitted HF field : 80 MHz 500 MHz 500 MHz... 1 GHz 10 V/m 3 V/m < 1 % EN61000-4-3 Electro-static discharge: Contact discharge Discharge in air Electro-magnetic field under wire dependant launching 150 khz 80 MHz 4 kv 8 kv B B EN61000-4-2 10 V < 1 % EN61000-4-6 Values given are in relation to upper range limit Common Data Ambient temperature Transport and storage temperature Relative humidity Electrical connections Housing, colour Dimensions Weight Protection type: standard design special design -40 C +85 C -40 C +100 C 95 % without condensation Screw connectors for cables with max. 2.5 mm2 wire cross section Polyamide PA6.6, black Ø = 43 mm, height = 20 mm 30 grams IP20 for mounting in housing with min. IP20 IP20 without additional housing 7

Explosion Protection KAT-W / KAT-P KAT-T.. Conformity certificate TÜV 01 ATEX 1710 In preparation Ignition protection type Intrinsic safety II 2 (1)G EEx ia IIC T6 Ambient temperature T1 T4 + 90 C T5 + 60 C T6 + 45 C Assembly Inside or outside the explosion-hazard area Electric supply circuit in II 2(1) G EEx ia IIC T6 ignition protection type intrinsic safety Max. values electric supply circuit Inner capacity / inductivity Ui = 28 V; li = 100 ma; Pi = 670 mw Ci = 10.3 nf; Li = 140 µh Max. values sensor electric Uo = 28 V; lo = 6.5 ma; circuit Max. permissibile outer EEx ia IIC Capacity / inductivity EEx ib IIC Po = 45.5 mw Co = 39 nf; Lo = 2 mh Co = 59 nf; Lo = 50 mh Inner capacity/inductivity Ci = 10.3 nf; Li = 36 µh Fault finding and service Fault description Possibile causes / remedies No output current - wrong pin assignment of the power supply - interrupted power supply line Output current constant at one value - too low power supply at the transmitter input terminals - defective sensor - simulator connected to input terminals Measured value does not match real value and/or output current does not match sensor signal - Sensor or feeler break, sensor short circuit - wrongly connected sensor, check polarity in the case of thermocouples, check wiring and line resistance in the case of resistance thermometers/potentiometers - contamination of connecting cables and/or pin connectors - power supply not inside specification Floating output signal - too high noise level on sensor side - insufficient or faulty grounding - power supply not inside specification 8

The transmitter KAT-W / KAT-T.. / KAT-P is designed in such a way that no maintenance is necessary. In the case of a malfunction a possible cause can be derived from the above indicated symptoms. Basically the power supply of the transmitter and all connected components should always be checked in a malfunction. In addition the sensor and its signal path should be checked. To check the functioning of the transmitter the sensor signal can be preset by a suitable simulator, and then the output signal can be measured. Packing If the transmitter is sent without its original packing, the unit must be sufficiently protected against shocks with air cushion film, foamed plastic or corrugated board. The thickness of the protection must be adapted to the type of packing, the mode of transport and the weight of the transmitter. Stickers Caution-Fragile and Caution-Sensitive Electronic Equipment should be put on the outside of the box. If the transmitter may be subjected during transport to high air humidity or even sea water, it must be shrink-wrapped in an air-tight film, inside of which a suitable desiccant should be placed. The quantity of the desiccant to be put inside the packing volume must correspond to the expected transport duration (at least 3 months). Validity: 07/02 Technical improvements reserved. Reproduction, copying and translation, even partially are not permitted unless authorized by Rössel Messtechnik Gmb 9