Frequently Asked Question on Isolated Power Supply(IPS)

Similar documents
Starkstrom s Isolated Power Supply System

Healthcare Isolation Power Systems. Presented by: David Knecht

TN, TT & IT Earthing Arrangements

National Marine Manufacturers Association Compliance Specialist Examination A.C. Electrical (2018 Model Year) ABYC E-11 Supplement 56

2.7. IT system floor-standing distribution cabinet Series -IPS-F/EDS

Industrial and Commercial Power Systems Topic 7 EARTHING

GROUNDED ELECTRICAL POWER DISTRIBUTION. Excerpt from Inverter Charger Series Manual BY: VIJAY SHARMA ENGINEER

ECE 528 Understanding Power Quality

A DUMMIES GUIDE TO GROUND FAULT PROTECTION

Chapter F Protection against electric shocks

ET 51 - Electrician Theory Examination Marking Schedule

Electrical Safety. Principles and examples of safety. History of (electrical) safety. Rules and regulations. Safety in the Hospital

Residual Current Operated Circuit-Breakers (RCCBs)

ELECTRICIAN S THEORY EXAMINATION 20 November 2010 QUESTION AND ANSWER BOOKLET

EASQ ELECTRICAL APPLIANCE SERVICEPERSON (QUALIFIED) MARKING SCHEDULE. SECTION 1 Marks Reference Marking notes Qu 1 A 10 MΩ (2 marks)

Chapter F Protection against electric shocks

SAUDI STANDARD NO. SASO IEC : 2007 SWITCHES FOR HOUSEHOLD AND SIMILAR FIXED ELECTRICAL INSTALLATIONS

SE-502 MANUAL GROUND-FAULT GROUND-CONTINUITY DETECTOR

Options to Improve the MEN System into the 21 st Century

Product Classroom. Introduction. Grounding Systems. TN system. Title. Grounding System Introduction. Date October, 2016.

VARIMETER. Residual current monitor (RCM) Insulation monitoring device (IMD) Insulation fault detection system (EDS) Our experience. Your safety.

USER S MANUAL. 1KSS60400/ ST Edition

INSTRUCTION MANUAL DIGITAL PSC-LOOP TESTER MODEL 4118A KYORITSU ELECTRICAL INSTRUMENTS WORKS,LTD.

A PQ Case Study CS 36 HOSP 14. A Case Study OF Harmonics Mitigation in a Hospital and its Benefits

Dr.Rajaa CH.11. أ.م.د. رجاء سهيل جنم جامعة تكريت كلية طب االسنان

Power Quality Solutions

Low Voltage Products. Enclosed Third Harmonic Filter THF and THF star Enclosed units. Brochure THFS1GB 03_04 1SCC330003C0201

Residual Current Operated Circuit-Breakers (RCCBs)

Grounding System Theory and Practice

2 Grounding of power supply system neutral

PRODUCT SPECIFICATION FOR A 15 AND 75 kva, THREE PHASE MODULAR POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING (Varian)

USER S MANUAL. 3KSS6050/ nd Edition

ELECTRICIAN S THEORY EXAMINATION 17 November 2012 QUESTION AND ANSWER BOOKLET

Chapter 6. WIRING SYSTEMS Safe Electrical Design

Maintenance/Connection/Installation Service life C/O cyclesx1000

Company Directive STANDARD TECHNIQUE : TP21A/2. Relating to Safety Limits for Touch and Step Voltages - Earthing System Design/Assessment

Form-IV. Form of Inspection/Test Report. (Under Regulation 43)

LIFE LINE PRODUCT SPECIFICATION FOR A 1 TO 3 KVA, SINGLE PHASE, POWER DISTRIBUTION SYSTEM WITH REGULATION AND CONDITIONING

TS RES - OUTSTANDING ISSUES

DANGER. DANGER indicates an imminently hazardous situation which, if not avoided, will result in death or serious injury. WARNING

HI-Physix Laboratory, L-83, Sector-1, DSIDC Industrial Area, Bawana, Delhi. Discipline Electronics Testing Issue Date

IEC ED.1 Safety secondary circuits in series circuits General safety requirements. a new draft

Webinar: An Effective Arc Flash Safety Program

FINAL - EST Electrical Service Technician Answer Schedule

Floating Circuits - Protection against electric shock

Protection and safety SQZ3 phase and sequence relay

Distribution systems and protection against indirect contact and earth fault

Title Substation Auxiliary Transformer from Rectifier Transformer Secondary. Reference Number PDS 01 (RIC Standard: EP SP)

Why? Why? "Fatal Four Bureau of Labor Statistics. Monitoring and Metering for Electrical Safety. Shock Fire Explosion Production

2.2 American National Standards Institute Corporation and its applicable standards C39.1, C80.1, C89, C84.1.

2 line filters for converters and power electronics

Arrester Disconnector

ELECTRICIAN S THEORY EXAMINATION 15 November 2014 QUESTION AND ANSWER BOOKLET

Summary of the Impacts of Grounding on System Protection

3 line sine wave EMC output filters for converters and power electronics

high RESISTANCE GROUNDING SYSTEM the power to protect www. ElectricalPartManuals. com Instruction Manual C-102

Protective earthing, protective conductor and automatic disconnection in case of a fault (Fault protection)

Functional Range. IWE - Earth Fault Relay. C&S Protection & Control Ltd.

INTERNATIONAL STANDARD

Licensed Electricians Practical Assessment (LEP)

NATIONAL RULES FOR ELECTRICAL INSTALLATIONS. Fourth Edition. Extracts from Amendment No.1: June 2011

Instruction Manual for Digital Grounding Resistance Meter

To Float or Not to Float? Analysis of a floating vs. grounded output Associated Power Technologies

Electrical network management. Vigilohm. The IT earthing system to improve electrical network availability. Catalogue 2013

FINAL - ET 60 - Electrician Theory Examination Marking Schedule

Grounding for Power Quality

Commercial/Medical. International + Linears

NeuVision 500. Abundant and friendly display interface, multifold ECG display screen:

ULTRA-K Series 600K - he

EPG. by Chris C. Kleronomos

Unit 3 Magnetism...21 Introduction The Natural Magnet Magnetic Polarities Magnetic Compass...21

Earthing of Electrical Devices and Safety

TEST REPORT DIN V VDE V :2006 Automatic disconnecting device

Preface...x Chapter 1 Electrical Fundamentals

Transformer Core for Ground Fault Circuit Interrupter (GFCI) (ELCB Earth leakage circuit breaker)

ET 40 - Electrician Theory Examination Marking Schedule

SINGLE PHASE BUCK & BOOST TRANSFORMERS INSTRUCTION MANUAL

Insulation Monitoring Relays CM range

Medical Safety Approvals (-M versions) Industrial Heavy Duty Terminals. Output Power up to 1500 W. High Power Density - 18W/in 3

ENSURING PUBLIC SAFETY THROUGH PROPER EARTHING IN LOW VOLTAGE NETWORKS

ELECTRICAL SAFETY TESTERS. Wings for Your Projects. APPLICATION NOTE

TABLE OF CONTENT

Chapter Two Review Questions Answer Key

FINAL - IT 30 ELECTRICAL INSPECTOR EXAMINATION ANSWER SCHEDULE. Question 1 Marks Reference Marking notes. (2 marks) EA 2

Used to overcome ventricular fibrillation may be due to coronary occlusion, shock, or abnormalities in blood chemistry

RAISING THE LEVEL OF PROTECTION IN YOUR ORS

A9 R Range Family Code Internal code Poles Code Rating (A) Code Acti 9 (A9) iid R

AC/DC. Monitoring Technique. VARIMETER IMD Insulation monitor RN 5897/300

TOSHIBA International Corp

Arc Flash Analysis and Documentation SOP

returned to your distributor for attention. 14. Do not operate the function switch while the instrument is connected to a circuit.

IEEE Southern Alberta Section, Industrial Applications and Power & Energy Chapter Technical Program. Venue: Operator. Speaker Travel: Stantec

QUESTIONNAIRE for Wind Farm Power Stations only

HO118 Binning Interface User Manual * * Version 02. User Manual. Test & Measurement

CONTENTS. 1. Introduction Generating Stations 9 40

Power Processor - Series 700F 10KVA to 150KVA

1. general. 1.1 electric shock. 1.2 direct and indirect contact. electric shock. indirect contact. direct contact

I P. /dt. di p V S Applications. Standards 1) IEC : 2007; IEC : ) IEC : 2016; IEC : 2017

4-range High voltage insulation resistance tester KEW 3126

CURRENT FUTURE REGULATIONS PROPOSALS

Transcription:

Frequently Asked Question on Isolated Power Supply(IPS) Q: What is an IPS? A: IPS is called as Isolated Power Supply or System and is used in a Hospital to ensure safe power supply to OT Operation Theaters and ICU Intensive Care Units. Q: What does it do? A: IPS protects the patients from electrical shock and ensures availability of power even when there is a fault as it avoids the tripping of breakers or Earth Leakage Circuit breakers (ELCB s) and ensures continuity of power to life saving equipment s. Q: What are the impacts of Leakage current in human body? A: Even small currents flowing through the human body can cause electric shock and put the patient s life and health at risk Perception ~1 ma Suffocation 35 ma Ventricular fibrillation 100 ma Rapid burning & tissue damage +200 ma The hazardous levels of current for many patients in a Hospital are much smaller than for normal healthy human beings. The hazard level for patients seems to vary between 10 microamperes (μa) and 180 μa. This is only a fraction of the level hazardous to normal healthy human beings. The most susceptible patient is the one exposed to externalized conductors, diagnostic catheters, or other electric contact to or near the heart. Surgical techniques bypass the patient s body resistance and expose the patient to electrical current from surrounding equipment. The highest risk is to patients undergoing surgery within the thoracic cavity. Increased use of such equipment as heart monitors, dye injectors, and cardiac catheters increases the threat of electrocution when used within the circulatory system. Infants are more susceptible to electric shock because of their smaller mass, and thus lower body resistance. The combination of factors for a patient like lowered body resistance, more electrical equipment, and conductors such as blood, urine, saline, and water makes it a challenge to increase electrical safety in a Hospital. Q: How does an IPS work? A: Typically we follow an TNS earthing System where neutral is grounded and the earth and neutral wire is different as shown in the below (Figure 1). As the neutral has an direct connection to earth, this path acts a least impedance path for the fault current to flow through. In this system when there is fault between phase & earth or neutral & earth, the leakage current will be limited based on impedance of the person who is in contact with the fault. The fault or the leakage current can be calculated based on the below formula Voltage Fault Current = ---------------------------------------------------------------Impedance of person + Impedance of the fault path 230V = ------------------------ = 230 ma 1KW + 0 W

Figure 1 TNS Earthing System The fault of 230mA is too dangerous for human body and could result in the death of the person. In order to provide safety to person, we have to limit the fault current. The best possible way to limit the fault current is to adapt an isolated earthing system (IT Earthing System) as shown below Figure 2 IT Earthing System As seen above, the IT earthing system has no connection of neutral to earth and the output neutral is floating. As there is no physical connection between the neutral & earth, this system acts as high impedance path for the fault current and typically at 1,500 kw The fault or the leakage current can be calculated based on the below formula Fault Current = Voltage ---------------------------------------------------------------Impedance of person + Impedance of the fault path

= 230V ------------------------ = 0.15 ma 1KW + 1500KW The system of IT earthing system will be used in an IPS, Isolated power supply to limit the leakage current and to protect the person who are in contact with the fault. The IPS provides an isolated ungrounded system and must also have a method to check the system integrity. This function is provided by an insulation monitoring device that continuously checks the resistance (impedance) of the total isolated ungrounded system to ground. The insulation monitor must respond audibly and visibly when the impedance of the system degrades to the extent that 5 ma of current will flow through either conductor of the system to ground in a zero impedance fault. An activated alarm does not mean hazardous current is flowing. It only predicts that 5 ma of current could flow from one conductor of the isolated system to ground if a path for the current is provided. This requires a second fault or electric failure to be present in the system before a true hazardous condition exists. The alarm only warns that the potential problem must be corrected as soon as possible but there is no need to interrupt procedures being conducted when the alarm sounds. Q: Is there any standard which refers to the usage of IPS? A: Yes, IEC 60364-7-710(Electrical installations of buildings requirements of special installations or locations Medical locations refer to the usage of medical IT system based on classification of locations. The classification of locations is as follows: Group 0: medical locations without applied parts Group 1: medical locations where applied parts are used externally or invasively to any part of the body, except for the locations described in group 2 Group 2: medical locations where applied parts are used in applications such as intra cardiac procedures, operating theatres and vital treatments where discontinuity of the supply can cause danger to life Q: What is the application area of IPS as per the classification of IEC? A: As per IEC 60364-7-710, all group 2 locations like operation theatre, heart catheterization room, ICU, neonatal ICU etc.. requires a medical IT System which is simply called as IPS. Q: Do we have any Indian standard mandating the requirement of IPS? A: The hospital locations has been categorized as P0/1-P7 in National Electric code, Part-3, Section-4: Medical establishments. For categories of P5 installation, The National electric code has stated that it is recommended to have a medical IT system or IPS for such locations.

Extract of Table 1 Safety Provisions (Clause 6.1.1) from National electric code is as below Provisions P5 P6 Principal Requirements Continuity of the mains supply maintained in case of a first insulation fault to earth and currents to earth restricted Reduction of fault currents and touch voltages in case of a fault in the basic insulation Installation Measures Isolated supply system with isolation monitoring Medical isolating transformer supplying one individually piece of equipment Q: Are there any other standard which needs to know? A: Yes, the Medical grade isolation Transformers must be designed in accordance with IEC 61558-2-15 and the insulation monitoring device should meet the requirement of IEC 61557-8 Q; What are the major components in IPS? A: The IPS has four major components which are 1. Medical Grade Isolation Transformer 2. Insulation Monitoring device 3. Fault locator 4. Remote Alarm panel Q: Can we use a standard isolation transformer for IPS? A: No, we can t. The isolation transformer used in IPS should have a leakage current of less than 0.5mA when the output winding is shorted to earth at rated voltage and rated frequency. Single-phase transformers shall be used to form the medical IT systems for portable and fixed equipment and the rated output shall not be less than 0.5 kva and shall not exceed 10 kva. If the supply of three-phase loads via an IT system is also required, a separate threephase transformer shall be provided for this purpose with output line-to-line voltage not exceeding 250 V. Monitoring of overload and high temperature for the medical IT transformer is required. Q: What is an IMD? A: IMD is an insulation monitoring device which monitors the insulation resistance between the Neutral and earth. Whenever the insulation resistance drops below 50kW,the IMD will show an insulation error which needs to corrected manually.

Q: What is a Remote Alarm Panel? A: Remote Alarm panel is a remote indication device with provides an audio-visual alarm in the event of insulation fault, over temperature of transformer or overload of transformer. Generally, the remote alarm panel are installed in electrical maintenance room or in a nurse station for immediate action. Illustration of IPS highlighting the major components of an IPS IPS