A New Control Method for Series Active Filter in Distribution System using Unit Vector Control

Similar documents
ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

Harmonics Elimination Using Shunt Active Filter

A Time Domain Reference-Algorithm for Shunt Active Power Filters

HYSTERESIS CONTROL FOR CURRENT HARMONICS SUPPRESSION USING SHUNT ACTIVE FILTER. Rajesh Kr. Ahuja

Harmonics Reduction using 4-Leg Shunt Active Power Filters

2020 P a g e. Figure.2: Line diagram of series active power filter.

PERFORMANCE ANALYSIS OF SVPWM AND FUZZY CONTROLLED HYBRID ACTIVE POWER FILTER

A Simple Control Algorithm for Three-Phase Shunt Active Power Filter for Reactive Power and Current Harmonic Compensation

Sinusoidal Current Control based Shunt Active Power Filter for Current Harmonics Reduction

A Novel Control Strategy of Shunt Active Filters

Zero-Sequence Harmonics Current Minimization Using Zero-Blocking Reactor and Zig-Zag Transformer

Control Of Shunt Active Filter Based On Instantaneous Power Theory

Improvement of the Electric Power Quality Using Series Active and Shunt Passive Filters P. Salmerón and S. P. Litrán

Analysis of Hybrid Power Conditioner in Three-Phase Four-Wire Distribution Power Systems for Suppressing Harmonics and Neutral-Line Current

SHUNT COMPENSATOR USED FOR POWER QUALITY IMPROVEMENT

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Enhancement of Power Quality using active power filter in a Medium-Voltage Distribution Network switching loads

Indirect Current Control of LCL Based Shunt Active Power Filter

A THREE PHASE SHUNT ACTIVE POWER FILTER FOR HARMONICS REDUCTION

Power Quality Improvement using Shunt Passive Filter

Simulation Study of PWM Techniques for Voltage Source Converters

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Improvement of Power Quality Using a Hybrid Interline UPQC

MODELLING & SIMULATION OF ACTIVE SHUNT FILTER FOR COMPENSATION OF SYSTEM HARMONICS

Implementation of SRF based Multilevel Shunt Active Filter for Harmonic Control

Comparison of Three leg and Four Leg VSC DSTATCOM for Power Quality Assessment

Literature Review for Shunt Active Power Filters

IJSTE - International Journal of Science Technology & Engineering Volume 2 Issue 12 June 2016 ISSN (online): X

Assessment of Different Compensation Strategies in Hybrid Active Power Filters

Review on Shunt Active Power Filter for Three Phase Four Wire System

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

Three Phase PFC and Harmonic Mitigation Using Buck Boost Converter Topology

Simulation of Three Phase Cascaded H Bridge Inverter for Power Conditioning Using Solar Photovoltaic System

Hybrid Active Power Filters for Reactive Power Compensation with Adaptive DC-Link Voltage Control

Performance Analysis of Three-Phase Four-Leg Voltage Source Converter

INSTANTANEOUS POWER CONTROL OF D-STATCOM FOR ENHANCEMENT OF THE STEADY-STATE PERFORMANCE

Improvement of Power Quality Using Hybrid Active Power Filter in Three- Phase Three- Wire System Applied to Induction Drive

Synchronous Reference Frame Control Algorithm Based Four -Leg Inverter DSTATCOM For Power Quality Improvement

PI-VPI Based Current Control Strategy to Improve the Performance of Shunt Active Power Filter

Design of Unified Power Quality Conditioner (UPQC) Connected To Three Phase Four Wire System

Universal power quality conditioner

HARMONIC ELIMINATION IN THREE PHASE SYSTEM BY MEANS OF A SHUNT ACTIVE FILTER

A NOVEL TCHNOLOGY FOR HARMONICS AND UNBALANCE COMPENSATION IN ELECTRIC TRACTION SYSTEM USING DIRECT POWER CONTROL METHOD

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

A MATLAB-SIMULINK APPROACH TO SHUNT ACTIVE POWER FILTERS

Key-Words: - NARX Neural Network; Nonlinear Loads; Shunt Active Power Filter; Instantaneous Reactive Power Algorithm

A Novel FPGA based PWM Active Power Filter for Harmonics Elimination in Power System

Improving the Power Quality by Four Leg VSI

Improving Passive Filter Compensation Performance With Active Techniques

Voltage Sensorless Control Algorithm for Power Quality Improvement in Distribution Network

Modeling and Simulation of Matrix Converter Using Space Vector PWM Technique

PERFORMANCE EVALUATION OF THREE PHASE SCALAR CONTROLLED PWM RECTIFIER USING DIFFERENT CARRIER AND MODULATING SIGNAL

CHAPTER 5 POWER QUALITY IMPROVEMENT BY USING POWER ACTIVE FILTERS

Performance of Indirectly Controlled STATCOM with IEEE 30-bus System

CURRENT HARMONICS REDUCTION IN 3 PHASES 4 WIRE SYSTEM USING HYBRID FILTERS R.Saravanakumar 1#, S.Amritha 2#

A Review on Simulation and Implementation of Thyristor controlled reactor and Shunt Hybrid Power Filter

Unit Vector Theory based Unified Power Quality Conditioner for Power Quality Improvement

Power Quality Improvement in Fourteen Bus System using UPQC

Modified Three-Phase Four-Wire UPQC Topology with Reduced DC-Link Voltage Rating

RECENTLY, the harmonics current in a power grid can

SIMULATION AND COMPARISON OF SPWM AND SVPWM CONTROL FOR TWO LEVEL UPQC

Enhancement of Power Quality Using Advanced Series Active Power Filters

Three Phase Active Shunt Power Filter with Simple Control in PSIM Simulation

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

ISSN Vol.03,Issue.07, August-2015, Pages:

Power Quality Improvement of Unified Power Quality Conditioner Using Reference Signal Generation Method

Size Selection Of Energy Storing Elements For A Cascade Multilevel Inverter STATCOM

Unbalanced Variable Nonlinear Load Compensation Using Multiple Shunt Active Filters

Power Quality improvement of a three phase four wire system using UPQC

Current Control Technique for Three Phase Shunt Active Power Filter by Using Adaptive Hysteresis Current Controller

Shunt active filter algorithms for a three phase system fed to adjustable speed drive

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

SHUNT ACTIVE POWER FILTER

Available online at ScienceDirect. Procedia Technology 21 (2015 ) SMART GRID Technologies, August 6-8, 2015

Power Quality Improvement using Active shunt Power filter using PI Controller

Cascaded Multilevel Inverter based Active Filter for Power Line Conditioners using Instantaneous mitigates

DESIGN AND IMPLEMENTATION OF THREE PHASE SHUNT APF CURRENT CONTROLLER WITH ANN TECHNIQUE

ISSN Vol.03,Issue.42 November-2014, Pages:

ISSN: Page 20. International Journal of Engineering Trends and Technology- Volume2Issue3-2011

Efficient Hybrid Shunt Active Power Filter for Improvement of Power Factor and Harmonic Suppression using MATLAB

ANALYSIS OF SYNCHRONOUS-REFERENCE-FRAME-BASED CONTROL METHOD FOR UPQC UNDER UNBALANCED AND DISTORTED LOAD CONDITIONS Salava Nagaraju* 1

Mitigation of Line Current Harmonics Using Shunt Active Filter With Instantaneous Real and Reactive Power Theory

IMPROVING EFFICIENCY OF ACTIVE POWER FILTER FOR RENEWABLE POWER GENERATION SYSTEMS BY USING PREDICTIVE CONTROL METHOD AND FUZZY LOGIC CONTROL METHOD

Scientific Journal Impact Factor: (ISRA), Impact Factor: 1.852

Design and Simulation of Three Phase Shunt Active Power Filter Using SRF Theory

Modeling & Simulation of Micro Grid Distribution System to reduce Harmonics Using Active Power Filters and PI controllers

MODELLING AND SIMULATION OF DIODE CLAMP MULTILEVEL INVERTER FED THREE PHASE INDUCTION MOTOR FOR CMV ANALYSIS USING FILTER

Analysis of Reference Current Generation for Shunt Active Power Filter Using SRF Algorithm to Compensate Harmonic Current

Bidirectional Ac/Dc Converter with Reduced Switching Losses using Feed Forward Control

International Journal of Emerging Researches in Engineering Science and Technology, Volume 1, Issue 2, December 14

Kanuru; Krishna (Dt); A.P, India. DOI: / Page. 1 G. Aruna Jyothi, 2 DR. P. V. R. L.

Implementation of D-STACTOM for Improvement of Power Quality in Radial Distribution System

Design of SVPWM Based Inverter for Mitigation of Harmonics in Power System

Simulation Results of a Shunt Active Power Filter with Control Based on p-q Theory

POWER QUALITY IMPROVEMENT BY USING ACTIVE POWER FILTERS

Three Phase Active Power Filter Based on Current Controlled Voltage Source Inverter

Power Factor Improvement Using a Three Phase Shunt Active Power Filter

Multi-Pulse Voltage Source Converter Statcom For Voltage Flicker Mitigation

ABSTRACT I. INTRODUCTION

Design of Shunt Active Power Filter by using An Advanced Current Control Strategy

Transcription:

A New Control Method for Series Active Filter in Distribution System using Unit Vector Control T.Guna Sekar Assistant Professor Kongu Engineering College Erode-638052, India R. Anita, PhD. Professor & Head Department of EEE IRTT, Erode-638 316 R.Chandrasekar M.E. (Applied Electronics) Kongu Engineering College Erode-638052, India ABSTRACT The Novel control strategy for reduction of harmonics in three-phase four-wire distribution systems was presented in this paper. The single phase loads connected to 3P4W distribution system causes an unbalance current which results in the flow of zero sequence harmonic component in the neutral conductor of the distribution system. This effect leads to over-burden on neutral conductor and also de-rates the distribution transformer. A Unit Vector Control (UVC) based series active filter was proposed to reduce the harmonic currents in the neutral conductor during both balanced and unbalanced loading conditions. In this method a series active filter is placed in series with the neutral conductor. The proposed method reduces the harmonics, improves the power factor and balances the asymmetrical loads. The detailed analysis of the proposed method based on unit vector control was presented. The simulation results based on MATLAB/SIMULINK were performed to verify the effectiveness of the proposed method. The results are found to be quite satisfactory in mitigating harmonics in the neutral current. Keywords Power Quality, Total Harmonic Distortion (THD), Active Power Filters, Neutral Conductor 1. INTRODUCTION Contamination of the power supply due to harmonics is a very harmful and serious problem in Electric Power System. With increase in the advancement of information technology, the large number of computers and power electronic devices are connected to the distribution systems. Electric power is distributed through a three-phase, four-wire system in many industrial and commercial sectors. Most of the loads in the distribution system are connected to any one of the phase of three-phase four- wire distribution system, which leads to the unbalanced loading conditions. Due to this, a zero sequence harmonic current and unbalance current flows through the neutral conductor [1]. The power supplies consists of rectifier with DC smoothening capacitors may also leads to excessive current harmonics in the neutral [2]. These excessive harmonic currents causes the problems viz; over loading of the neutral conductor, increases the size of the neutral conductor, de-rating of the distribution transformer and overheating of the distribution transformer. Survey results across computer sites in U.S. shows that 22.6% of the sites have neutral currents exceeding the full-load phase currents [3]. Almost 95% of the harmonic current in the neutral are zero sequence component (3 rd order harmonics). In order to overcome this, various techniques like passive filters, Zigzag transformer connections, active filter techniques were proposed. In order to attenuate these harmonic current in the distribution system, traditionally a passive filter was designed [4] [5] which was connected across the non-linear load. But this compensation leads to some of the drawbacks [6] like occurrence of series and parallel resonance which causes an incomplete potential. Also an effectiveness of the passive filter depends on the network impedance as well. [7] Proposed a zig-zag connection of transformer for harmonic suppression in the neutral conductor. This scheme can able to attenuate harmonics but leads to system complexity and increases the losses due to transformer windings. Due to advancement in the technology, active power filters have become most habitual compensation methods. Shunt active power filters for three-phase three-wire and three-phase four-wire distribution systems have been presented [8] [12]. This filter was widely used in transmission systems but has fewer effects on the distribution systems. In [13], author itself mentioned that shunt active filter compensation was not perfect solution. Improved solution to harmonic problem uses a hybrid active filter, which consists of shunt active and passive filter or series active and passive filters [14] [16]. Recently, in order to improve the power quality and to correct the unbalance voltage in the distribution system, a series active power filter is connected in series with the neutral conductor were proposed [17] [19]. The above mentioned methods used various controllers like Instantaneous reactive power theory [20], Synchronous Reference Frame theory [21] and Sliding Mode control theory [19]. All these theories were able to extract and mitigate the harmonics present in the neutral only under the balanced load conditions. In this paper, a novel control strategy based on Unit Vector Control is presented. The proposed method uses only an active power filter in series with the neutral conductor. It performs several functions simultaneously viz; current harmonics, load unbalance and neutral current cancellation. The rating of the proposed series active filter is less than 10% of the harmonic producing loads. The simulation results for parallel RC load with rectifier circuit are shown for both balanced and unbalanced conditions. In this paper section (2) discusses proposed system configuration, section (3) discusses about the Unit vector controller for series active filter, section (4) discusses about simulation results, followed by the conclusion in section (5). 8

2. PROPOSED SYSTEM CONFIGURATION The block diagram of the proposed method for threephase four-wire distribution system is shown in Fig 1 and the proposed system configuration is shown in Fig 3. UNIT VECTOR CONTROLLER FOR SERIES ACTIVE FILTER The controller based on Unit Vector Control is shown in Fig 3. Due to various single phase loads connected to three-phase four-wire distribution system, the unbalance current flows through the neutral conductor. This neutral current (I n ) contains both fundamental component (I nf ) and the harmonic component (I nh ). Fig 1. Block diagram of the proposed method Fig 3 Controller for Series active Filter The fundamental component is due to the unbalanced loading and the harmonic component is due to the non-linear loads in the system. The neutral current is multiplied by both cos function (cosᾠt) and sin function (sinᾠt) to extract the fundamental components from the neutral current. Then the component is passed through the low pass filter which extracts the DC component. The extracted DC component is converted in to ac component by multiplying again with cosᾠt and sinᾠt respectively. Fig 2. System configuration of the proposed method In the block diagram, I a, I b, I c and In represents a phase currents and the neutral current respectively. The neutral current is sensed and given to the controller. The controller generates the pulse equivalent to the harmonic currents which is given as triggering to the inverter. The inverted injects the harmonic current to the neutral there by harmonics in the neutral conductor gets suppressed. The series active filter is placed in the neutral conductor of the three phase four wire distribution system. It consists of 2-leg IGBT based inverter and a DC charging capacitor. The series active filter is connected to the neutral conductor through the linking capacitor (C f) and inductor (L f). In the distribution system, the single phase loads are connected between any one of the three lines and a neutral as shown in Fig 2. The each phase of three phases is connected to a rectifier with RC load. The active filter system consists of a two-leg inverter circuit with DC charging capacitor. Then the ac component of neutral current fundamental (I nf ) is extracted and multiplied with the constant for normalization. This component is subtracted with the neutral current I n, to obtain the harmonic component (I nh ) of the neutral current. Then the component is multiplied with the inverter gain (K h ) to get the voltage signal (V inv ) and compared to the triangular carrier to generate the PWM gating pulse through relational operator. V inv =K h I n I n = -(V La +V Lb +V Lc )/ (Z s +Z L +3Z n +3K h ), K h is the gain of the series active filter inverter. The gating pulse is applied to the series active filter inverter circuit to inject the corresponding harmonic component in the neutral conductor. Thus the injected harmonic current and the neutral harmonic current gets cancelled there by over burden on neutral conductor can be reduced. 4. SIMULATION RESULTS To validate the analysis and the effectiveness of the proposed neural network based controller for series active filter, the simulation is carried out using 9

MATLAB/SIMULINK. The following are the system parameters used for the simulations. V LN = 120V (Line to neutral voltage), Leakage reactance of the distribution transformer = 0.35mH, Output filter L f = 0.2mH and C f = 1µF, and System frequency = 50Hz. The simulations are carried out under two conditions; a) balanced loading b) unbalanced loading. 4.1 Balanced condition The proposed controller is simulated under balanced loading conditions. The load values are given as R a, R b, R c = 25Ω and C a, C b, C c = 1500µF. Fig 7 shows the simulation results for phase a, b, c and neutral current without series active filter. Fig 5 Waveform of phase and neutral currents without filter Fig 8 FFT analysis of phase currents (a, b and c) and neutral current before active filter compensation The simulation result shows that harmonic content flows through the neutral and phase conductors. The waveform of the phase currents are distorted and the neutral current also carries large amount of current due to non-linear loads. The FFT analysis of the phase and neutral currents without filter are shown in fig 8. It shows that the triplen harmonics especially 3 rd order harmonics are more predominant in the phases and the neutral conductors. The magnitude of 3 rd harmonic in the neutral is very high before the compensation of series active filter. The simulation results for phase a, b, c and neutral current after compensation of series active filter is shown in fig 9. The wave form of the neutral is nearly sinusoidal and its magnitude also reduced to large extent. Due to the effect of placing series active filter in the neutral conductor, the harmonic component present in the phase conductor also reduced and the waveform becomes nearly sinusoidal. Fig 9 Simulation results for phases and neutral with filter 10

R a = 15Ω, R b = 25Ω, R c = 50Ω and C a, C b, C c = 1000µF with the diode rectifier loads. The simulation results for phase a, b, c and neutral current without series active filter for unbalanced loading conditions was shown in Fig 4. The simulation result shows that unbalanced current was distributed over the neutral conductor of the distribution system. Due to the presence of non-linearity and unbalance loads, harmonic component flows through the neutral and phase conductors as well. The FFT analysis for unbalanced conditions of phase and neutral conductors were shown in Fig 5. Due to the unbalanced loading and non linear loading the harmonic current in the neutral current was significantly high. The THD values of phase conductors and the neutral conductors were very high. The simulation result under unbalanced condition after compensation was shown in Fig 6. Fig 4 Simulation results for phase and neutral current without filter Fig 10 FFT analysis of phase currents (a, b and c) and neutral current after active filter compensation Simulation Results under Unbalanced condition The proposed controller was simulated under unbalanced loading conditions. The load values were given as 11

Fig 5 FFT analysis of phase currents (a, b and c) and neutral current for unbalanced before active filter compensation In the waveform the harmonic contents were reduced much and it appears as sinusoidal. The harmonic content in the neutral were almost eliminated and it shown as purely sinusoidal. The FFT analysis for unbalanced system was shown in Fig 7. Fig 6 Simulation results for phase and neutral current with filter Fig 7 FFT analysis of phase currents (a, b and c) and neutral current for unbalanced before active filter compensation. 12

TABLE I - THD VALUES IN % FOR BALANCED AND UNBALANCED SYSTEM Methods Without Controller With Unit Vector controller Methods Without Controller Balanced System I a I b I c I n 94.35 94.35 94.35 138.3 16.81 17.92 16.68 5.69 Unbalanced System I a I b I c I n 29.49 43.99 56.35 148.3 With Unit Vector controller 10.29 15 17.321 4.9 5. CONCLUSION The Novel control techniques based on Unit Vector Control for harmonics compensation in distribution system using series active filter was presented. The active filter inverter acts as a high impedance for the current harmonics in the neutral conductor. After compensation of series active filter in the neutral conductor, it was found that the harmonic content was much suppressed in both phase and neutral conductors. Therefore, the unity source power factor at the positive sequence fundamental frequency was achieved. The control scheme was presented for both balanced and unbalanced loading conditions for rectifier loads. The proposed system uses only one active filter, so it avoids the series/parallel resonance problem and complexity of the system was less. Simulation results and the THD values showed the effectiveness of the proposed method in the threephase four-wire distribution 6. REFERENCES [1] T. M. Gruzs, A survey of neutral currents in threephase computer power systems, IEEE Transactions on Industry Applications, vol.26, no. 4, pp. 719-725, July/August 1990. [2] P.N.Enjeti, W.Shireen, P.Packebush and I.J.Pitel, Ananlsis and Design of a new active power filter to cancel neutral current harmonics in three-phase four-wire electric distribution systems, IEEE Transaction on Industrial Applicatiion, vol 30, pp. 1565-1572, Nov/Dec. 1994 [3] P. T. Cheng, Y. F. Huang, and C. C. Hou, A new harmonic suppression scheme for three-phase fourwire distribution systems, in Proc. IEEE APEC, vol. 2, 2001, pp. 1287 1293. [4] H. L. Ginn III and L. S. Czarnecki, An optimizationbased method for selection of resonant harmonic filter branch parameters, IEEE Transaction on Power Delivery., vol. 21, no. 3, pp. 1445 1451, Jul. 2006 [5] J. A. Pomilio and S. M. Deckmann, Characterization and compensation of harmonics and reactive power of residential and commercial loads, IEEE Transaction on Power Delivery, vol. 22, no. 2, pp. 1049 1055, Apr. 2007. [6] J. C. Das, Passive Filters Potentialities and Limitations, IEEE Transaction on Industry Applications, vol. 40, no. 1, January/Febuary 2004 [7] Hurng-Liahng Jou, Jinn-Chang Wu, Kuen-Der Wu, Wen- Jung Chiang, and Yi-Hsun Chen, Analysis of Zig-Zag Transformer Applying in the Three-Phase Four-Wire Distribution Power System, IEEE Transaction on Power Delivery, vol. 20, no. 2, April 2005 [8] M. Aredes, and E. H. Watanabe, New Control Algorithms for Series and Shunt Three-phase Four-Wire Active Power Filters," IEEE Transactions on Power Delivery, vol. 10, no. 3, pp. 1649-1656 (1995) [9] M. Ishihara, S. Mori, G. Nakagawa, and M. Nishitoba, Development of active filter for three-phase four-wire system", Rec. SPC meeting of IEEJ, no. SPC-96-128, pp. 63-70 (1996) (in Japanese) [10] M. Aredes, J. Hafner, and K. Heumann, Three-phase Four-wire Shunt active Filter Control Strategies," IEEE Transactions on Power Electronics, vol. 12, no. 2, pp. 311-318 (1997) [11] J. S. Lai, and T. S. Key, Effectiveness of harmonic mitigation equipment for commercial buildings," IEEE Transactions on Industry Applications, vol. 33, no. 4, pp. 1104-1110 (1997) [12] P. Cheng, Y. Huang, and C. Hou, Design of a neutral harmonic mitigator for three-phase four-wire distribution system," IEEE/IAS Annual Meeting, vol. 1, pp. 164-171 (2001) [13] Conor A. Quinn, Ned Mohan, A Four-Wire, Current- Controlled Converter Provides Harmonic Neutralization in Three-phase, Four- Wire Systems, in Proc. IEEE APEC, vol. 1, 1993 [14] Z. Wang, Q. Wang, W. Yao, and J. Liu, A series active power filter Adopting hybrid control approach, IEEE Transaction on Power Electronics, vol. 16, no. 3, pp. 301 310, May 2001 [15] F. Z. Peng, H. Akagi, and A. Nabae, A new approach to harmonic compensation in power systems-a combined system of shunt passive and series active filters, IEEE Transaction on Industrial Applications, vol. 26, no. 6, pp. 983 990, Nov./Dec. 1990. [16] A. Luo, Z. Shuai, W. Zhu, R. Fan, and C. Tu, Development of hybrid active power filter based on the adaptive fuzzy dividing frequency-control method, IEEE Transaction on Power Delivery, vol. 24, no. 1, pp. 424 432, Jan. 2009. 13

[17] Tadashi Fukami, Toshinari Onchi, Nobuyuki Naoe,, and Ryoichi Hanaoka, Compensation for Neutral Current Harmonics in a Three- Phase Four-Wire System by a Synchronous Machine, IEEE Transaction on Industry Applications, vol. 38,no. 5, September/October 2002 [18] Shigenori Inoue, Toshihisa Shimizu, and Keiji Wada, Control Methods and Compensation Characteristics of a Series Active Filter for a Neutral Conductor, IEEE Transaction on Industry Applications, vol. 54, no. 1, Febuary 2007 [19] T.Chatchanayuenyong, T. Khamriang, A. Kantarawichai, A Fast Series Active Filter using Sliding Mode Control to Correct and Regulate Unbalance Voltage in Three- Phase System, American Journal of Engineering and Applied Sciences 2 (2): 393-398, 2009 [20] F. Z. Peng and J. S. Lai, Generalized instantaneous reactive power theory for three phase power system, IEEE Transaction on Instrumentation and Measurement, vol. 45, no. 1, pp. 293 297, Feb 1996. [21] S. Bhattacharya and D. Divan, Synchronous frame based controller implementation for a hybrid series active filter system, IEEE/IAS Conference Proceedings, 1995, pp. 2531-2540 14