ISLANDING DETECTION USING DEMODULATION BASED FFT

Similar documents
Active Power Sharing and Frequency Control of Multiple Distributed Generators in A Microgrid

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System

Islanding Detection Method Based On Impedance Measurement

Design of Dynamic Voltage Restorer for three phase network as steady state device in the Distribution System

Wavelet Transform Based Islanding Characterization Method for Distributed Generation

Protection of Microgrids Using Differential Relays

Voltage Sag and Swell Mitigation Using Dynamic Voltage Restore (DVR)

Study of Centralized Anti-Islanding Method on Large-Scale Photovoltaic Power Plants

Grid Interconnection of Wind Energy System at Distribution Level Using Intelligence Controller

Islanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending on the Angle

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

ANALYSIS OF PWM STRATEGIES FOR Z-SOURCE CASCADED MULTILEVEL INVERTER FOR PHOTOVOLTAIC APPLICATIONS

State of Charge (SOC)-Based Active Power Sharing Method for Distributed Generations in an Islanded Microgrid

Modelling and Simulation of High Step up Dc-Dc Converter for Micro Grid Application

An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids

Z-SOURCE INVERTER BASED DVR FOR VOLTAGE SAG/SWELL MITIGATION

COMPENSATION OF VOLTAGE SAG USING LEVEL SHIFTED CARRIER PULSE WIDTH MODULATED ASYMMETRIC CASCADED MLI BASED DVR SYSTEM G.Boobalan 1 and N.

Harmonic Reduction in Five Level Inverter Based Dynamic Voltage Restorer

Grid Code Violation during Fault Triggered Islanding of Hybrid Micro-grid

Sag/Swell Compensation and Displacement Factor Improvement using IDVR in Distribution Network

An Enhanced Symmetrical Fault Detection during Power Swing/Angular Instability using Park s Transformation

Analysis of Modern Digital Differential Protection for Power Transformer

Control of a Back-to-Back VSC from Grid Connection to Islanded Modes in Microgrids

A Voltage Controlled DSTATCOM using Hybrid Renewable Energy DC Link VSI for Power Quality Improvement

An Accurate Power Sharing Method for Control of a Multi-DG Microgrid

NOWADAYS, there is much interest in connecting various

ISSN: ISO 9001:2008 Certified International Journal of Engineering Science and Innovative Technology (IJESIT) Volume 2, Issue 3, May 2013

A Power Control Scheme for UPQC for Power Quality Improvement

HARMONICS ANALYSIS USING SEQUENTIAL-TIME SIMULATION FOR ADDRESSING SMART GRID CHALLENGES

Synchronization and Smooth Connection of Solar Photovoltaic Generation to Utility Grid

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Islanding Detection Technique based on Simulation of IEEE16 Bus System

ISLANDING DETECTION IN DISTRIBUTION SYSTEM EMBEDDED WITH RENEWABLE-BASED DISTRIBUTED GENERATION. Saurabh Talwar

Power Quality Improvement Using Voltage Controlled Distributed Energy Resources (VC-DER)

MITIGATION OF VOLTAGE SAGS/SWELLS USING DYNAMIC VOLTAGE RESTORER (DVR)

Wind energy conversion system based on Vienna rectifier with fuzzy logic control technique

Hybrid Islanding Detection Method for Distributed Generators

Improvement of Power Quality using Unified Power Quality Conditioner with Distributed Generation

Simulation Analysis of Three Phase & Line to Ground Fault of Induction Motor Using FFT

Compensation of Different Types of Voltage Sags in Low Voltage Distribution System Using Dynamic Voltage Restorer

Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System

Modelling of Five-Level Inverter for Renewable Power Source

A novel active current disturbance method

Adaptive ANN based STATCOM and DVR for optimal integration of wind energy with grid using permanent magnet synchronous generator

A Versatile Control Scheme for UPQC for Power Quality Improvement using fuzzy controller

Power Quality Improvement of Grid-Connected Dual Voltage Source Inverter system

ISSN Vol.03,Issue.11, December-2015, Pages:

Power Quality Improvement of Distribution Network for Non-Linear Loads using Inductive Active Filtering Method Suresh Reddy D 1 Chidananda G Yajaman 2

Power Quality Improvement Using Hybrid Power Filter Based On Dual Instantaneous Reactive Power Theory With Hysteresis Current Controller

Design Requirements for a Dynamic Series Compensator for Voltage Sags Mitigation in Low Voltage Distribution System

A Comparative Study of Wavelet Transform Technique & FFT in the Estimation of Power System Harmonics and Interharmonics

p. 1 p. 6 p. 22 p. 46 p. 58

IDENTIFICATION OF POWER QUALITY PROBLEMS IN IEEE BUS SYSTEM BY USING NEURAL NETWORKS

Compare Stability Management in Power System Using 48- Pulse Inverter, D-STATCOM and Space Vector Modulation Based STATCOM

A New Subsynchronous Oscillation (SSO) Relay for Renewable Generation and Series Compensated Transmission Systems

Simulation and Implementation of DVR for Voltage Sag Compensation

New Direct Torque Control of DFIG under Balanced and Unbalanced Grid Voltage

Protection from Voltage Sags and Swells by Using FACTS Controller

@IJMTER-2016, All rights Reserved 241

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

Optimal sizing of battery energy storage system in microgrid system considering load shedding scheme

Australian Journal of Basic and Applied Sciences. Simulation and Analysis of Closed loop Control of Multilevel Inverter fed AC Drives

Voltage Support and Reactive Power Control in Micro-grid using DG

Acknowledgements Introduction p. 1 Electric Power Quality p. 3 Impacts of Power Quality Problems on End Users p. 4 Power Quality Standards p.

PRECISION SIMULATION OF PWM CONTROLLERS

A Novel Control Strategy of Shunt Active Filters

ENHANCED DISTANCE PROTECTION FOR SERIES COMPENSATED TRANSMISSION LINES

MMC based D-STATCOM for Different Loading Conditions

Dynamic Voltage Restorer for Voltage Compensation and Fault Current Limiting Functions

Keywords: Wavelet packet transform (WPT), Differential Protection, Inrush current, CT saturation.

MODELING AND SIMULATION OF UNIFIED POWER QUALITY CONDITIONER FOR POWER QUALITY IMPROVEMENT

Superconducting Fault Current Limiter for Energy Storage Protection in a Micro Grid

Analysis and modeling of thyristor controlled series capacitor for the reduction of voltage sag Manisha Chadar

Islanding Detection Techniques for Distributed Energy Resources-Review

Power Conditioning Equipment for Improvement of Power Quality in Distribution Systems M. Weinhold R. Zurowski T. Mangold L. Voss

MODELING AND ANALYSIS OF IMPEDANCE NETWORK VOLTAGE SOURCE CONVERTER FED TO INDUSTRIAL DRIVES

Fault Localization using Wavelet Transforms in 132kV Transmission Lines

ANALYSIS OF OPTIMAL LOCATION OF SUPERCONDUCTING FAULT CURRENT LIMITER FOR THE SMART GRID

Investigation and Correction of Phase Shift Delays in Power Hardware in Loop Real-Time Digital Simulation Testing of Power Electronic Converters

[Nayak, 3(2): February, 2014] ISSN: Impact Factor: 1.852

Improving Power Quality in Low Voltage Networks Containing Distributed Energy Resources

Simulation of Multi Converter Unified Power Quality Conditioner for Two Feeder Distribution System

[Mahagaonkar*, 4.(8): August, 2015] ISSN: (I2OR), Publication Impact Factor: 3.785

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System

INVESTIGATION OF HARMONIC DETECTION TECHNIQUES FOR SHUNT ACTIVE POWER FILTER

II. RESEARCH METHODOLOGY

Differential Protection for Microgrids with Embedded Generations

Control of grid connected inverter system for sinusoidal current injection with improved performance

High Gain Step Up DC-DC Converter For DC Micro-Grid Application

A simple output voltage control scheme for single phase wavelet modulated inverters

ISSN Vol.04,Issue.08, July-2016, Pages:

IJESRT. (I2OR), Publication Impact Factor: (ISRA), Impact Factor: Student, SV University, Tirupati, India.

UPQC for Power Quality Improvement in DG Integrated Smart Grid Network: a Review

Power Quality Improvement of Grid Connected Wind Energy System by Statcom for Balanced and Unbalanced Linear and Nonlinear Loads

Improvement of Power Quality in Distribution System using D-STATCOM With PI and PID Controller

Fault Detection and Isolation of a Loop Type Low Voltage DC Bus Microgrid

Application of Fuzzy Logic Controller in Shunt Active Power Filter

OPEN-CIRCUIT FAULT DIAGNOSIS IN THREE-PHASE POWER RECTIFIER DRIVEN BY A VARIABLE VOLTAGE SOURCE. Mehdi Rahiminejad

Transcription:

ISLANDING DETECTION USING DEMODULATION BASED FFT Kumaravel.K 1 and Vetrivelan. P.L 2 Department of Electrical and Electronics Engineering, Er.Perumal Manimekalai College of Engineering, Hosur, India Abstract when the load mismatch occurs, it clearly reveals that there exists an impedance mismatch in power distribution systems. This is a serious problem in power delivery. Hence in this method based on multiple frequency harmonic current injection is injecting two non-characteristic symmetric harmonic currents, and then according to the different harmonic voltages caused by different frequency harmonic currents, all three-phase impedances can be calculated accurately. This project proposes a novel method of Demodulation based FFT for three-phase grid impedance detection method based on dual-frequency harmonic current injection for islanding detection. This method differs from the conventional transform by the way of changing spectrum detection method. The estimation of harmonic content and based on the amount of harmonics islanding is decided. Using Fourier transforms always results in perfect harmonic estimation and hence the islanding also can be detected with our proposed method. Grid impedance detection based on single harmonic current injection is reliable in three-phase impedance balanced grid. Simulation and experiments are carried out under grid impedance balanced and unbalanced conditions. Keywords- PCC, Grid, DG, DFIG, FFT, PWM I. INTRODUCTION As the composition of power systems changes with the increased use of distributed generation (DG), the ability to maintain a secure supply with high power quality is becoming more challenging. The increased use of power electronic converters as part of loading systems could cause further power quality problems: converters act as strong harmonic current (or voltage) sources. The information on power system parameters (particularly the net power system impedance to source) at any instant in time is central to addressing these problems. For example, power system impedance monitoring is an important enhancement to active filter control. The impedance estimation can be embedded into the normal operation of grid connected power electronic equipment (PEE) such as sinusoidal rectifiers and active shunt filters (ASF). PWM harmonics associated with PEE, as measured in the active filter line current or voltage at the point of common connection (PCC) can provide non-invasive estimation of power system impedance changes, although it is not accurate enough to provide a suitable value for control. A small disturbance introduced by a short modification to the PEE s PWM strategy can be used to excite the power system impedance and the associated voltage and current transients can be used to determine more exactly the supply impedance back to source, Zs. This invasive method is only triggered when the non-invasive method determines a significant change in Zs. The previous estimation strategy required that the PEE line current and PCC line voltage be measured for 160 ms before the transient injection, and 160 ms post-transient in order to get a suitable frequency resolution for the impedance measurement (6.25 Hz). The analysis proposed in this paper would substantially reduce the period for data capturing to 5 ms post transient, and reduce pre-transient data requirement. This is because the Continuous Wavelet Transform (CWT) is used to process voltage and current transients for calculating the supply impedance. The proposed method therefore has the potential to determine the change in the supply impedance within half a supply cycle. This paper introduces the concept of real-time impedance estimation, and then describes how FFT is used to significantly speed up impedance estimation, demonstrating this capability with experimental results. The paper then goes on to describe how this estimation technique may be used to locate faults inside @IJMTER-2016, All rights Reserved 39

and outside a defined power zone. Fault identification and location is an important application of real-time impedance estimation, and may find use in renewable/distributed energy systems, and power grids for more-electric aircraft and more-electric ships. II. PROPOSED SYSTEM The power system impedance to source is measured by injecting a disturbance onto the system at PCC and analyzing the transient response using measured voltages and currents. The disturbance in this case is manufactured by manipulating two successive PWM cycles in the operation of PEE such that they appear to inject a very short disturbance. For this work, PEE is an active shunt filter as illustrated in Fig. 1. The presence of the ASF filter inductance (in Fig. 1) results in a short current spike, of approximately 1 ms long and 20 A peak, injected into PCC as shown in Fig. 2. Previous methods for analyzing data have included the use of a simple Digital Fourier Transform (DFT) on the measured data and the use of Welch s Averaged Period gram Algorithm. In both techniques, 8 cycles of pre-transient measurement data are subtracted from 8 cycles of transient data to compensate for the system fundamental and other harmonics frequencies normally The impedance estimates at harmonic frequencies are discarded and an interpolation routine is used to determine the impedance to source at such frequencies describe how the estimated impedance at 5th, 7th, and 11th harmonic frequencies are used to generate reference signals for ASF. The excellent control of the filter demonstrates how an active shunt filter can operate in standalone or sensorless mode (where sensorless means that ASF does not require an explicit measurement of supply or load currents). In order to calculate power system quantities, one needs to analyze amplitudes and phase differences between the related voltages and currents. Complex wavelet bases are capable of delivering instantaneous amplitudes of voltages and currents as well as instantaneous phase angles. Using this information, alternative system impedance definitions can be found with time and frequency localization properties. In a single-phase system, the complex wavelets transform will yield two series of complex wavelet coefficients for voltage and current. Using these coefficients, instantaneous values of amplitude and phase are derived for different sub-bands. Using the instantaneous voltage and current amplitude and the instantaneous phase difference between voltage and current, complex wavelet based system impedance is identified as In this case, the system impedance is defined in the wavelet domain. For calculation, a series of impedances are considered at different scales and time, and an average value is estimated over the first half cycle (0.01 second) of the system impedance in the frequency ranges of interest. This can be done by mapping each level of scale to the pseudo-frequency fs as: Where fc is the centre frequency of the wavelet in Hz, is the scale level, and delta t is the sampling period. The averaging of the estimated impedance will smooth the signal without using any particular threshold. Alternatively, taking the local maxima of CWT coefficients at each scale would provide similar results. @IJMTER-2016, All rights Reserved 40

Fig 1. One line diagram of three phase grid The diagram shown as fault is basically an injection of harmonic voltage and hence the current in specified harmonic order, other than the fundamental order. The proposed islanding estimation technique is evaluated and control action is performed based on breaker disconnection through threshold detection. The impedance measurement is used to identify the proximity of a grid fault to PEE. This measurement is used to decide whether PEE should ride through certain remote faults to avoid nuisance trips. Islanding may also be detected. Consider the system in Fig. 6 in which a small power system is defined to be a protected zone in a larger power system. Details of the system parameters, which are based on a medium voltage distribution system, are given in the Appendix. Within the zone there are distributed generation and power electronic equipment for example an active filter, a grid interface for a wind turbine, or photovoltaic system which are connected at the point of measurement (POM). The grid connection codes state that if a fault is detected usually through the Rate of Change of Frequency. PROTECTION ZONE Fig 2. One line circuit diagram of Power grid with impedance (ROCOF) measurement the distributed generator must be disabled. However, with the increasing interest in microgrids and other sustainable energy systems, it may be preferable to operate at the presence of certain faults (i.e., those outside the zone) and only shut down the zone if the fault occurs within the zone. It is possible to locate and specify a type of fault using the proposed impedance estimation. Fault within the zone corresponding to a single phase short circuit to ground, halfway along the internal feeder. Fault on the zone boundary corresponding to a single phase short circuit to ground. Fault outside the zone corresponding to a short circuit to ground halfway along the main feeder @IJMTER-2016, All rights Reserved 41

III. SIMULATION RESULTS To verify the feasibility of the proposed strategy, simulations are carried out. @IJMTER-2016, All rights Reserved 42

Fig.3. Proposed system Simulink diagram @IJMTER-2016, All rights Reserved 43

Fig.4. Three phase AC voltage and current Fig.5. Three phase AC voltage an current with faulty condition It could be seen that the third harmonic is being injected into the line from the time 0.015 to 0.2 s. This change in frequency has to be detected by the wavelet lifting scheme. Fig.6. Three phase AC voltage an current with faulty condition after inserting islanding included @IJMTER-2016, All rights Reserved 44

IV. CONCLUSIONS This project proposed a novel method of FFT based abnormality detection to decide the decision of islanding is needed or not and further control of grid through DCT while using the DC components amplitude. The problem of micro grid is its discontinuity in the power delivery based on the available power. This is a serious problem in power delivery. A Simulink model consisting of a distributed generator and the main power grid based generator is designed and faults are created at random times. In such conditions, islanding is needed to protect the loads, grids and even to maintain the continuity in the power delivery. FFT transform are the peculiar category of frequency domain approaches, frequency abnormality is detected accurately due to the demodulation based harmonic detection. Theoretical analysis and experiment results proved that the proposed method is practically feasible. REFERENCES [1] M. H. Bollen, J. Zhong, F. Zavoda, J. Meyer, A. McEachern, and F.Lopez, Power quality aspects of smart grids, Procedings of International Conference on Renewable Energies and Power Quality, 2010. [2] I. R. Aleksandar Janjic and Z. Stajic, Power quality requirements for the smart grid design, International Journal of Circuits, Systems and Signal Processing, 2011. [3] J. A. Peas Lopes, C. L. Moreira and A.G Madureira. Defining control strategies for microgrids islanded operation. IEEE Transactions on Power Systems, 21(2), 916-924. 2006 [4] M. A. Pedrasa and T. Spooner. A survey of techniques used to control microgrid generation and storage during island operation. Proceedings of the Australian Universities Power Engineering Conference. 2006 [5] C. K. Sao and P.W. Lehn. Control and power management of converter fed microgrids. IEEE Transactions on Power Systems, vol. 23, no. 3, pp. 1088-1098, August 2008. [6] H. Karimi, H. Nikkhajoei and R. Iravani A linear quadratic Gaussian controller for a stand-alone distributed resource unit-simulation case studies IEEE Power Engineering Society General Meeting, PES07, June2007. [7] Y. Li, D.M. Vilathgamuwa and P.C. Loh. Design, analysis, and real-time testing of a controller for multibus microgrid system. IEEE transactions on Power electronics, 19(5), 1195-1204. 2004 [8] F. Fernandes, R. Spaendonck, and C. Burrus, A new framework for complex wavelet transforms, IEEE Trans. Signal Process., vol. 51, no. 7, pp. 1825 1837, Jul. 2003. [9] J. Ren andm.kezunovic, Real-time power system frequency and phasors estimation using recursive wavelet transform, IEEE Trans. Power Del., vol. 26, no. 3, pp. 1392 1402, Jul. 2011. [10] P. Kang and G. Ledwich, Estimating power system modal parameters using wavelets, in Proc. 5th Int. Symp. Signal Process. Its Appl., Brisbane, Australia, Aug. 22 25, 1999, pp. 563 566. [11] G. Strang and T. Nguyen,Wavelets and Filter Banks. Wellesley,MA, USA: Wellesley-Cambridge, 1996. [12] M. Tsukamoto, S. Ogawa, Y. Natsuda, Y. Minowa, and S. Nishimura, Advanced technology to identify harmonics characteristics and results of measuring, in Proc. 9th IEEE Int. Conf. Harmonics Quality. @IJMTER-2016, All rights Reserved 45