Simulation of Autoground System for Antiislanding

Similar documents
An Anti-islanding Technique for Protection of Distribution Generation

Protective Relaying for DER

Reducing the Fault Current and Overvoltage in a Distribution System with an Active Type SFCL Employed PV System

Table of Contents. Introduction... 1

Babak Enayati National Grid Thursday, April 17

HIGH POWER FACTOR INDUCTION HEATING SYSTEM WITH INTERLEAVED VARIABLE DUTY CYCLE

Texas Reliability Entity Event Analysis. Event: May 8, 2011 Loss of Multiple Elements Category 1a Event

The Fault Level Reduction in Distribution System Using an Active Type SFCL

Islanding and Detection of Distributed Generation Islanding using Negative Sequence Component of Current

E N G I N E E R I N G M A N U A L

Anti-Islanding Protection of Distributed Generation Resources Using Negative Sequence Component of Voltage

Phase-phase/phase-neutral: 24/13.8 kv star, 13.8 kv delta, 12/6.9 kv star.

EMERGING distributed generation technologies make it

Islanding Detection Method Based On Impedance Measurement

UPGRADING SUBSTATION RELAYS TO DIGITAL RECLOSERS AND THEIR COORDINATION WITH SECTIONALIZERS

A Decision Tree Based Approach for Microgrid Islanding Detection

Impacts of the Renewable Energy Resources on the Power System Protection by: Brent M. Fedele, P.E., National Grid for: 11 th Annual CNY Engineering

Bearing Currents and Shaft Voltage Reduction in Dual-Inverter-Fed Open-End Winding Induction Motor With CMV PWM Methods Employing PID

Ripple Reduction Using Seven-Level Shunt Active Power Filter for High-Power Drives

Doãn Văn Đông, College of technology _ Danang University. 2. Local Techniques a. Passive Techniques

ADVANCED VECTOR SHIFT ALGORITHM FOR ISLANDING DETECTION

DP&L s Technical Requirements for Interconnection and Parallel Operation of Distributed Generation

Non-detection zone of LOM protection for converter connected wind turbines

ECE 528 Understanding Power Quality

Hybrid Anti-Islanding Algorithm for Utility Interconnection of Distributed Generation

A New Network Proposal for Fault-Tolerant HVDC Transmission Systems

Anti-Islanding Today, Successful Islanding in the Future

ISO Rules Part 500 Facilities Division 502 Technical Requirements Section Aggregated Generating Facilities Technical Requirements

Enhancement of Fault Current and Overvoltage by Active Type superconducting fault current limiter (SFCL) in Renewable Distributed Generation (DG)

Bearing Currents and Shaft Voltage Reduction in Dual-Inverter-Fed Open-End Winding Induction Motor With CMV PWM Methods Employing PID

Adaptive Relaying of Radial Distribution system with Distributed Generation

TRANSIENT AND DESIGN OPERATION ASSESSMENT OF RFCL IN BULK POWER SYSTEMS

BED INTERCONNECTION TECHNICAL REQUIREMENTS

Renewable Interconnection Standard & Experimental Tests. Yahia Baghzouz UNLV Las Vegas, NV, USA

Utility Interconnection and System Protection

PJM Manual 07:: PJM Protection Standards Revision: 2 Effective Date: July 1, 2016

Mitigation of Faults in the Distribution System by Distributed Static Compensator (DSTATCOM)

STATCOM with FLC and Pi Controller for a Three-Phase SEIG Feeding Single-Phase Loads

An Adaptive V-I Droop Scheme for Improvement of Stability and Load Sharing In Inverter-Based Islanded Micro grids

Intelligent Passive Anti-Islanding Protection for Doubly Fed Induction Generators

BIDIRECTIONAL SOFT-SWITCHING SERIES AC-LINK INVERTER WITH PI CONTROLLER

A Simple Technique for Islanding Detection with Negligible Nondetection Zone

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 04, 2016 ISSN (online):

ENOSERV 2014 Relay & Protection Training Conference Course Descriptions

A Novel Islanding Detection Technique for Distributed Generation (DG) Units in Power System

Modified three phase Unified Power Quality Conditioner with capacitor midpoint topology

GRID CODE COMPATIBLE PROTECTION SCHEME FOR SMART GRIDS

Power Quality Improvement in Fourteen Bus System using UPQC

Mitigation of Fault in the Distribution System by using Flexible Distributed Static Compensator (FD-STATCOM)

2012 Grid of the Future Symposium. Impacts of the Decentralized Photovoltaic Energy Resources on the Grid

ISSN Vol.07,Issue.21, December-2015, Pages:

A VOLTAGE SAG/SWELL ALONG WITH LOAD REACTIVE POWER COMPENSATION BY USING SERIES INVERTER of UPQC-S

Southern Company Interconnection Requirements for Inverter-Based Generation

IJCSIET--International Journal of Computer Science information and Engg., Technologies ISSN

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 4: (June 10, 2013) Page 1 of 75

Islanding Detection Technique based on Simulation of IEEE16 Bus System

SHORT CIRCUIT ANALYSIS OF 220/132 KV SUBSTATION BY USING ETAP

Synchronization and Smooth Connection of Solar Photovoltaic Generation to Utility Grid

Power Transmission of AC-DC Supply in a Single Composite Conductor

TECHNICAL GUIDELINE FOR THE INTERCONNECTION OF DISTRIBUTED ENERGY RESOURCES TO EPCOR DISTRIBUTION AND TRANSMISSION INC. S DISTRIBUTION SYSTEM

Microgrid Islanding with a Battery Energy Storage System (BESS) Gabriel Haines

SERIES ACTIVE power filters have proved to be an interesting

PRC Generator Relay Loadability. Guidelines and Technical Basis Draft 5: (August 2, 2013) Page 1 of 76

Islanding Detection and Frequency Circuit Measurement by Power Distribution Relation Depending on the Angle

Protection of Microgrids Using Differential Relays

A Fuzzy based MC-DPFC for Enhancement of Power Quality in Transmission Line

Comparison of Simulation and Experimental Results of UPFC used for Power Quality Improvement

INTERIM ARRANGEMENTS FOR GRID TIED DISTRIBUTED ENERGY RESOURCES. Technical Requirements for Grid-Tied DERs

Coordinated Control Strategy of Solar Photovoltaic Generators with MPPT and Battery Storage in Micro Grids

Technical Requirements for Connecting Small Scale PV (sspv) Systems to Low Voltage Distribution Networks

Numbering System for Protective Devices, Control and Indication Devices for Power Systems

The Connecticut Light and Power Company

REACTIVE POWER BASED ANTI-ISLANDING SCHEME FOR SYNCHRONOUS DISTRIBUTED GENERATORS

Minimization of Power Loss and Improvement of Voltage Profile in a Distribution System Using Harmony Search Algorithm

RESEARCH ON CLASSIFICATION OF VOLTAGE SAG SOURCES BASED ON RECORDED EVENTS

Anti-IslandingStrategyforaPVPowerPlant

Microgrid Protection

THE ROLE OF SYNCHROPHASORS IN THE INTEGRATION OF DISTRIBUTED ENERGY RESOURCES

Performance Analysis of Various Types of Fault Current Limiters Using PSCAD

Project Report. Project #: TIC706.1-A Islanding Risk of Synchronous Generator Based Distributed Generation Systems. Draft to be approved.

Protection from Voltage Sags and Swells by Using FACTS Controller

Reducing the Effects of Short Circuit Faults on Sensitive Loads in Distribution Systems

DG TRANSFER CONNECTION SCHEME IN ACTIVE DISTRIBUTION NETWORKS

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 26, NO. 3, JULY

ANALYSIS OF LIGHTNING ARRESTER OVERLOADING IN FUTURE DISTRIBUTION SYSTEMS WITH DISTRIBUTED GENERATION. A Thesis JONATHAN MICHAEL SNODGRASS

Load Compensation at a Reduced DC Link Voltage by Using DSTATCOM with Non-Stiff Source

[Jawalbankar*, 5(4): April, 2016] ISSN: (I2OR), Publication Impact Factor: 3.785

OPERATING, METERING AND EQUIPMENT PROTECTION REQUIREMENTS FOR PARALLEL OPERATION OF LARGE-SIZE GENERATING FACILITIES GREATER THAN 25,000 KILOWATTS

Power Frequency Droop Controller For Stability Analysis In Micro Grids

Micro grid Protection Using Digital Relays Mr.Karthik.P 1, Mrs.Belwin J. Brearley 2

Design Requirements for a Dynamic Voltage Restorer for Voltage Sags Mitigation in Low Voltage Distribution System

Analysis, Modeling and Simulation of Dynamic Voltage Restorer (DVR)for Compensation of Voltage for sag-swell Disturbances

Experiences in Integrating PV and Other DG to the Power System

Analysis of Hybrid Power Conditioner in Three-Phase Four-Wire Distribution Power Systems for Suppressing Harmonics and Neutral-Line Current

Wavelet Transform Based Islanding Characterization Method for Distributed Generation

SOLAR POWERED REACTIVE POWER COMPENSATION IN SINGLE-PHASE OPERATION OF MICROGRID

USE OF HVDC MULTI TERMINAL OPTIONS FOR FUTURE UPGRADE OF THE NATIONAL GRID

A New Control Strategy for Three- Phase Inverter Applied To Induction Motor of Micro Grid

Application of Fuzzy Logic Controller in UPFC to Mitigate THD in Power System

IMPROVED TRANSFORMERLESS INVERTER WITH COMMON-MODE LEAKAGE CURRENT ELIMINATION FOR A PHOTOVOLTAIC GRID-CONNECTED POWER SYSTEM

Transcription:

S.Ravikanth, B.Rama Krishna Singh, P.Janardhan Reddy and T.V.Subba Rao 6 Simulation of Autoground System for Antiislanding Protection of Distributed Generation with Renewable Application S.Ravikanth 1 B.Rama Krishna Singh 2 P.Janardhan Reddy 3 T.V.Subba Rao 4 1 Assistant Professor, Sarojini Institute of Technology, Telaprolu, Vijayawada, Krishna Dt, A.P, India 234 Assistant Professor, Narayana Engineering College, Nellore, A.P, India Abstract Due to the variety of distribution generation (DG) sizes and technologies connecting to distribution networks, and the concerns associated with out-of phase reclosing, antiislanding continues to be an issue where no clear solution exists. This paper presents an autoground approach that was proposed in the context of an IEEE working group on best practices for DG protection. A prototype system was constructed using standard distribution apparatus and a recloser controller, and it was tested on the utility s distribution test line. Results show that the anti-islanding detection time is approximately a cycle longer than the delay associated with application of the autoground. Once the autoground was applied, the DG was disconnected within 1 cycle on overcurrent protection. The solution is inherently scalable, applicable to all DG types, is configurable to various reclosing practices and does not require additional equipment or settings changes at the producer s site. Using this anti-islanding protection scheme, a renewable Application is presented for better distributed generation. Index Terms Distributed generation, distribution relaying, renewable energy. I. INTRODUCTION THE fast acting of distributed generator has grown over the past decade and some utilities have reached very high penetration levels. Despite this experience the debate between utilities and private producers rages o n a n u m b e r o f technical issues. Possibly the most contentious is that of antiislanding protection, a reliable high speed communication based transfer-trip scheme and a local passive approach methods, that relies only on the measurements of the voltage wave form is represent islanding respectively, the most conservative and modern approaches. The antiislanding system and line protection are the two fundamental protection requirements that need to be met by all distributed generation (DG) installations, as detailed in the DG interconnection standards Line protection consists of being able to detect all faults on the distribution feeder to which the DG is connected, while not disconnecting for faults on an adjacent feeder. Generally over current relaying is sufficient to meet this requirement, although in power electronic based generators, other strategies may be necessary due to the limited contribution to short circuits by these installations. Anti-islanding has been the subject of a number of studies these approaches can be typically divided into the following two Classifications: passive approaches using the local measurements of voltage and current, and variables derived from using these quantities, to delineate between islanding and grid connected operation and active approaches where By the DG perturbs the grid voltage or frequency, an approach intended to be benign while the grid is present, and to destabilize the system when the substation is open. A third approach is in fact a variant on communication based approaches, whereby using thyristor valves connected to ground, a disturbance is periodically injected at the substation-its presence at the DG s location indicates a normal condition, whereas its absence is indicative of an islanded grid have also suggested these thyristor based devices for fault identification in. Similar to active islanding techniques, this approach could be criticized alone on the impact on power quality. Additionally, in noisy grids or feeders that are particularly long, the issue of nuisance tripping is an issue. This paper presents an approach to anti-islanding protection that is based on applying a three-phase short circuit to the islanded distribution system just prior to reclosing or reenergization. Provides the theory and methodology for construction of this utility-owned equipment. Anti-islanding protection is required of any distributed generator connecting to the Distribution networks Continues to energize the feeder when the utility has opened-creating an unintentional island. An unintentional island, although rather unlikely in real life, could be created by one of two scenarios. DG sets / TG sets are finding more and more applications as captive power sources in modern day industrial plants.

S.Ravikanth, B.Rama Krishna Singh, P.Janardhan Reddy and T.V.Subba Rao 7 II. THEORY AND METHODOLGY Fig.1. Illustration of the proposed autogrounding system A DG set owner may decide to connect his DG to the local Electricity Grid supply (ie) the DG will be synchronized to the grid. The main objective here is to feed the plant load will both by the grid as well as the DG set. Whenever a DG is connected to the local grid, there can be two modes of operation as shown in DG is shown connected in parallel to EB power. Plant load is connected to the same bus where both DG and EB are present. The first case is a result of the inadvertent opening of the substation feeder breaker/recloses are one of the protection devices further down the feeder. This could be done in error or as a planned operation where the utility personnel do not realize that there is a DG present on the line. Eventually the line is re- energized and the risk of out-of-phase reclosing exists, if the DG remains online. The second, even less likely situation would be a temporary fault that leads to operation of the utility protection device, but the DG s protection does not operate before the self- clearing fault extinguishes, creating the temporary island. For example a tree branch might touch the line and it is clear at the moment the vacuum bottle interrupter of a Recloser operates. Although less likely, the latter of the two cases is generally used to define the anti-islanding requirements, which links the requirement to first period relaxing time of the local utility typical first operation releasing time off, although some are as fast as 0.5 s. This defines the speed at which the DG s anti- islanding protection must detect the island. Provides a comparison of the different types of anti-islanding approaches and the implications in terms of equipment, the installation site, relative cost, and pros and cons of each. The solution proposed in the present work, termed an auto ground, is seen as a compromise in terms of cost and performance between the transfer-trip and local passive measurements. Presents the autoground concept, where the autoground system is installed just down the line of the utility protection device (substation breaker or inline Recloser). In this configuration, following the opening of the utility breaker, the autoground opens the substation side device, denoted sectionalizing switch (SS) and closes the auto grounding switch (AS) effectively applying a three phase to ground fault. All DGs that have not already disconnected based on their antiislanding protection will be forced to disconnect based online protection. Here it is assumed that the DG s line protection has been properly configured in order to detect all faults, as required by In the case of inverter based DG, over current protection alone may not be sufficient and more advanced functions such as over current with voltage restraint may be required. However, the focus of the present work is on the validation of the concept. Following application of the autoground for the predefined time, it then flips states, opening AS following by closing of its SS. The utility breaker then re-energizes the system, without a risk of out-of-phase reclosing. Fig.2. Sequence of events in the Operation of the autoground. The autoground system consists of three main components: the sectionalizing switch the autoground switch, and the controller, which can be implemented using a variety recloser or breaker controls.

S.Ravikanth, B.Rama Krishna Singh, P.Janardhan Reddy and T.V.Subba Rao 8 Here we describe e a c h of these components in turn the SS is required only to mirror the state of the substation breaker. It is preferable to have the SS as a separate device for the simple reason that costs escalate when work within the substation is required. In this case, it is not required to interrupt fault current so any device that can provide automated sectionalized capabilities would be sufficient. For applications where the outgrown is paired with an in-line Recloser, the SS is not required as its functionality can simply be integrated into the Recloser it. The parameters of the synchronous generator and the over current protection are provided in the Appendix. Switches on feeders 2 and 3 were opened in order to feed them both from feeder 1.The testing consisted of first synchronizing the generator, balancing its output power with the 150 kw load and then initiate opening of the SS for three different configurations of the autoground with all three fuses in service; with one fuse removed; and with two of the three fuses removed. SYNCHRONOUS GENERATOR PARAMETERS SG PG VG IG (KVA) (KW0 (V) (A) 250 200 600 240 A. Results Fig3.Distribution test line model of Autogrounding operation Illustrates the vacuum bottle based recloser used in the experimental s e t -up as the SS. As the AS is connected in parallel with the distribution network only in order to apply the fault, it does not need to interrupt fault current either. As a result, the apparatus is even simpler, and is realized by a slight modification to an automated capacitor bank assembly. The simulation results for the three cases are summarized in the magnitudes of the peak current (which includes the DC component) are given, along with step voltage measured at 1 meter, and the neutral current. Torque measurements were taken but they are not presented as the reading saturated in each case at 45 N m. As can be noted, the magnitude of the phase current is roughly equivalent for the three cases; however, the neutral current is much higher, as expected, for the unbalanced autoground cases. This is reflected in the step voltage measurement, are the measured value represents no issue. Illustrates the case for balanced operation of the autoground that is, with the three fuses in operation. III. MATLAB CIRCUIT AND RESULTS Fig.4.The Monitoring of Proposed anti islanding technique Fig.5 Substation voltages (top) and currents (bottom) during Opening of SS and application of the AS.

S.Ravikanth, B.Rama Krishna Singh, P.Janardhan Reddy and T.V.Subba Rao 9 Autoground t e c h n o lo g y on t h e l o c a l d i s t r i b u t i o n p r o t e c t i o n philosophy. This would include ensuring that the autoground is compatible with the number and duration of reclosing operations. Fig.6a. Three phase voltages (top) of synchronous generator during opening of SS and application of the autoground Fig.6b. Three phase voltages (top) and currents (bottom) of synchronous generator during opening of SS and application of the autoground This c o u l d m e a n a d j u s t i n g t h e various delays m e n t i o n e d above, or in certain cases, requiring different delays for different reclosing operations. That the autoground should only need to be applied during the first reclosing period. To avoid equipment issues, it would be the best selection of the autoground apparatus. The scheme is also economically attractive to DG owners and utilities, especially for systems with multiple DG installations. This paper investigated the design considerations for the signal generator. A set of design formulas is established. Typical signal generator parameters are illustrated using actual system data. The proposed scheme can be implemented using other signalling techniques. Developing a signalling technique that can take advantage of the simple requirement of anti-islanding signalling to reduce the cost of signal generator is still opening of any components. This h a s resulted i n a significantly simplified Auto grounding scheme. In addition, a subject worth research Fig.7.Current waveforms of the synchronous generator during application of the autoground. Fig.9 Proposed anti islanding technique with renewable Application. Fig.8. Torque measurement of the synchronous generator Shaft during operation (expressed on the base of the real Power Prior to the islanding event). Fig. 10 output result voltages.

S.Ravikanth, B.Rama Krishna Singh, P.Janardhan Reddy and T.V.Subba Rao 10 IV. CONCLUSION This paper has presented a scalable, low cost approach for Anti-islanding protection of distributed generation, using a Utility owned and operated system referred to as an autoground. The design of the system and its control were presented and a prototype system was constructed using standard distribution utility equipment. Testing results were presented for symmetrical and asymmetrical operation of the system. In all cases, the DG s over current protection isolated the generator from the system in less than two cycles. The peak torque observed exceeded momentarily around 4 times the pre-fault value. Using this anti-islanding protection scheme, a renewable Application is presented for better distributed generation. The results validated the concept for a single generator based on a synchronous machine, while future work will study its applicability to systems with large numbers of DG, including those with power electronic interfaces. The solution shows promise due to its relatively low cost and inherent scalability. REFERENCES [1] Requirements for the Interconnection of Distributed Generati on to the Hydro-Québec Medium-Voltage Distribution System [Online]. Available:http://www.hydroquebec.com/transenergie/fr/commerce/racco rdement_distribution.html [2] IEEE application guide for IEEE std 1547, IEEE standard for interconnecting distributed resources with electric power systems, IEEE Std. 1547.2 2008, pp. 1 207, Apr. 2009. [3] J.Mulhausen, J.Schaefer, M.Mynam, A. Guzman, and M. Donolo, Anti-islanding today, successful islanding in the future, in Proc. Protective Relay Engineers,, Mar. 29 Apr. 1, 2010, pp. 1 8. [4] R.J.Best, D.J.Morrow, D.M.Laverty, andp.a.crossley, Synchrophasor Broadcast over internet protocol for distributed generator synchronization, IEEE Trans. Power Del.,vol. 25, no. 4, pp.2835 2841, Oct. 2010. [5] F. Katiraei, A. Foss, C. Abbey, and B. Strehler, Dynamic analysis and field verification of an innovative anti -islanding protection scheme based on directional reactive power detection, in Proc. 2007 IEEE Elect. Power Conf., Canada, Oct. 25 26, 2007, pp. 183 188. [6] C.AbbeyandP.Venne, Field validation of a reverse reactive powerrelay for anti-islanding protection of a synchronous generator, in Proc.CIGRE Canada Conf. Power Syst.,Sep.2011. [7] Vieira, J. C. M. Vieira, W. Freitas, W. Xu, and A. Morelato, Efficient Coordination of ROCOF and frequency relays for distributed generation Protection by using the application region, IEEE Trans. Power Del., vol. 21, no. 4, pp. 1878 1884, Oct. 2006. [8] K. El-Arroudi and G. Joos, Data mining approach to threshold settings of islanding relays in distributed generation, IEEE Trans. Power Syst.,vol. 22, no. 3, pp. 1112 1119, Aug. 2007. First Author: S.Ravikanth, graduate in electrical and electronics engineering (EEE) from Prasad Institute Of Technology and Sciences, Jaggayyapet,& his M.Tech from Nalanda Institute of Engineering and Technology, Kantepudi, Sattenapalli, Guntur Dist.,A.P,India,He is working as Assistant Professor in Dep. Of EEE at, Sarojini institute of Technology, Telaprolu, Vijayawad.Affliated to JNTUK, Kakinada, A.P, India His Research Interests are Power Systems, Power Electronics, and drives & FACTS devices. Second Author: B.Rama Krishna Singh, graduate in electrical and electronics engineering ( EEE) from Prasad Institute Of Technology and Sciences, Jaggayyapet,& his M.Tech from LBRCE Krishna Dist.,A.P,India,He is working as Assistant Professor in Dep. Of EEE at, Narayana Engineering College, Nellore, A.P, India.Affliated to JNTUA, Ananthpur, A.P, India His Research Interests are Power Systems, Power Electronics, and drives & FACTS devices. Third Author: P.JANARDHAN REDDY has received the B.Tech (EEE) degree from KSRM College of engineering kadapa and M.Tech (Electrical Power Syst ems) from Srinivasa institute of technology, Kadapa, AP, India, He is working as Assistant Professor in Dep. Of EEE at, Narayana Engineering College, Nellore, A.P, India.Affliated to JNTUA, Ananthpur, A.P, India, His Research Interests are Power Systems. Fourth Author: T.V.Subba Rao has completed BE from Nandanam college of engineering, Tamilnadu and M.Tech from Brahmaiah college of Engineering, Nellore, JNTUA, He is working as Assistant Professor in Dep. Of EEE at, Narayana Engineering College, Nellore, A.P, India.Affliated to JNTUA, Ananthpur, A.P, India, and His Research Interests are Power Systems.