Protective Relaying for DER

Similar documents
ECE 528 Understanding Power Quality

E N G I N E E R I N G M A N U A L

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Babak Enayati National Grid Thursday, April 17

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

Table of Contents. Introduction... 1

Focused Directional Overcurrent Elements (67P, Q and N) for DER Interconnection Protection

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM

Generation Interconnection Requirements at Voltages 34.5 kv and Below

The Connecticut Light and Power Company

Utility Interconnection and System Protection

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Substation applications

Sequence Networks p. 26 Sequence Network Connections and Voltages p. 27 Network Connections for Fault and General Unbalances p. 28 Sequence Network

IEEE sion/1547revision_index.html

COPYRIGHTED MATERIAL. Index

GUIDE FOR GENERATOR INTERCONNECTION THE WIRES OWNER DISTRIBUTION SYSTEM

Transmission Protection Overview

Generator Protection GENERATOR CONTROL AND PROTECTION

Experiences in Integrating PV and Other DG to the Power System

This document covers common questions concerning the design of an effectively grounded system.

System Protection and Control Subcommittee

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

NERC Protection Coordination Webinar Series July 15, Jon Gardell

Transmission Line Protection Objective. General knowledge and familiarity with transmission protection schemes

IEEE 1547: Standard for Interconnection and Interoperability of Distributed Energy Resources with Associated Electric Power Systems Interfaces

New Methods for Detecting Unintentional Islanding for a Distributed-Generation Inverter

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

Power Quality Basics. Presented by. Scott Peele PE

Education & Training

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

Catastrophic Relay Misoperations and Successful Relay Operation

Power Plant and Transmission System Protection Coordination Fundamentals

Grid Converters for Photovoltaic

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR INTERCONNECTION OF GENERATION FACILITIES NOT SUBJECT TO FERC JURISDICTION

The Effect of Various Types of DG Interconnection Transformer on Ferroresonance

Modelling Parameters. Affect on DER Impact Study Results

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

PROTECTION SIGNALLING

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

DRAFT. City of Lethbridge Electric ENGINEERING STANDARDS GUIDELINE FOR GENERATOR INTERCONNECTION THE CITY OF LETHBRIDGE ELECTRIC DISTRIBUTION SYSTEM

ANALYSIS OF LIGHTNING ARRESTER OVERLOADING IN FUTURE DISTRIBUTION SYSTEMS WITH DISTRIBUTED GENERATION. A Thesis JONATHAN MICHAEL SNODGRASS

Protection of Electrical Networks. Christophe Prévé

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

WD series DIN Rail or Screw Mounted Protective Relays

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

Protection Basics Presented by John S. Levine, P.E. Levine Lectronics and Lectric, Inc GE Consumer & Industrial Multilin

Wind Power Facility Technical Requirements CHANGE HISTORY

Inverter-Based Resource Disturbance Analysis

Waterpower '97. Upgrading Hydroelectric Generator Protection Using Digital Technology

SEL-311C TRANSMISSION PROTECTION SYSTEM

OPERATING, METERING, AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 2,000 KILOWATTS

Distribution/Substation Transformer

TABLE OF CONTENT

Appendix C-1. Protection Requirements & Guidelines Non-Utility Generator Connection to Okanogan PUD

Distributed Solar Integration Experiences

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

Power System Protection Where Are We Today?

Power Plant and Transmission System Protection Coordination

DER Ride-Through Performance Categories and Trip Settings Presentation at PJM Ride-Through Workshop, Philadelphia, PA, October 1-2, 2018

Adaptive Autoreclosure to Increase System Stability and Reduce Stress to Circuit Breakers

SECTION AUTOMATIC TRANSFER SWITCH

Revised IEEE 1547 Standard for Interconnecting Distributed Energy Resources with Electric Power Systems- National Grid Solar Program

Advantages and Disadvantages of EHV Automatic Reclosing

POWER FACTOR CORRECTION. HARMONIC FILTERING. MEDIUM AND HIGH VOLTAGE SOLUTIONS.

Microgrid Protection Student Laboratory

Technical Requirements For Generation Connected to The ODEC System

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Wind Aggregated Generating Facilities Technical Requirements

Protecting Feeders With Distributed Resource Scott Elling HDR Inc HDR, all rights reserved.

Section G2: PROTECTION AND CONTROL REQUIREMENTS FOR TRANSMISSION GENERATION ENTITIES

Generation and Load Interconnection Standard

A proven distribution feeder solution with integrated protection, monitoring, and control

Back to the Basics Event Analysis Using Symmetrical Components

Guide and Requirements for Service. at 69,000 to 287,000 Volts R 0.2

PSV3St _ Phase-Sequence Voltage Protection Stage1 (PSV3St1) Stage2 (PSV3St2)

DISTRIBUTION ENGINEERING PRACTICES

Generation and Load Interconnection Standard

Communications Assisted Islanding Detection

R10. IV B.Tech I Semester Regular/Supplementary Examinations, Nov/Dec SWITCH GEAR AND PROTECTION. (Electrical and Electronics Engineering)

Protection of a 138/34.5 kv transformer using SEL relay

HUTCHINSON UTILITIES COMMISSION TRANSMISSION INTERCONNECTION GUIDELINES

COPYRIGHTED MATERIAL. Introduction to protective relaying. 1.1 What is relaying?

A Novel Active Anti-Islanding Protection Scheme for Grid-Interactive Roof-Top Solar PV System

Transmission Interconnection Requirements for Inverter-Based Generation

IEEE Major Revision of Interconnection Standard

Protective Relays Digitrip 3000

Anti-Islanding Today, Successful Islanding in the Future

Electrical Protection System Design and Operation

Table of Contents. 1.0 Intent and Limitations Intent Limitations Contact Information General Requirements...

BC HYDRO REAL TIME OPERATIONS OPERATING ORDER 7T-30A. NORTH COAST INTERCONNECTION: SKEENA BOB QUINN SUBSYSTEM Supersedes OO 7T-30A dated 07 July 2014

BE1-67N GROUND DIRECTIONAL OVERCURRENT RELAY FEATURES ADDITIONAL INFORMATION. FUNCTIONS AND FEATURES Pages 2-4. APPLICATIONS Page 2

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

Notes 1: Introduction to Distribution Systems

TECHNICAL SPECIFICATIONS AND OPERATING PROTOCOLS AND PROCEDURES FOR SMALL GENERATION INTERCONNECTIONS

1 INTRODUCTION 1.1 PRODUCT DESCRIPTION

Using a Multiple Analog Input Distance Relay as a DFR

Transcription:

Protective Relaying for DER Rogerio Scharlach Schweitzer Engineering Laboratories, Inc. Basking Ridge, NJ

Overview IEEE 1547 general requirements to be met at point of common coupling (PCC) Distributed resource (DR) response to area electric power system (EPS) abnormal conditions

Overview Distributed generation (DG) impact on distribution feeders Real Life Operation of DR Interconnection Protection Introduction to Symmetrical Components

IEEE 1547 General Requirements to Be Met at PCC Voltage regulation Integration with area EPS grounding Synchronization Inadvertent energization of area EPS Monitoring provisions Isolation devices Interconnection integrity

DR Response to Area EPS Abnormal Conditions Faults Reclosing Voltage excursions Frequency excursions Loss of synchronism Reconnection to area EPS

DR Response to Area EPS Faults DR unit shall cease to energize area EPS for faults on area EPS circuit to which it is connected

DR Response to Area EPS Reclosing DR shall cease to energize area EPS circuit to which it is connected prior to reclosing by area EPS

DR Response to Voltage Excursions Voltage parameters are to be met at PCC Interconnection system responds to rms or fundamental voltage Phase to phase Phase to neutral Voltage Range (% of base voltage) Clearing Time (s) V < 50 0.16 50 V 88 2.00 110 V 120 1.00 V 120 0.16

DR Response to Frequency Excursions DR shall cease to energize area EPS when system frequency is in particular range DR Size Frequency Range (Hz) Clearing Time (s) 30 kw > 30 kw > 60.5 0.16 < 59.3 0.16 > 60.5 0.16 < 59.8 to 57.0 (adjustable) 0.16 to 300 (adjustable) < 57.0 0.16

DR Response to Loss of Synchronism In this case, DR response Applies only to synchronous generators Is primarily a risk to generators Standard addresses this condition as being of concern only if it results in voltage fluctuations that violate flicker limitations

DR Reconnection to Area EPS Reconnection is delayed up to 5 minutes after area EPS steady-state voltage and frequency are restored Ranges include Frequency 59.3 to 60.5 Hz Voltage see ANSI C84.1-1995, Table 1

Power Quality Limitation to dc injection Limitation of flicker induced by DR Harmonics

Islanding Unintentional Intentional

DG Impact on Distribution Feeders Increased fault duty Unintentional islanding Relay desensitization Nuisance tripping Automatic reclosing Voltage regulation and flicker Ferroresonance

Increased Fault Duty Is caused by addition of generating sources and rotating machinery of considerable size Affects capability of equipment to carry and interrupt fault currents Requires both local and area EPS equipment ratings to be reevaluated

Unintentional Islanding Occurs when portion of area EPS and DR become electrically isolated from rest of area EPS and DR continues to energize island Should be avoided for two major reasons There is potential for negative effects on voltage, frequency, and power quality Islanded generator complicates both automatic reclosing and manual switching

Relay Desensitization Available short-circuit current increases with addition of DR Short-circuit current splits between substation and DR Substation short-circuit contribution can be significantly reduced when compared with value before addition of DR

Relay Desensitization Fault Current Distribution Without DR Substation 323 198 R1 R2 Three-Phase 3I 0 323 A 198 A F1

Relay Desensitization Fault Current Distribution With DR Substation 199 24 R1 R2 200 246 DR Substation Three-Phase 3I 0 199 A 24 A DR 399 Three-Phase 3I 0 270 200 A 246 A F1

Nuisance Tripping Without DR F2 Substation 762 616 R1 R2 Three-Phase 3I 0 762 A 616 A

Nuisance Tripping With DR Substation 762 616 R1 1530 616 F2 R2 768 0 DR Substation Three-Phase 3I 0 762 A 616 A DR Three-Phase 3I 0 3E 0 768 A 0 A 0.729 pu 3E 0

Operation for Fault in Adjacent Zone I SYS + I FAULT SYS 1 I SYS I FAULT 2 3 I FAULT DR

Automatic Reclosing DR should be disconnected before open interval expires By interconnection protection (81U, 81O, 59, 27) By DTT Minimum open or dead time to allow arc deionization and to avoid restrike is

Automatic Reclosing If DR can form sustainable island when separated from system, restoration becomes issue Utility feeder breaker has to be equipped with synchronism-check element and / or live-bus and dead-line logic OR combination of both elements works as permissive for reclosing utility feeder breaker

Automatic Reclosing Close Permissives Utility Bus Feeder and bus are in synchronism Utility bus is hot and line is dead DR 3 C T 3 Live Bus / Dead Line or Synchronism 1 Temporary Fault Multifunction Relay

PV Array Real Life Operation of DR Interconnection Protection Isolation Transformer 380 Vac 13,800 Vac Neutral Grounding Reactor 51P 51G Pole-mounted Recloser T C I VY VZ 81 59 59G 27 Recloser Control Overhead Distribution Feeder Ø-G Fault Simplified Single-Line Diagram

Recloser Control Simplified Trip Logic 27-1 27-2 59-1 59-2 81-1 OR 81-2 81-3 59G 51P 51G OR OR TRIP RECLOSER

Relay Settings Element Setting Delay Description 27-1 50% 108.33 ms Definite time undervoltage level 1 27-2 88% 1.950 s Definite time undervoltage level 2 59-1 110% 950 ms Definite time overvoltage level 1 59-2 120% 108.33 ms Definite time overvoltage level 2 81-1 57 Hz 78.95 ms (@ 57 Hz) Definite time underfrequency level 1 81-2 58.5 Hz 102.6 s (@ 58.5 Hz) Definite time underfrequency level 2 81-3 60.5 Hz 74.38 ms (@ 60.5 Hz) Definite time overfrequency 59G 8,200 V 1.33 s Definite time residual ground overvoltage 51P 60 A NA Inverse time phase overcurrent 51G 19.8 A NA Inverse time residual ground overcurrent

Relay Underfrequency Settings

Feeder Fault (C-Ground)

Undervoltage Element Pickup Time 15.62 ms

Undervoltage Element Time Delay 108.33 ms

Recloser Interruption Time 17.71 ms

141.66 ms Total Clearing Time

Introduction to Symmetrical Components The solution of balanced multi-phase systems can be accomplished using singlephase methods The method of symmetrical components allows unbalanced multi-phase systems to be solved using single-phase methods. Introduced in 1918 by C.L. Fortescue

Insight it is shown that unbalanced problems can be solved by the resolution of the currents and voltages into certain symmetrical relations. When the constants are symmetrical, that is, when the system viewed from any phase is similar, then the symmetrical components of currents do not react upon each other so that it becomes possible to eliminate the mutual relations with their attendant complication in the solution of the problems. C.L. Fortescue

Decomposition of an Unbalancedd System

Symmetrical Components as a Function of Phase Quantities

Phase Quantities as a Function of Symmetrical Components

Phase-to-Ground Fault Two-Terminal System

Zero Sequence Network During the Fault + - N 0 ΔV 0 = I 0R * (3 x Z N + Z 0TR ) Z 0S I 0DR = 0 Z 0DR 3 x Z N I 0S 0 V 0Z X H 0 Z 0TR ΔV 0 CB CLOSED I 0S + I 0R R CLOSED V 0Z before trip = 2400 V < 2,735 V (pick up) V 0Z after trip = 3200 V > 2,735 V (pick up) H

Residual Ground Overvoltage

Sample DER Interconnected Through PV Array a Delta/ Wye Transformer Isolation Transformer Pole-mounted Recloser T C I VY VZ Overhead Distribution Feeder Ø-G Fault 51P 81 59 27 51G 59G Recloser Control Simplified Single-Line Diagram

E What is the 3V0 at the Recloser Location After Utility Separation? Z 1S I 1S = 0 CB OPEN Z 2S I 2S = 0 CB OPEN Z 0S I 0S = 0 Z 1L Z 2L V 1 V 2 V 0 R CLOSED R CLOSED I 1DR = 0 I 2DR = 0 Z 0DR X Z 1DR Z 1TR Z 2DR Z 2TR I 0DR = 0 H 0 Z0TR H CB OPEN Z 0L R CLOSED I 0R = 0

Conclusions There are several requirements to be met by DR at PCC location DR has to respond to abnormal conditions of area EPS Addition of DR to distribution feeder affects its protection, voltage regulation, fault duty, reclosing scheme, and so on

Conclusions Event report analysis is a great tool to validate DER interconnection protection settings Unbalanced phasors can be broken down into their symmetrical components Symmetrical components allow the use of simple single-phase calculations for analysis of unbalanced systems The resultant symmetrical components can be recombined into the phase components

Questions?

Questions to the audience Please provide 3 examples of DR impacts on distribution feeders. Please provide 3 examples of area EPS abnormal conditions that the DR has to respond to. Can a DR immediately reconnect following a successful feeder restoration? If not, how long is the qualifying time delay? What are the quantities monitored during the qualifying time delay?

Questions to the audience According to the theory of Symmetrical Components, an unbalanced set of currents can be decomposed in three other components. What are these components? How are the sequence networks interconnected to represent a phase-toground fault?